Subchapter 2 - TECHNICAL STANDARDS

Section 27-3024.

Section 27-3024.

  § 27-3024. Adoption of the electrical code technical standards. a. The
city  of  New  York  hereby adopts the 2008 edition of the National Fire
Protection Association NFPA 70 National Electrical Code as  the  minimum
requirements  for  the  design,  installation,  alteration  or repair of
electric wires and wiring apparatus and other appliances used or  to  be
used  for  the  transmission  of  electricity  for electric light, heat,
power, signaling, communication, alarm and data transmission in the city
subject to the amendments adopted by local law and set forth in  section
27-3025  of  this subchapter, which shall be known and cited as "the New
York city amendments to the 2008 National Electrical  Code".  Such  2008
edition  of  the  National  Fire Protection Association NFPA 70 National
Electrical Code with such New York city  amendments  shall  together  be
known  and  cited  as  the  "electrical  code  technical standards". The
commissioner  shall  make  a  copy  of  the  electrical  code  technical
standards   available   for  public  inspection  at  the  department  of
buildings.
  b. No later than August thirty-first, two thousand twelve  and  on  or
before  such date in every third year thereafter, the commissioner shall
submit to the city council proposed amendments that he or she determines
should be made to the electrical code technical standards to bring  them
up  to  date  with  the  latest  edition of the National Fire Protection
Association NFPA 70 National Electrical Code  or  otherwise  modify  the
provisions  thereof.  In  addition,  prior  to  the  submission  of such
proposal to the city council, such proposal shall  be  submitted  to  an
advisory  committee  established  by  the  commissioner pursuant to this
chapter for review and comment.

Section 27-3025

Section 27-3025

  § 27-3025 The New York city amendments to the 2008 National Electrical
Code.  The  following  New  York  City  amendments  to the 2008 National
Electrical Code are hereby adopted as set forth in this section. In  the
event  of  conflicts  between technical provisions, the more restrictive
shall apply:
  2008 NEC New York City Amendment

                               ARTICLE 90
                              Introduction

  Section 90.2
  Subsection 90.2(B)(5) - Delete paragraph (b) and add a  new  paragraph
(b) to read as follows:
  (b) Are located in legally established easements, rights-of-way, or by
other  agreements  either  designated by or recognized by public service
commissions, utility commissions, or other  regulatory  agencies  having
jurisdiction for such installations, or

                                Chapter 1
                                 General

                               ARTICLE 100
                               Definitions

  Coordination  (Selective)  Add  a  new  sentence  at  the  end  of the
definition of Coordination (Selective) to read as follows:
  For the purposes of this code two overcurrent protective devices shall
be deemed  selectively  coordinated  if  their  respective  time-current
characteristic  curves  do  not  intersect  at  a time of 0.1 seconds (6
cycles on 60 Hz systems) or longer.
  Electric Closet Add a new definition of  Electric  Closet  immediately
after "Dwelling Unit", to read as follows:
  Electric  Closet.  A  room designed for or dedicated to the purpose of
containing electrical distribution equipment such  as  vertical  risers,
bus ducts, transformers or panelboards.

                               ARTICLE 110
                Requirements for Electrical Installations

  Section 110.2
  Section  110.2 - Delete in its entirety and add a new section 110.2 to
read as follows:
  110.2 Approval of Electrical Materials, Equipment and Installations.
  (A) Listed  and  Approved  Materials  and  Equipment.  All  electrical
equipment,  apparatus,  materials, devices, appliances or wiring thereto
installed  or  used  in  any  electrical  construction  or  installation
regulated  by  the terms of this code, shall be designed and constructed
so as to be safe and suitable for the purpose intended.
  (1)  All  electrical   equipment,   apparatus,   materials,   devices,
appliances  and  wiring  used  in New York City shall be approved by the
commissioner, with submissions required in accordance with rules of  the
department.
  (2)  The  maker's  name, trademark or other identification, symbol and
number shall be placed on fittings, equipment and materials.  Additional
markings  shall  be provided, stating voltage, current, wattage or other
appropriate ratings as prescribed elsewhere in this code.

  (B) Installations. All electrical installations regulated by the terms
of this code shall be designed and constructed so  as  to  be  safe  and
suitable for the purpose intended.
  No  electrical  installations  as  described  in (1) through (5) below
shall be constructed unless a submission for approval has been  made  to
the  commissioner and approval has been granted. For the purpose of this
section an electrical "installation" shall refer to the installation  of
service  equipment,  transformers,  UPS  systems, generators, electrical
wiring of assembled photovoltaic arrays, generator paralleling equipment
or other sources.
  (1) A new installation of new equipment totaling 1000 kVA or larger.
  (2) Any change in an installation with a rating of 1000 kVA or larger,
up to and including 2nd level overcurrent protection unless it was fully
described and approved as "future" on the original approved plan.
  (3) Any addition to an existing installation, which  would  bring  the
total to 1000 kVA or larger.
  (4)  The  addition  of  any  equipment  in  a room, which would affect
clearances around the equipment of a 1000 kVA installation.
  (5) A new installation or revised installation above 600V irrespective
of kVA rating.
  Exception No. 1: No submission  is  required  solely  for  fire  alarm
service taps.
  Exception No. 2: No submission is required for the addition of one 2nd
level overcurrent protection device 200 amperes or less.
  (C) Capacity.
  (1)  The capacity of a utility service, in kVA, shall be determined by
summing the maximum ampere ratings of each service  disconnecting  means
and   calculating   total   kVA   at   the  operating  voltage.  Service
disconnecting means supplying  fire  pumps  shall  be  included  at  125
percent  of  the fire pump full load amps. The calculation shall include
all new and existing  service  disconnecting  means  supplied  from  the
common service entrance.
  (2)  The  capacity  of  a  transformer, UPS system, generator or other
source shall be its maximum kVA output rating.
  FPN: See  90.7,  Examination  of  Equipment  for  Safety,  and  110.3,
Examination,  Identification,  Installation,  and  Use of Equipment. See
definitions of "Approved," "Identified," "Labeled," and "Listed."
  Section 110.4
  Section 110.4 - Add a FPN at  the  end  of  the  section  to  read  as
follows:
  FPN:   See   Section  27-3004  of  the  Administrative  Code  for  the
definitions of Low Voltage Electrical Work and  Low  Voltage  Installer,
and  Section  27-3016.1  for  the  certification  requirements  of a Low
Voltage Installer.
  Section 110.25
  Section 110.25 - Add a new section 110.25 to read as follows:
  110.25 Electric Closets.   Electric  closets  shall  be  dedicated  to
electrical  distribution equipment. Electric closets shall be identified
as such,  shall  be  sized  to  provide  the  applicable  working  space
requirements,  and  shall  not  be  used for any other purpose including
storage. Electric closets shall  be  accessible  to  authorized  persons
only.
  Exception:  Other  systems  that  are  required  to  be installed by a
licensed electrician, such as Fire  Alarm  Panels,  Building  Management
Systems  and  Lighting  Control  Systems  may  be  installed in Electric
Closets.
  SECTION 110.26

  Subsection 110.26(H) - Add a  new  subsection  110.26(H)  to  read  as
follows:
  (H) Network Compartments. All network compartments shall have at least
two  means  of  access.  Each  door shall access an area that leads to a
legal exit.
  SECTION 110.31
  Section 110.31 - Revise the second sentence of the second paragraph to
read as follows:
  A fence shall not be less than 2.44m (8 ft) in height.
  Subsection 110.31(A) - Revise the second sentence to read as follows:
  The floors of vaults in contact with the earth shall  be  of  concrete
that  is  not  less  than  6  in. (150 mm) thick, but where the vault is
constructed with a vacant space or other stories  below  it,  the  floor
shall have adequate structural strength for the load imposed on it and a
minimum fire resistance of 3 hours.
  SECTION 110.33
  Subsection  110.33(A) - Revise the first sentence of the subsection to
read as follows:
  At least one entrance to enclosures for  electrical  installations  as
described  in  110.31  not less than 762 mm (30 in.) wide and 2 m (6 1/2
ft) high shall be provided to give access to the  working  space  around
the electrical equipment.
  SECTION 110.34
  Subsection  110.34(A)  -  Revise the last sentence of the Exception to
read as follows:
  Where rear access is required to work on  de-energized  parts  on  the
back  of  enclosed equipment, a minimum working space of 900 mm (36 in.)
horizontally shall be provided.

                                CHAPTER 2
                          Wiring and Protection

                               ARTICLE 210
                             Branch Circuits
  SECTION 210.11
  Subsection 210.11(C)(4) - Add a new subsection 210.11(C)(4) to read as
follows:
  (4) Air-Conditioning Branch Circuit. In  addition  to  the  number  of
branch  circuits  required by other parts of this section, an individual
branch circuit shall be provided for  each  air-conditioning  receptacle
required by 210.52(I).

Section 210.19
  Subsection  210.19(A)(1)  -  Add  a  new  sentence  at  the end of the
paragraph before the first Exception to read as follows:
  Conductors of branch circuits shall be sized to allow  for  a  maximum
voltage  drop  of  3 percent at the last outlet supplying light, heat or
power and the maximum voltage drop  allowable  for  feeders  and  branch
circuit combined shall not exceed 5 percent.
  FPN No. 4 - Delete the FPN in its entirety.
  Subsection  210.19(A)(4)  - Revise the first sentence of the paragraph
by replacing "14 AWG" with "12 AWG"
  Exception No. 3: Add a new Exception No. 3 to read as follows:
  Exception  No.  3:  Where  compliance  with  the   applicable   Energy
Conservation  Code  is  mandated  voltage drop requirements of that code
shall apply.

Section 210.24
  Section  210.24  Table  - Replace the value "14" that appears twice in
the column headed 15A, and once each in the columns headed 20A  and  30A
in the Circuit Rating Section with the value "12."

Section 210.25
  Section 210.25 - Add an Exception to (A) and (B) to read as follows:
  Exception to (A) and (B): Buildings built prior to January 1, 2003 are
exempt  from  the  requirements of 210.25(A) and (B) under either of the
following conditions:
  (1) undergoing renovation less than 50 percent.
  (2) repair to or replacement of existing equipment.

Section 210.52
  Subsection 210.52(E)(3) - Delete the Exception in its entirety.
  Subsection 210.52(I) - Add a  new  subsection  210.52(I)  to  read  as
follows:
  (I)  Outlet  Requirements  For  Residential  -  Type  Occupancies.  In
addition to the requirements set forth in subsections (A) through (H) of
this section, living rooms, bedrooms,  dining  rooms  or  similar  rooms
shall   have   at   least   one  receptacle  outlet  installed  for  air
conditioners. Such outlets shall be supplied  by  an  individual  branch
circuit.
  Exception:  Buildings with central air conditioning systems that serve
any of the above areas shall  not  require  separate  outlets  in  those
areas.
                               ARTICLE 215
                                 Feeders
  SECTION 215.2
  Subsection 215.2(A)(1) - Add two new sentences at the end of the first
paragraph, before the Exception, to read as follows:
  Feeder  conductors  shall be sized so that the maximum voltage drop at
the last overcurrent device does not exceed  3  percent  and  the  total
maximum voltage drop of feeder and branch circuit conductors to the last
outlet  does  not  exceed  5  percent. The minimum feeder size feeding a
dwelling unit shall be 8 AWG copper or 6  AWG  aluminum  or  copper-clad
aluminum conductors.
  Add  three new Exceptions No. 3, No. 4 and No. 5 and a FPN, to read as
follows:
  Exception No. 3: For  residential  occupancies  and  portions  of  the
electrical system of mixed use buildings serving exclusively residential
occupancies, the maximum voltage drop from the service point to the last
overcurrent  device  shall  not  exceed  4 percent and the total maximum
voltage drop to the last outlet shall not exceed 5 percent.
  Exception No. 4: Where the distance between the utility service  point
and  the service disconnecting means exceeds 15.2 m (50 ft), the voltage
drop between the service point and the service disconnecting  means  may
be  calculated  utilizing  the  service  capacity  limits defined by the
utility company in lieu of the computed load. The distance  between  the
service point and the service disconnecting means, the computed load and
a  letter  on utility company letterhead indicating service limits shall
be submitted for department approval.
  Exception  No.  5:  Where  compliance  with  the   applicable   Energy
Conservation  Code  is  mandated  voltage drop requirements of that code
shall apply.

  FPN: When using Exception No. 4, potential  future  increases  in  the
utility  service capacity limits should be considered to avoid exceeding
voltage drop limits at a later date.
  Subsection 215.2(A)(3)-Delete FPN No. 2.-Renumber FPN No. 3 as FPN No.
2, and revise to read as follows:
  FPN No. 2: See amended 210.19(A) for voltage drop on branch circuits.

                               ARTICLE 220
            Branch-Circuit, Feeder, and Service Calculations
  SECTION 220.14
  Section  220.14 - Delete the reference to subdivision (L) in the first
paragraph and replace it with a reference to subdivision (M) to read  as
follows:
  In  all  occupancies, the minimum load for each outlet for general-use
receptacles and outlets not used for general illumination shall  not  be
less  than  that  calculated  in  220.14(A) through (M), the loads shown
being based on nominal branch-circuit voltages.
  Subsection 220.14(M) - Add a  new  subsection  220.14(M)  to  read  as
follows:
  (M) Air Conditioning Circuits: A load of not less than 1500VA shall be
included  with  each  2 wire circuit. This load shall be permitted to be
included with the general lighting load and subject  to  section  220.42
and table 220.42.
  SECTION 220.87
  220.87 Determining Existing Loads.
  Delete "or service" from the first sentence.
                                ARTICLE 225
                   Outside Branch Circuits and Feeders
  SECTION 225.10
  Section 225.10 - Revise the first sentence to read as follows:
  The  installation  of outside wiring on surfaces of buildings shall be
permitted for circuits of not over 600 Volts, nominal, as multiconductor
cable, as type MI cable, as messenger supported wiring, in  rigid  metal
conduit,  in intermediate metal conduit, in cable trays, as cablebus, in
wireways, in auxiliary gutters, in liquidtight  flexible  metal  conduit
and in busways.
  SECTION 225.11
  Section 225.11 - Revise the first sentence to read as follows:
  Where  outside  branch  and feeder circuits leave or enter a building,
the requirements of 230.54 shall apply.
  SECTION 225.36
  Section 225.36 - At the end of the sentence, add the following:
  and shall comply with all the requirements  of  Article  408  and  its
amendments.
                                ARTICLE 230
                                Services
  SECTION 230.6(5)
  Subsection  230.6(5)  -  Add  a  new  subsection  230.6(5)  to read as
follows:
  (5) Where installed in service and fire pump rooms having 2 hour rated
construction
  SECTION 230.30
  Section 230.30 - Delete the Exception in its entirety.
  SECTION 230.31
  Subsection 230.31(B) - Revise to read as follows:
  (B) Minimum Size. The conductors shall  not  be  smaller  than  4  AWG
copper or 2 AWG aluminum or copper-clad aluminum.

  Exception:  Conductors supplying only limited loads of a single branch
circuit - such as small polyphase power, controlled water  heaters,  and
similar  loads  -  shall  not  be  smaller  than  10 AWG copper or 8 AWG
aluminum or copper-clad aluminum.
  SECTION 230.42
  Subsection 230.42(A) - Revise to read as follows:
  (A) General The ampacity of the service-entrance conductors before the
application  of  any  adjustment or correction factors shall not be less
than (A)(1) or (A)(2) below. Loads shall  be  determined  in  accordance
with  Part III, IV or V of Article 220, as applicable. Ampacity shall be
determined from 310.15 for respective conductor types  at  75°C.    When
service-entrance  conductors  consist  of  busbars  contained  in either
service busway or other service equipment, bus sizing shall  conform  to
the following table:
  Table 230.42 Service Equipment Busbar Ampere Density
Current Rating of  Maximum Current Per Square Inch in Amperes
Bus
                   Ventilated Housing        Unventilated Housing
                   Copper Bar  Aluminum Bar  Copper Bar    Aluminum Bar
Up to 1200 Amp     1000        750           800           600
1201 to 2000 Amp   800         600           700           525
2001 Amp and       700         525           500           375
greater
  (1) Ampacity of the service-entrance conductors for service below 1000
kVA shall not be less than either a or b:
  (a)  The  sum  of  the  noncontinuous  loads  plus  125 percent of the
continuous loads.
  (b) The sum of the noncontinuous loads plus the  continuous  loads  if
the service-entrance conductors terminate in an overcurrent device where
both the overcurrent device and its assembly are listed for operation at
100 percent of their rating.
  (2)  Ampacity of the service-entrance conductors for services 1000 kVA
and larger shall not be less than the sum of the maximum ampere  ratings
of the service disconnecting means. When including fire pump disconnects
in the calculation, 125 percent of the fire pump full load amperes shall
be added.
  Exception: The ampacity of service-entrance conductors need not exceed
the  maximum  demand  calculated in accordance with Article 220, up to a
maximum of 4000 amps per service
  FPN: See Subsection 110.2(C)(1) for determining service capacity.
  Section 230.43
  Section 230.43 - Revise to read as follows:
  230.43   Wiring   Methods   for   600   Volts,   Nominal,   or   Less.
Service-entrance  conductors  shall  be installed in accordance with the
applicable requirements of this Code covering the type of wiring  method
used and shall be limited to the following methods:
  (1) Type IGS cable.
  (2) Rigid metal conduit.
  (3) Intermediate metal conduit.
  (4) Electrical metallic tubing.
  (5) Metallic wireways.
  (6) Busways.
  (7) Metallic auxiliary gutters.
  (8) Rigid nonmetallic conduit, underground.
  (9) Mineral-insulated, metal-sheathed cable.
  (10) Flexible metal conduit not over 1.83 m (6 ft) long or liquidtight
flexible  metal conduit not over 1.83 m (6 ft) long between raceways, or
between raceway and service equipment,  with  equipment  bonding  jumper

