Article 801 - ENACTMENT AND UPDATE OF THE NEW YORK CITY MECHANICAL CODE

Section 28-801.1

Section 28-801.1

  §  28-801.1  Update.  No later than the third year after the effective
date of this section 28-801.1  and  every  third  year  thereafter,  the
commissioner  shall  submit to the city council proposed amendments that
he or she determines should be made to this code to bring it up to  date
with  the  latest  edition  of  the  International  Mechanical  Code  or
otherwise modify the provisions  thereof.  In  addition,  prior  to  the
submission  of such proposal to the city council, such proposal shall be
submitted to an  advisory  committee  established  by  the  commissioner
pursuant to this title for review and comment.

Section 28-801.2

Section 28-801.2

  §  28-801.2  Enactment  of  the New York city mechanical code. The New
York city mechanical code based on the 2003 edition of the International
Mechanical Code  published  by  the  International  Code  Council,  with
changes that reflect the unique character of the city, is hereby adopted
to read as follows:

EXPLANATION - Matter in braces { } in this document is superscript.

EXPLANATION - Matter in brackets [ ] in this document is subscript.
                    THE NEW YORK CITY MECHANICAL CODE
                                CHAPTER 1
                             ADMINISTRATION
                             SECTION MC 101
                                 GENERAL
  101.1  Title.  This  code  shall be known and may be cited as the "New
York City Mechanical Code," "NYCMC" or "MC". All section numbers in this
code shall be deemed to be preceded by the designation "MC".
  101.2 Scope.  This  code  shall  regulate  the  design,  installation,
maintenance,  alteration  and  inspection of mechanical systems that are
permanently installed and utilized to provide control  of  environmental
conditions  and related processes within buildings. This code shall also
regulate those mechanical  systems,  system  components,  equipment  and
appliances  specifically  addressed herein. The installation of fuel gas
distribution piping and equipment, fuel gas-fired  appliances  and  fuel
gas-fired  appliance  venting systems shall be regulated by the New York
City Fuel Gas Code.
  101.3 Intent. The purpose of this code is to provide minimum standards
to safeguard life or limb, health,  property,  public  welfare  and  the
environment  by  regulating  and  controlling  the design, construction,
installation, quality of materials, location, operation and  maintenance
or use of mechanical systems.
  101.4  Severability.  If  a  section,  subsection, sentence, clause or
phrase of this code is, for any reason,  held  to  be  unconstitutional,
such decision shall not affect the validity of the remaining portions of
this code.
                             SECTION MC 102
                              APPLICABILITY
  102.2  General. The provisions of this code shall apply to all matters
affecting or relating to  structures  and  premises,  as  set  forth  in
Section  101. Where, in a specific case, different sections of this code
specify  different  materials,  methods   of   construction   or   other
requirements, the most restrictive shall govern.
  102.2 Existing installations. Except as otherwise provided for in this
chapter  or  elsewhere  in this code, a provision in this code shall not
require the removal, alteration  or  abandonment  of,  nor  prevent  the
continued  utilization  and maintenance of, a mechanical system lawfully
in existence on the effective date of this code.
  102.3 Maintenance. Mechanical systems,  both  existing  and  new,  and
parts  thereof  shall  be  maintained  in  proper operating condition in
accordance  with  the  original  design  and  in  a  safe  and  sanitary
condition. Devices or safeguards that are required by this code shall be
maintained in compliance with the applicable provisions under which they
were  installed.  The  owner  shall  be  responsible  for maintenance of
mechanical systems. To determine compliance  with  this  provision,  the
commissioner  shall  have  the  authority to require existing mechanical
systems to be inspected.
  102.4  Additions,  alterations  or  repairs.  Additions,  alterations,
renovations   or  repairs  to  a  mechanical  system  shall  conform  to

requirements for a new mechanical system without requiring the  existing
mechanical  system  to comply with all of the requirements of this code.
Additions, alterations or repairs shall not cause an existing mechanical
system  to  become  unsafe,  hazardous  or  overloaded. Minor additions,
alterations, renovations and  repairs  to  existing  mechanical  systems
shall meet the provisions for new construction, unless such work is done
in the same manner and arrangement as was in the existing system, is not
hazardous and is approved.
  102.5  Change  in  occupancy.  Refer  to  Chapter 1 of Title 28 of the
Administrative Code.
  102.6 Reserved.
  102.7 Reserved.
  102.8 Referenced standards. The standards referenced herein  shall  be
those  that  are listed in Chapter 15 and in the rules of the department
and such standards shall be considered as part of  the  requirements  of
this  code  to  the  prescribed  extent  of  each  such reference. Where
differences occur between provisions of this  code  and  the  referenced
standards, the provisions of this code shall apply. Refer to Article 103
of  Chapter  1  of  Title  28  of the Administrative Code for additional
provisions relating to referenced standards.
  102.9 Requirements not covered by this  code.  Requirements  necessary
for  the  strength,  stability  or  proper  operation  of an existing or
proposed mechanical system, or for the public safety, health and general
welfare, not specifically covered by this code, shall be  determined  by
the commissioner.
                             SECTION MC 103
                         DEPARTMENT OF BUILDINGS
  103.1  General.  Refer  to  the New York City Charter and Chapter 1 of
Title 28 of the Administrative Code.
                             SECTION MC 104
           DUTIES AND POWERS OF THE COMMISSIONER OF BUILDINGS
  104.1 General. The commissioner shall have  the  authority  to  render
interpretations and to adopt rules establishing policies, and procedures
to   clarify   and   implement   the   provisions  of  this  code.  Such
interpretations and rules shall be in compliance  with  the  intent  and
purpose  of  this code. Refer to the New York City Charter and Chapter 1
of Title  28  of  the  Administrative  Code  for  additional  provisions
relating to the authority of the Commissioner of Buildings.
                             SECTION MC 105
                                 PERMITS
  105.1  General.  Permits  shall comply with this section, with Article
105 of Chanter 1 of Title  28  of  the  Administrative  Code,  and  with
requirements found elsewhere in this code.
  105.2   Required.  Any  owner  or  authorized  agent  who  intends  to
construct.   add to,  alter,  repair,  move,  demolish,  or  change  the
occupancy  of  a  building  or  structure, or to erect, install, add to,
alter, repair,  remove,  convert  or  replace  any  gas,  mechanical  or
plumbing,  system,  the installation of which is regulated by this code,
or to cause any such work to be done, shall first make  application  for
construction  document approval in accordance with Chapter 1 of Title 28
of the Administrative Code and this  chapter  and  obtain  the  required
permit.
  105.3  Work exempt from permit. Exemptions from permit requirements of
this code as  authorized in Chapter 1 of Title 28 of the  Administrative
Code  and  the  rules  of  the  department  shall not be deemed to grant
authorization for any work to be done in any manner in violation of  the
provisions of this code or any other laws or rules.

  105.4  Validity  of permit. The issuance or granting of a permit shall
not be construed to be a permit for, or an approval of, any violation of
any of the provisions  of  this  code  or  of  any  other  law.  Permits
presuming  to give authority to violate or cancel the provisions of this
code  or other law shall not be valid. The issuance of a permit based on
construction documents and other data shall not prevent the commissioner
from requiring the correction of errors in  the  construction  documents
and other data. The commissioner is also authorized to prevent occupancy
or  use  of  a structure where in violation of this code or of any other
law.
                             SECTION MC 106
                         CONSTRUCTION DOCUMENTS
  106.1 General. Construction documents shall comply with Article 104 of
Chapter 1 of title 28 of the Administrative Code  and  other  applicable
provisions of this code and its referenced standards.  Such construction
documents  shall be coordinated with architectural, structural and means
of egress plans.
  106.2 Required documents.  The  applicant  shall  submit  all  of  the
documents  specified  in Sections 106.3 through 106.10 as appropriate to
the nature and extent of the work proposed. Construction documents shall
indicate the heating, ventilation, refrigeration, and  other  mechanical
work  to  be  performed, so drawn as to conform to the architectural and
structural aspects of the building and to show in detail compliance with
this code.
  106.2.1  Composite  plans.  Composite  plans  showing  compliance   of
architectural,  structural,  and  mechanical  parts of a building may be
submitted provided that a  clear  understanding  of  each  part  is  not
impaired.
  106.3  Lot diagram. The lot diagram shall be provided where applicable
to the work proposed, including but not limited to the  installation  of
exterior or rooftop equipment.
  106.4  Building  classification  statement.  Where  applicable  to the
proposed work, the statement shall identify:
  1. The occupancy group or groups that apply to parts of  the  building
in accordance with Section 302 of the New York City Building Code;
  2.  The  occupancy  group of the main use or dominant occupancy of the
building;
  3. The construction class of the building in accordance  with  Section
602 of the New York City Building Code;
  4.  The  structural occupancy category in accordance with Table 1604.5
of the New York City Building Code;
  5. The height of the building as defined in Section 502.1 of  the  New
York City Building Code;
  6. The applicable measurements to the highest and lowest level of fire
department access; and
  7. Whether the building is inside or outside of the fire districts.
  106.5  Fuel-burning and fuel-oil storage equipment plans. Construction
documents for fuel-burning and fuel oil storage equipment shall  contain
plans that include the following data and information:
  1.  Diagrams  of all distribution piping, including vent and filtering
for oil systems, and all safety cut-off and relief devices and valves in
piping: indications of the sizes of distribution piping to be  used  and
the   fire   resistive  ratings  of  the  shafts  or  spaces  containing
distribution piping where required to be fire rated.
  2. Diagrammatic floor plans showing the size, location,  material  for
all fuel oil and transfer distribution piping and related equipment.
  3.  Floor  plans  or partial floor plans showing the location, layout,
size, and listing information for  all  fuel-burning  equipment,  tanks,

vents,  and  chimneys. The plans shall also indicate the method or means
of providing air to the equipment  space,  including  duct  and  opening
sizes.
  4.  Plans  indicating  the location and type of any relevant smoke and
heat detectors, alarm, and fire extinguishing systems.
  5. Seismic protection and restraint details for piping  and  equipment
as required by Chapter 16 of the New York City Building Code.
  6.  Details  indicating  the  location,  size  and  materials  for all
breechings; the thickness and type  of  insulation  materials;  and  the
clearances  from  combustible  walls,  partitions,  and ceiling; and the
fire-resistive ratings of rooms and spaces containing the equipment.
  7. Details describing the type, material, listing information, height,
and termination distances to  adjacent  properties  and  structures  for
chimneys and vents.
  8.  Details  showing  structural  supports  for fuel-burning equipment
where required.
  9. A statement as to the kind or grade of fuel to be used.
  10. Plans  indicating  the  location,  arrangement,  size,  load,  and
maximum capacity of the burning, storage and fuel-pumping equipment.
  11.  In  areas  of special flood hazards, construction documents shall
comply with Appendix G of the New York City Building Code.
  106.6 Heating systems.  Construction  documents  for  heating  systems
shall  include  the  temperature  to be maintained in every room and the
output capacity in BTU per hour of the central heating source.
  106.7 Boilers. Construction documents for boiler  installations  shall
indicate  the  output  capacity in BTU per hour, the operating weight of
each boiler, the pressure setting of the relief valves, and  such  other
data and information as required by this code.
  106.8 Air conditioning and ventilating systems. Construction documents
for  air  conditioning  and ventilating systems shall contain plans that
include the following data and information:
  1. The location and sizes of all ducts: the location of all  fire  and
smoke  dampers,  motors,  fans, and filters; the type, air capacity, and
size of all equipment; and where not shown  on  accompanying  structural
plans, the operating weight and manner of support of equipment.
  2. The locations of smoke detecting devices.
  3.  The  location  and  size  of  the  fresh  air  intake,  the design
population, and the required ventilation for each room or space.
  4. The amount of air to be exhausted or supplied from each outlet  for
each room or space.
  5.  In  the case of ventilating or exhaust systems for ranges, fryers,
ovens, and other similar types of restaurant or  bakery  equipment,  for
which  a  hood  is  required,  the  plans  shall  also  show the type of
extinguishing system, the location of heat detection  devices,  nozzles,
piping,  gas  controls,  manual  and automatic control valves, method of
joining ducts, method and location of discharging exhaust from building,
the location of break-glass controls, and the quantity in  cfm  designed
for each hood.
  106.9  Refrigerating systems. Construction documents for refrigerating
systems  shall  contain  plans  that  include  the  following  data  and
information:
  1.  The  location of all machinery; the horsepower of compressors; the
type and number of pounds  of  refrigerant  to  be  used;  and  the  air
quantities for, and means of ventilating the machinery space.
  2.  The  location  of  emergency  switches  for  compressors  and  for
ventilation in the machinery rooms.
  3.  The  location  of  pressure  relief  piping  and  any  city  water
connections and water-saving devices.

  4.  The  tonnage capacity of the machine and the suction and discharge
pressures at which the machine is rated.
  5. The operating weight of the equipment.
  6. The class of refrigerant utilized.
  106.10   Energy   efficiency.  Construction  documents  shall  include
compliance documentation  as  required  by  the  New  York  City  Energy
Conservation Code.
                              SECTION MC 107
                         INSPECTIONS AND TESTING
  107.1  General. Except as otherwise specifically provided, inspections
required by this code or by the department during the progress  of  work
may  be  performed  on  behalf  of the owner by approved agencies or, if
applicable, by special inspectors. However, in the  interest  of  public
safety,  the  commissioner  may  direct  that any of such inspections be
performed by the department. All inspections shall be performed  at  the
sole cost and expense of the owner. Refer to Article 116 of Chapter 1 of
Title  28  of the Administrative Code for additional provisions relating
to inspections. In addition to any  inspections  otherwise  required  by
this  code  or  applicable  rules,  the  following  inspections shall be
required:
  1. Progress inspections:
  1.1. Underground inspection shall be made after  trenches  or  ditches
are  excavated  and bedded, piping installed, and before backfill is put
in place. When excavated soil contains rocks,  broken  concrete,  frozen
chunks  and  other rubble that would damage or break the piping or cause
corrosive action, clean backfill shall be on the job site.
  Exception: Ground-source heat pump loop systems tested  in  accordance
with  Section  1208.1.1  shall  be  peg witted to be backfilled prior to
inspection.
  1.2. Rough-in inspection  shall  be  made  after  the  roof,  framing,
fireblocking  and  bracing  are  in  place  and  all  ducting  and other
components to be concealed are complete, and prior to  the  installation
of wall or ceiling membranes.
  2.  Special  inspections.  Special  inspections  shall be performed in
accordance with this code and Chapter 17 of the New York  City  Building
Code.
  3.  Final inspection. Refer to Article 116 of Chapter 1 of Title 28 of
the Administrative Code.
  4. Issuance of Certificate of Compliance. Upon satisfactory inspection
of service equipment and the satisfaction of all  the  requirements  for
sign-off,  the  department  shall  issue  a certificate of compliance as
applicable for the following service equipment:
  4.1. Air-conditioning and ventilation systems
  4.2.  Fuel-burning   and   fuel-oil   storage   equipment,   including
generators.
  4.3. Refrigeration systems,
  4.4. Heating systems, and
  4.5. Boilers.
  The  requirements of Section 107.1 shall not be considered to prohibit
the operation of  any  heating  equipment  or  appliances  installed  to
replace  existing  heating  equipment  or appliances serving an occupied
portion of a structure provided that a request for  inspection  of  such
heating  equipment  or appliances has been filed with the department not
more than 48 hours after such replacement work is completed, and  before
any  portion  of  such  equipment  or  appliances  is  concealed  by any
permanent portion of the structure.
  107.1.1 Approved inspection agencies. Refer to Articles 114 and 115 of
Chapter 1 of Title 28 of the Administrative Code.

