Article 5 - ACCESS REQUIREMENTS AND EXIT TYPES

Section 27-368

Section 27-368

  §  27-368  General.  (a)  Means  of  egress  shall be provided for all
buildings by one or more of the facilities listed below. Access and exit
facilities not specifically covered in this section shall not be used to
satisfy the exit requirements of this code. Fire escapes  shall  not  be
permitted  on  new construction, with the exception of group homes. Fire
escapes may be used as exits on buildings existing  on  December  sixth,
nineteen hundred sixty-eight when such buildings are altered, subject to
the  approval  of  the  commissioner,  or as provided in subdivision (b)
hereof. Elevators or escalators shall be provided in all  new  buildings
exceeding  four  stories  in  height  except  that buildings or building
sections classified in occupancy group H-2 exceeding one story in height
and buildings or building sections classified in occupancy  group  G  or
J-1 exceeding two stories in height shall be provided with elevators.
  (b)  In  group  homes all floors used by children shall have alternate
exits remotely located from each other and  readily  accessible  to  the
occupants.  Fire  escapes  shall  be  permitted  as  the second means of
egress.

Section 27-369

Section 27-369

  §  27-369  Corridors.  Corridors  shall be kept readily accessible and
unobstructed at all times. Corridors shall be kept free  of  combustible
contents  except that in buildings classified in occupancy groups G, H-1
and H-2, combustible contents may be stored  in  noncombustible  lockers
and  combustible  bulletin  boards meeting the requirements of table 5-4
shall be permitted.
  (a) Capacity. The capacity and minimum width of corridors shall be  as
listed  in  table  6-1. Width shall be measured in the clear between the
narrowest points produced by any projections such as radiators, lockers,
drinking fountains, or room or locker  door  swings,  except  that  such
width  may  be  reduced by projections up to eighteen inches wide to the
extent of two inches per unit of exit width if the total  area  of  such
projections  does  not  exceed  five per cent of the area of the wall on
which they occur.
  (b) Height. Corridors shall have a clear  height  of  seven  feet  six
inches  for  at  least  seventy-five per cent of the floor area, with no
point less than seven feet in height. No projection  below  the  ceiling
shall be located so as to obstruct full view of exit signs.
  (c)  Length.  Corridors  shall  be  subdivided  by  smoke barriers, as
defined in subchapter two, into the following lengths:
  Educational occupancy group G....................300 ft.
  Institutional occupancy groups H-1 and H-2.......150 ft.
  Residential occupancy groups J-1 and J-2.........150 ft.
  Where smoke barriers are penetrated by  doors,  such  doors  shall  be
smoke  stop  doors in conformance with subdivision (c) of section 27-371
of this article.
  (d) Dead ends. Dead ends in corridors  shall  not  exceed  the  length
listed  in  table  6-1,  except  that  in  all  occupancy  groups except
occupancy  group  H,  when  a  corridor  is   completely   enclosed   in
construction having a two hour fire-resistance rating, with all corridor
doors  being self-closing and having a fire protection rating of one and
one-half hours, the permissible length of dead ends may be increased one
hundred per cent above the length listed in table 6-1. Dead end distance
shall be measured from the centerline of the door opening nearest to the
closed end of the corridor to the center of an exit door opening, or the
center of that point in the corridor where travel to two or  more  exits
becomes available in two directions.
  (e)  Changes in level. Changes in level requiring less than two risers
in a corridor shall be by a ramp complying with section 27-377  of  this
article.  Risers  and  treads  shall  comply  with  the  requirements of
subdivision (e) of section 27-375 of this article.
  (f) Exterior corridors. Exterior corridors shall be roofed, and  shall
have  solid  floors  drained to prevent accumulations of standing water.
Such floors may serve as fire canopies  when  so  constructed.  Exterior
corridors  shall  be  protected  along  their  outer  side  by guards or
parapets at least three feet six inches  high.  Openings  in  guards  or
parapets shall be of such dimensions as to prevent the passage of a five
inch  dia.  ball.  Where  the outer side of an exterior corridor is more
than fifty per cent enclosed with solid material, it shall be treated as
an interior corridor.
  (g) Balconies. Balconies may serve as a means of egress from  dwelling
units in buildings classified in occupancy group J-2 under the following
conditions:
  (1) They shall serve at least two dwelling units.
  (2)  They  shall  be  constructed  as required for exterior corridors,
except that parapets or guards shall not be higher than four feet on the
outer side of the balcony.

  (3) The dwelling units served by balconies  shall  be  separated  from
each  other  by  construction having at least a two hour fire resistance
rating.  Such separation shall extend at least  three  feet  beyond  the
outside  face  of  the  exterior  wall  of  the  building, although such
projection  may  be  reduced  to  two  feet six inches provided that any
window opening on each such balcony served by the fire separation  shall
be at least two inches from such fire separation for every one inch that
such  separation  is  less  than  thirty-six inches. An opening at least
twenty inches wide shall be provided between the end of this  separation
and  the  balcony  parapet or guard, and the opening shall be maintained
free and unobstructed for the full height of the  balcony,  except  that
privacy  screens  openable  from  either  side  may  be permitted in the
opening.
  (4) Access from dwelling units to the balconies shall be through doors
having glass panels at least two feet wide and four feet  high,  without
muntins,  screens, or other obstructions to hinder entry by breaking the
glass panels. The doors shall  be  lockable  only  from  the  inside  by
devices  that can be easily released from the outside after breaking the
glass. A combination lock or lock required to be  opened  by  a  key  or
removable device or tool shall not be used.
  (h) Construction.
  (1)   Interior  corridors.  Interior  corridors  shall  be  completely
enclosed within fire separations to provide  a  minimum  fire-resistance
rating  of  one  hour  except  as  otherwise provided in subparagraphs a
through c of this paragraph:
  a. For buildings or spaces classified in occupancy group J-1 or J-2 of
combustible construction group  II  exceeding  two  stories  in  height,
except  for buildings not exceeding three stories in height and occupied
exclusively by not more than one family on each story without  boarders,
roomers  or lodgers, corridors shall be enclosed within fire separations
providing a minimum fire-resistance rating of two hours.
  b. Corridor partitions may be omitted or may be constructed of unrated
noncombustible material in buildings  in  occupancy  group  H-2  in  the
following  instances: nurses' stations not exceeding three hundred fifty
square feet in area, waiting spaces, lounges and recreational spaces for
patients and visitors which do not exceed five hundred  square  feet  in
area,  spaces  used  solely  for public telephones, and all other spaces
which are completely protected by  an  automatic  wet  sprinkler  system
complying  with the construction requirements of subchapter seventeen of
this code.
  c. Corridor partitions may be omitted in spaces of occupancy group H-1
used for detention of persons under legal restraint.
  (2) Exterior corridors and balconies. Exterior corridors and balconies
shall be constructed of noncombustible materials.
  (i) Borrowed lights. No operable transoms shall be permitted in  walls
of  corridors.  In corridors required to have a one hour fire-resistance
rating, fixed one-quarter inch wire glass panels may be installed in not
more than twenty percent of the common wall between the corridor and any
room or space, provided that  no  panel  exceeds  seven  hundred  twenty
square inches in area; however, openings permitted in paragraph three of
subdivision  (h)  of  section  27-370  of  this article may be permitted
provided all of the  limitations  and  requirements  specified  in  that
section  are  complied  with,  except  that  openings  in corridor walls
serving as fire divisions required  to  have  a  fire-resistance  rating
shall be limited to those specified in section 27-342 of article five of
subchapter five of this chapter.
  (j)  Ventilation. Corridors shall be ventilated in accordance with the
requirements of subchapter twelve of this chapter. Corridors  shall  not

be  used as open plenums or as ducts to exhaust air from rooms or spaces
opening upon them, except as permitted in reference standard RS 13-1.
  (k)  Interior  finish.  The  interior  finish of corridors shall be in
accordance with the requirements of table 5-4.