routed with the flexible metal conduit or the liquidtight flexible metal
conduit according to the provisions of Section 250.102(A), (B), (C), and
(E).
  Service  entrance conductors shall not run within the hollow spaces of
frame buildings.
  Section 230.46
  Section 230.46 - Revise to read as follows:
  230.46 Unspliced Conductors. Service-entrance conductors shall not  be
spliced  before  terminating  at the service disconnecting means, except
for the following terminations that are permitted:
  (1) in a service end line box.
  (2) taps  supplying  two  to  six  service  disconnecting  means  when
grouped.
  (3) approved terminals in meter enclosures.
  (4)  service-entrance  conductors  in  the  form  of  busway, shall be
connected as required in order to  assemble  the  various  fittings  and
sections.
  SECTION 230.50
  Subsection 230.50(B)(1)(3) - Delete the subsection in its entirety.
  Subsection 230.50(B)(1)(4) - Delete the subsection in its entirety.
  SECTION 230.52
  Section 230.52 - Delete the section in its entirety.
  SECTION 230.54
  Section  230.54  - Delete in its entirety and add a new section 230.54
to read as follows:
  230.54 Overhead Service Locations.
  (A) Raintight Service Head. Service raceways shall be equipped with  a
raintight  service  head  at  the  point  of  connection to service-drop
conductors.
  (B) Service Heads Above Service-Drop Attachment. Service  heads  shall
be  located above the point of attachment of the service-drop conductors
to the building or other structure.
  Exception: Where it is impracticable to locate the service head  above
the  point  of  attachment, the service head location shall be permitted
not farther than 600 mm (24 in.) from the point of attachment.
  (C) Separately Bushed Openings. Service heads shall have conductors of
different potential brought out through separately bushed openings.
  (D) Drip Loops. Drip loops shall be formed on  individual  conductors.
To  prevent  the entrance of water, service-entrance conductors shall be
connected to the service-drop conductors below the level of the  service
head.
  (E)  Arranged  that Water Will Not Enter Service Raceway or Equipment.
Service-drop  conductors  and  service-entrance  conductors   shall   be
arranged so that water will not enter service raceway or equipment.
  SECTION 230.64
  Section 230.64 - Add a new section 230.64 to read as follows:
230.64 Service Rooms or Areas.
  (A) General. The minimum sufficient working space shall be as provided
in Section 110.26 or 110.34 as applicable, in order to assure the safety
of operation, inspection, and repairs within the vicinity of the service
equipment.
  (B)  Service  Equipment  Totaling  1000  kVA, or Larger. Where service
equipment totaling 1000 kVA or larger is  installed  separately,  or  as
part  of  a  switchboard,  the room in which such switchboard is located
shall be constructed of noncombustible materials having a  2  hour  fire
rating  and shall be of dimensions adequate to house the switchboard and
to provide the following minimum clearances:

  (1) At least 1.5 m (5 ft) in front of the switchboard if it is in  one
line,  and  at  least  2.1  m (7 ft) in front of the board if boards are
installed facing each other.
  (2)  At  least 300 mm (12 in.) from the floor to any energized part of
the switchboard, except by special permission.
  (3) Where side and/or rear access is  required,  the  following  shall
also apply:
  -At least 900 mm (3 ft) at each end of the board
  -At  least  900  mm  (3  ft)  at  the  rear  of the board clear of all
obstructions or as specified in Table 110.26(A)(1) or Table 110.34(A) as
applicable, whichever is greater.
  (4) Front-only accessible switchboards may be  installed  300  mm  (12
in.)    or  less  from  a  wall.  However,  if the front-only accessible
switchboard is installed more than 300 mm (12 in.) from the wall, access
must be sealed at each end or comply with the restrictions herein.
  (5) Service equipment shall be arranged so that it is  reachable  from
the  entrance  door  without  having  to pass in front of, or behind any
other electrical equipment in the room. This requirement shall be waived
if a second entrance  door  is  provided  and  located  as  remotely  as
practical from the first. Each door shall access an area, which leads to
a legal exit.
  SECTION 230.70
  Subsection 230.70(A)(1) - Revise to read as follows:
  (1) Readily Accessible Location. The service disconnecting means shall
be  installed  at  a readily accessible location inside of a building or
structure nearest the point of entrance of the service conductors.
  Exception: Service disconnecting means may be installed on the outside
of residential buildings of one through four dwelling units.
  Subsection 230.70(B) - Revise to read as follows:
  (B) Marketing. Each service disconnecting means shall  be  permanently
marked  to identify it as a service disconnect. Each disconnecting means
shall be marked to indicate the load served.
  SECTION 230.76
  Section 230.76 - Add a new paragraph at the end of section  230.76  to
read as follows:
  Where remote control devices are used on service equipment or manually
operated  circuit  breaker devices totaling 1000 kVA or larger, it shall
be the responsibility of the owner  of  the  building  or  such  owner's
authorized  agent  to  have  the  opening  and closing mechanism of each
service switch or service breaker tested at least once every  year.  The
testing  need not be performed under load. A record showing the date and
signature of the qualified person making the test shall be  kept  posted
at the switch or circuit breaker.
  SECTION 230.94
  Section 230.94 - Revise Exception No. 3 to read as follows:
  Exception  No.  3:  Circuits for load management devices and emergency
supply shall be permitted to be connected on  the  supply  side  of  the
service  overcurrent  device  where separately provided with overcurrent
protection.
                                ARTICLE 240
                         Overcurrent Protection
  SECTION 240.12
  Subsection 240.12(A) - Add a  new  subsection  240.12(A)  to  read  as
follows:
  (A) Service Overcurrent Protective Device
  Where  the  service  overcurrent  protective  device  (OCPD) rating or
setting is above 601 Amps, such device shall be selectively  coordinated
with the next downstream OCPD.

  FPN No. 1: See definition of "Coordination (Selective)."
  Exception  No. 1: Selective coordination shall not be required between
two OCPDs in series with one another when  no  loads  are  connected  in
parallel with the downstream device.
  Exception  No.  2:  When the second level OCPD is a single main device
having the same  rating  or  setting  as  the  service  OCPD,  selective
coordination  shall  be required between the third level devices and the
two upstream devices.
  Exception No. 3: Selective coordination shall not be required  between
transformer  primary  and secondary OCPDs, where only one OCDP exists on
the transformer secondary.
  Renumber first paragraph of 240.12 as new  subsection  240.12(B),  and
retitle as follows:
  (B) Orderly Shutdown.
  SECTION 240.86
  Section 240.86 - Add a FPN after first paragraph to read as follows:
  FPN: See 240.12, 700.27 and 708.54.
                               ARTICLE 250
                          Grounding and Bonding
  SECTION 250.52
  Subsection 250.52(A)(1) - Delete the Exception in its entirety.
                               ARTICLE 285
             Surge - Protective Devices (SPDs), 1 kV or Less
SECTION 285.25
  Section 285.25 - Add a FPN at end of paragraph to read as follows:
  FPN:  Device to be used as per manufacturer's listing, available fault
current should be considered.
                                CHAPTER 3
                      Wiring Methods and Materials

                               ARTICLE 300
                             Wiring Methods
  SECTION 300.3
  Subsection 300.3(C)(1)(a) - Add a  new  subsection  300.3(C)(1)(a)  to
read as follows:
  (a)  Barriers  shall  be provided to isolate conductors energized from
different sources when system voltage  exceeds  250  volts  nominal  and
conductors are protected by first or second level overcurrent protective
devices.   Sources  include  service  entrance  points,  secondaries  of
different transformers, generators and UPS systems.
  SECTION 300.5
  Subsection 300.5(A) - Revise to read as follows:
  (A) Minimum Cover Requirements.  Direct-buried  cable  or  conduit  or
other raceways shall be installed to meet the minimum cover requirements
of  Table  300.5.  Direct-buried  cable shall not be installed except by
special permission from the commissioner.
  SECTION 300.6
  Subsection 300.6(B) - Revise to read as follows:
  (B)  Aluminum  Metal  Equipment.  Aluminum  raceways,   cable   trays,
cablebus,  auxiliary  gutters,  cable  armor,  boxes,  cable  sheathing,
cabinets, elbows, couplings, nipples,  fittings,  supports  and  support
hardware  shall  not  be permitted to be embedded in concrete or come in
direct contact with the earth.
  SECTION 300.22
  Subsection 300.22(C) - Revise the first paragraph to read as follows:
  (C) Other Space Used for Environmental Air. This  section  applies  to
non-fire rated spaces used for environmental air-handling purposes other
than  ducts  and  plenums as specified in 300.22(A) and (B). It does not

include habitable rooms or areas of  buildings,  the  prime  purpose  of
which is not air handling.
                               ARTICLE 328
                      Medium Voltage Cable: Type MV
  SECTION 328.10
  Section 328.10 - Revise to read as follows:
  328.10  Uses  Permitted.  Type MV cables shall be permitted for use on
power systems rated up to 35,000 volts nominal as follows:
  (1) In wet or dry locations,
  (2) In raceways.
  Section 328.12
  Section 328.12 - Revise to read as follows:
  328.12 Uses Not Permitted. Type MV cable shall not be used:
  (1) Where exposed to direct sunlight,
  (2) In cable trays,
  (3) Direct-buried,
  (4) In messenger-supported wiring.
  SECTION 328.80
  Section 328.80 - Delete the last sentence.
                               ARTICLE 330
                        Metal-clad Cable: Type MC
  SECTION 330.10
  Subsection 330.10(A)(1) - Delete the word "services".
  Subsection 330.10(A)(3) - Delete the words "or outdoors".
  Subsection 330.10(A)(5) - Revise to read as follows:
  To be direct-buried where identified  for  such  use  and  by  special
permission.
  Subsection 330.10(A)(8) - Delete the subsection in its entirety.
  Subsection 330.10(B)(3) - Delete the subsection in its entirety.
  SECTION 330.12
  Section 330.12 - Revise the first sentence to read as follows:
  330.12  Uses  Not Permitted. Type MC cable shall not be used under any
of the following conditions.
  Subsection 330.12(3) - Add a  new  subsection  330.12(3)  to  read  as
follows:
  (3) Where used as service conductors.
  Subsection  330.12(4)  -  Add  a  new  subsection 330.12(4) to read as
follows:
  (4) Where the cable  has  an  outer  jacket  of  PVC,  in  residential
buildings exceeding three floors above grade.
  Subsection  330.12(5)  -    Add  a new subsection 330.12(5) to read as
follows:
  (5) Where the cable has an outer jacket of PVC, in any  nonresidential
building  unless  concealed within non-plenum walls, floors and ceilings
where the walls, floors  and  ceilings  provide  a  thermal  barrier  of
material  that  has  at least a one hour rated assembly as identified in
listings of fire rated assemblies.
                               ARTICLE 334
           Nonmetallic-Sheathed Cable: Types NM, NMC, and NMS
  SECTION 334.10
  Section 334.10 - Revise to read as follows:
  334.10 Uses Permitted. Type NM, Type NMC, and Type NMS cables shall be
permitted to be used in the following:
  (1) One- and two-family dwellings.
  (2) Multifamily dwellings, except as prohibited in Section 334.12.
    FPN: See Section 310.10 for temperature limitation of conductors.
  Subsection 334.10(A)(1) - Revise to read as follows:
  (1) For both exposed and concealed work in normally dry locations.

  Subsection 334.10(B)(1) - Revise to read as follows:
  (1)  For  both  exposed  and  concealed  work  in  dry, moist, damp or
corrosive locations.
  Subsection 334.10(C)(1) - Revise to read as follows:
  (1) For both exposed and concealed work in normally dry locations.
  SECTION 334.12
  Subsection 334.12(A)(1) - Revise to read as follows:
  (1) In any multifamily dwelling exceeding three floors above grade.
  Subsection 334.12(A)(1) - Delete the Exception in its entirety.
  Subsection 334.12(A)(11) - Add a new subsection 334.12(A)(11) to  read
as follows:
  (11) In non-residential buildings.
  SECTION 334.15
  Subsection 334.15(B) - Change reference from 300.4(E) to 300.4(F).
  SECTION 334.30
  Subsection 334.30(C) - Delete the subsection in its entirety.
                               ARTICLE 336
                  Power and Control Tray Cable: Type TC
  SECTION 336.10
  Subsection 336.10(6) - Delete the subsection in its entirety.
  SECTION 336.12
  Subsection  336.12(5)  -  Add  a  new  subsection 336.12(5) to read as
follows:
  (5) As fire alarm circuit wiring.
  SECTION 336.104
  Subsection 336.104(A) - Delete the subsection in its entirety.
                               ARTICLE 338
                Service-Entrance Cable: Types SE and USE
  SECTION 338.10
  Subsection 338.10(A) - Add a second sentence to read as follows:
  Where installed as service entrance conductors, Type SE cable shall be
enclosed in a threaded metallic conduit.
  Subsection 338.10(B)(2) - Delete the Exception in its entirety.
  Subsection 338.10(B)(4)(b) - Revise to read as follows:
  (b) Exterior Installations. In addition  to  the  provisions  of  this
article,  service-entrance  cable  used  for feeders or branch circuits,
where installed as exterior wiring, shall be  installed  in  a  threaded
metallic conduit.
                               ARTICLE 340
          Underground Feeder and Branch-Circuit Cable: Type UF
  SECTION 340.10
  Subsection 340.10(1) - Revise to read as follows:
  (1) For use underground. For underground requirements, see 300.5.
  Subsection 340.10(5) - Delete the subsection in its entirety.
  Subsection 340.10(6) - Delete the subsection in its entirety.
  SECTION 340.12
  Subsection  340.12(12)  -  Add  a new subsection 340.12(12) to read as
follows:
  (12) Direct burial.
  Subsection 340.12(13) - Add a new subsection  340.12(13)  to  read  as
follows:
  (13) For Solar Photovoltaic Systems.
  SECTION 344.10
  Subsection  344.10(A)(3)  -  Revise  the second sentence of subsection
344.10(A)(3) to read as follows:
  Aluminum RMC shall not be permitted to be encased in concrete or  used
for direct burial.
  Subsection 344.10(B)(2) - Delete the subsection in its entirety.

                               ARTICLE 350
              Liquidtight Flexible Metal Conduit: Type LFMC
  SECTION 350.12
  Subsection  350.12(3)  -  Add  a  new  subsection 350.12(3) to read as
follows:
  (3) In lengths exceeding 1.83m (6 ft).
                               ARTICLE 352
               Rigid Polyvinyl Chloride Conduit: Type PVC
SECTION 352.10
  Subsection 352.10(I) - Add a  new  subsection  352.10(I)  to  read  as
follows:
  (I)  Residential Use. In any residential building or dwelling unit not
exceeding three floors above grade.
  Subsection 352.10(J) - Add a  new  subsection  352.10(J)  to  read  as
follows:
  (J) Non Residential Use. Unless prohibited elsewhere by other articles
of  this  code,  PVC  conduit  shall  be permitted in any nonresidential
building or residential building over 3 stories high. Rigid  nonmetallic
conduit  shall be concealed within non-plenum walls, floors and ceilings
where the walls, floors  and  ceilings  provide  a  thermal  barrier  of
material  that  has  at least a one hour rated assembly as identified in
listings of fire-rated assemblies.
                               ARTICLE 354
       Nonmetallic Underground Conduit with Conductors: Type NUCC
  SECTION 354.10
  Section 354.10 - Revised the heading and the first sentence to read as
follows:
  354.10 Uses Permitted by Special Permission Only. The use of NUCC  and
fittings shall be permitted by special permission only, as follows:
                               ARTICLE 355
            Reinforced Thermosetting Resin Conduit: Type RTRC
  SECTION 355.10
  Subsection  355.10(I)  -  Add  a  new  subsection 355.10(I) to read as
follows:
  (I) Residential Use. In any residential building or dwelling unit  not
exceeding three floors above grade.
  Subsection  355.10(J)  -  Add  a  new  subsection 355.10(J) to read as
follows:
  (J) Non Residential Use. Unless prohibited elsewhere by other articles
of this code, RTRC conduit shall  be  permitted  in  any  nonresidential
building or residential building over 3 stories high. RTRC conduit shall
be  concealed  within  non-plenum  walls,  floors and ceilings where the
walls, floors and ceilings provide a thermal barrier  of  material  that
has  at  least  a  one  hour rated assembly as identified in listings of
fire-rated assemblies.
                               ARTICLE 356
           Liquidtight Flexible Nonmetallic Conduit: Type LFNC
  SECTION 356.10
  Section 356.10 - Revise the heading and the first sentence to read  as
follows:
  356.10  Uses  Permitted  by  Special  Permission Only. The use of LFNC
shall be permitted by special permission only, as follows:
                               ARTICLE 358
                  Electrical Metallic Tubing: Type EMT
  SECTION 358.10
  Subsection 358.10(C) - Delete the subsection in its entirety.
  SECTION 358.12

  Subsection 358.12(7) - Add a  new  subsection  358.12(7)  to  read  as
follows:
  (7) For underground or exterior installations or in wet locations.
                               ARTICLE 362
                 Electrical Nonmetallic Tubing: Type ENT
  SECTION 362.10
  362.10 - Revise to read as follows:
  362.10  Uses  Permitted.  The use of electrical nonmetallic tubing and
fittings shall be permitted:
  (1) Concealed within walls, floors,  and  ceilings  where  the  walls,
floors,  and ceilings provide a thermal barrier of material which has at
least a 1 hour finish rating as identified  in  listings  of  fire-rated
assemblies.
  (2)  In locations subject to severe corrosive influences as covered in
300.6 and where  subject  to  chemicals  for  which  the  materials  are
specifically approved.
  (3) In concealed, dry, and damp locations not prohibited by 362.12.
  (4)  Above  suspended  ceilings where the suspended ceilings provide a
thermal barrier of material, which has at least a 1 hour  finish  rating
as identified in listings of fire-rated assemblies.
  (5)  Embedded  in poured concrete, provided fittings approved for this
purpose are used for connections.
  (6) For wet locations indoors or in a concrete slab on or below grade,
with fittings listed and approved for the purpose.
  FPN No. 1: Extreme cold may cause some types of  nonmetallic  conduits
to  become  brittle  and,  therefore,  more  susceptible  to damage from
physical contact.
  FPN No. 2: Extreme cold may cause some types of nonmetallic tubing  to
become  brittle and, therefore, more susceptible to damage from physical
contact.
  SECTION 362.12
  Subsection 362.12(11) - Add a new subsection  362.12(11)  to  read  as
follows:
  (11) In ducts, plenums and other air handling spaces.
                               ARTICLE 366
                            Auxiliary Gutters
  Section 366.10
  Subsection 366.10(B) - Revise the first sentence to read as follows:
  Nonmetallic  auxiliary  gutters  may  only  be  installed  by  special
permission and shall be listed for the maximum  ambient  temperature  of
the  installation  and  marked  for  the  installed conductor insulation
temperature rating.
                               ARTICLE 368
                                 Busways
  SECTION 368.2
  Section 368.2 - Change title from "Definition"  to  "Definitions"  and
add a new definition to read as follows:
  Service  Busway.  For  the  purpose of this article, service busway is
busway used to connect from the service point to the line  terminals  of
the service equipment.
  SECTION 368.119
  Section  368.119  - Add a new section 368.119, after the heading "III.
Construction", to read as follows:
  368.119  Service  Busway.  Service  busway  shall   conform   to   the
specifications listed in (A) through (I) below.
  (A)  Ampacity  and Ratings of Busbars. Ampacity and ratings of busbars
shall be in accordance with 230.42(A).