  107.1.2 Inspection of prefabricated construction assemblies. Prior  to
the  approval  of a prefabricated construction assembly having concealed
mechanical work and the issuance  of  a  permit,  the  department  shall
require  the  submittal of an evaluation report by an approved agency on
each   prefabricated  construction  assembly,  indicating  the  complete
details of the mechanical system, including a description of the  system
and  its components, the basis upon which the system is being evaluated,
test results and similar information, and other data  as  necessary  for
the commissioner to determine conformance to this code.
  107.1.2.1  Test  and  inspection records. Required test and inspection
records shall be available to the commissioner at all times  during  the
fabrication  of  the mechanical system and the erection of the building:
or such records as the commissioner designates shall be filed.
  107.2 Testing. Mechanical systems shall be tested as required in  this
code  and  in  accordance  with  Sections 107.2.1 through 107.2.3. Tests
shall be made by the permit holder and witnessed by the department or an
approved agency.
  107.2.1 New, altered, extended or  repaired  systems.  New  mechanical
systems and parts of existing systems, that have been altered, extended,
renovated  or repaired, shall be tested as prescribed herein to disclose
leaks and defects.
  107.2.2 Apparatus, material and labor for tests.  Apparatus,  material
and labor required for testing a mechanical system or part thereof shall
be furnished by the permit holder.
  107.2.3  Reinspection and testing. Where any work or installation does
not pass an initial test or inspection, the necessary corrections  shall
be  made  so  as  to  achieve  compliance  with  this  code. The work or
installation shall then be resubmitted to the department for  inspection
and testing.
  107.3 Sign-off of completed work. Refer to Article 116 of Chapter 1 of
Title 28 of the Administrative Code.
            107.4  Temporary connection. The commissioner shall have the
authority to authorize the temporary connection of a  mechanical  system
to  the  sources of energy for the purpose of testing mechanical systems
or for use under a temporary certificate of occupancy.
                             SECTION MC 108
                               VIOLATIONS
  108.1 General.  Refer  to  Chapters  2  and  3  of  Title  28  of  the
Administrative Code.
                                CHAPTER 2
                               DEFINITIONS

                             SECTION MC 201
                                 GENERAL
  201.1  Scope.  Unless  otherwise expressly stated, the following words
and terms shall, for the  purposes  of  this  code,  have  the  meanings
indicated in this chapter.
  201.2  Interchangeability. Words used in the present tense include the
future; words in the masculine gender include the feminine  and  neuter;
the singular number includes the plural and the plural, the singular.
  201.3  Terms  defined  in  other codes. Where terms are not defined in
this code and are defined in the New York City Building  Code,  the  New
York  City  Electrical  Code,  the New York City Fire Code, the New York
City Fuel Gas Code or the New York City Plumbing Code, such terms  shall
having meanings ascribed to them as in those codes.
  201.4  Terms  not  defined.  Where  terms  are not defined through the
methods authorized by this section, such  terms  shall  have  ordinarily
accepted meanings such as the context implies.

                             SECTION MC 202
                           GENERAL DEFINITIONS
  ABRASIVE   MATERIALS.   Moderately   abrasive   particulate   in  high
concentrations, and highly abrasive particulate  in  moderate  and  high
concentrations, such as alumina, bauxite, iron silicate, sand and slag.
  ABSORPTION  SYSTEM.  A  refrigerating  system  in which refrigerant is
pressured by pumping a chemical solution of  refrigerant  in  absorbent,
and then separated by the addition of heat in a generator, condensed (to
reject  heat),  expanded,  evaporated  (to  provide  refrigeration), and
reabsorbed in an absorber to repeat the cycle; the system may be  single
or  multiple  effect,  the  latter  using  multiple stages or internally
cascaded use of heat to improve efficiency.
  ACCESS (TO). That which enables a device, appliance or equipment to be
reached by ready access or by a means that first requires the removal or
movement of a panel, door or similar obstruction [see also "Ready access
(to)"];.
  AIR. All air supplied  to  mechanical  equipment  and  appliances  for
combustion,  ventilation,  cooling, etc. Standard air is air at standard
temperature and pressure,  namely,  70°F  (21°C)  and  29.92  inches  of
mercury (101.3 kPa).
  AIR CONDITIONING. The treatment of air so as to control simultaneously
the temperature, humidity, cleanness and distribution of the air to meet
the requirements of a conditioned space.
  AIR-CONDITIONING  SYSTEM.  A  system that consists of heat exchangers,
blowers, filters, supply, exhaust and return ducts,  and  shall  include
any apparatus installed in connection therewith.
  AIR DISTRIBUTION SYSTEM. Any system of ducts, plenums and air-handling
equipment  that  circulates  air  within  a space or spaces and includes
systems made up of one or more air-handling units.
  AIR, EXHAUST. Air being removed from any space, appliance or piece  of
equipment  and  conveyed directly to the atmosphere by means of openings
or ducts.
  AIR, INTAKE. Air supplied from the outdoors to any space, appliance or
piece of equipment.
  AIR, RELIEF. Air  removed  from  any  space,  appliance  or  piece  of
equipment.
  AIR-HANDLING   UNIT.   A  blower  or  fan  used  for  the  purpose  of
distributing supply air to a room, space or area.
  AIR, MAKEUP. Air that is provided to replace air being exhausted.
  AIR TRANSFER OPENING. An opening designed to  allow  the  movement  of
environmental air between two contiguous spaces.
  ALTERATION. Any construction, addition, change of use or occupancy, or
renovation to a building or structure in existence. See Section 28-101.5
of the Administrative Code.
  APPLIANCE.  A device or apparatus that is manufactured and designed to
utilize energy and for which this code provides specific requirements.
  APPLIANCE, EXISTING. Any appliance regulated by this  code  which  was
legally installed prior to the effective date of this code, or for which
a permit to install has been issued.
  APPLIANCE,  FUEL-FIRED.  An  appliance that burns solid, liquid and/or
gaseous fuel, including  but  not  limited  to  wood  stoves,  household
cooking  ranges,  furnaces,  boilers,  water heaters, clothes dryers and
gas-fired refrigerators.
  APPLIANCE, GAS (EQUIPMENT). Any apparatus or equipment that  uses  gas
as  a  fuel or raw material to produce light, heat, power, refrigeration
or air conditioning.
  APPLIANCE TYPE.

  High-heat appliance. Any appliance in which the products of combustion
at the point of entrance to the flue under normal  operating  conditions
have a temperature greater than 2,000°F (1093°C).
  Low-heat appliance (residential appliance). Any appliance in which the
products of combustion at the point of entrance to the flue under normal
operating conditions have a temperature of 1,000°F (538°C) or less.
  Medium-heat   appliance.  Any  appliance  in  which  the  products  of
combustion at the point of entrance to the flue under  normal  operating
conditions  have  a  temperature  of  more than 1,000°F (538°C), but not
greater than 2,000°F (1093°C).
  APPLIANCE, VENTED. An appliance  designed  and  installed  in  such  a
manner that all of the products of combustion are conveyed directly from
the  appliance  to the outside atmosphere through an approved chimney or
vent system.
  APPROVED. Acceptable to the commissioner. In reference to construction
documents, the determination by the department  after  full  examination
that  submitted  construction  documents comply with this code and other
applicable laws and rules. In reference to materials, the  determination
by  the  commissioner  that material is acceptable for its intended use.
See Section 28-101.5 of the Administrative Code.
  APPROVED AGENCY.  An  established  and  recognized  agency,  or  other
qualified  person,  regularly  engaged in conducting tests or furnishing
inspection services, when  approved  pursuant  to  department  rules  as
qualified  to  perform  or  witness  identified  testing  or  inspection
services. See Chapter 1 of Title 28 of the Administrative Code.
  APPROVED INSPECTION AGENCY. An approved agency that is approved by the
department as qualified to  perform  one  or  more  of  the  inspections
required  by  this code. See Chapter 1 of Title 28 of the Administrative
Code.
  APPROVED TESTING AGENCY. An approved agency that is  approved  by  the
department  as  qualified to test and evaluate the performance of one or
more of the materials regulated in their use by  this  code.  Such  term
shall include, when approved pursuant to department rules, a third party
testing  or certification agency, evaluation agency, testing laboratory,
testing service or other entity concerned with product  evaluation.  See
Chapter 1 of Title 28 of the Administrative Code.
  ARCHITECT. A person licensed and registered to practice the profession
of architecture under the Education Law of the state of New York.
  AUTOMATIC  BOILER.  Any  class  of  boiler  that  is equipped with the
controls and limit devices specified in Chapter 10.
  BATHROOM. A room containing a bathtub, shower, spa or similar  bathing
fixture.
  BOILER, HIGH-PRESSURE. An appliance (equipment) for supplying steam of
hot  water that, for a steam boiler, operates at a pressure of more than
15 psig (103 kPa gauge), and for a  hot  water  boiler,  operates  at  a
pressure  exceeding  160  psig  (1103  kPa  gauge)  or  at a temperature
exceeding 250°F (121°C).
  BOILER, LOW-PRESSURE. A self-contained appliance for  supplying  steam
or hot water as follows:
  Hot  water  heating  boiler.  A boiler in which no steam is generated,
from which hot  water  is  circulated  for  heating  purposes  and  then
returned  to  the  boiler,  and  that  operates  at  water pressures not
exceeding 160 pounds per square inch gauge (psig) (1103 kPa  gauge)  and
at water temperatures not exceeding 250°F (1212°C) at or near the boiler
outlet.
  Hot water supply boiler. A boiler, completely filled with water, which
furnishes  hot  water to be used externally to itself, and that operates

at water pressures not exceeding 160 psig (1103 kPa gauge) and at  water
temperatures not exceeding 250°F (121°C) at or near the boiler outlet.
  Steam-heating boiler. See "steam-heating boiler".
  BOILER  ROOM.  A  room  primarily  utilized  for the installation of a
boiler.
  BRAZED JOINT. A gas-tight joint obtained by the joining of metal parts
with metallic mixtures or alloys  which  melt  at  a  temperature  above
1,000°F  (538°C), but lower than the melting temperature of the parts to
be joined.
  BRAZING. A metal joining process wherein coalescence  is  produced  by
the  use  of  a  nonferrous  filler  metal  having a melting point above
1,000°F (538°C), but lower than that of the base metal being joined. The
filler material is distributed between the closely  fitted  surfaces  of
the joint by capillary attraction.
  Btu.  Abbreviation  for British thermal unit, which is the quantity of
heat required to raise the temperature of 1 pound (454 g) of  water  1°F
(0.56°C) (1 Btue = 1055 J).
  BUILDING.  Any structure used or intended for supporting or sheltering
any use or occupancy. The term shall be construed as if followed by  the
phrase  "structure,  premises,  lot  or  part  thereof" unless otherwise
indicated by the text. See Section 28-101.5 of the Administrative code.
  CEILING RADIATION DAMPER. A device installed  to  limit  radiant  heat
transfer  through an air outlet or air inlet opening in the ceiling of a
floor-ceiling or roof-ceiling assembly, which device has not less than a
1-hour fire-resistance rating.
  CHIMNEY. A primarily vertical structure containing one or more  flues,
for  the purpose of carrying gaseous products of combustion and air from
a fuel-burning appliance to the outside atmosphere.
  Factory-built chimney.  A  listed  and  labeled  chimney  composed  of
factory-made  components,  assembled  in  the  field  in accordance with
manufacturer's instructions and the conditions of the listing.
  Masonry chimney. A field-constructed chimney composed of solid masonry
units, bricks, stones or concrete.
  Metal chimney. A field-constructed chimney of metal.
  CHIMNEY  CONNECTOR.  A  pipe  or  metal  breeching  that  connects   a
fuel-burning appliance to a chimney.
  CLEARANCE.  The  minimum  distance  through  air  measured between the
heat-producing surface of the mechanical appliance, device or  equipment
and the surface of the combustible material or assembly.
  CLOSED   COMBUSTION  SOLID-FUEL-BURNING  APPLIANCE.  A  heat-producing
appliance that employs a combustion chamber that has no  openings  other
than  the  flue  collar,  fuel  charging  door  and  adjustable openings
provided to control  the  amount  of  combustion  air  that  enters  the
combustion chamber.
  CLOTHES  DRYER. An appliance used to dry wet laundry by means of heat.
Dryer classifications are as follows:
  Type 1. Factory-built package, multiple production. Primarily used  in
family  living  environment. Usually the smallest unit physically and in
function output.
  Type 2. Factory-built package, multiple production. Used  in  business
with  direct  intercourse  of the function with the public. Not designed
for use in individual family living environment.
  COMBUSTIBLE  ASSEMBLY.  Wall,  floor,  ceiling   or   other   assembly
constructed  of  one or more component materials that are not defined as
noncombustible.
  COMBUSTIBLE LIQUIDS. Any liquids having a  flash  point  at  or  above
100°F (38°C), and that are divided into the following characteristics:

  Class  II.  Liquids  having  flash points at or above 100°F (38°C) and
below 140°f (60°C).
  Class  IIIA.  Liquids having flash points at or above 140°F (60°C) and
below 200°F (93°C).
  Class IIIB. Liquids having flash points at or above 200°F (93°C).
  COMBUSTIBLE MATERIAL. Any material not defined as noncombustible.
  COMBUSTION. In the context of this code, refers to the rapid oxidation
of fuel accompanied by the production of heat or heat and light.
  COMBUSTION AIR. Air necessary  for  complete  combustion  of  a  fuel,
including theoretical air and excess air.
  COMBUSTION   CHAMBER.   The  portion  of  an  appliance  within  which
combustion occurs.
  COMBUSTION PRODUCTS. Constituents resulting from the combustion  of  a
fuel  with  the  oxygen  of  the  air,  including  the  inert gases, but
excluding excess air.
  COMMERCIAL  COOKING  RECIRCULATING   SYSTEM.   Self-contained   system
consisting  of the exhaust hood, the cooking equipment, the filters, and
the fire suppression system. The system is designed to  capture  cooking
vapors  and  residues  generated  from commercial cooking equipment. The
system removes contaminants from the exhaust air  and  recirculates  the
air to the space from which it was withdrawn.
  COMMERCIAL  COOKING  APPLIANCES.  Appliances used in a commercial food
service establishment for heating or  cooking  food  and  which  produce
grease  vapors,  steam,  fumes,  smoke  or odors that are required to be
removed through a local  exhaust  ventilation  system.  Such  appliances
include   deep   fat   fryers;  upright  broilers;  griddles;  broilers;
steam-jacketed   kettles;   hot-top   ranges;    under-fired    broilers
(charbroilers);  ovens;  barbecues; rotisseries; and similar appliances.
For the purpose of this definition, a food service  establishment  shall
include  any  building or a portion thereof used for the preparation and
serving of food.
  COMMERCIAL KITCHEN HOODS.
  Backshelf  Hood.  A  backshelf  hood  is  also  referred   to   as   a
low-proximity  hood, or as a sidewall hood where wall mounted. Its front
lower lip is low over the appliance(s) and is "set back" from the  front
of  the  appliance(s). It is always closed to the rear of the appliances
by a panel where free-standing,  or  by  a  panel  or  wall  where  wall
mounted, and its height above the cooking surface varies. (This style of
hood  can  be  constructed  with  partial  end  panels  to  increase its
effectiveness  in  capturing  the  effluent  generated  by  the  cooking
operation).
  Double  Island Canopy Hood. A double island canopy hood is placed over
back to back appliances or appliance lines. It is open on all sides  and
overhangs both fronts and the sides of the appliance(s). It could have a
wall  panel  between the backs of the appliances. (The fact that exhaust
air is drawn from both sides of the double canopy to meet in the  center
causes each side of this hood to emulate a wall canopy hood, and thus it
functions must the same with or without an actual wall panel between the
backs of the appliances).
  Eyebrow  Hood.  An  eyebrow hood is mounted directly to the face of an
appliance, such as an oven  and  dishwasher,  above  the  opening(s)  or
door(s)  from  which  effluent  is emitted, extending past the sides and
overhanging the front of the opening to capture the effluent.
  Pass-over Hood.  A  pass-over  hood  is  a  free-standing  form  of  a
backshelf hood constructed low enough to pass food over the top.
  Single  Island Canopy Hood. A single island canopy hood is placed over
a single appliance or appliance line.  It  is  open  on  all  sides  and
overhangs  the  front,  rear,  and  sides  of the appliance(s). A single

island canopy is more susceptible to cross drafts and requires a greater
exhaust air flow than an equivalent sized wall-mounted canopy to capture
and contain effluent generated by the cooking operation(s).
  Wall Canopy Hood. A wall canopy exhaust hood is mounted against a wall
above  a  single  appliance  or  line  of  appliance(s),  or it could be
free-standing with a back panel from the rear of the appliances  to  the
hood.  It  overhangs the front and sides of the appliance(s) on all open
sides. The wall acts as a back panel, forcing the makeup air to be drawn
across  the  front  of  the  cooking  equipment,  thus  increasing   the
effectiveness  of  the  hood to capture ad contain effluent generated by
the cooking operation(s).
  COMMISSIONER. The Commissioner of Buildings of the City of New York or
his or her duly authorized representative. See Section 28-101.5  of  the
Administrative Code.
  COMPENSATING  HOODS.  Compensating  hoods  are  those  having integral
(built-in) makeup air supply. The makeup air supply for  such  hoods  is
generally  supplied  from:  short-circuit flow from inside the hood, air
curtain flow from the bottom of the front face, and front face discharge
from the outside front wall of the hood. The compensating makeup airflow
can also be supplied from the rear or side of the  hood,  or  the  rear,
front, or sides of the cooking equipment. The makeup air flow can be one
or a combination of methods.
  COMPRESSOR.  A  specific  machine,  with  or  without accessories, for
compressing a gas.
  COMPRESSOR, POSITIVE DISPLACEMENT. A compressor in which  increase  in
pressure  is attained by changing the internal volume of the compression
chamber.
  COMPRESSOR UNIT. A compressor with its prime mover and accessories.
  CONCEALED  LOCATION.  A  location  that  cannot  be  accessed  without
damaging  permanent parts of the building structure or finished surface.
Spaces above, below or behind readily removable panels  or  doors  shall
not be considered as concealed.
  CONDENSATE.  The liquid that condenses from a gas (including flue gas)
caused by a reduction in temperature or increase in pressure.
  CONDENSER. A heat exchanger designed to liquefy refrigerant  vapor  by
removal of heat.
  CONDENSING  UNIT.  A  specific refrigerating machine combination for a
given refrigerant, consisting of one or more  power-driven  compressors,
condensers,   liquid   receivers  (when  required),  and  the  regularly
furnished accessories.
  CONDITIONED SPACE. An area, room or space being heated  or  cooled  by
any equipment or appliance.
  CONFINED  SPACES.  A space having a volume less than 50 cubic feet per
1,000 British thermal units  per  hour  (BTU/h)  (4.8  m{3}/kW)  of  the
aggregate input rating of all appliances installed in that space.
  CONSTRUCTION  DOCUMENTS.  Plans  and specifications and other written,
graphic and pictorial documents, prepared or  assembled  for  describing
the design, location and physical characteristics of the elements of the
project  necessary for obtaining a building permit. See Section 28-101.5
of the Administrative Code.
  CONTROL. A manual or automatic device designed to  regulate  the  gas,
air,  water  or  electrical  supply  to,  or  operation of, a mechanical
system.
  CONVERSION BURNER. A burner designed to  supply  gaseous  fuel  to  an
appliance originally designed to utilize another fuel.
  COOKING APPLIANCE. See "Commercial cooking appliances."
  DAMPER.  A  manually  or  automatically  controlled device to regulate
draft or the rate of flow of air combustion gases.

  Volume damper. A device that, when installed, will restrict, retard or
direct the flow of air in a duct, or the products  of  combustion  in  a
heat-producing appliance, its vent connector, vent or chimney therefrom.
  DESIGN  WORKING  PRESSURE.  The maximum allowable working pressure for
which a specific part of a system is designed.
  DIRECT REFRIGERATION SYSTEM. A  system  in  which  the  evaporator  or
condenser  of the refrigerating system is in direct contact with the air
or other substance to be cooled or heated.
  DIRECT-VENT APPLIANCES. Appliances that are constructed and  installed
so  that  all  air for combustion is derived from the outside atmosphere
and all flue gases are discharged to the outside atmosphere.
  DRAFT. The pressure difference existing between the equipment  or  any
component  part and the atmosphere, that causes a continuous flow of air
and products of combustion through the gas passages of the appliance  to
the atmosphere.
  Induced draft. The pressure difference created by the action of a fan,
blower or ejector, that is located between the appliance and the chimney
or vent termination.
  Natural  draft.  The  pressure difference created by a vent or chimney
because of its height, and the temperature difference between  the  flue
gases  and the atmosphere.DRIP. The container placed at a low point in a
system of piping to collect condensate and from which the condensate  is
removable.
  DRY  CLEANING SYSTEMS. Dry cleaning plans or systems are classified as
follows:
  Type I. Those systems using Class I flammable liquid solvents having a
flash point below 100°F (38°C).
  Type II. Those systems using  Class  II  combustible  liquid  solvents
having a flash point at or above 100°F (38°C) and below 140°F (60°C).
  Type  III.  Those  systems using Class III combustible liquid solvents
having a flash point at or above 140°F (60°C).
  Types IV and V. Those  systems  using  Class  IV  nonflammable  liquid
solvents.
  DUCT.  A  tube or conduit utilized for conveying air. The air passages
of self-contained systems are not to be construed as air ducts.
  DUCT  FURNACE.  A  warm-air  furnace  normally  installed  in  an  air
distribution  duct to supply warm air for heating. This definition shall
apply only to a warm-air heating appliance that,  for  air  circulation,
depends on a blower not furnished as part of the furnace.
  DUCT SYSTEM. A continuous passageway for the transmission or air that,
in addition to ducts, includes duct fittings, dampers, plenums, fans and
accessory air-handling equipment and appliances.
  DWELLING. A building or structure that is occupied in whole or in part
as the home, residence or sleeping place of one or more families.
  DWELLING UNIT. A single unit consisting of one or more habitable rooms
and  occupied  or  arranged  to  be occupied as a unit separate from all
other units within a dwelling.
  ELECTRIC HEATING APPLIANCE. An appliance that produces heat energy  to
create  a  warm  environment  by  the  application  of electric power to
resistance elements,  refrigerant  compressors  or  dissimilar  material
junctions.
  ENERGY  RECOVERY  VENTILATION  SYSTEM.  Systems that employ air-to-air
heat exchangers to recover energy from or reject energy to  exhaust  air
fro  the purpose of preheating, precooling, humidifying or dehumidifying
outdoor ventilation air prior to supplying such air to a  space,  either
directly or as part of an HVAC system.
  ENGINEER.  A person licensed and registered to practice the profession
of engineering under the Education Law of the State of New York.

  ENVIRONMENTAL AIR. Air that is supplied,  returned,  recirculated,  or
exhausted  from  a  space  for  the  purpose  of  modifying the existing
atmosphere within a building.
  EQUIPMENT.  All  piping,  ducts,  vents,  control  devices  and  other
components of  systems  other  than  appliances  which  are  permanently
installed  and integrated to provide control of environmental conditions
for  buildings.  This  definition  shall  also  include  other   systems
specifically regulated in this code.
  EQUIPMENT,  EXISTING.  Any  equipment regulated by this code which was
legally installed prior to the effective date of this code, or for which
a permit to install has been issued.
  EVAPORATIVE COOLER. A device used for reducing the  sensible  heat  of
air  for  cooling  by  the  process  of  evaporation  of  water  into an
airstream.
  EVAPORATIVE COOLING SYSTEM. The equipment and appliances  intended  or
installed  for  the  purpose  of environmental cooling by an evaporative
cooler from which the conditioned air is distributed  through  ducts  or
plenums to the conditioned area.
  EVAPORATOR.  That  part  of  the system in which liquid refrigerant is
vaporized to produce refrigeration.
  EXCESS AIR. The amount of air provided in addition to theoretical  air
to  achieve  complete  combustion  of  a  fuel,  thereby  preventing the
formation of dangerous-products of combustion.
  EXHAUST SYSTEM. An assembly of connected  ducts,  plenumns,  fittings,
registers, grilles and hoods through which air is conducted from a space
or spaces and exhausted to the outside atmosphere.
  EXTRA-HEAVY   DUTY   COOKING   APPLIANCE.   Extra-heavy  duty  cooking
appliances  include  appliances  utilizing  solid  fuel  such  as  wood,
charcoal,  briquettes,  and  mesquite  as the primary source of heat for
cooking.
  FIREPLACE. An assembly consisting of a  hearth  and  fire  chamber  of
noncombustible  material and provided with a chimney, for sue with solid
fuels.
  Factory-build fireplace. A listed and labeled  fireplace  and  chimney
system  composed  of factory-made components, and assembled in the field
in accordance with manufacturer's instructions and the conditions of the
listing.
  Masonry fireplace. A field-constructed  fireplace  composed  of  solid
masonry units, bricks, stones or concrete.
  FIREPLACE  STOVE. A free-standing chimney-connected solid-fuel-burning
heater, designed to be operated with the fire chamber  doors  in  either
the open or closed position.
  FLAME  SAFEGUARD.  A  device that will automatically shut off the fuel
supply to a main burner or group of burners when the mans of ignition of
such burners becomes inoperative, and when flame failure occurs  on  the
burner or group of burners.
  FLAME  SPREAD INDEX. The numerical value assigned to a material tested
in accordance with ASTM E 84.
  FLAMMABILITY CLASSIFICATION. Refrigerants shall be assigned to one  of
the three classes-1, 2 or 3-in accordance with ASHRAE 34.
  FLAMMABLE  LIQUIDS.  Any  liquid  that  has  a flash point below 100°F
(38°C), and has a vapor pressure not exceeding  40  psig  (276  KPa)  at
100°F  (38°C).   Flammable liquids shall be known as Class I liquids and
shall be divided into the following classifications:
  Class IA. Liquids having a flash point below 73°F (23°C) and a boiling
point below 100°F (38°C).
  Class IB. Liquids having a flash point below 73°F (23°C) and a boiling
point at or above 100°F (38°C).