Section 27-370

Section 27-370

  §  27-370  Exit passageways. Exit passageways shall be maintained free
of obstructions at all times. Not more than fifty percent of  the  total
number  of  vertical  exits  provided  for a building may be served by a
single exit passageway, except as provided in subdivision (h) of section
27-370 of this article.
  (a) Capacity. The capacity of exit passageways shall be as  listed  in
table 6-1.
  (b)  Width.  The width of an exit passageway serving one vertical exit
shall be equal to the width of the vertical exit. The width of  an  exit
passageway  serving  two  or  more  vertical  exits  shall  be  equal to
seventy-five percent of the width of all of the vertical exits  that  it
serves.  Width  shall  be  measured  in  the clear between the narrowest
points at any projections such as radiators, door swings, or pilasters.
  (c) Height. Exit passageways shall have a clear height of  seven  feet
six inches for at least seventy-five per cent of the floor area, with no
point  less  than  seven feet in height. No projection below the ceiling
shall be located so as to obstruct full view of exit signs.
  (d) Changes in level. Changes in level requiring less than two  risers
in  an  exit passageway shall be by a ramp complying with section 27-377
of this article. Risers and treads shall comply with the requirements of
subdivision (e) of section 27-375 of this article.
  (e) Construction. The construction of exit  passageways  shall  be  as
required  by  table  3-4  for  the  applicable construction class of the
building.
  (f) Openings. No openings other than exit doors shall be permitted  in
exit passageways, except as provided in subdivision (h) of this section.
  (g)  Interior finish. The interior finish of exit passageways shall be
in accordance with the requirements of table 5-4.
  (h) Street floor lobbies. Street floor lobbies may  be  used  as  exit
passageways  when  they comply with the requirements of subdivisions (a)
through (g) of this section subject to the following modifications:
  (1) VERTICAL EXITS SERVED. One hundred per cent of the total number of
vertical exits provided for a building may be served by a  street  floor
lobby,  if  egress  is  provided  in  two  different directions from the
discharge points of all vertical exits to open exterior spaces that  are
remote from each other.
  (2)  WIDTH.  Street floor lobbies serving as exit passageways shall be
increased in width to accommodate the occupant load of all communicating
spaces on the lobby floor that exit through them. The capacity per  unit
of width shall be as listed in table 6-1.
  (3)  OPENINGS.  Openings  between street floor lobbies serving as exit
passageways and elevators or communicating spaces shall comply with  the
following:
  a.  Doors.  1.  Doors  to  stairways  and elevators, and unsprinklered
communicating spaces classified in occupancy group B-2, D-2, F-1 or  F-2
shall  be  self-closing  fire  doors having a one and one-half hour fire
protection rating.
  2. Doors to unsprinklered communicating spaces classified in occupancy
group G, H or J,  or  sprinklered  communicating  spaces  classified  in
occupancy group B-2, D-2, F-1 or F-2 may be either:
  (a)   self-closing   fire  doors  having  a  three-quarter  hour  fire
protection rating, or
  (b) glass or other noncombustible doors installed in conjunction  with
automatic  fire  doors  having  a  one and one-half hour fire protection
rating, with sprinkler heads installed over the doors on the room side.
  3. No other door openings shall  be  authorized  except  as  otherwise
provided in this section.

  b.  Other  openings.  Other openings to spaces classified in occupancy
group C, E, F, G, H or J  shall  be  permitted,  provided  they  have  a
maximum  length  of  eight  feet and a maximum height of eight feet, are
glazed by one-quarter inch polished plate glass or  equivalent  and  are
protected  by  automatic  fire doors having a one and one-half hour fire
protection  rating  and  by  automatic  sprinklers  complying  with  the
construction  requirements  of subchapter seventeen of this chapter over
the openings on the room side.
  c. Separations and limitations. Openings permitted by subparagraphs  a
and  b of this paragraph shall not exceed in total length fifty per cent
of the length of such enclosure wall except where  the  length  of  such
wall  is  less  than sixteen feet. Adjoining openings shall be separated
from each other a minimum of three feet by  construction  having  a  two
hour fire-resistance rating.
  d.  Notwithstanding  the  restrictions in subparagraphs a, b, and c of
this paragraph, the following openings may be authorized:
  1. A space classified in occupancy group C, E, F-3 or, F-4 within fire
separations having a minimum fire-resistance rating of one hour, with an
area  not  exceeding  twenty-five  hundred  square  feet,  may  have  an
unlimited length of show window under the following conditions:
  (a) The maximum depth of show window shall be three feet.
  (b)  Automatic sprinklers complying with the construction requirements
of subchapter seventeen of this chapter, shall be provided in  the  show
window display area.
  (c)  The  show  window  display  area shall be protected on all sides,
except for  the  glazed  window,  by  construction  having  a  two  hour
fire-resistance  rating  with  access  provided  by means of a fireproof
self-closing door having a three-quarter hour fire protection rating.
  (d) The show window shall be glazed by one-quarter inch polished plate
glass or equivalent.
  (e) Glass or other noncombustible doors may be used for entrance to or
egress  from  the  space  within  fire  separations  when  installed  in
combination  with  automatic  fire  doors having a one and one-half hour
fire protection rating. Such automatic fire doors shall  be  located  on
the  room  side  and shall be held open by approved door-holding devices
actuated to release automatically upon the activation of smoke detecting
devices, whether of the photoelectric cell or other  approved  type.  In
addition,  automatic  sprinkler  heads,  complying with the construction
requirements of subchapter seventeen of this chapter, shall be  provided
over the door openings on the room side.
  2. A space classified in occupancy group C, E, F-3, or F-4 within fire
separations having a minimum fire-resistance rating of one hour, with an
area  not exceeding three thousand square feet, may have a maximum total
length of unprotected openings upon a corridor or  exit  passageway  not
exceeding  fifty  percent  of  the space frontage along such corridor or
exit passageway under the following conditions:
  (a) The entire space  shall  be  provided  with  automatic  sprinklers
complying  with the construction requirements of subchapter seventeen of
this chapter.
  (b) The show window shall be glazed by one-quarter inch polished plate
glass or equivalent.
  (c) All corridor or  exit  passageway  doors  shall  be  self-closing,
noncombustible, and smokeproof.
  3.  Show  windows  or  other openings of unlimited lengths and heights
shall  be  permitted  on  any  corridor  or  exit   passageway   without
requirements for fire-resistance doors under the following conditions:

  (a)   The   entire   floor  area,  including  the  corridors  or  exit
passageways, shall be provided with automatic sprinklers complying  with
the construction requirements of subchapter seventeen of this chapter.
  (b)  The  occupancy  of  all  spaces  on the floor shall be limited to
occupancy groups C, E, F-3 and F-4.
  (c) The widths of  the  corridors  or  passageways  shall  exceed  the
requirements  of table 6-1 or subdivision (b) of this section, whichever
is applicable, by at least fifty percent.
  (d) All doors opening on the corridors or exit  passageways  shall  be
smokeproof, noncombustible self-closing doors.
  (e) Show windows or other openings shall be glazed by one-quarter inch
polished plate glass or equivalent.
  (f)  Each  corridor  or exit passageway shall be provided with a fresh
air intake, a positive smoke exhaust system and smoke  detectors  which,
when activated, shall permit circulation only of fresh air.
  (4) OCCUPANCY. Street floor lobbies serving as exit passageways may be
occupied  by newsstands, candy and tobacco stands, information booths or
similar occupancies,  if  such  stands  or  booths  are  constructed  of
noncombustible   materials,  or  of  materials  which  comply  with  the
requirements of section 27-348 of article five  of  subchapter  five  of
this  chapter  for  interior  finish for exit passageways, provided that
such stands or booths:
  a. do not occupy more than one hundred square feet or five percent  of
the net floor area of the lobby, whichever is greater; and
  b.  do  not reduce the required clear width of the lobby at any point;
and
  c. if constructed of combustible materials are protected  by  no  less
than  two  automatic sprinkler heads. Water for such sprinkler heads may
be supplied from the domestic water supply system.