  (B) Length. Service busway shall be limited to a maximum of 3.0 m  (10
ft) in length.
  Exception: By special permission.
  (C)  Insulation. Busbars shall be insulated with a material listed for
the purpose and rated for use at a minimum of 600 Volts.
  Exception:  Bolted  busbar  joints  requiring  maintenance  shall   be
permitted to be uninsulated.
  (D)  Enclosure.  Enclosure  shall be fabricated from aluminum, minimum
3.2 mm (1/8 in.) thick or other non-magnetic material  approved  by  the
commissioner.
  (E)  Enclosure  Vents.  Ventilating openings shall be permitted in the
sides and bottom of the enclosure. Top of enclosure must be solid.
  (F)  Mounting.  Busbars  shall  be  mounted  on  insulating  supports,
properly  spaced  and  braced  to  withstand the maximum available short
circuit current.
  (G) Clearance. A minimum clearance of 102 mm (4 in.) shall be provided
from the phase bars to the enclosure.
  (H) Plating. All busbar joints and connections shall  be  plated  with
silver, tin or nickel.
  (I)   Accessibility.  All  busbar  joints  and  connections  shall  be
accessible.
                               ARTICLE 370
                                Cablebus
  SECTION 370.3
  Section 370.3 - Delete "and services" from the last  sentence  of  the
first paragraph, so that it reads as follows:
  Cablebus  shall  be  permitted  to  be  used  for  branch circuits and
feeders.
                               ARTICLE 376
                             Metal Wireways
  SECTION 376.22
  Section 376.22 - Add an Exception after  subsection  (B)  to  read  as
follows:
  Exception:  Metallic  auxiliary  gutters  may contain up to 40 service
entrance conductors without applying derating factors.
                                ARTICLE 378
                          Nonmetallic Wireways
  SECTION 378.10
  Section 378.10 - Revise the heading and first sentence of the  section
to read as follows:
  378.10   Uses  Permitted  by  Special  Permission  Only.  The  use  of
nonmetallic wireways shall be permitted by special  permission  only  as
follows:
                                ARTICLE 380
                          Multioutlet Assembly
  SECTION 380.2
  Subsection  380.2(B)(7)  - Add a new subsection 380.2(B)(7) to read as
follows:
  (7) Where cord and plug connected unless listed for the purpose.
                                ARTICLE 382
                         Nonmetallic Extensions
SECTION 382 II
  Section 382 II - After subheading "II. Installation" of  the  Article,
add a sentence to read as follows and delete remainder of the Article:
  II. Installation
  Installation of non-metallic extensions shall not be permitted.
                               ARTICLE 388
                      Surface Nonmetallic Raceways

SECTION 388.12
  Subsection  388.12(8)  -  Add  a  new  subsection 388.12(8) to read as
follows:
  (8) In residential buildings exceeding three floors above grade.
  Subsection 388.12(9) - Add a  new  subsection  388.12(9)  to  read  as
follows:
  (9) In non-residential buildings.
                               ARTICLE 392
                               Cable Trays
Subsection 392.3(E) - Add a new sentence at end of existing paragraph to
read as follows:
  Nonmetallic cable trays may be used by special permission only.
                               ARTICLE 394
                     Concealed Knob-and-Tube Wiring
SECTION 394 II
  Section  394 II - After subheading "II. Installation" of this Article,
add a sentence to read as follows and delete the rest of the Article:
  II. Installation
  Installation of Concealed Knob-and-Tube Wiring shall not be permitted.
                               ARTICLE 396
                       Messenger-Supported Wiring
SECTION 396
  Table 396.10(A) - Delete second line of Table in its entirety.

                                CHAPTER 4
                        Equipment for General Use

                               ARTICLE 404
                                Switches
SECTION 404.10
  Subsection 404.10(A) - Delete the subsection in its entirety.
                               ARTICLE 408
                      Switchboards and Panelboards
  SECTION 408.60
  Section 408.60 - Add new section 408.60 to read as follows:
  408.60 Special Requirements. Switchboards shall  be  listed,  approved
and  constructed  in  accordance with UL 891, Eleventh Edition, Standard
for Switchboards. Panelboards shall be listed, approved and  constructed
in  accordance  with  UL 67, Eleventh Edition, Standard for Panelboards.
Additional construction specifications shall be in accordance  with  (A)
thru (G) below.
  (A) Neutral Disconnect Link in Service Switchboards
  A  bus  link  shall  be provided for disconnecting the neutral service
conductor(s)  from  the  outgoing  load   neutral   conductor(s).   Such
disconnect  link  shall  be readily accessible and located downstream of
the main bonding jumper and grounding electrode conductor terminal. In a
multi-section switchboard  a  single  neutral  disconnect  link  may  be
provided for all service disconnects.
  Exception:  A  single  cable lug accommodating a maximum of two cables
may be used in lieu of a neutral disconnect link for service disconnects
800 amperes or less.
  (B)  Dielectric  Test.  All  service   and   distribution   equipment,
switchboards,  control panels, and panelboards shall be given a 60 Hz AC
dielectric test, phase to phase and phase  to  ground,  at  twice  rated
voltage  plus  1,000  volts for one minute (minimum 1500 volts) prior to
shipment from factory. A dielectric test voltage  which  is  20  percent
higher than that in the one minute test may be applied for one second as
an alternative to the one minute test. The date of the test and the name

and  title  of the individual certifying the test shall be clearly shown
on a label affixed to the equipment.
  (C)  Warning  Label.  All  480/277  volt switchboards, panelboards and
panelboard back  boxes  shall  have  a  visible  label,  clearly  marked
"WARNING 480/277 VOLTS" and in compliance with ANSI Standard Z535.4.
  (D)  Grounding  Switchboard  Frames. Switchboard frames and structures
supporting switching  equipment  shall  be  grounded.    A  multisection
switchboard  shall  be  provided with an internal ground bus, which will
electrically connect all of the sections of the switchboard. This ground
bus shall have a minimum cross section of 1/2 square inch of  copper  or
3/4  square  inch  of  aluminum.  The  contact surfaces of the equipment
ground connections shall provide an effective electrical ground path for
fault currents.
  Exception: Frames  of  direct  current,  single-polarity  switchboards
shall not be required to be grounded if effectively insulated.
  (E) Busbars.
  (1)  General.  Busbars shall be sized based on 1000 amperes per square
inch for copper and 750 amperes per square inch for aluminum.
  Exception: In service switchboards, generator paralleling switchboards
and when connecting to devices rated over 2500 amperes. See 408.60(E)(2)
and (E)(3) below.
  (2) In Service  Equipment  And  Switchboards  Supplied  Directly  From
Separately  Derived  Systems.  Line-side busbars in service switchboards
and  all  busbars  in  generator  paralleling  switchboards   shall   be
considered  service conductors and shall comply with the requirements of
230.42(A).
  (3) Connection to Devices Rated over 2500 Amperes.  Busbars  shall  be
sized  in  accordance  with (a) and (b) below when connected to a device
(switch or circuit breaker) over 2500 amperes:
  (a) Over 2500 amperes but less than 5000  amperes,  busbars  shall  be
sized  based  on  800 amperes per square inch for copper and 600 amperes
per square inch for aluminum.
  (b) 5000 amperes and over, busbars shall be sized based on 700 amperes
per square inch for copper and 525 amperes per square inch for aluminum.
  Exception: Beyond a minimum distance of 1.2m (4 ft) along the  current
path  from  the device, the busbar may be reduced in size, in accordance
with 408.60(E)(1) above.
  (4) Ampacity of Through (Main) Bus. The through (main) bus that  feeds
four  or more overcurrent protective devices of a switchboard shall have
a minimum ampacity of 70 percent of the sum of the frame ratings of  all
devices fed by that through bus. If provisions are made for the addition
of   overcurrent   protective   devices  in  the  future,  the  expected
overcurrent protective device ratings shall be  included  in  the  above
calculations.  The  through  bus  ampacity  shall  not be required to be
greater than the frame rating of  the  upstream  overcurrent  protective
device.
  Exception:  In  service  equipment  and switchboards supplied directly
from separately derived systems and for devices rated over 2500  amperes
refer to 408.60(E)(2) and (E)(3) above.
  (5)  Ampacity  of  Section Bus. The section bus is that portion of the
bus that serves one  or  more  overcurrent  protective  devices  in  the
switchboard  section  and  includes  that  part  of  the bus between the
through bus and the branch distribution bus. The minimum ampacity of the
section bus of a switchboard shall be determined by the table below. The
section bus ampacity shall not be required to be greater  than  that  of
the through bus.
  Total  Number  of Branch          Minimum Ampacity of Section Bus as a
Overcurrent Devices                    percentage of the

                                          Sum    Total     of     Branch
Overcurrent Devices*
      1-2                               100
      3-4                                80
      Over 4                             70
  *  For  fusible  switches,  the  maximum  fuse size shall be used. For
interchangeable trip circuit breakers, the maximum trip rating shall  be
used.  If  provisions  are  made  for  the future installation of branch
overcurrent protective devices, the ampacity of  these  units  shall  be
included in the calculation.
  Exception:  In  service  equipment  and switchboards supplied directly
from separately derived systems and for devices rated over 2500  amperes
refer to 408.60(E)(2) and (E)(3) above.
  (6)  Busbar  Joints. All busbar joints and connections shall be plated
with silver, tin or nickel. The current density at contact  surfaces  in
busbar  joints  shall  not exceed 200 amperes per square inch for cooper
and 150  amperes  per  square  inch  for  aluminum.  A  permanent  label
providing torque values or tightening instructions for all busbar joints
shall be affixed to each section of a switchboard.
  (F)  Hinged  Doors. Freestanding switchboards, which have rear access,
shall have hinged rear doors fastened  by  captive  screws  or  suitable
latches.
  (G)  Barriers  In  Switchboards Rated Over 150 Volts To Ground. Listed
and approved barriers shall be placed between adjacent sections  of  the
switchboard.  Listed  and  approved barriers shall be placed between the
switchboard and its pullbox, whether located at the top or bottom of the
equipment. All openings in the barriers for busbars and cables shall  be
closed  with  snug  fitting,  listed  and  approved non-hygroscopic, arc
resistant material.
                               ARTICLE 409
                        Industrial Control Panels
  SECTION 409.108
  Section 409.108 - At the end of the first paragraph,  add  "and  shall
comply with section 408.60."
                               ARTICLE 410
                   Luminaires, Lampholders, and Lamps
  SECTION 410.30
  Subsection  410.30(B)(1) - At the first sentence, insert "intended for
use in a wet location" between "A pole" and "shall have"
  SECTION 410.151
  Subsection 410.151(B) - Number the existing FPN as FPN No. 1, and  add
a second FPN to read as follows:
  FPN No. 2: See the applicable Energy Conservation Code.
                               ARTICLE 422
                               Appliances
  SECTION 422.12
  Section 422.12 - Revise to read as follows:
  422.12 Central Heating Equipment. Central heating equipment other than
fixed   electric   space-heating  equipment  shall  be  supplied  by  an
individual branch circuit.
  Exception  No.  1:  Auxiliary  equipment,  such  as  a  pump,   valve,
humidifier,  or  electrostatic  air cleaner directly associated with the
heating equipment, may be connected to the same branch circuit.
  Exception No. 2: Permanently connected air-conditioning equipment  may
be connected to the same branch circuit.
  (A)  Low  Pressure  Boiler.  Any  steam boiler operating at 15 psig or
less, any hot water boiler operating below 160 psig, or any boiler rated
at 10 horsepower or less, regardless of pressure.

  (B) Controls on Low Pressure Boilers. An  electrical  pressure  switch
with  normally  closed  contacts shall be connected to the steam drum of
every boiler ahead of all valves. The pressure switch shall  be  set  to
open  at  safe  working  pressure  of the boiler. This boiler electrical
high-pressure  cut-off  switch  shall  be  designed to reclose only by a
reset device, which shall be manually controlled.  One  and  two  family
residences are exempt from these provisions.
  (C)  Circuit Voltage and Safety Devices Connections. Conductors of the
control circuits shall only be connected to circuits not  exceeding  150
volts to ground, or not more than 150 volts between conductors.
  All  safety devices, such as pressure controls, fire controls, relays,
etc. shall have their electric  switching  mechanism  connected  to  the
ungrounded conductor.
  SECTION 422.16
  Subsection  422.16(B)(4)  -  Replace the term "range hood(s)" with the
term "combination range hood/microwave  oven(s)"  in  the  title,  first
paragraph and the Exception.
                               ARTICLE 430
                 Motors, Motor Circuits, and Controllers

SECTION 430.5
  Table 430.5 - Add the following items to the Table:
  "Services 230" and "Switchboards and panelboards 408"

SECTION 430.95
  Section  430.95 - At the end of the first paragraph add a new sentence
to read as follows:
  When the equipment is utilized  as  service  equipment,  a  means  for
disconnecting  the neutral service conductor(s) complying with 408.60(A)
is required.

SECTION 430.97
  Section 430.97 - After the title,  add  a  new  sentence  to  read  as
follows:
  When the equipment is utilized as service equipment, the busbars shall
comply with 408.51.

                               ARTICLE 450
     Transformers and Transformer Vaults (Including Secondary Ties)

SECTION 450.9
  Section 450.9 - Add a new third paragraph to read as follows:
  Mechanical  ventilation  and/or air conditioning shall be provided and
shall be adequate to dispose of the transformer full-load losses without
exceeding 40°C (104°F) ambient temperature in the room.
  SECTION 450.25
  Section 450.25 - Delete the section in its entirety.
  SECTION 450.42
  Section 450.42 - Revise to read as follows:
  450.42 Walls, Roofs and Floors. The vault shall be of  such  dimension
as  to permit the installation of all electrical equipment in accordance
with 110.26 or 110.34 as applicable. The vault  shall  be  of  fireproof
construction  with  a minimum fire resistance rating of three hours with
floors, walls and ceilings 152 mm (6 in.) thick if made of concrete,  or
203  mm  (8 in.) thick if made of brick, or 203 mm (8 in.) thick if made
of filled cement block. All building steel forming  part  of  the  vault
construction  shall  have  a  comparable  fire  resistance  rating. Each
compartment within a vault shall be built to the same specifications  in

respect  to the thickness of walls and fireproof door, as the vault. The
floors shall be of ample strength to carry the weight of  the  equipment
to  be installed in the vault. The floors and wall, to the height of the
sill, shall be given a hard impervious finish and painted to prevent the
absorption of oil.
  Exception:  Where transformers are protected with automatic sprinkler,
carbon dioxide, or gas suppression system, construction of 1-hour rating
shall be permitted.
  SECTION 450.43
  Subsection 450.43(A) - Delete the FPN, and revise the  subsection  and
Exception to read as follows:
  (A)  Type of Door. Each doorway leading into a vault from the building
interior shall be provided with a tight-fitting door that has a  minimum
fire  rating  of  3  hours. Where practicable, basement vaults or vaults
opening up on a roof shall be provided with an outside entrance so  that
no  entrance  directly  into the vault from the interior of the building
will be necessary. Where entrance into the vault is from the interior of
the building, the vault shall open upon a  vestibule,  passage  hall  or
switchboard room not commonly in public use.
  Exception:  Where transformers are protected with automatic sprinkler,
carbon dioxide, or gas suppression system, construction of 1-hour rating
shall be permitted.
  SECTION 450.45
  Section 450.45 - Revise the first paragraph to read as follows:
  A system of ventilation shall be provided to  dispose  of  transformer
full  load losses and maintain a vault ambient temperature not to exceed
40°C (104°F). Minimum criteria for ventilation shall  be  in  accordance
with (A) through (F) below:
  Subsection 450.45(C) - Add an Exception to read as follows:
  Exception:  Where  required to meet the ventilation conditions of this
section,  the  minimum  of  three  square  inches  per  kVA  of  natural
ventilation  may  be  supplemented by a dedicated mechanical ventilation
system.
  SECTION 450.46
  Section 450.46 - Revise to read as follows:
  450.46 Drainage.  Where practicable, vaults containing more  than  100
kVA  transformer  capacity shall be provided with a drain or other means
that will carry off any accumulation of oil or water in the vault unless
local conditions make this impracticable. The floor shall be pitched  to
the drain where provided. Drainage shall be permitted to carry off water
accumulation.    Such  drainage  shall  prevent  drainage of transformer
coolant into  the  water  drainage  system  and  shall  be  provided  in
accordance   with  the  New  York  City  Construction  Codes  and  other
authorities having applicable regulations.
                                CHAPTER 5
                           Special Occupancies
                               ARTICLE 500
   Hazardous (Classified) Locations, Classes I, II, and III, Divisions
                                 1 and 2
  SECTION 500.8
  Subsection 500.8(A)(3) - Revise to read as follows:
  (3) Evidence acceptable to the authority having jurisdiction.
                               ARTICLE 501
                            Class I Locations
  SECTION 501.10
  Subsection 501.10(B)(1)(7) - Delete the words  "and  Schedule  80  PVC
conduit,  factory  elbows,  and  associated  fittings"  from  the  first
paragraph.