  Class IC. Liquids having a flash point at or  above  73°F  (23°C)  and
below 100°F (38°C).
  FLAMMABLE  VAPOR  OR FUMES. Mixtures of gases in air at concentrations
equal to or greater than the LFL and less than or  equal  to  the  upper
flammability limit (UFL).
  FLASH  POINT.  The minimum temperature corrected to a pressure of 14.7
psig (101 kPa) at which the application  of  a  test  flame  causes  the
vapors  of  a  portion  of  the  sample  to  ignite under the conditions
specified by the test procedures and apparatus. The  flash  point  of  a
liquid  shall  be  determined in accordance with ASTM D 56, ASTM D 93 or
ASTM D 3278.
  FLOOR AREA, NET. The actual occupied area,  not  including  unoccupied
accessory areas or thickness of walls.
  FLOOR  FURNACE. A completely self-contained furnace suspended from the
floor of the space being heated, taking air for combustion from  outside
such  space  and  with  means  for  observing  flames  and  lighting the
appliance from such space.
  FLUE. A passageway within a chimney  or  vent  through  which  gaseous
combustion products pass.
  FLUE  CONNECTION (BREECHING). A passage fro conducting the products of
combustion from a fuel-fired appliance to the vent or chimney (see  also
"Chimney connector" and "Vent connector").
  FLUE GASES. Products of combustion of excess air.
  FLUE  LINER  (LINING).  A  system  or material used to form the inside
surface of a flue in a chimney or vent, for the  purpose  of  protecting
the  surrounding  structure  from the effects of combustion products and
conveying combustion products without leakage into the atmosphere.
  FUEL GAS. A natural gas, manufactured gas, liquefied petroleum gas  or
a mixture of these.
  FUEL  OIL.  Kerosene  or  any hydrocarbon oil having a flash point not
less than 100°F (38°C).
  FUEL-OIL PIPING  SYSTEM.  A  closed  piping  system  that  connects  a
combustible  liquid  from  a  source  of  supply  to  a fuel-oil-burning
appliance.
  FURNACE. A completely self-contained heating unit that is designed  to
supply  heated  air  to  spaces remote from or adjacent to the appliance
location.
  FURNACE ROOM. A  room  primarily  utilized  for  the  installation  of
fuel-burning  space-heating  and  water-heating  appliances  other  than
boilers (see also "Boiler room").
  FUSIBLE PLUG. A device arranged to relieve pressure by operation of  a
fusible member at a predetermined temperature.
  GROUND  SOURCE  HEAT  PUMP LOOP SYSTEM. Piping buried in horizontal or
vertical excavations or placed in a body of water  for  the  purpose  of
transporting  heat  transfer liquid to and from a heat pump. Included in
this  definition  are  closed  loop  systems  in  which  the  liquid  is
recirculated  and  open loop systems in which the liquid is drawn from a
well or other source.
  HAZARDOUS LOCATION. Any location considered to be a  fire  hazard  fro
flammable  vapors,  dust, combustible fibers or other highly combustible
substances. The location is not necessarily categorized in the New  York
City Building Code as a high-hazard use group classification.
  HEAT  EXCHANGER.  A  device  that  transfers  heat  from one medium to
another.
  HEAT  PUMP.  A  refrigeration  system  that  extracts  heat  from  one
substance  and  transfers it to another portion of the same substance or
to a second substance at a higher temperature for a beneficial purpose.

  HEAT TRANSFER LIQUID. The operating or thermal  storage  liquid  in  a
mechanical  system,  including water or other liquid base, and additives
at the concentration present under operating  conditions  used  to  move
heat from one location to another. Refrigerants are not included as heat
transfer liquids.
  HEAVY-DUTY  COOKING  APPLIANCE.  Heavy-duty cooking appliances include
electric under-fired broilers, electric chain (conveyor)  broilers,  gas
under-fired  broilers,  gas  chain  (conveyor) broilers, gas open-burner
ranges (with or without oven), electric and gas wok ranges, and electric
and gas over-fired (upright) broilers and salamanders.
  HIGH-PROBABILITY SYSTEMS. A refrigeration system in  which  the  basic
design  or  the  location  of  components  is  such  that  a  leakage of
refrigerant from a failed connection, seal or component  will  enter  an
occupancy classified area, other than the machinery room
  HIGH-SIDE  PRESSURE.  The  parts  of  refrigerating  system subject to
condenser pressure.
  HOOD. An air-intake device used to capture by entrapment, impingement,
adhesion or similar means, grease and similar  contaminants  before  the
enter a duct system.
  Type  I.  A kitchen hood for collecting and removing grease vapors and
smoke.
  Type II. A general kitchen hood for  collecting  and  removing  steam,
vapor, heat and odors.
  HOOD, FUME. A hood used to hazardous exhaust systems.
  HYDROGEN   GENERATING   APPLIANCE.   A   self-contained   package   or
factory-matched packages of integrated systems  for  generating  gaseous
hydrogen.   Hydrogen   generating   appliances   utilize   electrolysis,
reformation, chemical, or other processes to generate hydrogen.
  IGNITION SOURCE. A flame, spark or hot  surface  capable  of  igniting
flammable  vapors  or  fumes.  Such  sources  include appliance burners,
burner ignitors and electrical switching devices.
  IMMEDIATELY DANGEROUS TO LIFE OR HEALTH (IDLH). The  concentration  of
air-borne  contaminants  that  poses  a  threat  of  death, immediate or
delayed permanent adverse health effects, or effects that could  prevent
escape from such an environment. This contaminant concentration level is
established  by the National Institute of Occupational Safety and Health
(NIOSH) based  on  both  toxicity  and  flammability.  It  is  generally
expressed  in  parts  per  million by volume (ppm v/v) or milligrams per
cubic meter (mg/m{3}).
  INDIRECT REFRIGERATION SYSTEM. A system in which a  secondary  coolant
cooled or heated by the refrigerating system is circulated to the air or
other   substance   to   be  cooled  or  heated.  Indirect  systems  are
distinguished by the method of application shown below:
  Closed system. A system in which a secondary fluid is either cooled or
heated by the refrigerating system and then circulated within  a  closed
circuit in indirect contact with the air or other substance to be cooled
or heated.
  Double-indirect  open-spray  system.  A  system in which the secondary
substance for an indirect open-spray system is heated or  cooled  by  an
intermediate coolant circulated from a second enclosure.
  Open-spray  system. A system in which a secondary coolant is cooled or
heated by the refrigerating system and then circulated in direct contact
with the air or other substance to be cooled or heated.
  Vented closed system. A system in which a secondary coolant is  cooled
or  heated  by the refrigerating system and then passed through a closed
circuit in the air or other substance to be  cooled  or  heated,  except
that  the  evaporator or condenser is placed in an open or appropriately
vented tank.

  JOINT, FLANGED. A joint made by bolting together  a  pair  of  flanged
ends.
  JOINT,  FLARED.  A metal-to-metal compression joint in which a conical
spread is made on the end of a tube that is compressed by  a  flare  nut
against a mating flare.
  JOINT,  MECHANICAL. A general form of gas-tight joints obtained by the
joining  of  metal   parts   through   a   positive-holding   mechanical
construction, such as flanged joint, screwed joint or flared joint.
  JOINT,  PLASTIC  ADHESIVE. A joint made in thermoset plastic piping by
the use of an adhesive substance which forms a continuous  bond  between
the mating surfaces without dissolving either one of them.
  JOINT,  PLASTIC  HEAT  FUSION. A joint made in thermoplastic piping by
heating the parts sufficiently to permit fusion of  the  materials  when
the parts are pressed together.
  JOINT, PLASTIC SOLVENT CEMENT. A joint made in thermoplastic piping by
the  use  of  a  solvent or solvent cement which forms a continuous bond
between the mating surfaces.
  JOINT, SOLDERED. A gas-tight joint obtained by the  joining  of  metal
parts  with  metallic  mixtures  of  alloys  which  melt at temperatures
between 400°F (204°C) and 1,000°F (538°C).
  JOINT, WELDED. A gas-tight joint obtained  by  the  joining  of  metal
parts in molten state.
  LABELED.  Material to which has been attached a label, symbol or other
identifying mark of the manufacturer  that  contains  the  name  of  the
manufacturer,  the  function  and  performance  characteristics  of  the
product or material, and the name  and  identification  of  an  approved
agency  and  that indicates that a representative sample of the material
has been tested and evaluated by an approved agency for compliance  with
nationally  recognized standards or tests to determine suitable usage in
a specified manner. See Section 28-101.5 of the Administrative Code.
  LIGHT-DUTY COOKING APPLIANCE. Light-duty  cooking  appliances  include
gas  and  electric ovens (including standard, bake, roasting, revolving,
retherm, convection, combination convection/steamer, conveyor,  deck  or
deck-style  pizza, and pastry), electric and gas steam-jacketed kettles,
electric and gas compartment steamers (both  pressure  and  atmospheric)
and electric and gas cheesemelters.
  LIMIT CONTROL. A device responsive to changes in pressure, temperature
or level for turning on, shutting off or throttling the gas supply to an
appliance.
  LIMITED  CHARGE  SYSTEM.  A system in which, with the compressor idle,
the design pressure will not be exceeded when the refrigerant charge has
completely evaporated.
  LISTED. Material identified in a list published by an approved  agency
that  maintains  periodic inspection of production of listed material or
periodic evaluation services and whose listing states  either  that  the
material  meets  identified  nationally recognized standards or has been
tested and found suitable for a  specified  purpose  when  installed  in
accordance with the manufacturer's installation instruction. See Section
28-101.5 of the Administrative Code.
  LIVING  SPACE.  Space  within  a  dwelling  unit  utilized for living,
sleeping, eating, cooking, bathing, washing and sanitation purposes.
  LOWER EXPLOSIVE LIMIT (LEL). See "LFL".
  LOWER  FLAMMABILITY  LIMIT  (LFL).  The   minimum   concentration   of
refrigerant  that is capable of propagating a flame through a homogenous
mixture of refrigerant and air.
  LOW-PRESSURE HOT-WATER-HEATING BOILER. A boiler furnishing hot water a
pressures not exceeding 160 psig (1103  kPa)  and  at  temperatures  not
exceeding 250°F (121°C).

  LOW-PRESSURE  STEAM-HEATING  BOILER.  A  boiler  furnishing  steam  at
pressures not exceeding 15 psig (103 kPa).
  LOW-PROBABILITY  SYSTEMS.  A  refrigeration  system in which the basic
design or  the  location  of  components  is  such  that  a  leakage  of
refrigerant  from  a failed connection, seal or component will not enter
an occupancy-classified area, other than the machinery room.
  LOW-SIDE PRESSURE. The parts of  a  refrigerating  system  subject  to
evaporator pressure.
  MACHINERY  ROOM.  A room meeting prescribed safety requirements and in
which refrigeration systems  or  components  thereof  are  located  (see
Sections 1105 and 1106).
  MECHANICAL  DRAFT  SYSTEM. A venting system designed to remove flue or
vent gases by  mechanical  means,  that  consists  of  an  induced-draft
portion  under  nonpositive  static  pressure  or a forced-draft portion
under positive static pressure.
  Forced-draft venting system. A portion of a venting system using a fan
or other mechanical means to cause the removal of  flue  or  vent  gases
under nonpositive static vent pressure.
  Power  venting  system.  A  portion of a venting system using a fan or
other mechanical means to cause the removal of flue or vent gases  under
positive static vent pressure.
  MECHANICAL   EQUIPMENT/APPLIANCE  ROOM.  A  room  or  space  in  which
nonfuel-fired mechanical equipment and appliances are located.
  MECHANICAL EXHAUST SYSTEM. A system for removing air from  a  room  or
space by mechanical means.
  MECHANICAL  JOINT.  A connection between pipes, fittings, or pipes and
fittings, which is neither screwed, caulked, threaded, soldered, solvent
cemented, brazed nor welded. Also,  a  joint  in  which  compression  is
applied along the centerline of the pieces being joined. Some joints are
part of a coupling, fitting or adapter.
  MECHANICAL  SYSTEM.  A  system specifically addressed and regulated in
this code and composed of components, devices, appliances and  equipment
which become part of the building.
  MEDIUM-DUTY  COOKING APPLIANCE. Medium-duty cooking appliances include
electric discrete element ranges (with or without  oven),  electric  and
gas  hot-top  ranges.  electric  and  gas  griddles,  electric  and  gas
double-sided griddles, electric and gas fryers (including open deep  fat
fryers,  donut fryers, kettle fryers, and pressure fryers), electric and
gas pasta cookers, electric and gas conveyor pizza ovens,  electric  and
gas tilting skillets (braising pans) and electric and gas rotisseries.
  MODULAR  BOILER. A steam or hot-water-heating assembly consisting of a
group of individual boilers called modules intended to be installed as a
unit with no intervening stop valves. Modules are under  one  jacket  or
are  individually jacketed. The individual modules shall be limited to a
maximum input rating of 400,000 Btu/h (117 228 W/h) gas, 3  gallons  per
hour (gph) (11.4 L/h) oil, or 115 kW (electric).
  NATURAL DRAFT SYSTEM. A venting system designed to remove flue or vent
gases under nonpositive static vent pressure entirely by natural draft.
  NATURAL  VENTILATION.  The  movement  of  air  into and out of a space
through intentionally provided openings, such as windows and  doors,  or
through nonpowered ventilators.
  NONABRASIVE/ABRASIVE   MATERIALS.   Nonabrasive  particulate  in  high
concentrations, moderately abrasive  particulate  in  low  and  moderate
conditions,  and highly abrasive particulate in low concentrations, such
as alfalfa, asphalt, plaster, gypsum and salt.
  NONCOMBUSTIBLE MATERIALS. Materials that, when  tested  in  accordance
with  ASTM  E  136, have at least three of four specimens tested meeting
all of the following criteria:

  1. The recorded temperature of the surface and interior  thermocouples
shall  not  at any time during the test rise more than 54°F (30°C) above
the furnace temperature at the beginning of the test.
  2.  There  shall  not  be flaming from the specimen after the first 30
seconds.
  3. If the weight loss  of  the  specimen  during  testing  exceeds  50
percent,   the   recorded   temperature  of  the  surface  and  interior
thermocouples shall not at any time  during  the  test  rise  above  the
furnace  air  temperature  at the beginning of the test, and there shall
not be flaming of the specimen.
  OCCUPANCY. The purpose or activity for which a building  or  space  is
used or is designed, arranged or intended to be used.
  OFFSET  (VENT).  A combination of approved bends that make two changes
in direction bringing one section of the vent out of  line  but  into  a
line parallel with the other section.
  OUTDOOR AIR. Air taken from the outdoors, and therefore not previously
circulated through the system.
  OUTDOOR  OPENING.  A  door, window, louver or skylight openable to the
outside atmosphere.
  OUTLET, GAS. A threaded connection or bolted flange in a piping system
to which a gas-burning appliance is attached.
  PANEL HEATING. A method of radiant space  heating  in  which  heat  is
supplied  by  large  heated  areas of room surfaces. The heating element
usually consists of warm water piping, warm  air  ducts,  or  electrical
resistance elements embedded in or located behind ceiling, wall or floor
surfaces.
  PELLET  FUEL-BURNING  APPLIANCE. A closed-combustion, vented appliance
equipped with a fuel-feed mechanism for  burning  processed  pellets  of
solid fuel of a specified size and composition.
  PIPING.  Where  used  in  this code, "piping" refers to either pipe or
tubing, or both.
  Pipe. A rigid conduit of iron, steel, copper, brass or plastic.
  Tubing. Semirigid conduit of copper, aluminum, plastic or steel.
  PLASTIC, THERMOPLASTIC. A plastic that is capable of being  repeatedly
softened  by  increase  of  temperature  and  hardened  by  decrease  of
temperature.
  PLASTIC, THERMOSETTING. A plastic that is  capable  of  being  changed
into  a  substantially  infusible  or insoluble product when cured under
application of heat or chemical means.
  PLENUM. A compartment or chamber located in one story  only  to  which
one  or  more  air  ducts  are connected and which forms part of the air
supply or return system and may be part of  the  building  construction,
such as the concealed space above a ceiling.
  PORTABLE  FUEL  CELL  APPLIANCE. A fuel cell generator of electricity,
which is not fixed in place. A portable fuel cell appliance  utilizes  a
cord  and  plug  connection  to a grid-isolated load and has an integral
fuel supply.
  POWER BOILER. See "Boiler".
  PREMISES. Land, improvements, thereon, or any part thereof.
  PRESSURE, FIELD TEST. A test performance in the field to prove  system
tightness.
  PRESSURE-LIMITING  DEVICE. A pressure-responsive mechanism designed to
stop automatically the operation of the pressure-imposing element  at  a
predetermined pressure.
  PRESSURE  RELIEF  DEVICE. A pressure-activated valve or rupture member
designed to relieve excessive pressure automatically.