Section 27-371

Section 27-371

  §  27-371  Doors. Exit doors and doors providing access to exits shall
comply with the following:
  (a) Exit  doors.  Doors  for  required  exits  shall  be  self-closing
swinging  doors  with  a  one  and one-half hour fire protection rating,
except in occupancy group J-3 buildings and except that:
  (1) Exterior street floor exit doors having an exterior separation  of
more than fifteen feet need not have a fire-protection rating.
  (2)  Doors  into  stairs  and  exit  passageways shall have at least a
three-quarter hour fire protection rating.
  (b) Corridor doors. Doors that provide access  to  interior  corridors
required to have a one hour fire-resistance rating shall be self-closing
swinging  fire  doors  with a three-quarter hour fire-protection rating,
except that in buildings classified in occupancy group G,  in  which  an
acceptable  interior fire alarm system is installed and in which regular
supervised fire drills are held, the doors to rooms  or  spaces  devoted
exclusively  to  nonhazardous  uses  in  occupancy  group  G need not be
fire-rated,  provided  they   are   swinging,   self-closing   one   and
three-quarter  inch  solid  core  wood, and have a maximum area of seven
hundred twenty square inches  of  one-quarter  inch  thick  wired  glass
vision  panels.  Other  corridor  doors  except  those  provided  for in
subdivision  (d)  of  section  27-369  of   this   article,   shall   be
self-closing,  swinging,  noncombustible  or  one and three-quarter inch
solid core wood doors, except that in buildings classified in  occupancy
group  H-2 the doors need not be self-closing. Noncombustible mail slots
having an area not exceeding forty square  inches  may  be  provided  in
corridor  doors  when the opening is protected by a closure activated by
gravity or a spring device so as to keep it  closed  when  not  in  use.
Noncombustible  louvers  may be installed in corridor doors opening into
toilets, service sink closets, and electric closets. Notwithstanding the
foregoing restrictions in this  subdivision,  doors  not  prohibited  by
subdivision (d) of this section may open from spaces into corridors when
in  compliance  with  all  of  the  provisions  of  paragraph  three  of
subdivision (h) of section 27-370 of this article.
  (c) Smoke stop doors. Smoke stop doors shall be self-closing, swinging
doors of metal, metal covered, or one and three-quarter inch solid  core
wood  with  clear wire glass panels having a minimum area of six hundred
square inches per door and a maximum area of twelve  hundred  ninety-six
square  inches  per  door, except that in buildings not over two stories
high, smoke stop doors may be of one and three-eighths inch  solid  core
wood  with  clear  wire  glass panels, unless the doors are also used as
horizontal exits in which case they shall comply with the provisions  of
subdivision  (b)  of  section 27-373 of this article. In addition, smoke
stop doors may be constructed of tempered glazing or the equivalent  and
be   protected   by  sprinkler  heads  constructed  in  accordance  with
subchapter seventeen of this chapter and installed a maximum of six feet
(6'-0") on centers on each side of the opening. Smoke stop doors may  be
double-acting  but  shall  close  the  opening completely with only such
clearance as is reasonably necessary for proper  operation.  Smoke  stop
doors  shall normally be in the closed position, except that they may be
left open if they are arranged to close  automatically  by  an  approved
device  which  is  actuated by an interior fire alarm system meeting the
requirements of subchapter seventeen  of  this  chapter  or  upon  smoke
detection.  Tempered  glass  smoke  stop  doors  shall  be  marked where
required in accordance with the rules of  the  board  of  standards  and
appeals.
  (d)  Prohibited doors. Vertically sliding doors, rolling shutters, and
folding doors shall not be used as exit  doors  or  as  corridor  doors,
except  that  overhead  garage  doors  may serve as exits from buildings

classified in occupancy group J-3, and except that  sliding  or  rolling
doors  or  gates may be used in F-2 places of assembly provided they are
kept open when the place of assembly is occupied. Revolving doors may be
used  only  to the extent permitted by subdivision (m) of section 27-371
of this article. Automatic horizontally  sliding  fire  doors  shall  be
permitted  only in horizontal exits in fire divisions required to have a
four hour fire-resistance rating as specified in table 5-3.
  (e) Door opening widths.  The  capacity  of  exit  and  corridor  door
openings  shall  be  as listed in table 6-1. Door jambs or stops and the
door thickness when open shall not reduce the  required  width  by  more
than three inches for each twenty-two inches of width. The maximum width
of  any  swinging  door  leaf  shall  be forty-eight inches. The minimum
nominal width of corridor and exit door  openings  shall  be  thirty-six
inches, except that where a door opening is divided by mullions into two
or  more  door  openings, the minimum nominal width of each such opening
shall be thirty-two inches. The minimum  nominal  width  of  other  door
openings shall be as follows:
  (1)  Door  openings  to all habitable and occupiable rooms--thirty-two
inches.
  (2) Door swinging in pairs (no mullion), opening--forty-eight inches.
  (3) Door openings to rooms used by bedridden patients and  all  single
door  openings  used by patients in buildings classified occupancy group
H-2--forty-four inches.
  (4) Door openings to toilet rooms in buildings to which the public has
free access shall be thirty-two inches.
  (5) Door openings giving access to at least one toilet,  lavatory  and
bathtub  or  shower  in  each  dwelling  unit,  in  buildings  or spaces
classified in occupancy group J-1 or J-2, when  such  dwelling  unit  is
accessible to individuals in wheel chairs--thirty-two inches.
  (6)  Door  openings  giving  access  to  all  toilets,  lavatories and
bathtubs or showers serving single room occupancies which are accessible
to individuals in wheelchairs--thirty-two inches.
  (7) Door  openings  for  people  having  physical  disabilities  shall
additionally comply with the requirements of reference standard RS 4-6.
  (f) Door heights. The minimum nominal door opening height for exit and
corridor doors shall be six feet eight inches. Door jambs, stops, sills,
and closers shall not reduce the clear opening to less than six feet six
inches.
  (g)  Door  swing.  Exit  doors,  corridor  doors  from rooms or spaces
classified in high hazard  occupancy  group  A,  or  from  factories  as
defined in the labor law, and corridor doors from rooms required to have
more  than  one  door  under the provisions of section 27-365 of article
four of this subchapter, shall swing in the direction  of  exit  travel,
except:
  (1)  Doors  from  rooms  of  instruction  in  buildings  classified in
occupancy group G, having an occupant load  of  less  than  seventy-five
persons.
  (2)  Exterior  street  floor  exit  doors  from  lobbies  in buildings
classified in occupancy groups J-2 and J-3.
  (3) Exterior street floor exit doors from spaces in occupancy group  C
or  E  not  exceeding  two thousand square feet in area, and occupied by
less than fifty persons, where the maximum travel  distance  to  a  door
does not exceed fifty feet.
  (h)  Floor  level.  The  floor  on both sides of all exit and corridor
doors shall be essentially  level  and  at  the  same  elevation  for  a
distance, perpendicular to the door opening, at least equal to the width
of  the  door  leaf,  except that where doors lead out of a building the