  Subsection  501.10(B)(2)  -  Delete  item  (4)  "Liquidtight  flexible
nonmetallic conduit with listed fittings".
                               ARTICLE 502
                           Class II Locations
  SECTION 502.10
  Subsection  502.10(A)(2)  -  Delete  item  (3)  "Liquidtight  flexible
nonmetallic conduit with listed fittings".
  SECTION 502.100
  Subsection 502.100(B)(2) - Revise to read as follows:
  (2) Containing Askarel. The use of transformers containing Askarel  is
prohibited. Delete (1), (2), (3).
                               ARTICLE 503
                           Class III Locations
  SECTION 503.10
  Subsection 503.10(A) - Delete the words "rigid nonmetallic conduit".
  Subsection  503.10(A)(2)  -  Delete  the  words  "liquidtight flexible
nonmetallic conduit with listed fittings".
                               ARTICLE 505
                   Class I, Zone 0, 1, and 2 Locations

  SECTION 505.15
  Subsection 505.15(C)(1)(g) - Delete the words  "and  Schedule  80  PVC
conduit, factory elbows, and associated fittings".
  Subsection  505.15(C)(2)  -  Delete  the  words  "liquidtight flexible
nonmetallic conduit with listed fittings".

                               ARTICLE 506
    Zone 20, 21, and 22 Locations for Combustible Dusts or Ignitible
                             Fibers/Flyings

  SECTION 506.9
  Subsection 506.9(A)(3) - Delete the words "such  as  a  manufacturer's
self-evaluation or an owner's engineering judgment".
  SECTION 506.15
  Subsection  506.15(A)(5)  -  Delete  the  words  "liquidtight flexible
nonmetallic conduit with listed fittings".

                               ARTICLE 511
                 Commercial Garages, Repair and Storage

  SECTION 511.7
  Subsection 511.7(A)(1) - Delete the words "rigid nonmetallic  conduit,
electrical  nonmetallic tubing" and "or liquidtight flexible nonmetallic
conduit".

                               ARTICLE 515
                           Bulk Storage Plants

  SECTION 515.7
  Subsection 515.7(A) - Delete the words ", Schedule 80 PVC conduit".

                               ARTICLE 516
            Spray Application, Dipping and Coating Processes
  SECTION 516.3
  Subsection 516.3(C)(2)(a) - Revise to read as follows:
  (a) The exhaust ventilation system shall be interlocked with the spray
application equipment, the Division 2 or Zone 2  location  shall  extend
1.5  m  (5  ft)  horizontally and 900 mm (3 ft) vertically from the open

face or open front of the booth or room, as shown in figure 516.3(B)(2),
top.
  Subsection 516.3(C)(2)(b) - Delete the subsection in its entirety.

                               ARTICLE 517
                         Health Care Facilities

  SECTION 517.30
  Subsection  517.30(B)(4)  -  At  the  end  of  the  paragraph, add the
following:
  A separate automatic transfer switch shall be required for:
  (1) The fire pump. For fire pump requirements refer to Article  695  -
Fire Pumps.
  (2) Alarm and alerting systems.
  (3) Automatic smoke control or venting.
  (4) Stair pressurization systems.
  FPN Figures 517.30, No. 1 and 517.30, No. 2, add the following:
  This  figure  does  not  reflect  the  switches and automatic transfer
switches required above.
  Subsection 517.30(C)(3)(1) - Delete the words ", or  Schedule  80  PVC
conduit".
  SECTION 517.41
  Subsection 517.41(B) - At the end of the paragraph, add the following:
  A separate automatic transfer switch shall be required for:
  (1)  The  fire pump. For fire pump requirements refer to Article 695 -
Fire Pumps.
  (2) Alarm and alerting systems.
  (3) Automatic smoke control or venting.
  (4) Stair pressurization systems.
  FPN Figures 517.41, No. 1 and 517.41, No. 2, add the following:
  This figure does not  reflect  the  switches  and  automatic  transfer
switches required above.

                               ARTICLE 518
                          Assembly Occupancies

  SECTION 518.1
  Section 518.1 - Revise to read as follows:
  518.1  Scope.  This  article  covers  all  buildings  or  portions  of
buildings or structures classified as Assembly Occupancies  in  the  New
York City Construction Codes.
  SECTION 518.2
  Subsection  518.2(A)  - Delete the first sentence and replace with the
following:
  (A) General. Assembly Occupancies shall be  classified  as  places  of
assembly  in  accordance  with  New York City Construction Codes and the
Fire Code (under Titles 28 & 29 of  the  New  York  City  Administrative
Code) and shall include the following:
  Subsection 518.2(B) - Revise to read as follows:
  (B)  Multiple Occupancies. Multiple occupancies shall be classified in
accordance with the New York City Construction Codes.
  SECTION 518.4
  Subsection 518.4(B) - Delete the subsection in its entirety.
  Subsection 518.4(C) - Delete the subsection in its entirety.
                               ARTICLE 520
   Theaters, Audience Areas of Motion Picture and Television Studios,
                Performance Areas, and Similar Locations
  SECTION 520.5

  Subsection 520.5(C) - Delete the subsection in its entirety.
  SECTION 520.6
  Section  520.6  -  Delete  the  words  "rigid  nonmetallic  conduit as
permitted in this article," from the first sentence.
                               ARTICLE 522
           Control Systems for Permanent Amusement Attractions
SECTION 522.1
  Subsection 522.1 - Before  "electrical  equipment"  insert  the  words
"(new and existing)".
                               ARTICLE 525
             Carnivals, Circuses, Fairs, and Similar Events
  SECTION 525.20
  Subsection  525.20(G)  -  In  the  first  sentence,  delete  the words
"permitted to be" and add the word "secured" in front of  "nonconductive
matting".

                               ARTICLE 545
                         Manufactured Buildings

  SECTION 545.3
  Section 545.3 - Add new section 545.3 to read as follows:
  545.3  Wiring  Generally.  Approval  of all wiring within manufactured
buildings, including branch circuit wiring,  shall  be  subject  to  the
installation and permitting requirements of this code.
  SECTION 545.4
  Subsection 545.4(A) - Revise to read as follows:
  (A)  Methods  Permitted.  The  wiring shall be installed in accordance
with the requirements of Chapter 3.
  SECTION 545.6
  Section 545.6 - Delete the Exception in its entirety.
  SECTION 545.10
  Section 545.10 - Delete the section in its entirety.

                               ARTICLE 547
                         Agricultural Buildings

  SECTION 547.5
  Subsection  547.5(A)  -  Delete  the   words   "liquidtight   flexible
nonmetallic conduit".
  Subsection   547.5(D)   -   Delete  the  words  "liquidtight  flexible
nonmetallic conduit".

                               ARTICLE 550
         Mobile Homes, Manufactured Homes, and Mobile Home Parks

  SECTION 550.3
  Section 550.3 - Add a new section 550.3 to read as follows:
  550.3 Wiring Generally. Approval  of  all  wiring  within  mobile  and
manufactured homes, including branch circuit wiring, shall be subject to
the installation and permitting requirements of this code.

                               ARTICLE 590
                         Temporary Installations

  SECTION 590.4
  Subsection  590.4(J)  -  Add  the  following  at  the beginning of the
subsection:

  Temporary wiring for lighting  shall  be  properly  and  substantially
supported  on noncombustible, nonabsorbtive insulators and shall be kept
off the floor and free and clear of contact with woodwork,  metal  pipes
and metal portions of the building structure.
  Subsection  590.4(K)  -  Add  a  new  subsection  590.4(K)  to read as
follows:
  (K) Permanent Feeders and Branch Circuits used for Temporary Light and
Power. Permanent feeders may be used for temporary light, heat or  power
service  if  run  in  approved  raceways  or conduits from the source of
supply  directly  to  the  distribution  center.   Temporary   polarized
lampholders  may be connected to permanent branch circuit wiring pending
the erection of the permanent fixtures.
  Subsection 590.4(L) -  Add  a  new  subsection  590.4(L)  to  read  as
follows:
  (L)  Grounding. All portable machines shall be grounded. All grounding
shall conform with Article 250.
  SECTION 590.6
  Section 590.6 - Add an Exception after the first paragraph, to read as
follows:
  Exception: Temporary wiring installations that are accessible  to  the
public  and  used  to supply temporary power for illumination of outdoor
areas  during  construction,   remodeling,   maintenance,   repair,   or
demolition  of  buildings,  structures, equipment, or similar activities
shall comply with all other requirements  of  this  code  for  permanent
wiring and shall be provided with ground-fault protection for personnel.
  SECTION 590.8
  Section 590.8 - Add a new section 590.8 to read as follows:
  590.8 Sidewalk Shed Lighting. All sidewalk shed lighting installations
shall  comply  with  the  following  conditions in addition to all other
relevant provisions of this code:
  (1) Such lighting shall be installed in a metal raceway  approved  for
outdoor use.
  (2) All junction boxes shall be suitable for damp or wet locations.
  (3) A minimum wire size of 12 AWG shall be used for the installation.
  (4) All fixtures shall be suitable for outdoor locations.
  (5)  Ground-Fault Circuit Interrupter (GFCI) protection is required on
receptacles and lighting.
  (6) The installation shall be properly grounded and bonded.
  (7) The panel supplying power to the sidewalk shed lighting shall have
a directory that clearly indicates which circuit is being used to supply
power.
                                CHAPTER 6
                            Special Equipment
                               ARTICLE 600
                   Electric Signs and Outline Lighting
  SECTION 600.3
  Section 600.3 - Add the following subsections:
  (C) Inspection. Electric signs manufactured for  installation  in  the
city  shall  be  inspected  by  the  department  and  approved  prior to
installation.  The department may direct that such inspection take place
at the factory before final assembly or at the place of installation.
  (D) Relocated Signs. The relocation  of  an  approved  sign  from  one
location to another may be permitted without inspection provided that no
alterations  in  or  additions  to  the  existing sign are made, and the
application to connect at the new location shows the previous  location,
lettering, and the connected electrical load of the sign.
  (E)  Plastic  Materials.  All  plastic  materials  to  be  used in the
manufacture of electric signs shall be submitted for approval.

  (F) Markings. Each individual  plastic  section  or  letter  shall  be
permanently  marked with the material manufacturer's name, trademark, or
other identification symbol.
  (G)  Receptacles.  Only  receptacles  for  sign  maintenance  shall be
installed in or on sign enclosures.
  SECTION 600.7
  Subsection 600.7(B)(7)(a) - Replace "14 AWG" with "12 AWG".
  SECTION 600.8
  Subsection 600.8(C) - Revise to read as follows:
  (C) Minimum Thickness of Enclosure Metal.  Sheet  steel  shall  be  at
least  0.635mm  (0.0250 in./24 U.S.S.G.) thick. Sheet copper or aluminum
shall be of equivalent strength.
                               ARTICLE 604
                       Manufactured Wiring Systems
  SECTION 604.1
  Subsection 604.1(A) -  Add  a  new  subsection  604.1(A)  to  read  as
follows:
  (A)  General.  All  such  wiring  systems  shall  be  approved  by the
department, and shall comply with the installation requirements of  this
code in addition to the standards listed below. Each manufactured wiring
system   manufacturer  shall  add  the  following  to  its  installation
instructions:
  (1) With the electrical permit application for each  installation,  or
any  subsequent  modification  thereof,  the  licensed electrician shall
include a diagram or specification sheet clearly defining the boundaries
where the wiring method will be installed.
  (2) Manufactured wiring systems shall not be used for  emergency  exit
signs or emergency lighting.
  (3) Such wiring shall be used only for general lighting circuits above
an accessible hung ceiling or where no finished ceiling exists.
  SECTION 604.4
  Section 604.4 - Delete Exceptions No. 1 and No. 2 in their entirety.
  SECTION 604.6
  Subsection  604.6(A)(2)  - Revise the first paragraph by inserting the
word "metal" between "liquidtight flexible" and "conduit".
                               ARTICLE 605
    Office Furnishings (Consisting of Lighting Accessories and Wired
                               Partitions)
  SECTION 605.4
  Section 605.4 - Revise to read as follows:
  605.4 Partition Interconnections. The  electrical  connection  between
partitions shall be flexible assemblies listed and approved for use with
wired partitions or metallic raceways that do not exceed 610mm (2 ft) in
length.
  SECTION 605.6
  Section 605.6 - Revise to read as follows:
  605.6  Fixed-Type  and  Freestanding-Type Partitions. Wired partitions
that are fixed (secured  to  building  surfaces)  or  freestanding  (not
fixed)  shall be permanently connected to the building electrical system
by one of the wiring methods of this code.  Where  liquidtight  flexible
metal conduit is used, the maximum length shall be 457mm (18 in.).
  SECTION 605.7
  Section 605.7 - Delete the section in its entirety.
  SECTION 605.8
  Section 605.8 - Delete the section in its entirety.
                               ARTICLE 620
  Elevators, Dumbwaiters, Escalators, Moving Walks, Platform Lifts, and
                           Stairway Chairlifts

  SECTION 620.12
  Subsection 620.12(B) - Revise to read as follows:
  (B)  Other  Wiring. All signaling and operating control circuits shall
be minimum 24 AWG copper.
  SECTION 620.21
  Section 620.21 - Delete the  words  "rigid  nonmetallic  conduit"  and
"liquidtight flexible nonmetallic conduit" throughout.
  Subsection  620.21(A)(1)(d)  -  Delete paragraphs (d)(3) and (d)(4) in
their entirety.
  Subsection 620.21(A)(2)(d) - Delete paragraphs (d)(3)  and  (d)(4)  in
their entirety.
  Subsection 620.21(A)(3)(e) - Delete the subsection in its entirety.
  Subsection 620.21(A)(4) - Delete the subsection in its entirety.
  SECTION 620.23
  Subsection  620.23(C)  -  Insert  the words "with ground-fault circuit
interrupter" between "duplex receptacle" and "shall be provided".
  SECTION 620.24
  Subsection 620.24(A) - Revise the second sentence to read as follows:
  Required lighting and/or sump pump shall not be connected to the  load
side of a ground-fault circuit interrupter.
  FPN-replace "2004" with "2003".
  SECTION 620.61
  Section 620.61 - Add a second sentence to read as follows:
  For  multiple  elevators  connected  to the same feeder, each elevator
circuit must be properly protected.
  SECTION 620.82
  Section 620.82 - Insert the words "including all door panels"  between
"metal enclosures" and "for all electrical equipment".
                               ARTICLE 640
   Audio Signal Processing, Amplification, and Reproduction Equipment
  SECTION 640.3
  Subsection 640.3(J) - Delete the subsection in its entirety.
                               ARTICLE 645
                    Information Technology Equipment
  SECTION 645.17
  Subsection  645.17  -  Delete  the words: "each panelboard has no more
than 42 overcurrent devices and".
                               ARTICLE 668
                           Electrolytic Cells
  SECTION 668.1
  Section 668.1 - Add a new paragraph at the end of the section to  read
as follows:
  No  new  electrolytic  cell  line shall be installed, nor any existing
cell line modified, without special permission.
                               ARTICLE 680
          Swimming Pools, Fountains, and Similar Installations
  SECTION 680.4
  Section 680.4 - At the end of the paragraph add the following:
  All applicable provisions of the  New  York  City  Construction  Codes
shall apply.
  SECTION 680.9
  Subsection 680.9 - At the end of the paragraph add the following:
  All  such circuits shall be provided with GFPE. Electric water heaters
of the immersion or submersible type shall not be permitted.
  SECTION 680.21
  Subsection 680.21(A)(3) - Revise by deleting the words "or liquidtight
flexible nonmetallic conduit".
  SECTION 680.23

  Subsection 680.23(B)(1)  -  Revise  the  first  sentence  to  read  as
follows:
  Listed and approved forming shells shall be installed for the mounting
of  all wet-niche underwater luminaires (fixtures) and shall be equipped
with provisions for conduit entries.
  Subsection 680.23(B)(2) - Revise by deleting  the  words  "liquidtight
flexible nonmetallic" throughout.
  Subsection  680.23(B)(2)(b)  -  Revise  the  first sentence to read as
follows:
  Where a rigid nonmetallic conduit is used, an 8 AWG insulated solid or
stranded copper equipment grounding conductor shall be installed in this
conduit unless  a  listed  low-voltage  lighting  system  not  requiring
grounding is used.
  Subsection 680.23(D) - Revise to read as follows:
  (D)  No-Niche Luminaires (Fixtures). A no-niche lighting fixture shall
be supplied from a transformer meeting the requirements of  680.23(A)(2)
and shall:
  (1) Have no exposed metal parts
  (2) Have an impact resistant polymeric lens and body, and
  (3) Be listed and approved for the purpose
  Subsection 680.23(F)(1) - Revise to read as follows:
  (1)  Wiring  Methods.  Branch-circuit  wiring  on  the  supply side of
enclosures and junction boxes connected to conduits run to wet-niche and
no-niche luminaires (fixtures), and the  field  wiring  compartments  of
dry-niche  luminaires  (fixtures),  shall  be installed using listed and
approved rigid metal  conduit,  intermediate  metal  conduit,  or  rigid
nonmetallic conduit.
  Exception: Electrical metallic tubing shall be permitted to be used to
protect conductors, when installed within buildings.
  SECTION 680.33
  Section 680.33 - Revise to read as follows:
  680.33   Storable  Pool  Luminaires  (Lighting  Fixtures).  Luminaires
(lighting fixtures) for storable pools shall not be permitted.
  SECTION 680.41
  Section 680.41 - Revise section by deleting the last sentence.
  SECTION 680.42
  Subsection 680.42(A)(1) - Revise  subsection  by  deleting  the  words
"liquidtight flexible nonmetallic conduit" throughout.