  PRESSURE RELIEF VALVE. A pressure-activated valve  held  closed  by  a
spring  or other means and designed to relieve pressure automatically in
excess of the device's setting.
  PRESSURE  VESSELS.  Closed  containers,  tanks  or  vessels  that  are
designed to contain liquids or gases, or both, under pressure.
  PRESSURE VESSELS-REFRIGERANT. Any refrigerant-containing receptacle in
a refrigerating system. This does not  include  evaporators  where  each
separate  section  does  not  exceed  0.5  cubic  foot  (0.014  m{3}) of
refrigerant-containing  volume,  regardless  of   the   maximum   inside
dimensions, evaporator coils, controls, headers, pumps and piping.
  PROTECTIVE  ASSEMBLY  (REDUCED CLEARANCE). Any noncombustible assembly
that is labeled or constructed in accordance with  Table  308.6  and  is
placed  between  combustible  materials  or  assemblies  and  mechanical
appliances, devices or equipment, for the purpose of  reducing  required
airspace  clearances.  Protective  assemblies  attached  directly  to  a
combustible assembly shall not be considered as part of that combustible
assembly.
  PURGE. To clear of air, water or other foreign substances.
  QUICK-OPENING VALVE. A valve that opens  completely  by  fast  action,
either   manually   or   automatically  controlled.  A  valve  requiring
one-quarter round turn or less is considered to be quick opening.
  RADIANT HEATER. A heater designed to transfer heat primarily by direct
radiation.
  READY ACCESS (TO). That which enables a device, appliance or equipment
to be directly reaches, without requiring the removal or movement of any
panel, door or similar obstruction (see "Access (to)").
  RECEIVER, LIQUID. A vessel permanently connected  to  a  refrigeration
system by inlet and outlet pipes for storage of liquid refrigerant.
  RECIRCULATED  AIR.  Air  removed from a conditioned space and intended
for reuse as supply air.
  RECLAIMED  REFRIGERANTS.  Refrigerants   reprocessed   to   the   same
specifications  as for new refrigerants by means including distillation.
Such refrigerants have been  chemically  analyzed  to  verify  that  the
specifications  have  been  met.  Reclaiming  usually implies the use of
processes or procedures that are available only  at  a  reprocessing  or
manufacturing facility.
  RECOVERED  REFRIGERANTS.  Refrigerants  removed  from  a system in any
condition without necessarily testing or processing them.
  RECYCLED REFRIGERANTS. Refrigerants from which contaminants have  been
reduced  by  oil separation, removal of noncondensable gases, and single
or multiple passes through devices that  reduce  moisture,  acidity  and
particulate  matter,  such  as  replaceable  core  filter  dryers. These
procedures usually are performed at the field job site  or  in  a  local
service shop.
  REFRIGERANT.  A  substance  utilized  to  produce refrigeration by its
expansion or vaporization.
  REFRIGERANT  SAFETY  CLASSIFICATIONS.  Groupings  that  indicate   the
toxicity and flammability classes in accordance with ASHRAE 34.
  REFRIGERATED  ROOM OR SPACE. A room or space in which an evaporator or
brine coil is located for the purpose of  reducing  or  controlling  the
temperature within the room or space to below 68°F (20°C).
  REFRIGERATING     SYSTEM.     A    combination    of    interconnected
refrigerant-containing parts constituting one closed refrigerant circuit
in which a refrigerant is circulated for the purpose of extracting heat.
  REFRIGERATION MACHINERY ROOM. See "machinery room."
  REFRIGERATION      SYSTEM,      ABSORPTION.      A      heat-operated,
closed-refrigeration  cycle  in  which a secondary fluid (the absorbent)

absorbs a primary fluid (the refrigerant) that has been vaporized in the
evaporator.
  Direct  system.  A system in which the evaporator is in direct contact
with  the  material  or   space   refrigerated,   or   is   located   in
air-circulating passages communicating with such spaces.
  Indirect  system.  A  system  in  which  a  brine  coil  cooled by the
refrigerant is circulated to the material or space refrigerated,  or  is
utilized   to   cool   the  air  so  circulated.  Indirect  systems  are
distinguished by the type or method of application.
  REFRIGERATION  SYSTEM  CLASSIFICATION.   Refrigeration   systems   are
classified   according   to   the  degree  of  probability  that  leaked
refrigerant from a failed connection, seal or component  will  enter  an
occupied  area. The distinction is based on the basic design or location
of the components.
  REFRIGERATION SYSTEM,  MECHANICAL.  A  combination  of  interconnected
refrigeration-containing   parts  constituting  one  closed  refrigerant
circuit in  which  a  refrigerant  is  circulated  for  the  purpose  of
extracting  heat  and  in which a compressor is used for compressing the
refrigerant vapor.
  REFRIGERATION SYSTEM, SELF-CONTAINED. A complete factory-assembled and
tested system that is shipped  in  one  or  more  sections  and  has  no
refrigerant-containing  parts that are joined in the field by other than
companion or block valves.
  REGISTERED DESIGN PROFESSIONAL. Refer to Chapter 1 of Title 28 of  the
Administrative Code.
  RETURN AIR. Air removed from an approved conditioned space or location
and recirculated or exhausted to the outside atmosphere.
  RETURN  AIR SYSTEM. An assembly of connected ducts, plenums, fittings,
registers and grilles through which air from the space or spaces  to  be
heated  or cooled is conducted back to the supply unit (see also "Supply
air system").
  ROOM HEATER, VENTED. A free-standing heating  unit  burning  solid  or
liquid  fuel  for direct heating of the space in and adjacent to that in
which the unit is located.
  SAFETY VALVE. A valve that relieves pressure  in  a  steam  boiler  by
opening  fully  at  the  rated  discharge  pressure. The valve is of the
spring-pop type.
  SELF-CONTAINED  EQUIPMENT.  Complete,  factory-assembled  and  tested,
heating,  air-conditioning  or  refrigeration  equipment  installed as a
single unit, and having all working parts, complete with  motive  power,
in an enclosed unit of said machinery.
  SHAFT.  An  enclosed  space extending through one or more stories of a
building, connecting vertical openings in successive floors,  or  floors
and the roof.
  SHAFT ENCLOSURE. The walls or construction forming the boundaries of a
shaft.
  SMOKE  DAMPER.  A listed device that is designed to resist the passage
of air and smoke. The  device  is  arranged  to  operate  automatically,
controlled by a smoke detection system, and when required, is capable of
being positioned manually from a remote command station.
  SMOKE-DEVELOPED INDEX. A numerical value assigned to a material tested
in accordance with ASTM E 84.
  SOLID  FUEL  (COOKING  APPLICATIONS).  Applicable  to  commercial food
service operations only,  solid  fuel  is  any  bulk  material  such  as
hardwood,  mesquite, charcoal or briquettes that is combusted to produce
heat for cooking operations.

  SOURCE CAPTURE  SYSTEM.  A  mechanical  exhaust  system  designed  and
constructed  to  capture air contaminants at their source and to exhaust
such contaminants to the outdoor atmosphere.
  STATIONARY   FUEL  CELL  POWER  PLANT.  A  self-contained  package  or
factory-matched packages  which  constitute  an  automatically  operated
assembly  of  integrated systems for generating useful electrical energy
and recoverable thermal energy that is permanently connected  and  fixed
in place.
  STEAM-HEATING  BOILER. A boiler operated at pressures not exceeding 15
psig (103 kPa gauge) for steam.
  STOP VALVE. A shutoff valve for controlling  the  flow  of  liquid  or
gases.
  STORY.  That  portion of a building included between the upper surface
of a floor and the upper surface of the floor next  above,  except  that
the  topmost  story shall be that portion of a building included between
the upper surface of the topmost floor and the ceiling or roof above.
  STRENGTH, ULTIMATE. The highest stress level that the  component  will
tolerate without rupture.
  SUPPLY  AIR.  That  air delivered to each or any space supplied by the
air distribution system  or  the  total  air  delivered  to  all  spaces
supplied   by  the  air  distribution  system,  which  is  provided  for
ventilating,  heating,  cooling,  humidification,  dehumidification  and
other similar purposes.
  SUPPLY  AIR SYSTEM. An assembly of connected ducts, plenums, fittings,
registers and grilles through which air, heated or cooled, is  conducted
from  the supply unit to the space or spaces to be heated or cooled (see
also "Return air system").
  THEORETICAL AIR. The exact amount of air required to supply oxygen for
complete combustion of a given quantity of a specific fuel.
  THERMAL RESISTANCE (R). A measure of the ability to retard the flow of
heat. The R-value is the reciprocal of thermal conductance.
  TLV-TWA   (THRESHOLD   LIMIT   VALUE-TIME   WEIGHTED   AVERAGE).   The
time-weighted  average  concentration of a refrigerant or other chemical
in air for a normal 8-hour workday and  a  40-hour  workweek,  to  which
nearly  all  workers  are  repeatedly  exposed,  day  after day, without
adverse effects, as adopted by the  American  Conference  of  Government
Industrial Hygienists (ACGIH).
  TOILET  ROOM.  A  room  containing  a  water closet and, frequently, a
lavatory, but not a bathtub, shower, spa or similar bathing fixture.
  TOXICITY CLASSIFICATION. Refrigerants shall be classified for toxicity
to one of two classes in accordance with ASHRAE 34.
  TRANSITION FITTINGS, PLASTIC TO STEEL. An adapter for joining  plastic
pipe  to  steel  pipe.  The  purpose  of  this  fitting  is to provide a
permanent pressure-tight connection between two materials  which  cannot
be joined directly one to another.
  UNCONFINED  SPACE. A space having a volume not less than 50 cubic feet
per 1,000 Btu/h (4.8 m{3}/kW) of  the  aggregate  input  rating  of  all
applicants  installed  in  that space. Rooms communicating directly with
the space in which the appliances are installed,  through  openings  not
furnished with doors, are considered a part of the unconfined space.
  UNIT  HEATER. A self-contained appliance of the fan type, designed for
the delivery of warm air directly into the space in which the  appliance
is located.
  UNUSUALLY   TIGHT   CONSTRUCTION.  Construction  meeting  all  of  the
following requirements:
  1. Walls exposed to the outside atmosphere having a  continuous  water
vapor  retarder  with  a rating of 1 perm (57 ng/s*m{2}*Pa) or less with
openings gasketed or sealed; and

  2. Openable windows and doors meeting the air leakage requirements  of
the New York City Energy Conservation Code, Section 802.3.1; and
  3.  Caulking  or  sealants are applied to areas, such as joints around
window  and  door  frames,  between  sole  plates  and  floors,  between
wall-ceiling  joints, between wall panels, at penetrations for plumbing,
electrical and gas lines, and at other openings.
  VENT. A pipe or other conduit  composed  of  factory-made  components,
containing a passageway for conveying combustion products and air to the
atmosphere,  listed and labeled for use with a specific type or class of
appliance.
  Pellet  vent.  A  vent  listed  and  labeled  for  use   with   listed
pellet-fuel-burning appliances.
  Type L vent. A vent listed and labeled for use with the following:
  1. Oil-burning appliances that are listed for use with Type L vents.
  2. Gas-fed appliances that are listed for use with Type B vents.
  VENT   CONNECTOR.  The  pipe  that  connects  an  approved  fuel-fired
appliance to a vent.
  VENT DAMPER DEVICE, AUTOMATIC. A device intended for  installation  in
the  venting  system,  in  the  outlet  of  an  individual automatically
operated fuel-burning appliance that is designed  to  open  the  venting
system automatically when the appliance is in operation and to close off
the  venting  system automatically when the appliance is in a standby or
shutdown condition.
  VENTILATION.  The  natural  or   mechanical   process   of   supplying
conditioned  or  unconditioned  air  to,  or removing such air from, any
space.
  VENTILATION AIR. That portion  of  supply  air  that  comes  from  the
outside  (outdoors),  plus any recirculated air that has been treated to
maintain the desired quality of air within a designated space.
  VENTING SYSTEM. A continuous open passageway from the flue  collar  of
an  appliance to the outside atmosphere for the purpose of removing flue
or vent gases. A venting system is usually  composed  of  a  vent  or  a
chimney  and  vent  connector,  if  used,  assembled  to  form  the open
passageway.
  WATER HEATER. Any heating appliance or equipment  that  heats  potable
water  and  supplies  such  water  to the potable hot water distribution
system.
                                CHAPTER 3
                           GENERAL REGULATIONS

                             SECTION MC 301
                                 GENERAL
  301.1 Scope. This chapter shall govern the approval  and  installation
of  all  equipment  and  appliances  that comprise parts of the building
mechanical systems regulated by this code  in  accordance  with  Section
101.2.
  301.2  Energy  utilization.  Heating, ventilating and air-conditioning
systems of all structures shall be designed and installed for  efficient
utilization  of  energy  in  accordance  with  the  New York City Energy
Conservation Code.
  301.3 Fuel gas appliances and equipment. The approval and installation
of fuel gas distribution piping and equipment, fuel gas-fired appliances
and fuel gas-fired appliance venting systems shall be in accordance with
the New York City Fuel Gas Code.
  301.4 Listed and labeled. All appliances regulated by this code  shall
be listed and labeled.
  301.5  Testing  of materials and equipment. Refer to Section 28-113 of
the Administrative Code.