floor level inside may be seven and  one-half  inches  higher  than  the
level outside.
  (i) Closed doors. Exit doors and corridor doors shall normally be kept
in  the  closed  position,  except  that  corridor  doors  in  buildings
classified in occupancy group H-2 shall be exempt from this requirement.
  (j) Door and window hardware. Doors and windows shall be equipped with
hardware as follows:
  (1) Fire protection requirements.
  a. Exit doors and corridors shall be readily  openable  at  all  times
from  the  side  from which egress is to be made and shall not require a
key to operate from that side, except that:
  1. Locks may be used in penal and mental institutions and areas, where
required for security.
  2. Locks may be used in  banks,  museums,  jewelry  stores  and  other
places  where  extra safeguards are required, subject to the approval of
the commissioner, and provided the locks are  equipped  with  electrical
release devices for remote control in case of emergency.
  3. Stairways leading from the top floor to a roof may be provided with
locked  wire  mesh  gates  openable  by  key  in buildings classified in
occupancy group G. The use of a hook  and  eye  closing  device  on  the
inside of all doors to roofs shall be permitted.
  b.  Doors  opening  into interior stair enclosures shall not be locked
from either side with the following exceptions:
  1. Doors may be located to prevent access to the stair at  the  street
floor.
  2. In buildings classified in occupancy group E, less than one hundred
feet  in height, the doors may be locked on the stair side on each floor
above the street floor.
  3. In buildings classified in occupancy group E, one hundred  feet  or
more  in  height, and existing office buildings one hundred feet or more
in height, the doors may be locked on the stair side  above  the  street
floor  except  that at intervals of four stories or less, doors shall be
openable from the stair side without the use of a key to permit  reentry
at  such  floors.  In  addition,  the  door on every floor where a keyed
switch is required by the provisions  of  subchapter  eighteen  of  this
chapter  shall  be openable from the stair side without the use of a key
to permit reentry at such floors.
  4. When a locked door is provided with an automatic fail  safe  system
for  opening  such  door in the event of the activation of any automatic
fire detecting device or when any elevator in readiness as  provided  in
section 27-989 of subchapter eighteen of this chapter is activated, such
door  shall  be deemed as openable from the stair side. The installation
of such automatic fail safe system shall comply with the requirements of
reference standards RS17-3A and RS17-3B, whichever is applicable.  Stair
reentry  signs  required  under  section  27-394 of article nine of this
subchapter shall specify that  reentry  is  provided  only  during  fire
emergencies.
  c.  Latch bolts shall be provided on all exit doors and corridor doors
to hold them in a closed position  against  the  pressure  of  expanding
gases  except  that  this  requirement shall not apply to doors in stair
enclosures in buildings classified in occupancy group G.
  (2) Security requirements. The following provisions shall apply to all
buildings erected or altered  after  December  sixth,  nineteen  hundred
sixty-eight  that  may be classified in residential occupancy group J-2.
Existing buildings in such group shall comply with the  requirements  of
article eleven of subchapter two.
  a.  Building  entrance  doors  and  other exterior exit doors shall be
equipped with heavy duty lock sets with auxiliary latch bolts to prevent

the latch from being manipulated by means other than a key.  Latch  sets
shall  have  stopwork  in the inside cylinder controlled by a master key
only. Outside cylinders of main entrance door locks shall be operated by
the  tenants'  key,  which  shall not be keyed to also open the tenant's
apartment door. A light or lights shall  be  provided  at  or  near  the
outside of the front entranceway of the building providing not less than
five  foot  candles  intensity  measured at the floor level for the full
width of the entranceway.
  b. Doors to dwelling units shall be equipped with a heavy  duty  latch
set  and a heavy duty dead bolt operable by a key from the outside and a
thumb-turn from the inside. Those doors shall also be  equipped  with  a
chain  guard  so as to permit partial opening of the door. Dwelling unit
entrance doors shall also be equipped with a viewing device  located  so
as  to  enable  a  person  on  the inside of the entrance door to view a
person immediately outside.
  c. All openable windows shall be equipped with sash locks designed  to
be  openable from the inside only. Grilles lockable from the inside only
may be placed on the inside or outside of windows  that  are  accessible
from grade but that do not serve to provide access to exits.
  d.  Buildings  classified  in  occupancy group J-2 containing eight or
more dwelling units shall be provided with an intercommunication  system
located  at  the  door giving access to the main entrance hall or lobby,
consisting of a device or devices for voice  communication  between  the
occupant  of  each  dwelling  unit and a person outside said door to the
main entrance hall or lobby and permitting such dwelling  unit  occupant
to release the locking mechanism of said door from the dwelling unit.
  (k) Panic hardware.
  (1)  Exit  doors shall be equipped with fire exit bolts when providing
an exit from:
  a. Buildings classified  in  occupancy  group  G,  except  exit  doors
opening directly outdoors at grade from rooms having an occupant load of
less than seventy-five persons,
  b. F-1 places of assembly,
  c.  F-2,  F-3  and  F-4  places  of  assembly  having an occupant load
exceeding three hundred persons, except places of assembly having  doors
that are not equipped with locks and are openable at all times.
  (2)  Fire  exit  bolts shall be of an approved type, and shall release
when a pressure exceeding fifteen pounds is  applied  to  the  releasing
device  in the direction of exit travel. The bars or panels shall extend
at least two-thirds of the width of the door  and  shall  be  placed  at
least  thirty  inches,  but  not  more  than forty-four inches above the
floor.
  (l) Power operated doors.  Power  operated  doors  or  power  assisted
manually  operated doors, may be used as exit or corridor doors provided
they remain closed in case  of  power  failure  but  shall  be  manually
operable.  No  power  operated door shall be credited as a required exit
unless it swings in the direction of exit travel.
  (m) Revolving doors. Revolving doors shall not be  used  as  exits  in
buildings  classified  in occupancy group F-1 or F-2, G, or H; nor shall
revolving doors be used in any occupancy  as  interior  doors  providing
access  to  exits,  at  the  foot  of stairs, or at the head of basement
stairs. Where revolving doors are used as exits, they shall comply  with
the following:
  (1)  They  may  provide  not more than one unit or exit width for each
revolving door and not more than fifty per cent  of  the  required  exit
capacity  at any location, provided that the revolving doors are located
adjacent to, or within twenty feet, of swinging doors that  provide  the
remaining required exit capacity at that location.

  (2)  They  shall be collapsible, and designed and constructed so that:
a.  Each wing is independently supported by a hanger  with  a  corrosion
resistant safety release which, when pressure of between sixty to eighty
pounds  is  exerted simultaneously on the wings on opposite sides of the
door pivot, the door wings will fold back on themselves in the direction
of egress.
  b. Each wing is provided with at least one push bar and glazed with at
least 7/32 in. plate or tempered glass.
  c.  The  inside  diameter  of  the  enclosure is at least six feet six
inches.
  d. The freely operable maximum rate of revolving speed  is  controlled
so that it is not greater than fifteen rpm.
  e.  The upper surface of the floor finish within the door enclosure is
flush with the adjacent floor area, and permanently secured in place.
  (3) The owner shall be responsible at all times for the operation  and
maintenance  of  revolving  doors, and shall have the doors inspected at
intervals not to exceed six months. All parts of  the  doors,  including
the  safety releases and speed control mechanism, shall be maintained in
good working order. Inspection reports shall be made in writing and kept
on file at the premises for at least two years.
  (n) Turnstiles. No turnstile or  other  device  designed  to  restrict
travel  shall be placed so as to obstruct any required exit, except that
approved turnstiles that turn freely in the direction of exit travel may
be used in any occupancy where revolving doors are permitted. Turnstiles
shall be not more than thirty-six inches nor  less  than  thirty  inches
high  and  shall be of such design as to provide twenty-two inches clear
width as the turnstile rotates. Each turnstile may be  credited  with  a
capacity  of one unit of exit width. Not more than fifty per cent of the
required exit capacity may be provided by turnstiles  at  any  location.
The  balance of the required exit capacity shall be provided by swinging
doors located within twenty feet  of  the  turnstiles.  Turnstiles  over
thirty-six  inches  high  shall meet the applicable requirements of this
code for revolving doors.