                               ARTICLE 682
              Natural and Artificially Made Bodies of Water

  SECTION 682.1
  Section  682.1  -  Add  the  words "and water parks" at the end of the
section.
  SECTION 682.2
  Section 682.2 - Add the words "and water parks"  at  the  end  of  the
first sentence of the definition of "Artificially Made Bodies of Water".
  SECTION 682.13
  Section   682.13  -  In  the  first  sentence  delete  the  words  "or
liquidtight flexible nonmetallic conduit".

                               ARTICLE 690
                       Solar Photovoltaic Systems

  SECTION 690.1
  Section 690.1 - At the end of the section add the following:

  A detailed diagram of the photovoltaic system must be  made  available
upon request of the department.

                               ARTICLE 695
                               Fire Pumps

  SECTION 695.1
  Subsection  695.1(A)(3)  - Add a new subsection 695.1(A)(3) to read as
follows:
  (3) Modification of existing fire pump power supply.
  SECTION 695.2
  Section 695.2 - After the first definition, "Fault  Tolerant  External
Control Circuits", add two new definitions to read as follows:
  Fire Pump. For the purposes of this section, a fire pump is any Manual
Standpipe  Fire  Pump,  Automatic Standpipe Fire Pump, Sprinkler Booster
Pump, Special Service Fire Pump, Spray Mist Fire Pump or Foam Fire  Pump
located at or below street level or with a motor rating exceeding 30hp.
  Limited  Service  Fire  Pump.    For  the  purposes of this section, a
Limited Service Fire Pump is a fire pump located above street level with
a motor rating not exceeding 30hp and connected  to  a  limited  service
fire pump controller.
  Revise  the  third definition, "On-Site Standby Generator", to read as
follows:
  On-Site Emergency Generator. An on-site  facility  producing  electric
power as the alternate supply of electric power meeting the requirements
of Article 700.
  After  the  last  definition,  "On-Site  Standby Generator", add a new
definition to read as follows:
  Sprinkler booster pump. For the purposes of this section, a  Sprinkler
Booster  Pump  is  a  fire  pump  installed  in J-2 occupancies, where a
minimum of 5 psig is maintained at the highest line of sprinklers,  that
complies with the definition of Limited Service Fire Pump.
  SECTION 695.3
  Subsection 695.3(B) - Revise to read as follows:
  (B) Multiple Sources. Where required by the New York City Construction
Codes,  power  from sources described in 695.3(A) shall be supplied from
an approved combination of two or  more  such  sources  or  an  approved
combination  of  one such source and an on-site emergency generator. The
on-site emergency generator, complying with this section,  shall  be  of
sufficient capacity to allow normal starting and running of the motor(s)
driving  the  fire  pump(s)  while  supplying  all  other simultaneously
operated loads. Optional standby loads shall be automatically shed  when
necessary to ensure the proper starting and operation of the fire pump.
  Subsection  695.3(C)  -  Add  a  new  subsection  695.3(C)  to read as
follows:
  (C) Multiple Independent Sources. Two or more  feeder  sources  routed
separately  to  the building and independently operated may be permitted
for compliance with this section, as approved by the commissioner, where
the reliability of the sources can be demonstrated.
  SECTION 695.4
  Section 695.4 - Revise to read as follows:
  695.4 Continuity of Power. Circuits that supply electric  motor-driven
fire  pumps  shall  be  supervised  from  inadvertent  disconnection  in
accordance with (A) or (B) below.
  (A) General. Each utility and generator supply circuit  that  supplies
an electric motor-driven fire pump or limited service fire pump shall be
supplied  from  a  single  dedicated  service  disconnecting  means  and

associated overcurrent protective device  installed  between  the  power
source and one of the following:
  (1) A listed fire pump controller
  (2) A listed fire pump power transfer switch
  (3)  A  listed  combination  fire  pump  controller and power transfer
switch
  Exception 1: The service conductors may  directly  connect  the  power
source  to  either  the  listed fire pump controller or combination fire
pump controller and power transfer switch where available short  circuit
current  is  less  than  the  rating  of  the  fire  pump  controller or
combination fire pump controller and power transfer switch.
  Exception 2: Where a limited service fire  pump  is  connected  to  an
emergency  generator  in  addition  to  the electric utility source, the
disconnecting means for either source is not required to  be  a  service
disconnecting means.
  Exception  3:  Where the building service disconnecting means consists
of multiple utility sources over 600 volts arranged through transformers
to supply a network secondary, a disconnecting means  connected  to  the
network complies with the requirements of this section.
  (B) Disconnecting Means and Overcurrent Protection
  (1)  Utility  Service. Fire pumps and limited service fire pumps shall
have overcurrent protection selected as to allow the  operation  of  the
fire  pump  for  as  long  as  the fire pump remains capable of running,
except where direct connection is made in accordance with 695.4(A)(3)
  Exception 1:
  (1) Fire Pump. Fire pump overcurrent protection shall be  selected  at
between 300 percent and 600 percent of motor full load current.
  (2)  Limited  Service  Fire  Pump. Limited service fire pumps shall be
protected by overcurrent devices selected at 150 percent of  motor  full
load  current.  The  next larger available device size may be used where
selection results in a non-standard device size.
  (3) Disconnecting  means  shall  be  listed  to  accept  the  selected
overcurrent device with no modification.
  (2)  Generator  Supply.  When required to be connected to an emergency
generator,  fire  pumps  and  limited  service  fire  pumps  shall  have
overcurrent protection selected in accordance with the following, except
where direct connection is made in accordance with 695.4(A)(3) Exception
1:
  (1) Fire Pump. Fire pumps shall be protected by an over current device
selected  at  not less than 150 percent and not more than 300 percent of
motor full load current.
  (2) Limited Service Fire Pump. Limited service  fire  pumps  shall  be
protected by an overcurrent device selected at 150 percent of motor full
load current. The next larger available size may be used where selection
results in a non-standard size.
  (3) Disconnecting means shall be listed to accept the selected fuse or
circuit breaker trip with no modification.
  (4) A tap ahead of the on-site emergency generator disconnecting means
shall be required for the fire pumps.
  Exception:  Where  multiple  generators  operate in parallel, the fire
pump tap may be made on the parallel distribution bus.
  (3) Disconnecting Means. The disconnecting means shall comply with the
following:
  (1) Be identified as suitable for use as service equipment.
  (2) Be lockable in  the  closed  position.  Locking  provisions  shall
remain in place with or without an installed lock.
  (3)  Not located within equipment that feeds loads other than the fire
pump.

  (4)  Be  located  as  remote  as  practicable   from   other   service
disconnecting means with a minimum separation of 305mm (12in.).
  Exception: (1), (3), and (4) shall not apply to fire pumps and limited
service fire pumps connected to emergency generators.
  (4)  Disconnect Marking. The disconnecting means shall be marked "Fire
Pump - Do Not Disconnect". The letters shall be at least 25 mm  (1  in.)
in  height,  and  they shall be visible without opening enclosure doors.
Disconnecting means shall be red in color.
  (5) Controller Marking. A placard shall be placed adjacent to the fire
pump controller stating overcurrent setting at 300 percent of motor full
load current, the location of the disconnecting means, and the  location
of the key (if the disconnecting means is locked).
  (6)  Supervision.  The  power continuity shall be supervised by one of
the following:
  (1) Central station signals confirming power source  availability  and
pump running where central station connection is provided as required by
building occupancy or use.
  (2)  Local  signaling  device,  audible  and  visual, for power source
availability and pump running  which  is  activated  at  a  continuously
attended  location  where  central  station  connection is not otherwise
required.
  SECTION 695.5
  Section 695.5 - Revise to read as follows:
  Section 695.5 Accessory Equipment
  (A) Transformers. Where the service or  system  voltage  is  different
from  the  utilization  voltage  of  the  fire pump motor, a transformer
protected by  disconnecting  means  and  overcurrent  devices  shall  be
permitted  to  be  installed between the system supply and the fire pump
controller in accordance with the following.
  (1) Size. Transformers shall be rated at a minimum of 125  percent  of
the sum of the fire pump motor(s) and pressure maintenance pump(s) motor
loads,   and   100  percent  of  the  remaining  load  supplied  by  the
transformer.
  (2)  Overcurrent   Protection.   Primary   disconnecting   means   and
overcurrent  devices  shall  be selected in accordance with 695.4(B)(1).
Secondary disconnecting means  and  overcurrent  devices  shall  not  be
permitted.
  (3)  Feeder  Source.  The  feeders on the primary and secondary of the
transformer shall be sized in accordance with the requirements of  695.6
adjusted for the primary and secondary voltage.
  (B)   Utility   Meters.  Metering  of  fire  pumps  shall  be  current
transformer driven or bypass type  such  that  meter  removal  will  not
interrupt  service  to  the  fire pump. Metering may be dedicated to the
fire pump or coincident with other building power use.
  (C) Rectifiers. Rectifiers may be used to supply existing DC fire pump
installation in accordance with the following.
  (1) Size. Where a rectifier supplies  an  existing  DC  electric  fire
pump,  it  shall  be  rated at a minimum of 125 percent of the fire pump
full load current plus 100 percent of the full load current of all other
equipment connected to the rectifier.
  Exception: If largest motor is other than  the  fire  pump,  rectifier
shall  be  sized  at 125 percent of the largest motor and 100 percent of
all other equipment.
  (2)  Overcurrent  Protection.  The  primary  disconnecting  means  and
overcurrent  device  shall be rated at 150 percent of the rectifier full
load current. The  DC  fire  pump  shall  be  supplied  by  a  dedicated
connection  on  the  secondary of the rectifier. Disconnecting means and
overcurrent devices shall not be permitted.

  (3) Feeder Source. The feeders on the primary  and  secondary  of  the
rectifier  shall  be  sized in accordance with the requirements of 695.6
adjusted for the primary and secondary voltage.
  (4) Other Loads. Rectifiers installed to supply existing DC fire pumps
shall  be  permitted  to supply other loads. Rectifier capacity shall be
increased in accordance with 695.5(C)(1). Each DC supply shall include a
disconnecting means and overcurrent  device  sized  in  accordance  with
applicable sections of the code.
  SECTION 695.6
  Section 695.6 - Revise to read as follows:
  695.6  Power  Wiring.  Power  circuits and wiring methods shall comply
with the requirements in 695.6(A)  through  (E),  and  as  permitted  in
230.90(A),  Exception  4; 230.94, Exception 4; 230.208; 240.4(A); 240.13
and 430.31.
  (A) Supply Conductors: Fire pump and limited service fire pump  supply
conductors shall be physically routed outside a building(s) and shall be
installed as service entrance conductors. Where supply conductors cannot
be  physically  routed  outside  buildings, routing through buildings is
permitted where installed in accordance with Section 230.6(1), (2),  (4)
or (5).
  Exception:  The  supply  conductors  located in the electrical service
room and generator room where they originate and in the fire  pump  room
shall not be required to have the minimum 2-hour fire separation or fire
resistive rating.
  (B) Circuit Conductors:
  (1)  Fire  Pumps.  Fire  pump  supply  conductors, including emergency
supply conductors where emergency power is provided, on the load side of
the final disconnecting means  and  overcurrent  device  shall  be  kept
entirely  independent  of all other wiring. They shall supply only loads
that are directly associated with the fire pump  system,  and  shall  be
protected  to  resist  potential  damage by fire, structural failure, or
operational damage. They shall be  permitted  to  be  routed  through  a
building(s) using one of the following methods:
  (1)  Encased  in  a minimum of 50mm (2 in.) concrete using rigid metal
conduit (steel RMC), intermediate  metal  conduit,  electrical  metallic
tubing or schedule 80 non-metallic conduit.
  (2)  Rigid  metal  conduit (steel RMC) within an enclosed construction
dedicated to the fire pump circuit(s) having a minimum of a 2-hour  fire
resistance rating.
  (3)  A  listed  electrical  circuit  protective  system with a minimum
2-hour fire resistance rating. The installation shall  comply  with  any
restrictions   provided   in  the  listing  of  the  electrical  circuit
protective system.
  Exception: The supply conductors located  in  the  electrical  service
room  and  generator room where they originate and in the fire pump room
shall not be required to have the minimum 2-hour fire separation or fire
resistive rating.
  (2) Limited Service Fire  Pumps.  Limited  service  fire  pump  supply
conductors  shall  be  installed  in  rigid metal conduit (steel RMC) or
intermediate metal conduit (steel IMC).
  Exception: Where there are multiple sources of supply  with  means  of
automatic  transfer  from  one  source to the other, electrical metallic
tubing (EMT) shall also be permitted.
  (C) Conductor Size. Conductors supplying a  fire  pump  or  a  limited
service  fire  pump shall have a rating not less than 125 percent of the
full load current of the pump motor  selected  at  no  greater  than  75
degrees operating temperature of the conductor type used.

  (D)  Overload  Protection.  See  695.5(C)(2)  for  overload protection
requirements.
  (E)  Pump  Wiring.  All wiring from the controllers to the pump motors
shall be in rigid metal conduit (steel RMC) or  have  a  minimum  1-hour
fire separation or fire resistance rating.
  Exception  No. 1: Liquidtight flexible metal conduit (maximum of 915mm
(36 in.)) is permitted for final connection to motor terminal housing.
  Exception No. 2: Intermediate metal conduit (steel IMC) and electrical
metallic tubing (EMT) shall be permitted for limited service fire pumps.
  SECTION 695.10
  Section 695.10 - Revise to read as follows:
  695.10 Listed Equipment. Diesel engine driven fire  pump  controllers,
electric  fire  pump  controllers,  electric  motors, fire pump transfer
switches, foam pump controllers, and limited service  controllers  shall
be listed and approved for fire pump use.
  SECTION 695.14
  Subsection 695.14(E): - Revise to read as follows:
  (E)  Electric  Fire  Pump  Control  Wiring Methods. All electric motor
driven fire pump  control  wiring  shall  be  in  rigid  metal  conduit,
intermediate  metal  conduit, liquidtight flexible metal conduit or Type
MI cable.
  Exception: Electrical metallic tubing (EMT)  shall  be  permitted  for
limited service fire pump control wiring.
  Subsection 695.14(F) - Add an Exception to read as follows:
  Exception:  Electrical  metallic tubing shall be permitted for limited
service fire pump control wiring where provided with emergency generator
supply.