  301.6 Label information.  A  permanent  factory-applied  name-plate(s)
shall  be  affixed  to  appliances  on  which  shall  appear  in legible
lettering, the manufacturer's  name  or  trademark,  the  model  number,
serial number and the seal or mark of the approved agency. A label shall
also include the following:
  1.  Electrical  equipment  and appliances: Electrical rating in volts,
amperes  and  motor  phase;  identification  of  individual   electrical
components  in  volts,  amperes or watts, motor phase; Btu/h (W) output;
and required clearances.
  2. Absorption units: Hourly rating in Btu/h (W); minimum hourly rating
for units having step or automatic modulating controls;  type  of  fuel;
type  of  refrigerant;  cooling  capacity  in  Btu/h  (W);  and required
clearances.
  3. Fuel-burning units: Hourly  rating  in  Btu/h  (W);  type  of  fuel
approved for use with the appliance; and required clearances.
  4.  Electric  comfort  heating  appliances: Name and trade-mark of the
manufacturer; the model number or equivalent;  the  electric  rating  in
volts,  ampacity  and phase; Btu/h (W) output rating; individual marking
for each electrical component in amperes  or  watts,  volts  and  phase;
required clearances from combustibles; and a seal indicating approval of
the appliance by an approved agency.
  301.7  Electrical.  Electrical  wiring,  controls  and  connections to
equipment and appliances regulated by this code shall be  in  accordance
with the New York City Electrical Code.
  301.8 Plumbing connections. Potable water supply and building drainage
system  connections  to  equipment and appliances regulated by this code
shall be in accordance with the New York City Plumbing Code.
  301.9 Fuel types. Fuel-fired appliances shall be designed for use with
the type of fuel to which they will be connected  and  the  altitude  at
which they are installed. Appliances that comprise parts of the building
mechanical  system  shall  not be converted for the usage of a different
fuel, except  where  approved  and  converted  in  accordance  with  the
manufacturer's  instructions. The fuel input rate shall not be increased
or decreased beyond the limit rating  for  the  altitude  at  which  the
appliance is installed.
  301.10 Vibration isolation. Where vibration isolation of equipment and
appliances   is  employed,  supplemental  restraint  shall  be  used  to
accomplish the support and restraint.
  301.11 Repair. Defective  material  or  parts  shall  be  replaced  or
repaired  in  such  a  manner so as to preserve the original approval or
listing.
  301.12 Wind resistance. Mechanical equipment, appliances and  supports
that  are  exposed to wind shall be designed and installed to resist the
wind pressure determined in accordance with the New York  City  Building
Code.
  301.13  Flood hazard. For structures located in areas of special flood
hazard, mechanical systems, equipment and appliances shall  comply  with
Appendix G of the New York City Building Code.
  301.14   Rodent  proofing.  Buildings  or  structures  and  the  walls
enclosing habitable or occupiable rooms  and  spaces  in  which  persons
live,  sleep  or  work, or in which feed, food or foodstuffs are stored,
prepared, processed, served or sold, shall  be  constructed  to  protect
against  the  entrance  of  rodents in accordance with the New York City
Building Code.
  301.15 Seismic resistance. When earthquake  loads  are  applicable  in
accordance  with  the  New  York  City  Building Code, mechanical system
supports shall be designed and  installed  for  the  seismic  forces  in
accordance with the New York City Building Code.

                             SECTION MC 302
                         PROTECTION OF STRUCTURE
  302.1  Structural  safety.  The  building  or  structure  shall not be
weakened by the installation of mechanical systems. Where floors, walls,
ceilings or any other portion of the building or structure are  required
to  be altered or replaced in the process of installing or repairing any
system, the building or structure shall be left  in  a  safe  structural
condition in accordance with the New York City Building Code.
  302.2     Penetrations     of     floor/ceiling     assemblies     and
fire-resistance-rated   assemblies.   Penetrations   of    floor/ceiling
assemblies  and  assemblies  required  to  have a fire-resistance rating
shall be protected in accordance with the New York City Building Code.
  302.3 Cutting, notching and  boring  in  wood  framing.  The  cutting,
notching  and  boring of wood framing members shall comply with Sections
302.3.1 through 302.3.4.
  302.3.1 Joist notching. Notches on the ends of joists shall not exceed
one-fourth the joist depth. Holes bored in joist shall not be  within  2
inches  (51  mm)  of the top or bottom of the joist, and the diameter of
any such hole shall not exceed one-third the depth of the joist. Notches
in the top or bottom of joists shall not exceed one-sixth the depth  and
shall not be located in the middle third of the span.
  302.3.2  Stud  cutting  and  notching.  In  exterior walls and bearing
partitions, any wood stud is permitted to  be  cut  or  notched  not  to
exceed 25 percent of its depth. Cutting or notching of studs not greater
than  40  percent  of  their depth is permitted in nonbearing partitions
supporting no loads other than the weight of the partition.
  302.3.3 Bored holes. A hole not greater in diameter than 40 percent of
the stud depth is permitted to be bored in any wood  stud.  Bored  holes
not  greater  than  60 percent of the depth of the stud are permitted in
nonbearing partitions or in any wall where each bored stud  is  doubled,
provided  not  more than two such successive doubled studs are so bored.
In no case shall the edge of the bored hole be nearer  than  0.625  inch
(15.9  mm)  to the edge of the stud. Bored holes shall not be located at
the same section of stud as a cut or notch.
  302.3.4 Engineered wood products. Cuts, notches  and  holes  bored  in
trusses,  laminated  veneer  lumber, glue-laminated members and I-joists
are  prohibited  except  where  the  effects  of  such  alterations  are
specifically considered in the design of the member.
  302.4  Alterations  to trusses. Truss members and components shall not
be cut, drilled, notched,  spliced  or  otherwise  altered  in  any  way
without   written  concurrence  and  approval  of  a  registered  design
professional.  Alterations resulting in the addition  of  loads  to  any
member  (e.g.,  HVAC  equipment,  water  heaters) shall not be permitted
without verification that  the  truss  is  capable  of  supporting  such
additional loading.
  302.5  Cutting,  notching  and  boring  in steel framing. The cutting,
notching and boring of steel framing members shall comply with  Sections
302.5.1 through 302.5.3.
  302.5.1  Cutting,  notching  and  boring  holes  in  structural  steel
framing.  The cutting, notching and boring of holes in structural  steel
framing  members  shall  be  as  prescribed  by  the  registered  design
professional.
  302.5.2 Cutting,  notching  and  boring  holes  in  cold-formed  steel
framing.    Flangers  and lips of load-bearing cold-formed steel framing
members shall not be cut or  notched.  Holes  in  webs  of  load-bearing
cold-formed   steel   framing  members  shall  be  permitted  along  the
centerline of the web of the framing member and  shall  not  exceed  the
dimensional  limitations,  penetration  spacing  or  minimum  hole  edge

distance as prescribed by the registered design  professional.  Cutting,
notching  and  boring  holes  of  steel  floor/roof  decking shall be as
prescribed by the registered design professional.
  302.5.3   Cutting,   notching   and   boring  holes  in  nonstructural
cold-formed steel  wall  framing.  Flanges  and  lips  of  nonstructural
cold-formed  steel wall studs shall not be cut or notched. Holes in webs
of nonstructural cold-formed steel walls studs shall be permitted  along
the  center-line  of the web of the framing member, shall not exceed 1.5
inches (38 mm) in width or 4 inches (102 mm) in length, and shall not be
spaced less than 24 inches (610 mm) center to center from  another  hole
or less than 10 inches (254 mm) from the bearing end.
                             SECTION MC 303
                    EQUIPMENT AND APPLIANCE LOCATION
  303.1  General.  Equipment and appliances shall be located as required
by this section, specific requirements elsewhere in this  code  and  the
conditions of the equipment and appliance listing.
  303.2  Hazardous  locations.  Appliances  shall  not  be  located in a
hazardous  location  unless  listed  and  approved  for   the   specific
installation.
  303.3 Prohibited locations. Fuel-fired appliances shall not be located
in, or obtain combustion air from, any of the following rooms or spaces:
  1. Rooms occupied for sleeping purposes.
  2. Bathrooms.
  3.  Appliances  installed  in  a  dedicated  enclosure  in  which  all
combustion air is taken directly from the outdoors, in  accordance  with
Section  703.    Access to such enclosure shall be through a solid door,
weather-stripped in  accordance  with  the  exterior  door  air  leakage
requirements  of the New York City Energy Conservation Code and equipped
with an approved self-closing device.
  4. Storage closets.
  5. Surgical rooms.
  Exception: This section shall not apply to the following appliances.
  1. Direct-vent appliances that obtain all combustion air directly from
the outdoors.
  2. Solid fuel-fired  appliances  provided  that  the  room  is  not  a
confined space and the building is not of unusually tight construction.
  3.  Appliances  installed  in  a  dedicated  enclosure  in  which  all
combustion air is taken directly from the outdoors, in  accordance  with
Section  703.    Access to such enclosure shall be through a solid door,
weather-stripped in  accordance  with  the  exterior  door  air  leakage
requirements  of  the  Energy Conservation Construction Code of New York
State and equipped with an approved self-closing device.
  303.4 Protection from damage. Appliances shall not be installed  in  a
location where subject to mechanical damage unless protected by suitable
barriers.
  303.5  Indoor  locations. Fuel-fired furnaces and boilers installed in
closets and alcoves shall be listed for such installation. For  purposes
of  this section, a closet or alcove shall be defined as a room or space
having a volume less than  12  times  the  total  volume  of  fuel-fired
appliances other than boilers and less than 16 times the total volume of
boilers.  Room  volume  shall be computed using the gross floor area and
the actual ceiling height up to a maximum computation height of  8  feet
(2438 mm).
  303.6  Outdoor  locations.  Appliances  installed in other than indoor
locations shall be listed and labeled for outdoor installation.
  303.7 Pit locations. Appliances installed in pits or excavations shall
not come in direct contact with the surrounding soil. The sides  of  the
pit  or  excavation  shall  be held back a minimum of 12 inches (305 mm)

from the appliance. Where the death exceeds 12  inches  (305  mm)  below
adjoining  grade, the walls of the pit or excavation shall be lined with
concrete or masonry. Such concrete or masonry shall extend a minimum  of
4  inches  (102  mm)  above  adjoining  grade  and shall have sufficient
lateral load-bearing capacity to resist collapse. The appliance shall be
protected from flooding.
  303.8 Elevator shafts. Mechanical systems shall not be located  in  an
elevator shaft.
                             SECTION MC 304
                              INSTALLATION
  304.1 General. Equipment and appliances shall be installed as required
by the terms of their approval, in accordance with the conditions of the
listing,  the  manufacturer's  installation  instructions and this code.
Manufacturer's installation instructions shall be available on  the  job
site at the time of inspection.
  304.2  Conflicts. Where conflicts between this code and the conditions
of listing or the manufacturer's installation  instructions  occur,  the
provisions of this code shall apply.
  Exception:  Where  a  code  provision  is  less  restrictive  than the
conditions  of  the  listing  of  the  equipment  or  appliance  or  the
manufacturer's  installation instructions, the conditions of the listing
and the manufacturer's installation instructions shall apply.
  304.3 Elevation of ignition source. Equipment and appliances having an
ignition source and located in hazardous locations and  public  garages,
private   garages,   repair  garages,  automotive  motor-fuel-dispensing
facilities and parking garages shall be elevated such that the source of
ignition is not less than 18 inches (457 mm) above the floor surface  on
which  the  equipment  or appliance rests. Such equipment and appliances
shall not be installed in Group H occupancies  or  control  areas  where
open  use, handling or dispensing of combustible, flammable or explosive
materials occurs. For the purpose of this section, rooms or spaces  that
are not part of the living space of a dwelling unit and that communicate
directly  with  a private garage through openings shall be considered to
be part of the private garage.
  304.4  Hydrogen  generating   and   refueling   operations.   Hydrogen
generation  and  refueling  operations  shall  be  prohibited  except as
permitted by the Commissioner of the Fire Department.
  304.5 Public garages. Appliances located in public garages, motor fuel
dispensing facilities, repair garages or other areas frequented by motor
vehicles, shall be installed a minimum of 8 feet  (2438  mm)  above  the
floor.  Where  motor  vehicles exceed 6 feet (1829 mm) in height and are
capable of passing under an appliance, appliances shall be  installed  a
minimum of 2 feet (610 mm) higher above the floor than the height of the
tallest vehicle.
  Exception:  The requirements of this section shall not apply where the
appliances are protected from motor  vehicle  impact  and  installed  in
accordance with Section 304.3 and NFPA 88B.
  304.6  Private  garages.  Appliances  located  in  private garages and
carports shall be installed with a minimum clearance of 6 feet (1829 mm)
above the floor.
  Exception: The requirements of this section shall not apply where  the
appliances  are  protected  from  motor  vehicle impact and installed in
accordance with Section 304.3.
  304.7 Construction and protection.  Boiler  rooms  and  furnace  rooms
shall be protected as required by the New York City Building Code.
  304.8 Clearances to combustible construction. Heat-producing equipment
and appliances shall be installed to maintain the required clearances to
combustible  construction as specified in the listing and manufacturer's

instructions. Such clearances shall be reduced only in  accordance  with
Section   308.   Clearances   to   combustibles   shall   include   such
considerations as door  swing,  drawer  pull,  overhead  projections  or
shelving  and window swing, shutters, coverings and drapes. Devices such
as doorstops or limited, closets, drapery ties or guards  shall  not  be
used to provide the required clearances.
  304.9  Clearances  from  grade.  Equipment and appliances installed at
grade level shall be  supported  on  a  level  concrete  slab  or  other
approved  material extending above adjoining grade or shall be suspended
a minimum of 6 inches (152 mm) above adjoining grade.
  304.10 Guards. Guards shall be provided where  appliances,  equipment,
fans or other components that require service are located within 10 feet
(3048 mm) of a roof edge or open side of a walking surface and such edge
or  open  side  is located more than 30 inches (762 mm) above the floor,
roof or grade below. The guard shall extend not less than 30 inches (762
mm) beyond each end of such appliance, equipment, fan or  component  and
the  top of the guard shall be located not less than 42 inches (1067 mm)
above the elevated surface adjacent to the guard.  The  guard  shall  be
constructed  so as to prevent the passage of a 21-inch-diameter (533 mm)
sphere and shall comply with the load requirements for guards  specified
in the New York City Building Code.
  304.11  Area  served. Appliances serving different areas of a building
other than where they are installed shall be permanently  marked  in  an
approved  manner  that uniquely identifies the appliance and the area it
serves.
                             SECTION MC 305
                             PIPING SUPPORT
  305.1 General. All mechanical system  piping  shall  be  supported  in
accordance with this section.
  305.2  Materials.  Pipe  hangers  and  supports  shall have sufficient
strength to withstand  all  anticipated  static  and  specified  dynamic
loading  conditions  associated  with the intended use. Pipe hangers and
supports that are in direct contact with piping shall  be  of  materials
that  are  compatible with the piping and that will not promote galvanic
action.
  305.3 Structural attachment. Hangers and anchors shall be attached  to
the building structure.
  305.4  Interval of support. Piping shall be supported at distances not
exceeding the spacing specified in Table 305.4, or  in  accordance  with
MSS SP-69.
                               TABLE 305.4
                        PIPING SUPPORT SPACING{a}
    ---------------------------------------------------------------
                                       |   MAXIMUM   |   MAXIMUM
                                       |  HORIZONTAL |   VERTICAL
                                       |   SPACING   |   SPACING
        PIPING MATERIAL                |   (feet)    |   (feet)
    ---------------------------------------------------------------
     ABS pipe                          |      4      |    10{c}
    ---------------------------------------------------------------
     Aluminum pipe and tubing          |      10     |     15
    ---------------------------------------------------------------
     Brass pipe                        |      10     |     10
    ---------------------------------------------------------------
     Brass tubing, 1-1/4-inch diameter |      6      |     10
     and smaller                       |             |
    ---------------------------------------------------------------
     Brass tubing, 1-1/2-inch diameter |      10     |     10