Section 27-372

Section 27-372

  §  27-372  Area  of  refuge.  Areas  of  refuge  shall comply with the
following:
  (a) Separation. Areas of refuge shall be separated from the area which
they serve by construction having at least a  two  hour  fire-resistance
rating.
  (b)  Floor  area.  Areas of refuge shall provide clear public space or
space occupied by the same tenant or owner, adequate in size to hold the
occupant load it receives from the floor area it serves as  computed  by
the  provision  of section 27-367 of article four of this subchapter, in
addition to its own occupant load, allowing at least three  square  feet
per  person,  except that in buildings classified in occupancy group H-2
for patient areas only, the allowance shall be at  least  thirty  square
feet per person.
  (c)  Required  exits.  Areas of refuge shall be provided with at least
one vertical exit. When an area of refuge is  located  higher  than  the
eleventh floor of a building, the vertical exit shall be supplemented by
at least one elevator.
  (d)  Locking.  Doors providing access to areas of refuge shall be kept
unlocked at all times when any floor area served by the area  of  refuge
is occupied.

Section 27-373

Section 27-373

  §  27-373 Horizontal exits. A horizontal exit to an area of refuge may
consist of doors through walls or partitions having at least a two  hour
fire-resistance  rating;  of  a  balcony  or  exterior vestibule leading
around the end of a fire division to another fire area or  building;  or
it  may  be  a  bridge or tunnel between two buildings. Horizontal exits
shall comply with the following:
  (a) Capacity. The capacity of horizontal exits shall be as  listed  in
table  6-1.  Only  the widths of doors swinging in the direction of exit
travel to the area of refuge shall be counted.
  (b) Door requirements. Doors shall  be  swinging,  self-closing  doors
having  a  fire protection rating of one and one-half hours, except that
door in fire divisions having a three hour or four hour  fire-resistance
rating  shall  have  opening  protective  as required by table 5-3. Each
swinging door shall swing in the direction  of  exit  travel,  and  when
travel is in both directions, as when two areas of refuge serve as areas
of  refuge for each other, at least two door openings shall be provided,
the doors of which shall swing in opposite directions.  Signs  shall  be
placed  over each door on the side from which egress is made, indicating
the exit door.
  (c) Balconies, bridges and tunnels. When serving as horizontal  exits,
balconies, bridges, and tunnels shall comply with the following:
  (1)  Their  width  shall  be  equal to at least the width of the doors
opening on them, but in no case less than three feet eight inches.
  (2) They shall be  enclosed  at  each  end  by  doors  complying  with
subdivision (b) of this section.
  (3) The floor level at doors shall be the same as that of the building
except  that  the floor level of open balconies or open bridges shall be
approximately seven and one-half inches lower.
  (4) Where there is a difference in level between the areas  connected,
the floors of the horizontal exit shall be ramped not more than one inch
in ten inches.
  (5) Exterior wall openings within thirty feet horizontally of any open
bridge  or balcony or below any open bridge or balcony shall be provided
with opening protectives having a  three-quarter  hour  fire  protection
rating.
  (6)  Balconies  shall  not  face  or open on yards or courts less than
twelve feet wide, and shall be  constructed  as  required  for  exterior
corridors.
  (7) Exterior bridges shall be constructed of noncombustible materials.
Interior  bridges or tunnels shall be constructed of materials providing
a two hour fire-resistance rating.

Section 27-374

Section 27-374

  § 27-374 Supplemental vertical exits. Enclosed interior stairs, ramps,
or escalators may provide access to an area of refuge located on a floor
nearer to the street floor, when complying with the following:
  (a)  Limitation.  They shall be supplemental vertical exits serving no
other purpose than to connect a floor area with an area of refuge.
  (b) Capacity. The capacity of supplemental vertical exits shall be  as
listed for stairs in table 6-1.
  (c) Construction. Supplemental vertical exits shall comply with all of
the construction requirements for interior stairs as provided in section
27-375 of this article.
  (d) Openings. There shall be no openings in supplemental vertical exit
enclosures  other than the exit doors and doors leading into the area of
refuge.
  (e) Identification. Every supplemental vertical exit shall have a sign
at the entrance designating its destination reading, "EXIT  TO  AREA  OF
REFUGE ON......FLOOR."

Section 27-375

Section 27-375

  §  27-375  Interior  stairs.  Interior  stairs  shall  comply with the
following requirements:
  (a) Capacity. The capacity of interior stairs shall be  as  listed  in
table 6-1.
  (b)  Width.  The  width  of  interior  stairs shall be the clear width
between walls, grilles, guards, or  newel  posts.  Stair  stringers  may
project into the required width not more than two inches on each side of
the stair.  No interior stair shall be reduced in width in the direction
of exit travel. Interior stairs shall be at least forty-four inches wide
except as follows:
  (1)  Interior  stairs may be not less than thirty-six inches wide when
serving not more than  thirty  occupants  per  stair  on  any  floor  in
buildings  classified  in  occupancy  groups J-1 and J-2 or when serving
buildings classified in occupancy group J-3 and exceeding  four  stories
in  height,  or  when serving not more than sixty occupants per stair on
any floor in buildings classified in occupancy groups E, B, and D.
  (2) Interior stairs may be not  less  than  thirty  inches  wide  when
serving  mezzanines  having  an  occupant load not exceeding twenty-five
persons or when located in buildings classified in occupancy  group  J-3
not  more  than  three  stories in height. Interior stairs in four story
buildings classified in occupancy  group  J-3  shall  be  a  minimum  of
thirty-three inches in width.
  (c)  Headroom. The clear headroom shall be at least seven feet, except
that in buildings classified  in  occupancy  groups  J-2  and  J-3,  the
minimum  clear  headroom  may  be  six  feet eight inches. Headroom in a
flight of stairs shall  be  measured  vertically  between  two  parallel
inclined  planes,  one of which contains the line of the nosing or upper
front edge of each tread and extends to its intersection with a  landing
and  the  other  of  which is through any point directly above the first
plane that limits the headroom of the stair.
  (d) Landings and platforms. Landings and platforms shall  be  provided
at  the  head  and  foot of each flight of stairs, except at the head of
basement stairs in one- and two-family dwellings, and shall comply  with
the following:
  (1)  The  minimum width of landings and platforms perpendicular to the
direction of travel shall be equal to at least the width of  the  stairs
except  that  on  a  straight-run  stair, the distance between risers of
upper and lower flights at intermediate landings or platforms  need  not
be more than forty-four inches.
  (2)  The  maximum  vertical  rise of a single flight of stairs between
floors, between landings or platforms, or between a floor and a  landing
or  platform  shall  not  exceed  eight  feet in buildings classified in
occupancy groups F and H, and twelve feet in all other occupancy groups.
No flight of stairs shall have less than two risers.
  (3) Landings and platforms  shall  be  enclosed  on  sides  by  walls,
grilles or guards at least three feet high.
  (e)  Risers  and treads. Risers and treads shall comply with table 6-4
and with the following:
  (1) The sum of two risers plus one tread exclusive of nosing shall  be
not less than twenty-four nor more than twenty-five and one-half inches.
  (2)  Riser  height  and tread width shall be constant in any flight of
stairs from story to story.
  (3) Winders shall not be permitted in required exit stairs  except  in
one-  and  two-family dwellings and except as permitted in subdivision l
of this section. The width  of  winder  treads  when  measured  eighteen
inches  from  the  narrower  end shall be at least equal to the width of
treads above or below the winding section.