                                CHAPTER 7
                           SPECIAL CONDITIONS

                               ARTICLE 700
                            Emergency Systems

  SECTION 700.4
  Subsection 700.4(A) - Revise to read as follows:
  (A) Acceptance Test. A  licensed  professional  shall  submit  to  the
department  a  testing  report of the complete system upon installation.
Such testing report shall be from an authorized testing entity.
  Subsection 700.4(E) - Revise to read as follows:
  (E) Installation Test Requirements. The  installation  test  shall  be
conducted and documented in accordance with NFPA 110-2005, Section 7-13,
amended as follows:
  7.13.3: Delete in its entirety.
  7.13.4.1(11):  Revise  to read as follows: The load test with building
load or other loads that simulate intended load  shall  continue  for  2
hours  observing  and recording load changes and the resultant effect on
voltage and frequency.
  7.13.10.2:  Delete  and  replace  with  the  following:  The  complete
crank/rest  cycle  shall  consist  of  3-15  second crank cycles with 15
second rest periods between cranks.
  7.13.13: Add a new paragraph to read  as  follows:  Transfer  switches
shall be tested in accordance with 8.4.6 as modified herein.
  Subsection  700.4(F)  -  Add  a  new  subsection  700.4(F)  to read as
follows:
  (F) Maintenance and Operational Testing. Maintenance  and  operational
testing  shall  be  performed  and  documented  in  accordance with NFPA
110-2005, Section 8, amended as follows:

  8.2: Delete in its entirety.
  8.3.4:  Delete and replace with the following: A written record of the
EPSS inspection, tests, exercising,  operation,  and  repairs  shall  be
maintained  on premises and made available to the department on request.
Records  shall  be  inclusive  of  the  transfer  switches  and  storage
batteries.
  8.4.4.1:  Add  a  new  sentence  to  read as follows: Inspection shall
consist of examination of all EPSS components for leaks, abnormal device
position and of all alarm/trouble indicators.
  8.4.5: Delete in its entirety.
  8.4.6: Replace "monthly" with "semi-annually".
  8.4.6.1: Replace "monthly" with "semi-annually".
  SECTION 700.5
  Subsection 700.5(B) - Delete third paragraph  of  subsection  700.5(B)
and add a FPN to read as follows:
  FPN: Peak reduction program may require utility approval.
  SECTION 700.6
  Subsection  700.6(E)  -  Add  a  new  subsection  700.6(E)  to read as
follows:
  (E) Mechanical Operation. Means  shall  be  provided  to  mechanically
operate the switch without hazard to personnel.
  Subsection  700.6(F)  -  Add  a  new  subsection  700.6(F)  to read as
follows:
  (F)  Temporary  Connections   for   Portable   Generators.   Temporary
connection  of  a portable generator without transfer equipment shall be
permitted where qualified persons maintain and supervise service of  the
installation,  and  where  the  normal  source  of  supply is physically
isolated by a lockable disconnecting means or by  disconnection  of  the
normal  supply  conductors.  Portable generators shall not be paralleled
except by special permission.
  Subsection 700.6(G) -  Add  a  new  subsection  700.6(G)  to  read  as
follows:
  (G)  Permanent  Connections for Portable Generators. Where a permanent
connection is made for a portable generator, a disconnecting  means  and
overcurrent  protection shall be provided at the point of connection for
the portable generator. Capacity shall not exceed the  capacity  of  the
permanent installation.
  SECTION 700.7
  Section 700.7 - Revise to read as follows:
  Audible  and visual signal devices shall be provided at a continuously
supervised location for the following purposes:
  SECTION 700.9
  Subsection 700.9(A) - At the end of the subsection add the following:
  All accessible raceways,  boxes  and  enclosures  (including  transfer
switches,  generators  and power panels) for emergency circuits shall be
permanently marked so they will be readily identified as a component  of
an  emergency  circuit or system. Accessible raceways shall be marked at
least once every 3 m (10 ft). Acceptable means of marking shall include,
but is not limited to, a permanently affixed  identification  nameplate,
yellow in color with black lettering.
  Subsection 700.9(B) - Revise Exception to (5)(b) to read as follows:
  Exception  to (5)(b): Overcurrent protection shall be permitted at the
source  for  the  equipment,  provided  the  overcurrent  protection  is
selectively  coordinated  in  the  overcurrent range with the downstream
overcurrent protection.
  SECTION 700.10
  Section 700.10 - Add a new section 700.10 to read as follows:
  700.10 Conductors for Emergency Circuits.

  (A) Ampacity. See 445.13.
  (B)  Installation  of Generator Conductors. Generator conductors shall
be installed in accordance with the requirements of Article 230.
  (C) Overcurrent Devices. There shall be no  limit  to  the  number  of
overcurrent devices connected to the generator terminal devices.
  (D)  Fire  System  Pumps.  Fire  system pumps or fire protection pumps
requiring connection directly to the emergency generator as  defined  in
the New York City Construction Codes shall be connected as follows:
  (1)  Circuits  supplying fire system pumps shall be connected directly
to the emergency generator with only one overcurrent  protective  device
which  shall be rated at not less than 150 percent and not more than 600
percent of the pump full load current.
  Exception: Limited  service  fire  pumps  shall  be  protected  by  an
overcurrent  device  selected at 150 percent of motor full load current.
The next largest available device  size  may  be  used  where  selection
results in a non-standard device size.
  (2)  Where  multiple generators are paralleled, the connection for the
fire system pumps shall be taken from the generator paralleling bus.
  Exception: Limited service fire pumps are not required to be  directly
connected to the emergency generator and may have additional overcurrent
protective devices.
  (3)  Conductors  and transformers feeding the system shall be sized at
125 percent of the pump full load current.
  (4) Separate circuits shall be used for each fire system pump.
  (E) Alarm Systems. All  building-wide  fire  alarm  systems  shall  be
provided  with  a dedicated transfer switch and be directly connected to
the emergency generator overcurrent protective devices as follows:
  (1) 208/120V systems-by a dedicated fused disconnecting means.
  (2) 460/265V systems-by a dedicated  fused  disconnecting  means  with
fused   disconnecting   means   on   the  secondary  of  the  associated
transformer.
  SECTION 700.12
  Section 700.12 - Revise the fourth paragraph, add a new  Exception  to
read as follows and delete the FPNs:
  Fire, sprinkler, standpipe, smoke detection, oxygen, nitrous oxide and
other alarm or extinguishing systems shall be connected to the line side
of the service equipment and shall have separate overcurrent protection.
  Exception:  Such systems installed for local area protection only, may
connect ahead of the supply to the area protected.
  Subsection 700.12(A) - Revise the first paragraph and  add  a  FPN  to
read as follows:
  Storage  batteries  may  be  used  as  a source of power for emergency
lighting systems and shall be of suitable rating and capacity to  supply
and maintain the total load for a minimum period of 1 1/2 hours, without
the  voltage applied to the load falling below 87 1/2 percent of normal.
Storage batteries may be used for other  emergency  systems  only  where
special permission is granted for such use.
  FPN:  See  Article  760  for  additional  information  on  the  use of
batteries for fire alarm systems.
  Subsection 700.12(B)(2) - Revise first sentence and add a FPN to  read
as follows:
  Where  internal  combustion  engines  are  used as the prime mover, an
on-site fuel supply shall be provided sufficient for  not  less  than  6
hours of operation at full demand load.
  FPN:  Some installations may require more than 6 hours of fuel supply.
See Articles 517 and 708.
  Subsection 700.12(B)(6) - Revise to read as follows:

  (6)  Outdoor  Generator  Sets.  Where  an  outdoor  generator  set  is
permanently  installed  and  is  equipped with a disconnecting means and
such generator set is located within sight of the building or  structure
supplied,  an additional disconnecting means shall not be required where
ungrounded   conductors   pass   through   the  building  or  structure.
Appropriate signage shall be provided at the generator set  and  at  the
first disconnecting means within the building or structure supplied.
  Subsection  700.12(B)(7)  - Add new subsection 700.12(B)(7) to read as
follows:
  (7) Temporary Generators. The equipment grounding conductor(s) of  the
derived system shall be bonded to the grounding electrode system.
  FPN: See 250.34 for grounding of generator frame.
  (a) Separately Derived System. Where a temporary portable generator is
a  separately  derived  system,  it shall be grounded in accordance with
250.30.
  (b) Not A  Separately  Derived  System.  Where  a  temporary  portable
generator  is  not  a  separately derived system, a grounding connection
shall not be made to the grounded circuit conductor.
  Subsection 700.12(C) - Revise to read as follows:
  (C) Uninterruptible Power Supplies. Uninterruptible power supplies may
be used to provide  power  for  emergency  systems  only  where  special
permission is granted for such use.
  Subsection 700.12(D) - Revise the first sentence of subsection to read
as follows:
  Where  acceptable  to  the  commissioner  as  suitable  for  use as an
emergency source, a second service independent of  the  source  normally
supplying the building shall be permitted.
  Subsection  700.12(E)  - Revise the first sentence to read as follows:
Fuel cell systems shall be permitted to be used as a source of power for
emergency systems in R-2 occupancies and shall be of suitable rating and
capacity to supply and maintain the total load for not less than 6 hours
of full-demand operation.
  SECTION 700.26
  Section 700.26 - Revise to read as follows:
  700.26 Ground Fault Protection of Equipment. The alternate source  for
emergency systems shall not be permitted to have ground fault protection
for   equipment   with   automatic  disconnecting  means.  Ground  fault
indication of  the  emergency  source  shall  be  provided  pursuant  to
700.7(D).
  SECTION 700.27
  Section 700.27 - Revise to read as follows:
  700.27  Coordination. Emergency system(s) overcurrent devices shall be
selectively coordinated in the overcurrent range with  all  supply  side
overcurrent protective devices.
  SECTION 700.30
  Section  700.30  -  Add  a  new  section  700.30 under a new part "VII
Grounding" to read as follows:
  VII. Grounding
  700.30 General. Grounding shall be in accordance with  the  provisions
of Article 250.
  SECTION 700.31
  Section 700.31 - Add a new section 700.31 to read as follows:
  700.31 Control Circuits.
  (A)  Grounding.  Low  voltage control circuits and DC control circuits
derived from engine generator starting  batteries  shall  have  one  leg
grounded.

  (B)  Arrangements.  Control  circuits  shall  be  arranged  so that an
additional accidental ground shall not cause operation of the  connected
devices.
  (C)  Return Path. Control circuits shall not make use of the equipment
grounding conductor as a circuit path.
  ARTICLE 701
  Legally Required Standby Systems
  SECTION 701.5
  Subsection 701.5(A)-Revise to read as follows:
  (A) Acceptance Test. A  licensed  professional  shall  submit  to  the
department  a  testing  report of the complete system upon installation.
Such testing report shall be from an authorized testing entity.
  Subsection 701.5(E)-Revise to read as follows:
  (E) Installation Test Requirements. The  installation  test  shall  be
conducted and documented in accordance with 700.4(E).
  Subsection 701.5(F)-Add a new subsection 701.5(F) to read as follows:
  (F)  Maintenance  and Operational Testing. Maintenance and operational
testing shall be performed and documented in accordance with 700.4(F).
  SECTION 701.6
  Section 701.6-Add a new FPN to read as follows:
  FPN: Peak reduction program may require utility approval.
  SECTION 701.7
  Subsection 701.7(D)-Add a new subsection 701.7(D) to read as follows:
  (D) Mechanical Operation. Means  shall  be  provided  to  mechanically
operate the switch without hazard to personnel.
  Subsection 701.7(E)-Add a new subsection 701.7(E) to read as follows:
  (E)   Temporary   Connections   for   Portable  Generators.  Temporary
connection of a portable generator without transfer equipment  shall  be
permitted  where qualified persons maintain and supervise service of the
installation, and where  the  normal  source  of  supply  is  physically
isolated  by a lockable disconnecting means or by a disconnection of the
normal supply conductors. Portable generators shall  not  be  paralleled
except by special permission.
  Subsection 701.7(F)-Add a new subsection 701.7(F) to read as follows:
  (F)  Permanent  Connections for Portable Generators. Where a permanent
connection is made for a portable generator, a disconnecting  means  and
overcurrent  protection shall be provided at the point of connection for
the portable generator. Capacity shall not exceed the  capacity  of  the
permanent installation.
SECTION 701.8
Section 701.8 - Revise the first sentence to read as follows:
Audible  and  visual  signal devices shall be provided at a continuously
supervised location for the following purposes:
SECTION 701.10
Section 701.10 - Revise to read as follows:
701.10 Wiring and Conductors for Legally Required Standby Systems.
  (A) Wiring. Wiring for  legally  required  standby  systems  shall  be
permitted  to  occupy  the same raceways, cables, boxes, and cabinets as
other general wiring.
  (B) Conductors.
  (1) Ampacity. See 445.13.
  (2) Installation of Generator Conductors. Generator conductors to  the
first  disconnecting  means  shall  be  installed in accordance with the
requirements of Article 230.
  (3) Overcurrent Devices. There shall be no  limit  to  the  number  of
overcurrent devices connected to the generator terminal devices.
SECTION 701.11
Subsection 701.11(B)(2)-Revise to read as follows:

(2)   Internal   Combustion  Engines  as  Prime  Mover.  Where  internal
combustion engines are used as the prime mover, an on-site  fuel  supply
shall  be provided sufficient for not less than 6 hours of operations at
full demand load.
  Exception:  Legally required standby generators relying on natural gas
as a fuel supply shall not be  required  to  maintain  an  on-site  fuel
supply.
  FPN:  Some installations may require more than 6 hours of fuel supply.
See Articles 517 and 708.
Subsection 701.11(B)(6)-Add a new subsection  701.11(B)(6)  to  read  as
follows:
  (6)  Temporary  Generators.  The equipment grounding conductors of the
derived system shall be bonded to the grounding electrode system.
  FPN: See 250.34 for grounding of the generator frame.
  (a) Separately Derived System. Where a temporary portable generator is
a separately derived system, it shall be  grounded  in  accordance  with
250.30.
  (b)  Not  A  Separately  Derived  System.  Where  a temporary portable
generator is not a separately derived  system,  a  grounding  connection
shall not be made to the grounded circuit conductor.
  Subsection  701.11(F)-Revise  the  first  sentence to read as follows:
Fuel cell systems used as a source of power for legally required standby
systems shall be of suitable rating and capacity to supply and  maintain
the total load for not less than 6 hours of full-demand operation.
  SECTION 701.18
  Section 701.18 - Revise to read as follows:
  Section   701.18  Coordination.  Legally  required  standby  system(s)
overcurrent devices shall be selectively coordinated in the  overcurrent
range with all supply side overcurrent protective devices.
  ARTICLE 702
  Optional Standby Systems
  SECTION 702.2
  Section 702.2 - Revise the first sentence to read as follows:
  Those  systems  not  required  by  municipal, state, federal, or other
codes or by any governmental agency having jurisdiction.
  SECTION 702.6
  Section 702.6 - At the Exception, add a second  sentence  to  read  as
follows:
  Portable  generators  shall  not be paralleled with permanent optional
standby sources, except by special permission.
  SECTION 702.12
  Section 702.12 - Add a new section 702.12 to read as follows:
  702.12 Portable  and  Temporary  Generators.  Portable  and  temporary
generators shall comply with 700.6(G) and 700.12(B)(7).
  §  2.  Paragraph  3.9  of  subdivision  3  of  section 28-109.3 of the
administrative code of the city of New York, as added by  local  law  33
for the year 2007, is amended to read as follows:
   3.9. Emergency and standby power systems.

                               ARTICLE 705
            Interconnected Electric Power Production Sources

  SECTION 705.40
  Section 705.40 - Add a new paragraph after the first paragraph to read
as follows:
  Special  detection  methods  shall  be  required  to  determine that a
primary source supply system outage  has  occurred,  and  whether  there
should  be  automatic  disconnection.  When the primary source supply is

restored, special detection methods shall be required to limit  exposure
of power production to out-of-phase reconnection.
  Delete the Exception in its entirety.
  Delete FPN No. 1 in its entirety.
  SECTION 705.42
  Section  705.42  - Delete the words "or legally required standby" from
the last sentence and delete the Exception in its entirety.

                               ARTICLE 708
                Critical Operations Power Systems (COPS)

  ARTICLE 708
  Critical Operations Power Systems (COPS) -  Re-designate  FPN  as  FPN
No.2 and add FPN No.1 to read as follows:
  FPN  No.1:  Determination  of  a  Designated  Critical Operations Area
(DCOA) and the Critical Operations Power Systems (COPS)  needed  in  its
support  shall  be  made by the local, state or federal authority having
jurisdiction (AHJ) over the operation. Such authority will establish the
basis for the risk assessment, confirm acceptability of  the  mitigation
strategy and determine compliance with the requirements of this article.

                               ARTICLE 725
      Class 1, Class 2, and Class 3 Remote-Control, Signaling, and
                         Power-Limited Circuits

  SECTION 725.2
  Section 725.2 - Revise the first definition, "Abandoned Class 2, Class
3, and PLTC Cable" and FPN as follows:
  Abandoned  Class 2, Class 3 and PLTC Cable. Installed Class 2, Class 3
and PLTC Cable that are not terminated at equipment and  not  identified
for  future  use  with a tag at each end identifying the location of the
opposing end.
  FPN Replace "725.21" with "725.41".
  SECTION 725.3
  Subsection 725.3(C) - Revise the Exception to read as follows:
  Exception: Type CL2P or Type CLP3P cables shall be permitted for Class
2 and Class 3 circuits installed in other spaces used for  environmental
air in accordance with 725.154(A).
  SECTION 725.24
  Section  725.24  - Revise the third sentence and add a new FPN to read
as follows:
  Such cables shall be supported  by  approved  non-combustible  straps,
staples,   cable   ties,   hangers   or  similar  fittings  and  related
installation accessories designed and installed so as not to damage  the
cables.
  FPN:  Exposed wiring is intended to be securely held in place to avoid
entanglement of fire response personnel during fire conditions.
  SECTION 725.25
  Section 725.25 - Revise the title to read as follows:
  Abandoned Cables, Power Sources and Other Associated Equipment.
  Add an additional sentence at the end of  the  paragraph  to  read  as
follows:
  Abandoned  Cables,  Power Sources and other associated equipment shall
be removed.  Power sources and other associated equipment not tagged for
future use shall be de-energized.
  SECTION 725.127
  Section 725.127 - Revise the Exception by replacing "14 AWG" with  "12
AWG."