     and larger                        |             |
    ---------------------------------------------------------------
     Cast-iron pipe{b}                 |      5      |     15
    ---------------------------------------------------------------
     Copper or copper-alloy pipe       |      12     |     10
    ---------------------------------------------------------------
     Copper or copper-alloy tubing,    |      6      |     10
     1 1/4-inch diameter and smaller   |             |
    ---------------------------------------------------------------
     Copper or copper-alloy tubing,    |      10     |     10
     1 1/2-inch diameter and larger    |             |
    ---------------------------------------------------------------
     CPVC pipe or tubing, 1 inch and   |      3      |    10{c}
     smaller                           |             |
    ---------------------------------------------------------------
     CPVC pipe or tubing 1 3/4 inch    |      4      |    10{c}
     and larger
    ---------------------------------------------------------------
     Steel pipe                        |      12     |     15
    ---------------------------------------------------------------
     Lead pipe                         |  Continuous |     4
    ---------------------------------------------------------------
     PB pipe or tubing                 |    2 2/3    |     4
                                       | (32 inches) |
    ---------------------------------------------------------------
     PEX tubing                        |    2 2/3    |    10{c}
                                       | (32 inches) |
    ---------------------------------------------------------------
     PVC pipe                          |      4      |    10{c}
    ---------------------------------------------------------------
     For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
     a. See Section 301.14.
     b. The maximum horizontal spacing of cast-iron pipe hangers shall
        be increased to 10 feet where 10-foot lengths of pipe are installed.
     c. Mid-story guide.
  305.5 Protection against physical damage. In concealed locations where
piping,  other  than  cast-iron  or steel, is installed through holes or
notches in studs, joists, rafters  or  similar  members  less  than  1.5
inches  (38  mm)  from the nearest edge of the member, the pipe shall be
protected by shield plates. Protective shield plates shall be a  minimum
of  0.062-inch-thick  (1.6  mm)  steel, shall cover the area of the pipe
where the member is notched or bored, and shall extend a  minimum  of  2
inches (51 mm) above sole plates and below top plates.
                             SECTION MC 306
                        ACCESS AND SERVICE SPACE
  306.1  Clearances  for  maintenance and replacement. Clearances around
appliances  to  elements  of  permanent  construction,  including  other
installed  equipment  and  appliances,  shall  be  sufficient  to  allow
inspection,  service,  repair  or  replacement  without  removing   such
elements  of  permanent  construction  or  disabling  the  function of a
required fire-resistance-rated assembly.
  306.1.1 Central furnaces.  Central  furnaces  within  compartments  or
alcoves shall have a minimum working space clearance of 3 inches (76 mm)
along  the sides, back and top with a total width of the enclosing space
being at least 12 inches (305  mm)  wider  than  the  furnace.  Furnaces
having  a  firebox  open  to the atmosphere shall have at least 6 inches
(152  mm)  working  space  along  the  front  combustion  chamber  side.

Combustion  air  openings  at  the rear or side of the compartment shall
comply with the requirements of Chapter 7.
  Exception:  This  section  shall  not  apply to replacement appliances
installed in existing compartments and alcoves where the  working  space
clearances   are   in   accordance   with  the  equipment  or  appliance
manufacturer's installation instructions.
  306.2 Appliances  in  rooms.  Rooms  containing  appliances  requiring
access  shall  be  provided  with  a door and an unobstructed passageway
measuring not less than 36 inches (914 mm) wide and 80 inches (2032  mm)
high.
  Exception:   Within   a  dwelling  unit,  appliances  installed  in  a
compartment, alcove, basement or similar space shall be accessed  by  an
opening  or  door and an unobstructed passageway measuring not less than
24 inches (610 mm) wide and large enough to allow removal of the largest
appliance in the space, provided that a level space of not less than  30
inches  (762 mm) deep and the height of the appliance, but not less than
30 inches (762 mm), is present at the  front  or  service  side  of  the
appliance with the door open.
  306.3  Appliances  in  attics.  Attics containing appliances requiring
access shall be provided with an  opening  and  unobstructed  passageway
large  enough  to allow removal of the largest appliance. The passageway
shall not be less than 30 inches (762 mm) high and 22  inches  (559  mm)
wide  and  not  more than 20 feet (6096 mm) in length measured along the
centerline of the passageway from the  opening  to  the  appliance.  The
passageway  shall have continuous solid flooring not less than 24 inches
(610 mm) wide. A level service space not less than 30  inches  (762  mm)
deep  and  30  inches  (762  mm)  wide  shall be present at the front or
service side of the appliance. The clear access opening dimensions shall
be a minimum of 20 inches by 30 inches (508 mm by 762  mm),  where  such
dimensions are large enough to allow removal of the largest appliance.
  Exception:  The  passageway  and  level service space are not required
where the appliance is capable of being serviced and removed through the
required opening.
  306.3.1 Electrical requirements. A lighting  fixture  controlled  y  a
switch  located  at  the  required  passageway  opening and a receptacle
outlet shall be provided at or near the appliance location in accordance
with the New York City Electrical Code.
  306.4 Appliances under floors. Underfloor spaces containing appliances
requiring  access  shall  be  provided  with  an  access   opening   and
unobstructed  passageway  large  enough to remove the largest appliance.
The passageway shall not be less than 30 inches (762  mm)  high  and  22
inches (559 mm) wide, nor more than 20 feet (6096 mm) in length measured
along  the  centerline  of  the  passageway  from  the  opening  to  the
appliance. A level service space not less than 30 inches (762  mm)  deep
and  30  inches  (762  mm) wide shall be present at the front or service
side of the appliance. If the depth of the  passageway  or  the  service
space exceeds 12 inches (305 mm) below the adjoining grade, the walls of
the passageway shall be lined with concrete or masonry. Such concrete or
masonry  shall extent a minimum of 4 inches (102 mm) above the adjoining
grade and shall  have  sufficient  lateral-bearing  capacity  to  resist
collapse.  The  clear access opening dimensions shall be a minimum of 22
inches by 30 inches (559 mm by 762 mm), where such dimensions are  large
enough to allow removal of the largest appliance.
  Exception:  The  passageway  is  not  required where the level service
space is present when the access is open and the appliance is capable of
being serviced and removed through the required opening.
  306.4.1 Electrical requirements. A lighting fixture  controlled  by  a
switch  located  at  the  required  passageway  opening and a receptacle

outlet shall be provided at or near the appliance location in accordance
with the New York City Electrical Code.
  306.5  Equipment and appliances on roofs or elevated structures. where
equipment and appliances requiring access  are  installed  on  roofs  or
elevated structures at a height exceeding 16 feet (4877 mm), such access
shall  be  provided  by a permanent means of access, the extent of which
shall be from grade or floor level  to  the  equipment  and  appliances'
level  service  space.  Such  access  shall  not  require  climbing over
obstructions greater than 30 inches (762 mm) high or  walking  on  roofs
having  a  slope  greater  than  4 units vertical in 12 units horizontal
(33-percent slope).
  Permanent ladders installed  to  provide  the  required  access  shall
comply with the following minimum design criteria:
  1.  The  side  railing shall extend above the parapet or roof edge not
less than 30 inches (762 mm).
  2. Ladders shall have rung spacing not to exceed 14 inches (356 mm) on
center.
  3. Ladders shall have a toe spacing not less than 6  inches  (152  mm)
deep.
  4. There shall be a minimum of 18 inches (457 mm) between rails.
  5.  Rungs  shall  have  a  minimum 0.75 inch (19.1 mm) diameter and be
capable of withstanding a 300-pound (136.1 kg) load.
  6. Ladders over 30 feet (9144 mm) in height  shall  be  provided  with
offset  sections  and  landing capable of withstanding 100 pounds (488.2
kg/m{2}) per square foot.
  7. Ladders shall be protected against corrosion.
  Catwalks installed to provide the required access shall  be  not  less
than  24  inches  (610  mm) wide and shall have railings as required for
service platforms.
  Exception: This section shall not apply to Group R-3 occupancies.
  306.6 Sloped roofs. Where appliances are installed on a roof having  a
slope  of  3 units vertical in 12 units horizontal (25-percent slope) or
greater and having an edge more than 30 inches (762 mm) above  grade  at
such  edge,  a  level  platform  shall  be  provided on each side of the
appliance to which access is required by the manufacturer's installation
instructions for service, repair or maintenance. The platform shall  not
be  less  than 30 inches (762 mm) in any dimension and shall be provided
with guards in accordance with Section 304.10.
                             SECTION MC 307
                           CONDENSATE DISPOSAL
  307.1  Fuel-burning  appliances.  Liquid  combustion  by-products   of
condensing  appliances  shall  be collected and discharged to a plumbing
fixture  or  disposal  area  in  accordance  with   the   manufacturer's
installation    instruction.    Condensate    piping    shall    be   of
corrosion-resistant material and shall not be  smaller  than  the  drain
connection  on  the  appliance.  Such  piping  shall  maintain a minimum
horizontal slope in the direction of discharge of not less than 1/8 unit
vertical in 12 units horizontal (1-percent slope).
  307.2 Evaporators and cooling coils. Condensate drain systems shall be
provided for equipment and appliances containing evaporators or  cooling
coils.  Condensate  drain  systems  shall  be  designed, constructed and
installed in accordance with Sections 307.2.1 through 307.2.4.
  307.2.1  Condensate disposal. Condensate from all  cooling  coils  and
evaporators  shall  be  conveyed from the drain pan outlet to a place of
disposal. Condensate shall not discharge into a street, alley  or  other
areas so as to cause a nuisance.
  307.2.2  Drain  pipe materials and sizes. Components of the condensate
disposal  system  shall  be  cast  iron,   galvanized   steel,   copper,

cross-linked  polyethylen, polyethylen, ABS, CPVC or PVC pipe or tubing.
All components shall be selected for the pressure and temperature rating
of the installation. Condensate waste and drain line size shall  be  not
less  than  3/4 inch (19 mm) internal diameter and shall not decrease in
size from the drain pan connection to the place of condensate  disposal.
Where  the  drain  pipes from more than one unit are manifolded together
for condensate drainage, the pipe or tubing shall be sized  accordingly.
All  horizontal  sections  of drain piping shall be installed in uniform
alignment at a uniform slope.
  307.2.3 Auxiliary and secondary drain  systems.  In  addition  to  the
requirements  of  Section 307.2.3 Auxiliary and secondary drain systems.
In addition to the requirements of Section 307.2.1, a secondary drain or
auxiliary drain pan shall be required for  each  cooling  or  evaporator
coil  where  damage to any building components will occur as a result of
overflow from the equipment drain pan  or  stoppage  in  the  condensate
drain piping. One of the following methods shall be used:
  1.  An  auxiliary  drain  pan  with a separate drain shall be provided
under the coils on which condensation  will  occur.  The  auxiliary  pan
drain  shall  discharge  to  a  conspicuous  point  of disposal to alert
occupants in the event of a stoppage of the primary drain. The pan shall
have a minimum depth of 1.5 inches (38 mm), shall not b e  less  than  3
inches  (76 mm) larger than the unit or the coil dimensions in width and
length  and  shall  be  constructed  of  corrosion-resistant   material.
Metallic   pans  shall  have  a  minimum  thickness  of  not  less  than
0.0276-inch (0.7 mm) galvanized sheet metal. Nonmetallic pans shall have
a minimum thickness of not less than 0.0625 inch (1.59 mm).
  2. A separate overflow drain line shall be connected to the drain  pan
provided  with  the  equipment. Such overflow drain shall discharge to a
conspicuous point of disposal to alert  occupants  in  the  event  of  a
stoppage  of the primary drain. The overflow drain line shall connect to
the drain pan at a higher level than the primary drain connection.
  3. An auxiliary drain pan without  a  separate  drain  line  shall  be
provided  under the coils on which condensate will occur. Such pan shall
be equipped with a water-level detection device that will shut  off  the
equipment  served  prior to overflow of the pan. The auxiliary drain pan
shall be constructed in accordance with Item 1 of this section.
  307.2.4 Traps. Condensate drains shall be trapped as required  by  the
equipment or appliance manufacturer.
  307.3  Exceptions.  This  section  applies  to  permanently  installed
equipment. Window units and through-the-wall air-conditioning units  are
exempt from the requirements of this section.
                             SECTION MC 308
                           CLEARANCE REDUCTION
  308.1  Scope.  This  section  shall  govern  the reduction in required
clearances to  combustible  materials  and  combustible  assemblies  for
chimneys,  vents,  kitchen exhaust equipment, mechanical appliances, and
mechanical devices and equipment.
  308.2 Listed appliances and equipment. The reduction of  the  required
clearances  to  combustibles  for  listed  and  labeled  appliances  and
equipment shall be in accordance with the requirements of  this  section
except  that  such  clearances  shall  not be reduced where reduction is
specifically prohibited by the  terms  of  the  appliance  or  equipment
listing.
  308.3  Protective  assembly  construction  and  installation.  Reduced
clearance  protective  assemblies,  including  structural  and   support
elements,  shall  be  constructed  of non-combustible materials. Spacers
utilized to maintain an airspace between the protective assembly and the
protected material or assembly shall be non-combustible. Where  a  space