  (4) Curving or skewed stairs may be used as exits when the  tread  and
riser  relationship  is  in accordance with table 6-4 when measured at a
point eighteen inches in from the narrow end of the tread; and no  tread
shall  be  more  than three inches narrower or three inches wider at any
point than the width established eighteen inches in from the narrow end.
  (f)  Guards and handrails. Stairs shall have walls, grilles, or guards
at the sides and shall have handrails on both sides, except that  stairs
less  than  forty-four inches wide may have a handrail on one side only.
Handrails shall provide a finger clearance of one and  one-half  inches,
and  shall  project  not  more  than  three and one-half inches into the
required stair width.
  (1) Stairs more than eighty-eight inches wide shall have  intermediate
handrails  dividing  the  stairway into widths that maintain the nominal
multiples of twenty-two inches, but the widths shall not be greater than
eighty-eight inches nor less than forty-four inches.
  (2) The height of handrails above the nosing of treads  shall  be  not
more than thirty-four inches nor less than thirty inches.
  (3)  Handrails  shall  be returned to walls and posts when terminated,
except in one- and two-family dwellings.
  (4) Handrails shall be designed to support loads  in  compliance  with
the requirements of subchapter nine of this chapter.
  (5)   Handrails   in  all  stairs  shall  be  of  materials  having  a
flame-spread rating not exceeding one hundred fifty.
  (g) Stair doors. Doors providing access to stairs  shall  comply  with
the requirements of subdivision (a) of section 27-342 of article five of
subchapter five of this chapter and subdivision (e) of section 27-371 of
this  article.  The swing of stair doors shall not block stairs or stair
landings, nor shall any door at  any  point  of  its  swing  reduce  the
effective  width  of  the  landing  or  stair  to less than seventy-five
percent of the required width of the landing or stair, or to  less  than
the  width  of the door opening on them. The width of doors from a stair
shall not be less than the number of units of exit  width  required  for
the  capacity  of the stair, but in no case shall the door width be less
than required by subdivision (e) of section 27-371 of this article.
  (h)  Stair  construction.   Risers,   treads,   stringers,   landings,
platforms,  and  guards,  exclusive  of  handrails,  shall  be  built of
noncombustible materials except that interior  stairs  in  buildings  of
construction group II may be built of combustible materials in buildings
classified  in occupancy group B-2, C, D or E when the buildings are two
stories in height or less, and  in  buildings  classified  in  occupancy
group  J-2  or J-3 when the buildings are not more than three stories in
height, and in the case of J-2 occupancy group,  when  occupied  by  not
more  than  three families. Interior stairs shall have solid treads. All
risers shall be closed except as otherwise provided in  subdivision  (i)
of  this  section.    When  of  combustible  construction, the soffit of
interior stairs shall be fire protected by  material  having  a  minimum
fire  resistive  rating  of  one hour or five-eighths inches gypsum wall
board or equivalent, or the space  beneath  shall  be  enclosed  without
openings  by  material  having  a one hour fire resistance rating unless
permitted to have open risers by subdivision (i) of this section.  Where
two separate interior stairs are contained within the same enclosure (so
called  "scissor  stairs"), each stair shall be separated from the other
by noncombustible construction having a fire resistance rating equal  to
that required for the stair enclosure.
  Stairs, platforms, and landings shall be designed to support all loads
in  compliance with the requirements of subchapter nine of this chapter.
Treads  and  landings  shall  be  built  of  or  surfaced  with  nonskid
materials.

  (i) Stair enclosures.
  (1) Interior stairs shall be enclosed with construction complying with
the requirements of table 3-4 except that:
  (a)  In  buildings  three  stories  or  less in height excluding those
classified in occupancy group J-1 or J-2 combustible construction  group
II,  the  enclosing  construction  may  have  a  one hour fire resistant
rating.
  (b) Stairs in buildings or spaces classified in  occupancy  group  J-3
and  not  more than three stories in height, need not be enclosed except
as otherwise required in subdivision (a) of section  27-341  of  article
five  of subchapter five of this chapter. Stairs may have open risers in
one family dwellings and group homes.
  (c) Unenclosed stairs in buildings classified  in  assembly  occupancy
group  F  may  be  permitted  as  provided  in  subchapter eight of this
chapter.
  (d) Stairs from floors or mezzanines may be unenclosed, with  open  or
closed risers.
  (e)   In   buildings   classified  in  occupancy  group  J-2  occupied
exclusively by not more than one family on each story without  boarders,
roomers  or  lodgers  and  not  more  than  three stories in height, the
enclosing construction may have a one hour fire-resistance rating  which
may  be  constructed  of  combustible  material  provided that the stair
enclosure is protected with an automatic sprinkler system complying with
the construction provisions of subchapter seventeen of this chapter.
  (f) In buildings classified in occupancy group J-1  or  J-2  not  more
than  two  stories  in  height of combustible construction group II, the
enclosing construction may have a one hour fire-resistance rating  which
may  be  constructed  of  combustible  material; however, where only one
vertical exit  is  provided  the  stair  enclosure  shall  be  protected
throughout  with an automatic sprinkler system constructed in accordance
with the provisions of subchapter seventeen of this chapter.
  (g) Except as provided in subparagraphs  (a),  (e)  and  (f)  of  this
paragraph,  in all buildings or spaces classified in occupancy group J-1
or J-2, the enclosing construction shall be of masonry  or  an  approved
equivalent material having at least a two hour fire-resistant rating.
  (2)  Access  stairs  connecting not more than two stories which do not
serve as a required exit may be  constructed  without  an  enclosure  in
buildings  classified  in  other  than  occupancy group H-2. Such stairs
shall be additional to and shall not obstruct or interfere with required
exit facilities. When the first  story  below  grade  is  served  by  an
interior, unenclosed access stair, it shall be sprinklered in accordance
with  the  construction  provisions  of  subchapter  seventeen  of  this
chapter.
  (3) The interior finish of  interior  stair  enclosures  shall  be  in
accordance with the requirements of table 5-4.
  (4)   Stair   enclosures  shall  be  vented  in  accordance  with  the
requirements for shafts in subdivision (d) of section 27-344 of  article
five of subchapter five of this chapter except that stair enclosures for
buildings  or  spaces  classified in occupancy group J-1 or J-2 shall be
vented as follows:
  a. In occupancy group J-2 buildings three stories in height  and  with
not  more than one dwelling unit per story or two stories in height with
not more than two dwelling units per story, shall  be  provided  with  a
skylight at least nine square feet in area, glazed with plain glass with
a  wire  screen  over  and  under  and  provided  with  fixed or movable
ventilators having a minimum open area of forty square inches.
  b. In occupancy group J-1 or J-2 buildings two stories in height  with
more than two dwelling units per story shall be provided with a skylight