  SECTION 725.130
  Section  725.130(A)  -  Delete  Exception  No.  2 and the FPN in their
entirety.
  SECTION 725.136
  Section 725.136 - Delete the words "non-power limited fire alarm".
  Subsection 725.136(B) -  Delete  the  words  "non-power  limited  fire
alarm".
  Subsection  725.136(C)  -  Delete  the  words  "non-power limited fire
alarm".
  Subsection 725.136(D) -  Delete  the  words  "non-power  limited  fire
alarm".
  Subsection  725.136(H) - Delete the words "rigid nonmetallic conduit,"
and "liquidtight flexible nonmetallic conduit,".
  SECTION 725.139
  Section 725.139(E)(1) - Delete the subsection in its entirety.
  SECTION 725.154
  Section 725.154(A) - Revise the title and first and  second  sentences
to read as follows:
  (A) Spaces Used For Environmental Air. Cables installed in spaces used
for  environmental  air shall be Class CL2P or CL3P. Cables shall not be
installed in ducts or plenums.
                               ARTICLE 727
                  Instrumentation Tray Cable: Type ITC
  SECTION 727.4
  Section 727.4 - Revise to read as follows:
  727.4  Uses  Permitted.  Where  approved,  Type  ITC  cable  shall  be
permitted  to  be  used  as  follows  in industrial establishments where
conditions of maintenance and supervision  ensure  that  only  qualified
persons will service the installation:
  (1) In cable trays.
  (2) In raceways.
  (3)  In  hazardous  locations  as permitted in 501.10, 502.10, 503.10,
504.20, 504.30, 504.80 and 505.15.
  (4) Enclosed  in  a  smooth  metallic  sheath,  continuous  corrugated
metallic sheath, or interlocking tape armor applied over the nonmetallic
sheath  in  accordance  with  727.6.  The  cable  shall be supported and
secured at intervals not exceeding 1.83m (6 ft).
  (5) Between cable tray and equipment in lengths not  to  exceed  7.62m
(25 ft), where the cable complies with the crush and impact requirements
of  Type  MC  cable  and  is identified for such use. The cable shall be
supported and secured at intervals not exceeding 1.83m (6 ft).

                               ARTICLE 760
                           Fire Alarm Systems

  SECTION 760.1
  Section 760.1 - Revise FPN No. 1 by deleting the words "guard's tour,"
in first sentence and revise the last sentence to read as follows:
  For  further  information  on  the  installation  and  monitoring   of
integrity  requirements  for  fire  alarm  systems,  refer  to  NFPA 72,
National Fire Alarm Code, 2002 edition.
  Add a new FPN No. 3 to read as follows:
  FPN No. 3: See Section BC 907 of the NYC Building Code for  components
description and use.
  SECTION 760.2
  Section  760.2 - At the end of the definition of "Abandoned Fire Alarm
Cable" add the following words: "However, a tag shall be securely  fixed
to each end indicating location of opposing end."

  SECTION 760.3
  Subsection 760.3(B) - Delete the subsection in its entirety.
  Subsection 760.3(F) - Revise to read as follows:
  (F)  Optical Fiber Cables. Where optical fiber cables are utilized for
fire alarm circuits, the cables shall be  supervised  and  installed  in
raceway  per Articles 342, 344 or 358 in accordance with Article 770 and
terminated in equipment listed for fire alarm use.
  Subsection 760.3(G) - Revise to read as follows:
  (G) Installations of  Conductors  with  Other  Systems.  Installations
shall comply with 300.8 and 760.136.
  SECTION 760.24
  Section  760.24 - Add the following words at the end of the paragraph:
"Raceways, where installed shall be minimum 1.9cm (3/4 in.) trade  size.
See 760.52 and 760.131 for installations requiring raceways."
  SECTION 760.25
  Section 760.25 -  Add the following words at the end of the paragraph:
".. and securely fixed to each end indicating location of opposing end."
  SECTION 760.32
  Section 760.32 - Revise to read as follows:
  760.32  Fire  Alarm  Circuits  Extending  Beyond  One Building. Power-
limited fire alarm circuits that extend  beyond  one  building  and  run
outdoors  shall  be installed in raceway in accordance with Articles 342
or 344. Non-power limited fire alarm circuits  that  extend  beyond  one
building  and  run  outdoors shall meet the installation requirements of
Part 1 of Article 300 and the applicable sections of Part 1  of  Article
225  and shall be installed in raceway in accordance with Article 342 or
344.
  SECTION 760.33
  Section 760.33 -  Add a new section 760.33 to read as follows;
  760.33 Fire Alarm Circuit and Equipment Grounding. Fire alarm circuits
and equipment shall be grounded in accordance with Article 250 and shall
comply with the following requirements:
  (A) Grounding Electrode Conductor.  A  grounding  electrode  conductor
shall  be  sized  and  installed  in  accordance with Article 250, Table
250.66, using a minimum of 10 AWG, at the primary  and  secondary  power
source supplying the fire alarm system.
  (B)   Equipment   Grounding  Conductor.  A  separate  green  insulated
equipment grounding conductor shall be sized and installed in accordance
with Article 250, Table 250.122, using a minimum of 10 AWG, where  there
are  conduits supplying 120V to the fire command center, control unit or
distributed control cabinets.
  (C) Grounding Separately Derived Supply. A green  insulated  equipment
grounding  conductor  shall  be  sized  and installed in accordance with
Article 250, Table 250.122, using a minimum of 10  AWG,  in  distributed
cabinets  where  the 120V supply is not derived from the main fire alarm
power supply. In steel framed buildings,  an  additional  connection  to
local steel shall be permitted.
  SECTION 760.41
  Section  760.41  -  Delete  the section in its entirety and replace to
read as follows:
  760.41 Power Source Requirements. The  power  source  for  fire  alarm
circuits shall comply with the following:
  (A)  Primary  Power  Source. All fire alarm circuits shall be provided
with a primary power source. The primary power source shall be generated
electric power not exceeding 277/480 volts, supplied by utility  company
power  or  isolated  plant.  The  primary power supply to the fire alarm
system shall comply with the following:

  (1) Primary Power Supply for the  Fire  Alarm  System.  Primary  power
supply for the fire alarm system shall be connected to the primary power
source  ahead  of  all  building service disconnecting means so that the
building service disconnecting means can be opened without de-energizing
the  fire  alarm  supply. All utility metering of the fire alarm system,
including  disabling  or  removal  of  meters,  shall   maintain   power
continuity to the fire alarm system at all times.
  (2)  Limited  Interior  Fire  Alarm  Systems. Primary power supply for
sub-systems  or  other  limited  interior  fire  alarm  systems  may  be
connected to the power supply through the protected area of such systems
by  means of a connection ahead of the disconnecting means for the power
supply to the protected area.
  FPN: Sub-systems and limited interior fire alarm systems may also  use
the connected means defined in paragraph (1) where available.
  (B)  Secondary  Power  Source.  Where  an  emergency  power  system is
provided or required to be provided for emergency system loads, the fire
alarm  circuits  shall  be  provided  with  a  secondary  power  source.
Batteries  shall not be a substitute for connection to a secondary power
source.  The secondary power source shall comply with  the  requirements
for emergency power systems and/or emergency generator that are used for
emergency systems loads as articulated below:
  (1)  Generally.  Emergency  power systems complying with Chapter 27 of
the 2008 Building Code shall be permitted to serve as a secondary  power
source or
  (2)  Existing  Buildings.  Emergency  power  systems  and/or emergency
generators in existing buildings in compliance with Title 27, chapter 1,
subchapter 6, section 27-396.4 of the Administrative Code (also referred
to as the 1968 Building  Code)  shall  be  permitted  to  serve  as  the
secondary power source.
  The  secondary  power  supply  shall  be connected such that all other
disconnecting means serving other building emergency loads can be opened
without de-energizing the facility fire alarm secondary power supply.
  FPN: The use of a main  disconnecting  means  on  the  output  of  the
generator(s)  is  permitted  where  the disconnection of all other loads
does not interrupt  the  facility  fire  alarm  system  secondary  power
supply.
  (C)  Battery.  Regardless  of whether a secondary power source is also
provided, each fire alarm system and subsystem shall be equipped with  a
storage   battery  power  supply  sized  to  meet  the  operating  power
requirements of the system in accordance with (1), (2) or (3) below  and
shall  automatically  connect  to and operate the fire alarm system upon
failure of the primary or secondary power supply or  sources.  Batteries
shall  not  be  a  substitute for connection to a secondary power source
when a secondary power source is required  pursuant  to  subsection  (B)
above.
  (1) With Voice Communications Capability. Supervisory operation for 24
hours followed by full load operation for 6 hours for systems with voice
communications capability.
  FPN:  A  45  minute period of voice and alarm operation at the maximum
connected load shall be considered equivalent to 6 hours of total system
operation.
  (2) Without Voice Communications Capability. Supervisory operation for
24 hours followed by full load operation  for  15  minutes  for  systems
without voice communications capability.
  (3)   Sub-systems  or  Other  Limited  Interior  Fire  Alarm  Systems.
Supervisory operation for 24 hours followed by full load operation for 5
minutes for sub-systems or other limited  interior  fire  alarm  systems

operating  within  a  facility that reports to the overall facility fire
alarm system.
  (D)  Arrangement  of  Power  Sources.  One  source  of  power shall be
connected to the fire  alarm  system  at  all  times.  The  primary  and
secondary  power  sources  shall be arranged and controlled by automatic
transfer switches dedicated to the  fire  alarm  system  such  that  the
secondary  source  will  be  automatically  connected  to the fire alarm
system should the primary power source fail.  The  following  conditions
shall be observed:
  (1)  Intermediary  devices  between the fire alarm system power supply
and the power source, other than fused disconnect switches, transformers
and  automatic  transfer  switches  are  prohibited.   Such   disconnect
switches, transformers and automatic transfer switches shall supply only
the  fire  alarm  system  and  other  systems  specifically permitted by
applicable New York City rules and regulations.
  (2) The primary and secondary power source shall each be provided with
a means of disconnect from the fire alarm system. Each disconnect  shall
consist  of a fused disconnect switch, locked in the ON position and the
key shall be kept on premises and made  accessible  only  to  authorized
personnel.   Such  disconnect  shall  be  painted  red  and  permanently
identified as a fire alarm circuit and  labeled  as  to  system/location
served,  with  a  means  of  interrupting  the  unfused grounded and all
ungrounded conductors.
  (3) The fire alarm system fused disconnect switch on  the  transformer
secondary  side  shall  comply  with the requirements of the primary and
secondary power source fused disconnect  switches  pursuant  to  Article
240.
  (4)  For  buildings  served  at up to 300 volts to ground, the service
voltage shall be transformed to 208/120 volts  and  a  fire  alarm  fuse
disconnect  provided  within a circuit length of ten (10) feet, shall be
connected at the transformer secondary on the 208/120 volt  side.  Fused
cutouts  shall  be  provided  where  multiple  circuits  are required to
support the fire alarm system and related auxiliaries mounted in a fused
cutout panel suitable for the number of circuits needed.
  SECTION 760.43
  Section 760.43 - Revise the first sentence by replacing "14 AWG"  with
"12 AWG" and delete the last sentence.
  SECTION 760.45
  Section 760.45 - Delete the Exceptions and the FPN in their entirety.
  SECTION 760.46
  Section 760.46 - Revise to read as follows:
  760.46  NPLFA  Circuit  Wiring. Installation of non-power limited fire
alarm circuits shall  be  in  accordance  with  applicable  portions  of
110.3(B),  300.7,  300.15,  300.17  and  other  appropriate  articles of
Chapter 3 using raceway methods described in 342 and 344 or use Type  MI
Cable in accordance with 332.
  Exception No. 1: As provided in 760.48 through 760.53.
  Exception  No.  2:  Where  other  articles  of this Code require other
methods.
  SECTION 760.48
  Subsection 760.48(A) - Revise to read as follows:
  (A) NPLFA Circuits. Non-power limited fire  alarm  circuit  conductors
shall  not  be  permitted to occupy the same cable, enclosure or raceway
with circuit conductors of other systems.
  Subsection 760.48(B) - Revise to read as follows:
  (B) Fire Alarm with Power-Supply Circuits. Power supply and fire alarm
circuit conductors shall be permitted in the same enclosure  only  where
connected to the same equipment.

  SECTION 760.49
  Subsection 760.49(A) - Revise to read as follows:
  (A) Sizes and Use. Only copper conductors size 12 AWG and larger shall
be permitted to be used as NPLFA circuit conductors.
  Subsection  760.49(B)  -  Delete the FPN in its entirety and revise to
read as follows:
  (B) Insulation. Insulation on conductors shall  be  suitable  for  600
volts, 90 degrees C, and shall comply with Article 310. Conductors shall
be  Type  THHN,  THWN/THHN,  TFFN, TFN, FEP, RHH, RHW2, XHH, XHHW, MI or
CI-NYC Certified Cable. Application of conductor ampacity  shall  be  in
accordance with 110.14 for terminal device ratings.
  Subsection 760.49(C) - Revise to read as follows:
  (C)  Conductor  Materials. Conductors shall be solid copper up to size
10 AWG. Stranded copper conductors shall be used for  sizes  8  AWG  and
larger.
  SECTION 760.51
  Subsection  760.51(A)  -  Delete  the  words "and Class 1 Circuits" in
title and "and Class 1 circuit" in text.
  Subsection 760.51(B) - Delete the subsection in its entirety.
  Subsection 760.51(C) - Revise to read as follows:
  (C) Cable Trays. Where non-power limited fire alarm circuit conductors
are installed in cable trays,  they  shall  comply  with  392.9  through
392.11  and  shall  be  barriered from any other wiring installed in the
cable tray.
  Section 760.52
  Section 760.52 - Add a new section 760.52 to read as follows:
  760.52 Mechanical Execution of Work. Installation  shall  comply  with
the following:
  (A)  Mechanical  Rooms, Elevator Rooms, Garages and Loading Docks. All
wiring installed up to 2.4m (8 ft.) above the finished floor in garages,
loading docks, mechanical rooms,  and  elevator  rooms  shall  meet  the
installation requirements of Article 344. All wiring installed over 2.4m
(8   ft.)   above   the  finished  floor  shall  meet  the  installation
requirements of Articles 332, 342, 344 or 358.
  Exception: For mechanical rooms and elevator rooms having a floor area
of less than 900 square feet, installation  pursuant  to  Articles  332,
342, 344 or 358 is permitted without height limitation.
  (B)   Installation.   Installation  of  raceways,  boxes,  enclosures,
cabinets and wiring shall conform to the following requirements:
  (1) Covers of boxes, enclosures and cabinets shall be painted red  and
permanently identified as to use.
  (2)  Penetrations  through  rated  walls, ceilings and floors shall be
fire stopped.
  (3) Raceways or wiring shall not penetrate  the  top  of  any  control
equipment cabinet or enclosure.
  (4)  Raceways  installed  up  to  2.4m  (8 ft.) in stairways shall not
reduce or obstruct required stairway radius or egress path.
  SECTION 760.53
  Section 760.53 - Delete the section in its  entirety  and  replace  to
read as follows:
  760.53  Fire  Alarm  Circuit Integrity (CI) Cable. Cables suitable for
use in fire alarm systems to ensure survivability of  critical  circuits
during a specified time under fire conditions shall be listed as circuit
integrity  cable.  Cables  so  identified  shall have the classification
"CI-NYC certified fire alarm cable".
  SECTION 760.121
  Subsection 760.121(A) - Delete FPN Nos. 1 and 2 in their entirety.
  SECTION 760.124

  Section 760.124 - Delete the FPN in its entirety.
  SECTION 760.127
  Section 760.127 - Delete the Exception in its entirety.
  SECTION 760.130
  Subsection  760.130(A)  -  Revise  Exception  No. 2 by adding "760.51"
after "760.49", delete Exception No. 3  and  delete  the  FPN  in  their
entirety.
  Subsection 760.130(B) - Revise the last sentence to read as follows:
  Devices  shall  be  installed  in  accordance  with Sections 110.3(B),
300.11(A) and 300.15 with all wiring supported  independently  from  the
building structure.
  Subsection 760.130(B)(1) - Revise to read as follows:
  (1) Exposed or Fished in Concealed Spaces. In raceway or exposed above
2.4m  (8  ft.)  on  the  surface  of  ceiling and sidewalls or fished in
concealed spaces, cable splices or terminations shall be made in  listed
fittings,   boxes,   enclosures,   fire  alarm  devices  or  utilization
equipment. Where installed exposed,  cables  shall  be  supported  at  a
maximum of 1.5m (5 ft.) spacing and installed in such a way that maximum
protection against physical damage is afforded by building construction.
Where  located  within  2.4m  (8  ft.)  of  the  floor,  cables shall be
installed in raceway as per Article 342, 344, 358 or 386.
  Subsection 760.130(B)(2) - Revise to read as follows:
  (2) Passing Through a Floor or Wall. In metal raceways  where  passing
through  a  floor  or  wall to a height of 2.4m (8 ft.) above the floor,
unless adequate protection can be afforded by building  construction  as
per 760.130(B)(1) or unless an equivalent solid guard is provided.
  FPN:  Protection by building construction includes, but is not limited
to, raised floors, shafts, telephone and communications equipment  rooms
and closets, and rooms used exclusively for fire alarm equipment.
  Subsection   760.130(B)(3)  -  Delete  the  words  "rigid  nonmetallic
conduit,".
  Subsection 760.130(B)(4) - Add a new subsection 760.130(B)(4) to  read
as follows:
  (4)  Terminations  and Splices. Terminations and splices shall be made
with terminal blocks and in listed  fittings,  boxes,  enclosures,  fire
alarm  devices  or  utilization  equipment.  Splices shall be limited to
locations where the  conditions  of  installation  require  the  use  of
splices.  Splices and terminations in riser cables are prohibited except
where made in fire alarm equipment terminal cabinets.  Conductors  shall
be  mechanical connections listed in accordance with UL 486 (2003) A & C
or  if  soldered,  conductors  shall  first  be  joined  so  as  to   be
mechanically  and  electrically  secure  prior to soldering. Temperature
rating of completed splices shall be equal to or exceed the  temperature
rating of the highest rated conductor.
  SECTION 760.131 -
  Section 760.131 - Add a new section 760.131, to read as follows:
  760.131  Mechanical  Execution  of Work. Installation shall conform to
the following requirements:
  (A) Mechanical Rooms, Elevator Rooms, Garages and Loading  Docks.  All
wiring installed up to 2.4m (8 ft.) above the finished floor in garages,
loading  docks,  mechanical  rooms,  and  elevator  rooms shall meet the
installation requirements of Article 344.
  Exception: For mechanical rooms and elevator rooms having a floor area
of less than 900 square feet, installation  pursuant  to  Articles  332,
342, 344 or 358 is permitted without height limitation.
  (B)  Extinguishing  Systems.  Extinguishing  and  suppression  systems
activated by automatic fire detection and using fire alarm cables  shall
be  installed  pursuant  to  Articles 332, 342, 344 or 358. Such systems

shall include, but not  be  limited  to,  pre-action  sprinkler,  deluge
sprinkler,  water mist, clean air agent, Halon, range hood, CO2, and dry
chemicals.
  (C)   Installation.   Installation  of  raceways,  boxes,  enclosures,
cabinets and wiring shall conform to the following requirements:
  (1) Covers of boxes, enclosures and cabinets shall be painted red  and
permanently identified as to use.
  (2)  Penetrations  through  rated  walls, ceilings and floors shall be
fire stopped.
  (3) Raceways or wiring shall not penetrate  the  top  of  any  control
equipment cabinet or enclosure.
  (4)  Raceways  installed  up  to  2.4m  (8 ft.) in stairways shall not
reduce or obstruct required stairway radius or egress path.
  (5) Cables shall be secured by cable ties, straps or similar  fittings
designed  and  installed so as to not damage cables. Such fittings shall
be secured in place at intervals not exceeding 1.5m (5  ft.)  on  center
and within 0.3m (1 ft.) of associated cabinet, enclosure, or box.
  SECTION 760.136
  Subsection  760.136(D)(2)(a)  -  Replace  "Type  FPL,  FPLR,  FPLP  or
permitted substitute cables" with "type FPLP 'NYC certified  fire  alarm
cable'" or other NYC certified fire alarm cable".
  Subsection 760.136(D)(2)(b) - Delete the subsection in its entirety.
  Subsection  760.136(F)  -  From  the  first  sentence,  delete  "rigid
nonmetallic conduit" and "liquidtight flexible nonmetallic conduit".
  Subsection 760.136(G)(1)(b) - Revise to read as follows:
  (b) all of the power-limited fire alarm circuit conductors  are  in  a
raceway or metal-sheathed or metal-clad cables.
  SECTION 760.139
  Section 760.139 - Delete the section in its entirety.
  SECTION 760.142
  Section 760.142 - Revise to read as follows:
  760.142 Conductor Size. Conductors shall not be smaller than 18 AWG in
size.
  SECTION 760.143
  Section 760.143 - Revise to read as follows:
  760.143  Support  of  Conductors.  Power-limited  fire  alarm  circuit
conductors shall not be strapped, taped, or attached by any means to the
exterior of any piping, duct, conduit, or raceway as a means of support.
  SECTION 760.154
  Subsection 760.154(A) - Revise to read as follows:
  (A)  Cables  in  Other  Spaces  Used  for  Environmental  Air.  Cables
installed in other spaces used for environmental air, or where permitted
to  run  exposed  in other areas, shall be Type FPLP "NYC Certified Fire
Alarm Cable".
  Subsection 760.154(B)(1) - Replace "Type FPLR" with  "Type  FPLP  'NYC
Certified  Fire Alarm Cable' or other NYC Certified Fire Alarm Cable" in
each of two locations.
  Subsection 760.154(B)(2) - At the beginning of the  sentence,  replace
"Other cables" with "FPLP 'NYC Certified Fire Alarm Cable'".
  Subsection  760.154(C)  -  Delete  the  subsection in its entirety and
revise to read as follows:
  (C) Other  Wiring  Within  Buildings.  Cables  installed  in  building
locations  other  than  those covered in 760.154(A) or (B) shall be Type
FPLP "NYC Certified Fire Alarm Cable."
  Subsection 760.154(D) - Revise the subsection to read as follows:
  (D) Fire Alarm Cable Substitutions. Substitutions of  Type  FPLP  "NYC
Certified  Fire  Alarm  Cable"  or other NYC Certified Fire Alarm Cables
shall not be permitted.

  Delete the Figure, Table and FPN in their entirety.
  SECTION 760.176
  Section 760.176(G) - Delete the first sentence of the first paragraph,
the FPN and the Table in their entirety.
  SECTION 760.179
  Section 760.179 - Revise the title to read as follows:
  760.179  Listing  and  Marking of PLFA Cables and Insulated Continuous
Line-Type Fire Detectors.
  Subsection 760.179(B) - Revise to read as follows:
  (B)  Conductor  Size.  The   size   of   conductors   in   single   or
multi-conductor cables shall not be smaller than 18 AWG.
  Subsection  760.179(D)  - Delete the FPN in its entirety and revise to
read as follows:
  (D) Type FPLP. Type FPLP  power-limited  fire  alarm  cable  shall  be
listed  to  UL 1424-05, Standard for Cables for Power-Limited-Fire-Alarm
Circuits  with  the  listing  agency  certifying  compliance  with   the
following requirements:
  (1)  Type  FPLP  only;  minimum  insulation thickness 15 mils; minimum
temperature 150 C.
  (2) Red colored jacket overall; minimum thickness 25 mils.
  (3) Cable marked as per UL 1424 must bear additional description "ALSO
CLASSIFIED NYC CERT. FIRE ALARM CABLE," legible without removing jacket.
  Subsection 760.179(E) - Delete the subsection in its entirety.
  Subsection 760.179(F) - Delete the subsection in its entirety.
  Subsection 760.179(G)  -  Revise  by  deleting  "CI"  from  the  first
sentence  of  the first paragraph and replacing with "CI- 'NYC Certified
Circuit Integrity Fire Alarm Cable'" and  deleting  "(E),  (F)"  in  the
second sentence of the first paragraph.
  Subsection 760.179(H) - Replace "Type FPLP, FPLR, or FPL cable" at end
of sentence with "Type FPLP 'NYC certified fire alarm cable'".
  Subsection  760.179(I)  -  Delete  subsection 760.179(I) and add a new
760.179(I) to read as follows:
  (I) Cable Marking. The  cable  shall  be  marked  in  accordance  with
subsection 760.179(D)(3) and its rating as NYC Cert. Fire Alarm Cable or
NYC Cert. Circuit Integrity Cable.
  Subsection  760.179(J)  -  Delete  "through (F)" in fourth line of the
paragraph.
  Subsection 760.179(K) - Add  new  subsection  760.179(K)  to  read  as
follows:
  760.179(K)   Listed   Fire-Rated  Assemblies.  MI  cable  meeting  the
requirements of Article 332 or listed fire-rated assemblies that have  a
minimum  fire  rating  of  2  hours shall be permitted when installed in
accordance with the listing requirements.
                               ARTICLE 770
                    Optical Fiber Cables and Raceways
  SECTION 770.2
  Section 770.2 - Revise the  definition  of  "Abandoned  Optical  Fiber
Cable" to read as follows:
  Abandoned  Optical  Fiber Cable. Installed optical fiber cable that is
not terminated at equipment other than a connector  and  not  identified
for  future use with a tag securely fixed to each end and indicating the
location of the opposing end.
  SECTION 770.3
  Section 770.3 - Revise first sentence to read as follows:
  Circuits and equipment shall comply with 770.3(A), (B) and (C).
  Subsection 770.3(C) -  Add  a  new  subsection  770.3(C)  to  read  as
follows:

  (C)  Electric closets. Fiber optic circuits and equipment shall not be
installed in electric closets.
  SECTION 770.25
  Section  770.25  -  Revise  title  to read "Abandoned Cables and Power
Sources." and add a new third sentence to read as follows:
  Abandoned Power  Sources  and  other  associated  equipment  shall  be
removed.    Power  sources and other associated equipment not tagged for
future use shall be de-energized.
  SECTION 770.48
  Subsection 770.48(A) - Revise subsection 770.48(A) to read as follows:
  (A) Conductive  and  Nonconductive  Cables.  Unlisted  conductive  and
nonconductive  outside  plant optical fiber cables shall be permitted to
be installed in locations as described in 770.154(C), where  the  length
of  the  cable  within the building, measured from its point of entrance
does not exceed 15 m (50 ft) and the cable enters the building from  the
outside  and  is  terminated  in an enclosure. All other cables shall be
considered to be within the building.
  Exception No. 1: In areas of  special  flood  hazard,  as  defined  in
Section  G201.2  of  Appendix  G of the New York City Building Code, the
length of such cabling may exceed 15 m (50 ft) to the  extent  necessary
to  provide  direct  delivery  to a level 1.52 m (5 ft) above the design
flood elevation specified in Section 7.1 (Table 7-1) of  Section  G501.1
of Appendix G of the New York City Building Code, provided that:
  (1)  Such  cabling  shall  not extend more than 3 m (10 ft) beyond the
lowest story having its floor above the design flood elevation; and
  (2)  Such  cabling  shall  not  be  installed  in   ducts   used   for
environmental air or in plenums used for environmental air.
  Exception  No.  2:  In  areas  designated  within  a shaded X-Zone, as
defined in Section G201.2 of Appendix G of the New  York  City  Building
Code,  the  length of such cabling may exceed 15 m (50 ft) to the extent
necessary to provide direct delivery to a level 1.52 m (5 ft) above  the
500-year  flood elevation, as defined in Section G201.2 of Appendix G of
the New York City Building Code, provided that:
  (1) Such cabling shall not extend more than 3 m  (10  ft)  beyond  the
lowest story having its floor above the design flood elevation; and
  (2)   Such   cabling   shall  not  be  installed  in  ducts  used  for
environmental air or in plenums used for environmental air.
  FPN No. 1: Splice cases or terminal boxes, both metallic  and  plastic
types,  typically  are  used  as  enclosures for splicing or terminating
optical fiber cables.
  FPN No. 2: See 770.2 for the definition of Point of Entrance.
  Subsection 770.48(B) - Delete the words "Article 352, Rigid  Polyvinyl
Chloride Conduit: Type PVC".
  SECTION 770.100
  Subsection  770.100(A)(3) - Revise the first sentence by replacing "14
AWG" with "12 AWG".
  SECTION 770.133
  Subsection 770.133(A)  -  Delete  the  words  "non-power-limited  fire
alarm" throughout.
  Subsection 770.133(B)(2) - Delete the subsection in its entirety.
  Subsection  770.133(D)  -  Add  a new subsection 770.133(D) to read as
follows:
  (D) Electric Closets. Equipment and cabling shall not be installed  in
electric closets.
  SECTION 770.154
  Subsection 770.154(A) - Revise to read as follows:
  (A)  Spaces  Used for Environmental Air. Cables shall not be installed
in ducts or plenums. Cables installed in spaces used  for  environmental

air  shall be Type OFNP or OFCP. Abandoned cables shall not be permitted
to remain. Types OFNR, OFCR, OFNG, OFN, OFCG, and OFC  cables  installed
in  compliance  with  300.22  shall  be permitted. Listed plenum optical
fiber raceways shall be permitted in spaces used to convey environmental
air  or as described in 300.22(c). Only Type OFNG, and OFCP cables shall
be permitted to be installed in these raceways.

                                Chapter 8
                         Communications Systems
                               ARTICLE 800
                         Communications Circuits

  SECTION 800.2
  Section 800.2 - Revise the  definition  of  "Abandoned  Communications
Cable" to read as follows:
  Abandoned Communications Cable. Installed communications cable that is
not  terminated  at  both ends at a connector or other equipment and not
identified for future use with a tag securely  fixed  to  each  end  and
indicating the location of the opposing end.
  SECTION 800.24
  Section 800.24 - Revised the second sentence to read as follows:
  Cables  installed  exposed  on  the  surface of ceilings and sidewalls
shall be supported by the building structure in such a manner  that  the
cable  will  not  be  damaged by normal building use or present a safety
hazard.
  SECTION 800.25
  Section 800.25 - Revise the  title  and  first  sentence  to  read  as
follows:
  800.25  Abandoned  Cables, Power Sources & Other Associated Equipment.
The accessible portion of abandoned communications cables, power sources
and other special equipment shall be removed. Cables, power sources  and
other special equipment not tagged for future use shall be de-energized.
  SECTION 800.48
  Section  800.48  -  Add two exceptions to the end of section 800.48 to
read as follows:
  Exception No. 1: In areas of  special  flood  hazard,  as  defined  in
Section  G201.2  of  Appendix  G of the New York City Building Code, the
length of such cabling may exceed 15 m (50 ft) to the  extent  necessary
to  provide  direct  delivery  to a level 1.52 m (5 ft) above the design
flood elevation specified in Section 7.1 (Table 7-1) of  Section  G501.1
of Appendix G of the New York City Building Code, provided that:
  (1)  Such  cabling  shall  not extend more than 3 m (10 ft) beyond the
lowest story having its floor above the design flood elevation; and
  (2)  Such  cabling  shall  not  be  installed  in   ducts   used   for
environmental air or in plenums used for environmental air.
  Exception  No.  2:  In  areas  designated  within  a shaded X-Zone, as
defined in Section G201.2 of Appendix G of the New  York  City  Building
Code,  the  length  of such cabling may exceed 15m (50 ft) to the extent
necessary to provide direct delivery to a level 1.52m (5 ft)  above  the
500-year  flood elevation, as defined in Section G201.2 of Appendix G of
the New York City Building Code, provided that:
  (1) Such cabling shall not extend more than  3m  (10  ft)  beyond  the
lowest story having its floor above the design flood elevation; and
  (2)   Such   cabling   shall  not  be  installed  in  ducts  used  for
environmental air or in plenums used for environmental air.
  SECTION 800.100
  Subsection 800.100(A)(3) - Replace "14 AWG" with "12 AWG".
  SECTION 800.133

  Section 800.133 - Revise to read as follows:
  800.133 Communications wires, cables and equipment inside of buildings
shall  not  be  installed  in  electric  closets  and  shall comply with
800.133(A) through (D).
  Subsection 800.133(D) - Add a new subsection  800.133(D)  to  read  as
follows:
  (D)  Electric  Closets. Communications equipment and cabling shall not
be installed in Electric Closets.
  SECTION 800.154
  Subsection 800.154(A) - Revise to read as follows:
  (A) Spaces Used for Environmental Air. Cables installed in spaces used
for environmental air shall be Type CMP. Cables and raceways  shall  not
be  installed  in  ducts  or    plenums.  Abandoned  cables shall not be
permitted to remain. Types CMP, CMR, CMG, CM, and CMX and communications
wire installed in compliance with  300.22  shall  be  permitted.  Listed
plenum  communications  raceways  shall  be permitted to be installed in
spaces used for environmental air as described in 300.22(C).  Only  Type
CMP cable shall be permitted to be installed in raceways.
  Subsection  800.154(F)  - Add the following sentence at the end of the
subsection:
  Installation  of  hybrid  power  and  communications  cable  shall  be
performed by licensed master or special electricians.
                                ARTICLE 810
                     Radio and Television Equipment
  Section 810.58
  Subsection 810.58(C) - Replace "14AWG" with "12 AWG".
                               ARTICLE 820
       Community Antenna Television and Radio Distribution Systems
  SECTION 820.2
  Section  820.2 - Revise the definition of "Abandoned Coaxial Cable" to
read as follows:
  Abandoned  Coaxial  Cable.  Installed  coaxial  cable  that   is   not
terminated   at  equipment  other  than  a  coaxial  connector  and  not
identified for future use with a tag securely  fixed  to  each  end  and
indicating the location of the opposing end.
  SECTION 820.25
  Section 820.25 - Revise to read as follows:
  820.25  Abandoned  Cables. The accessible portion of abandoned coaxial
cables shall be removed. Where a coaxial cable is identified for  future
use with a tag, the tag shall be of sufficient durability.
  SECTION 820.100
  Subsection 820.100(A)(3) - Replace "14 AWG" with "12 AWG".
  SECTION 820.133
  Subsection   820.133(A)(1)   Exception   No.  1  -  Delete  the  words
"non-power-limited fire alarm,".
  Subsection 820.133(A)(1)(a)(2) -  Delete  820.133(A)(1)(a)(2)  in  its
entirety.
  Subsection   820.133(A)(2)   Exception   No.  1  -  Delete  the  words
"non-power-limited fire alarm,".
  Subsection 820.133(A)(2) - Delete Exception No. 2 in its entirety.
  Subsection 820.133(C) - Add a new subsection  820.133(C)  to  read  as
follows:
  (C) Electric Closets. Television and radio equipment and cabling shall
not be installed in Electric Closets.
  SECTION 820.154
  820.154(A) Revise the title to read as follows:
  (A) Spaces Used for Environmental Air.

                               ARTICLE 830
           Network - Powered Broadband Communications Systems

  SECTION 830.2
  Section  830.2  -  Revise the definition of "Abandoned Network-Powered
Broadband Communications Cable" to read as follows:
  Abandoned Network-Powered Broadband  Communications  Cable.  Installed
network-powered broadband communications cable that is not terminated at
equipment  other than a connector and not identified for future use with
a tag securely fixed to each end and  indicating  the  location  of  the
opposing end.
  SECTION 830.25
  Section 830.25 - Revise the second sentence to read as follows:
  Where  a  network-powered broadband communications cable is identified
for future use with a tag, the tag shall be of sufficient durability.
  SECTION 830.100
  Subsection 830.100(A)(3) - Replace "14 AWG" with "12 AWG".
  SECTION 830.133
  Subsection  830.133(A)(1)(b)(2)  -  Delete  the  subsection   in   its
entirety.
  Subsection   830.133(A)(1)(d)   -  Delete  the  following  words  from
Exception No. 1: "non-power limited fire alarm".
  Subsection 830.133(D) - Add a new subsection  830.133(D)  to  read  as
follows:
  (D)  Electric  Closets. Broadband communications equipment and cabling
shall not be installed in Electric Closets.