of  at least twenty square feet in area, glazed with plain glass, with a
wire  screen  over  and  under  and  provided  with  fixed  or   movable
ventilators having a minimum open area of forty square inches.
  c.  In  occupancy  group J-1 buildings exceeding two stories in height
and in occupancy group J-2 buildings three stories in height  with  more
than  one  dwelling  unit per story or exceeding three stories in height
shall be provided with a skylight at least twenty square feet  in  area,
glazed  with  plain glass with a wire screen over and under and provided
with fixed or movable ventilators having a  minimum  open  area  of  one
hundred   forty-four   square  inches.  In  lieu  of  the  skylight  and
ventilators a window of equal area may be provided  with  fixed  louvres
having  a  minimum  open  area  of  one hundred forty-four square inches
installed in or immediately adjacent to the window.
  (5) When dwelling  units  are  located  over  a  space  classified  in
occupancy  group C or E on the street floor, they shall be provided with
a separate enclosed interior stair, or with an exterior stair.
  (6) Impact resistance. Stair  enclosures  serving  occupancy  group  E
spaces  (office  spaces)  in high rise buildings constructed pursuant to
applications filed on or after July 1, 2006 shall comply with  rules  to
be   promulgated   by   the  commissioner  establishing  minimum  impact
resistance standards. Such rules shall permit compliance with assemblies
comprising approved reinforced construction  boards  affixed  onto  stud
framing.  The  commissioner  shall  promulgate  such  rules on or before
January 1, 2006.
  (j) Openings and obstructions to stair enclosures. No  piping  of  any
kind,  with  the exception of piping required or permitted in subchapter
seventeen of this code, shall be permitted within a stair enclosure.  No
openings of any kind, other than windows, fire department access panels,
exit doors and openings specifically authorized in reference standard RS
5-18  shall  be  permitted  within  a stair enclosure. Pipes required or
permitted by such  subchapter  seventeen  and  protected  in  accordance
therewith  which  do not reduce the required clearances of the enclosure
may be permitted. Ducts protected in accordance with the requirements of
subchapter thirteen of this chapter, which do not  reduce  the  required
clearances of the enclosure, may be permitted. In addition, in buildings
in  occupancy  group  J-2, which are three stories or less in height and
occupied by not more than two families on each story,  a  door  from  an
apartment  may  open  directly into a stair, and the door may swing into
the apartment.
  (k) Roof access. (1) Except as otherwise provided  for  in  paragraphs
two  and three of this subdivision, in buildings or in building sections
more than three stories or forty feet high with roofs having a slope  of
less  than  twenty  degrees,  access to the roof shall be provided by at
least one interior stair, except that access to setback roof  areas  may
be  through  a  door  or  window  opening  to  the roof. Interior stairs
extending to roofs shall be  enclosed  in  bulkheads  of  fire-resistant
construction  meeting  the  requirements  of  subchapter  five  of  this
chapter.
  (2) In buildings or in building sections classified in occupancy group
J-1 or J-2 more than two stories in height, except as otherwise provided
for in paragraph three of this subdivision, with roofs having a slope of
fifteen degrees or less all interior stairs, except those terminating at
a level of a setback roof,  shall  extend  to  the  roof  and  shall  be
enclosed   in  bulkheads  of  fire-resistive  construction  meeting  the
requirements of subchapter five of this chapter. Stairs  terminating  at
the  level  of  a setback shall provide access to the setback roof areas
through a door except where the setback is less than four feet in width,

measured from the inside of the parapet wall, and less than ten feet  in
length.
  (3) In buildings or in building sections classified in occupancy group
J-1  or  J-2  two  stories  in  height  and in occupancy group J-2 three
stories in height with not more than one dwelling unit  per  story  with
roofs  having  a  slope  of  fifteen degrees or less, access to the roof
shall be provided through a scuttle at least twenty-one inches in  width
and  twenty-eight inches in length and shall comply with subdivision (c)
of section 27-338 of article four of subchapter five  of  this  chapter.
Scuttles  shall be located within each stair enclosure with a stationary
iron ladder leading thereto.
  (l) Spiral stairs. Spiral stairs may serve as  access  stairs  between
two  floors or levels in accordance with the provisions of paragraph two
of subdivision (i) of  this  section.  Such  stairs  may  not  serve  as
required  exits,  except  that  unenclosed  spiral  stairs when built of
noncombustible materials and having a tread length of  at  least  thirty
inches  may  serve  as  exits  from  mezzanines  or  balconies having an
occupant load not exceeding twenty-five persons.

         Table 6-4 Maximum Riser Height and Minimum Tread Width
========================================================================
  Occupancy Group Classification       Maximum Riser    Minimum Tread{1}
             of Building                Height (in.)      Width (in.)
------------------------------------------------------------------------
Residential J-3 (with closed risers)..      8 1/4    9 plus 1 1/4 nosing
Residential J-3 (with open risers)....      8 1/4    9 plus 1/2 nosing
Residential J-2 (with only three......
dwelling units).......................      8 1/4    9 plus 1 1/4 nosing
Assembly F............................      7 1/2    9 1/2 plus nosing
Institutional H-2.....................      7       10 plus nosing
All others{2}.........................      7 3/4    9 1/2 plus nosing
========================================================================

Notes:
  {1} Treads may be undercut a distance equal to the  nosing.  A  nosing
shall not be required when tread width is eleven inches or wider.
  {2}  The  proportions  and  dimensions  of  treads  and  risers may be
adjusted in buildings classified in occupancy group G to suit the age of
occupants, subject to the approval of the commissioner.

Section 27-376

Section 27-376

  § 27-376 Exterior stairs. Exterior stairs may be used as exits in lieu
of interior stairs provided they comply with all of the requirements for
interior stairs, except enclosure, and except as modified below:
  (a)  Capacity.  The  capacity of exterior stairs shall be as listed in
table 6-1.
  (b) Height limitation. No exterior  stair  shall  exceed  seventy-five
feet or six stories in height.
  (c)  Construction.  Exterior  stairs  shall be constructed entirely of
noncombustible  materials,  except  that  in  buildings  classified   in
occupancy  groups  other  than  G,  F,  or  H, of construction group II,
located outside the fire districts, exterior  stairs  may  be  built  of
combustible  materials when the buildings are two stories or thirty feet
in height or less and have an occupant load not exceeding forty  persons
per  floor  above the street below. Exterior stairs shall be roofed, and
shall be protected along their outer  sides  as  required  for  exterior
corridors  in subdivision (f) of section 27-369 of this article. Treads,
landings, and platforms shall be solid and unperforated. Risers  may  be
partially open to permit water and snow to drain.
  (d)  Opening  protective.  In  buildings four stories or fifty feet in
height or more, there  shall  be  no  openings  in  the  building  walls
adjoining  exterior  stairs  other  than  one-quarter  hour self-closing
swinging fire doors, and no openings nearer than ten feet to  the  stair
(measured  horizontally)  that  are not provided with three-quarter hour
opening protectives.
  (e) Location. No exterior stair shall be located nearer than ten  feet
to an interior lot line.
  (f) Discharge. Exterior stairs shall extend continuously to grade.

Section 27-376.1

Section 27-376.1

  §  27-376.1  Fire  tower.  Fire towers may be used as exits in lieu of
interior stairs provided they comply with all of  the  requirements  for
interior stairs, except as modified below.
  (a)  The  enclosing  walls  of  fire  towers shall be of incombustible
materials or assemblies having a fire-resistance rating of at least four
hours. Such walls shall be without openings, except for doors serving as
means of egress.
  (b) At each story served by a fire tower, access to the  stairways  of
such fire tower shall be provided through outside balconies or fireproof
vestibules.  Such  balconies  or vestibules shall be at least three feet
eight inches in width and shall have unpierced floors  of  incombustible
materials and shall be provided with substantial guard railings at least
four feet high, without any openings greater than five inches in width.
  (c)  Such  balconies  or vestibules of fire towers shall be level with
the floors of the structure and the platforms of the stairs connected by
such balconies. Such balconies or vestibules shall be separated from the
structure and the stairs by self-closing swinging doors with a  one  and
one-half  hour fire protection rating, capable of being opened from both
sides without the use of a key or other unlocking device.
  (d) Balconies or vestibules of fire towers shall open on a  street  or
yard,  or  on  a  court  open vertically to the sky for its full height,
having a minimum net area of one hundred five square feet and a  minimum
dimension  of  seven feet. The opening from the vestibule to the street,
yard or court shall have a minimum area of eighteen square  feet  and  a
minimum  dimension of two feet six inches. It shall be unlawful to leave
openings in the court walls surrounding an interior  fire  tower,  other
than  the  openings  from  the  vestibules,  within  fifteen feet of the
balcony, except that self-closing windows with a three-quarter hour fire
protection rating may be used if such windows are at least ten feet from
the balcony, provided that the area of the court is at least twelve feet
by twenty-four feet.
  (e) Fire towers shall terminate at grade level and shall exit directly
to the street independently of corridors serving other stairways, except
when the fire tower terminates in the ground floor corridor  outside  of
the inner vestibule and within ten feet of the building line.
  (f)  Fire  tower  stairs  shall  comply in all other respects with the
applicable requirements of section 27-375 of this code.

Section 27-377

Section 27-377

  §  27-377  Ramps.  Interior  or exterior ramps may be used as exits in
lieu of interior or  exterior  stairs  provided  they  comply  with  the
applicable  requirements  for  interior stairs in section 27-375 of this
article  or  exterior  stairs  in  section,  27-376  of   this   article
respectively, and with the following:
  (a) Capacity. The capacity of ramps shall be as listed in table 6-1.
  (b)  Maximum  grade. Ramps shall not have a slope steeper than 1 in 8,
except that in buildings classified in occupancy group H the slope shall
not exceed 1 in 12, and except as provided in subchapter eight  of  this
chapter for places of assembly.
  (c) Design.
  (1)  CHANGES  IN  DIRECTION.  Ramps shall be straight, with changes in
direction being made at level platforms or landings, except  that  ramps
having  a  slope  not  greater  than  one in twelve at any place, may be
curved.
  (2) LENGTH. The sloping portion of ramps shall be at least three  feet
but not more than thirty feet long between level platforms or landings.
  (3)  PLATFORMS.  Level  platforms or landings, at least as wide as the
ramp, shall be provided at the  bottom,  at  intermediate  levels  where
required, and at the top of all ramps. Level platforms shall be provided
on each side of door openings into or from ramps having a minimum length
in the direction of exit travel of three feet, and when a door swings on
the platform or landing a minimum length of five feet.
  (4)  DOORS.  Door  openings  into  or from ramps shall comply with the
requirements for stairs in subdivision (g) of  section  27-375  of  this
article. No door shall swing over the sloping portion of a ramp.
  (5)  GUARDS  AND  RAILINGS.  Guards and railings of ramps shall comply
with the applicable requirements of subdivision (f) of section 27-375 of
this article except that only ramps having a slope steeper than  one  in
twelve  need comply with the requirements for handrails and intermediate
handrails shall not be required.
  (6) SURFACE. Interior ramps exceeding a slope of one in  ten  and  all
exterior ramps shall be provided with nonslip surfaces.
  (7)  Ramps  for people having physical disabilities shall additionally
comply with the requirements of reference standard RS 4-6.

Section 27-378

Section 27-378

  §  27-378  Escalators.  Escalators  may  be  used  as exits in lieu of
interior stairs provided they comply with all  of  the  requirements  of
subchapter eighteen of this chapter and with the applicable requirements
for enclosed interior stairs, except as modified below:
  (a)  Capacity. The capacity of escalators as listed in table 6-1 shall
be based on the following:

                         MINIMUM WIDTH (IN.) AT:
========================================================================
                                                       Units of
         Step        Balustrade{1}    Enclosure{2}    Exit Width
------------------------------------------------------------------------
          24             32               52             1-1/2
          40             48               68             2
========================================================================

Notes:
  {1} Measured twenty-seven inches above front edge of tread.
  {2} Clear width above handrails.

  (b) Acceptable exits. Only escalators moving in the direction of  exit
travel  may  be  credited  as  exits,  except  that any escalator may be
credited when it is connected to an automatic fire detection system that
will cause it to stop simultaneously with the  detection  of  fire.  The
detection  system  shall  comply  with  the  construction  provisions of
subchapter seventeen of this chapter. Where an escalator  provides  exit
facilities  from  only  one floor of a building, the automatic detection
system shall be located on that floor.  Where  escalators  provide  exit
facilities  from  more  than  one  floor,  the detection system shall be
located on all floors so served,  and  shall  cause  escalators  on  all
floors of the section of the building that they serve to stop operating.
The  stopping  mechanism  shall  operate  to  bring  the  escalator to a
gradual, rather than an abrupt stop.
  (c) Escalators not used as exits. Escalators  that  do  not  serve  as
exits,  and  that  connect more than two stories of a building, shall be
completely  enclosed   with   noncombustible   construction   having   a
three-quarter  hour  fire-resistance  rating,  except  that in buildings
completely protected by an automatic sprinkler system complying with the
construction requirements of subchapter seventeen of this chapter,  such
escalators  may,  alternatively,  be  protected  by  one  of the methods
specified in subchapter eighteen of this chapter.

Section 27-379

Section 27-379

  §  27-379  Moving walkways. Pedestrian walkways consisting of conveyor
belts shall be considered as exit passageways if level, or as  ramps  if
inclined,  and  shall  be  acceptable  as  exits if they comply with the
applicable requirements for exit passageways  or  ramps,  and  with  the
following:
  (a)  Capacity.  The capacity shall be as listed under exit passageways
or ramps, as the case may be, in table 6-1.
  (b) Acceptable exits. Only walkways moving in the  direction  of  exit
travel  may  be credited as exits, except that any moving walkway may be
credited when it is connected to an automatic fire detection system that
will cause it to stop simultaneously with the detection of fire  on  the
floor   it   serves.   Such  detection  system  shall  comply  with  the
construction provisions of subchapter seventeen of this chapter.
  (c)  Design  and  construction.  Walkways  shall   comply   with   the
requirements of subchapter eighteen of this chapter.
  (d)  Enclosure.  Walkways that do not serve as exits, but are inclined
so as to require an opening in any floor, shall be enclosed as  required
for escalators in subdivision (c) of section 27-378 of this article.

Section 27-380

Section 27-380

  §  27-380 Fire escapes. Fire escapes constructed on existing buildings
when altered or as a second means of egress for group homes as permitted
by section 27-368 of this article shall comply with the following:
  (a) Capacity. The capacity of fire escapes shall be as listed in table
6-1 for stairs.
  (b)  Stairs.  The  minimum  width  of  fire  escape  stairs  shall  be
twenty-two  inches.  Treads  shall have a minimum width of eight inches,
exclusive of a required one inch nosing. The maximum  height  of  risers
shall  be  eight inches. No flight of stairs shall exceed twelve feet in
height between landings.
  (c) Landings. Landings shall be provided at each story served by  fire
escapes.  The  minimum  width  of  landings shall be three feet, and the
minimum length shall be four feet six inches. Floor openings in landings
shall be at least twenty-two inches by twenty-eight inches.
  (d) Handrails  and  guards.  Handrails  having  a  minimum  height  of
thirty-two inches above the tread nosing shall be provided on both sides
of stairs, and guards having a minimum height of thirty-six inches shall
be  provided  on all open sides of landings, openings in guards shall be
of such dimensions as to prevent the passage of a five inch dia. ball.
  (e) Construction. Fire escapes shall be constructed of  noncombustible
materials  adequately  protected  against  deterioration by corrosion or
other effects of exposure to the  weather,  and  shall  be  designed  to
comply with the requirements of subchapter nine of this chapter.
  (f) Access. Access to fire escapes shall be by doors or windows having
a minimum clear opening of twenty-four inches in width and thirty inches
in  height. Such doors or windows shall have a fire protection rating of
three-quarters of an hour except in buildings  classified  in  occupancy
group J-2.
  (g)  Discharge. The top landing of fire escapes shall be provided with
a stair or gooseneck ladder  leading  to  the  roof,  except  that  this
requirement  shall  not  apply  to buildings having a roof pitch of more
than twenty degrees. The lowest landing of fire  escapes  shall  be  not
more than sixteen feet above grade and shall be provided with a stair to
grade which may be counterbalanced.