between  the  protective  assembly and protected combustible material or
assembly is specified, the same space shall be provided around the edges
of the protective assembly and the spacers shall  be  places  so  as  to
allow air circulation by convention in such space. Protective assemblies
shall  not  be  places  less  than  1  inch  (25 mm) form the mechanical
appliances, devices or equipment, regardless of  the  allowable  reduced
clearance.
  308.4  Allowable  reduction.  The  reduction of required clearances to
combustible assemblies or combustible materials shall be  based  on  the
utilization of a reduced clearness protective assembly in assurance with
Section 308.5 or 308.6.
  308.5  Labeled  assemblies. The allowable clearness reduction shall be
based on a reduced clearance protective assembly that  has  been  tested
and bears the label of an approved agency.
  308.6  Reduction  table.  The  allowable  clearance reduction shall be
based on one of the methods specified in  table  308.6.  Where  required
clearances  are  not listed in Table 308.6, the reduced clearances shall
be determined by linear interpolation between the  distances  listed  in
the  table.  Reduced  clearances  shall  not be derived by extrapolation
below the range of the table.
                                TABLE 308.6
                       CLEARANCE REDUCTION METHODS
------------------------------------------------------------------------
                                        |   REDUCED CLEARANCE WITH
                                        |   PROTECTION (inches){a}
                                        --------------------------------
                                        |               |Horizontal com-
                                        |               |bustible assem-
                                        |               |blies located
                                        |Horizontal com-|beneath the
                                        |bustible assem-|heat source and
                                        |blies located  |all vertical
                                        |above the heat |combustible
                                        |source         |assemblies
                                        --------------------------------
                                        |Required clear-|Required clear-
                                        |ance to combus-|ance to combus-
                                        |tibles without |tibles without
                                        |  protection   |  protection
                                        |  (inches){a}  |  (inches){a}
                                        --------------------------------
   TYPE OF PROTECTIVE ASSEMBLY{a}       |36 |18 | 9 | 6 |36 |18 | 9 | 6
------------------------------------------------------------------------
Galvanized sheet metal, minimum nominal |   |   |   |   |   |   |   |
thickness  of .0296 inch (No. 22 Gage), |   |   |   |   |   |   |   |
mounted on 1-inch glass  fiber or min-  |18 | 9 | 5 | 3 |12 | 6 | 3 | 3
eral wool batt  reinforced with wire on |   |   |   |   |   |   |   |
the  back, 1 inch off the combustible   |   |   |   |   |   |   |   |
assembly                                |   |   |   |   |   |   |   |
------------------------------------------------------------------------
Two layers of galvanized  sheet metal,  |   |   |   |   |   |   |   |
minimum  nominal thickness of  0.024    |   |   |   |   |   |   |   |
inch (No. 24 Gage), having a 1-inch air-|18 | 9 | 5 | 3 |12 | 6 | 3 | 3
space  between layers, spaced  1-inch   |   |   |   |   |   |   |   |
off the combustible  assembly           |   |   |   |   |   |   |   |
------------------------------------------------------------------------
0.5-inch inorganic  insulating board    |   |   |   |   |   |   |   |
over 1 inch of fiberglass or mineral    |24 |12 | 6 | 4 |18 | 9 | 5 | 3

wool batt, against the combustible      |   |   |   |   |   |   |   |
assembly                                |   |   |   |   |   |   |   |
------------------------------------------------------------------------
3.5-inch brick wall, spaced 1 inch off  | - | - | - | - |12 | 6 | 6 | 6
the combustible wall                    |   |   |   |   |   |   |   |
------------------------------------------------------------------------
3.5-inch brick wall, against the        | - | - | - | - |24 |12 | 6 | 5
combustible wall                        |   |   |   |   |   |   |   |
------------------------------------------------------------------------
For  SI:  1 inch = 25.4 mm. °C = [(°F)-321]1.8, 1 pound per cubic foot =
16.02 kg/m{3}, 1.0 Btu - in/ft{2} - h - °F = 0.144 W/m{2} - K.
a. Mineral wool and glass fiber batts  (blanket  or  board)  shall  have
   minimum  density  of  8  pounds  per cubic foot and a minimum melting
   point of 1,500°F. Insulation material utilized as part of a clearance
   reduction system shall have a  thermal  conductivity  of  1.0  Btu  -
   in./(ft{2}-h-°F)  or  less.  Insulation  board  shall  be  formed  of
   non-combustible material.
  308.7 Solid fuel-burning appliances. The clearance  reduction  methods
specified  in  Table 308.6 shall not be utilized to reduce the clearance
required  for  solid  fuel-burning  appliances  that  are  labeled   for
installation  with  clearances  of  12  inches  (305  mm) or less. Where
appliances are labeled for installation with clearances of greater  than
12 inches (305 mm), the clearance reduction methods of Table 308.6 shall
not reduce the clearance to less than 12 inches (305 mm).
  308.8  Masonry  chimneys. The clearance reduction methods specified in
Table 308.6 shall not be utilized to reduce the clearances required  for
masonry  chimneys  as  specified  in  Chapter  8  and  the New York City
Building Code.
  308.9 Chimney connector pass-throughs. The clearance reduction methods
specified in Table 308.6 shall not be utilized to reduce the  clearances
required  for  chimney  connector  pass-throughs as specified in Section
803.10.4.
  308.10 Masonry fireplaces. The clearance reduction  methods  specified
in  Table  308.6 shall not be utilized to reduce the clearances required
for masonry fireplaces as specified in Chapter 8 and the New  York  City
Building Code.
  308.11   Kitchen   exhaust  ducts.  The  clearance  reduction  methods
specified in Table 308.6 shall not be utilized  to  reduce  the  minimum
clearances  required  by  Section  506.3.10  for  kitchen  exhaust ducts
enclosed in a shaft.
                             SECTION MC 309
                           TEMPERATURE CONTROL
  309.1  Space-heating  systems.  Interior  spaces  intended  for  human
occupancy shall be provided with active or passive space-heating systems
capable  of maintaining a minimum indoor temperature of 68°F (20°C) at a
point 3 feet (914 mm)  above  floor  on  the  design  heating  day.  The
installation  of  portable  space  heaters  shall not be used to achieve
compliance with this section. Refer to Section 1204 of the New York City
Building Code.
  Exception: Interior spaces where the primary purpose is not associated
with human comfort.
                             SECTION MC 310
                            EXPLOSION CONTROL
  310.1 Required. Structures occupied for purposes  involving  explosion
hazards  shall  be  provided  with  explosion control in compliance with
rules of the commissioner of  the  fire  Department.  Explosion  control
systems  shall be designed and installed in accordance with the New York
City Fire Code.

                             SECTION MC 311
                          SMOKE AND HEAT VENTS
  311.1  Required.  Approved  smoke and heat vents shall be installed in
the roofs of one-story buildings where required by  the  New  York  city
fire  code.  Smoke  and  heat  vents  shall be designed and installed in
accordance with the New York City Fire Code.
                             SECTION MC 312
                  HEATING AND COOLING LOAD CALCULATIONS
  312.1 Load calculations. Heating and cooling system design  loads  for
the  purpose  of  sizing  systems,  appliances  and  equipment  shall be
determined in accordance with the procedures  described  in  the  ASHRAE
Handbook of Fundamentals. Heating and cooling loads shall be adjusted to
account  for  load  reductions  that  are  achieved when energy recovery
systems are utilized in the HVAC system in accordance  with  the  ASHRAE
Handbook - HVAC Systems and Equipment. Alternatively, design loads shall
be determined by an approved equivalent computation procedure, using the
design  parameters  specified  in  Chapter 3 of the New York City Energy
Conservation Code. Heating and  cooling  system  design  loads  for  the
purpose  of  sizing  systems, appliances and equipment shall also comply
with the requirements of Section 1204 of  the  New  York  City  Building
Code.
                                 CHAPTER 4
                               VENTILATION

                             SECTION MC 401
                                 GENERAL
  401.1  Scope.  This  chapter  shall  govern  the ventilation of spaces
within a building intended to be occupied. This chapter does not  govern
the  requirements  for  smoke  control  systems. See Section 513 of this
code.
  401.2 Ventilation required. Every occupied space shall  be  ventilated
by  natural  means in accordance with Section 402 or by mechanical means
in accordance with Section 403.
  401.3 When required. Ventilation shall be provided during the  periods
that the room or space is occupied.
  401.4  Exits.  Equipment  and  ductwork for exit enclosure ventilation
shall comply with one of the following items:
  1. Such equipment and  ductwork  shall  be  located  exterior  to  the
building  and  shall  be  directly  connected  to  the exit enclosure by
ductwork enclosed in construction as  required  by  the  New  York  City
Building code for shafts.
  2.  Where  such  equipment  and  ductwork  is  located within the exit
enclosure, the intake air shall be taken directly for the  outdoors  and
the  exhaust  air  shall be discharged directly to the outdoors, or such
air shall be conveyed through ducts enclosed in construction as required
by the New York City Building code for shafts.
  3. Where located within the  building,  such  equipment  and  ductwork
shall  be  separated from the remainder of the building, including other
mechanical equipment, with construction as required by the New York city
Building Code for shafts.
  In each case, openings into fire-resistance-rated  construction  shall
be  limited  to  those needed for maintenance and operation and shall be
protected by self-closing fire-resistance-rated  devices  in  accordance
with  the  New  York  City  Building  Code  for  enclosure  wall opening
protectives.
  Exit enclosure ventilation  systems  shall  be  independent  of  other
building ventilation systems.

  401.5  Opening location. Outside air exhaust and intake openings shall
be located a minimum of 10 feet (3048 mm) from lot lines or buildings on
the same lot. Where openings front  on  a  street  or  public  way,  the
distance  shall  be  measured  to the centerline of the street or public
way.  Outdoor  intakes  for  high-rise  office buildings having occupied
floors located more than 75 feet (22 860 mm) above the lowest  level  of
fire department vehicle access serving spaces above the second story and
serving  spaces  greater  than 10,000 square feet (929 square meters) of
floor area shall be located at least 20  feet  (6096  mm)  above  ground
level, at least 30 feet (9144 mm) from exhaust outlets and other exhaust
discharges,  and  at least 20 feet (6096 mm) from areas that may collect
vehicular exhaust, such as off street loading bays.
  Exception: Group R-3.
  401.5.1 Intake openings. Mechanical and  gravity  outside  air  intake
openings,  shall  be  located  a  minimum  of 20 feet (6096 mm) from any
hazardous or noxious  contaminant  such  as  vents,  chimneys,  plumbing
vents,  streets,  alleys,  parking  lots  and  loading  docks, except as
otherwise specified in this code.  Where  a  source  of  contaminant  is
located  within  20  feet  (6096  mm) of an intake opening, such opening
shall be located a minimum of 2 feet  (610  mm)  below  the  contaminant
source.
  An  outdoor air intake opening with gross area of more than 144 square
inches (.0929 m{2}) shall  be  provided  with  dire  dampers  and  smoke
dampers, or combined fire and smoke dampers when such opening is located
as follows:
  1. Less than 30 feet (9144 mm) above grade.
  2.  Less  than  30 feet (9144 mm) in any direction from any opening in
another building.
  3. Less than 15 feet (4572 mm) from a lot line.
  4. Less than 50 feet (15 240 mm) above and less than 50 feet  (15  240
mm)  in any direction from a roof constructed of combustible material or
a building in which the exterior walls are constructed wholly or  partly
of wood.
  Exceptions:
  1. Smoke dampers shall not be required for outdoor air intake openings
installed  in any construction required to have a fire resistance rating
that is less than two hours.
  2. Smoke dampers shall not be required for outdoor air intake openings
of systems greater than 15,000 cfm (7.1 m{3}/s) which are provided  with
smoke  dampers in accordance with Chapter 6 of this code and arranged so
as to not introduce smoke into the  building,  or  space  in  which  the
equipment is located.
  401.5.2  Exhaust  openings. To minimize the hazard from fires and from
noxious, toxic or obnoxious discharges to structures,  any  exhaust  air
discharge to the outside atmosphere shall terminate at or above the roof
or  setback  roof  of  the  buildings or in an exterior wall adjoining a
street, yard or court. Exhaust air discharges shall be at least 10  feet
(3048  mm) above the  sidewalk or ground and shall terminate at least 10
feet (3048 mm) from any window in another building or from any window in
a residential portion of the same building, or  from  any  fire  escape,
exterior  stair,  or  balcony. Exhaust system openings shall be provided
with vanes or louvers constructed so as to  direct  the  air  away  from
windows, other openings, and pedestrians.
  Exception:  In  occupancy groups R-2 and R-3 each dwelling unit may be
individually exhausted  directly  to  the  outdoors  with  a  dedicated,
continuously operated exhaust fan and shall comply with the following:

  1.  The  exhaust  system  for  the kitchen and the toilet/baths may be
combined to the inlet of a single  fan,  provided  such  exhaust  system
serves only one dwelling unit.
  2.  The  dedicated  exhaust  from each dwelling unit shall be directed
away from any window serving, the same  dwelling  unit  from  which  the
exhaust  is taken, and in addition, such exhaust opening shall terminate
at least:
  2.1. 2 feet (610 mm) from any window serving the same dwelling unit.
  2.2. 4 feet (1219 mm) from any window serving  an  adjoining  dwelling
unit.
  2.3.  4 feet (1219 mm) from any window serving another occupancy group
in the same building.
  2.4. 10 feet (3048 mm) from any outdoor air intake opening.
  2.5. 10 feet (3048 mm) above the public sidewalk  adjoining  the  same
building.
  3. All other minimum distances described in 401.5 shall be met.
  401.5.3 Flood hazard. For structures located in areas of special flood
hazard, outdoor exhaust openings shall comply with Appendix G of the New
York City Building Code.
  401.6 Outdoor opening protection. Air exhaust and intake openings that
terminate  outdoors shall be protected with corrosion-resistant screens,
louvers or grilles. Openings in louvers, grilles and  screens  shall  be
sized  in  accordance  with  Table 401.6, and shall be protected against
local weather  conditions.  Outdoor  air  exhaust  and  intake  openings
located  in  exterior  walls shall meet the provisions for exterior wall
opening protectives in accordance with the New York City Building Code.

                               TABLE 401.6
    OPENING SIZES IN LOUVERS, GRILLES AND SCREENS PROTECTING OUTDOOR
                     EXHAUST AND AIR INTAKE OPENINGS
   ------------------------------------------------------------------
                                 | MINIMUM AND MAXIMUM OPENING SIZES
                                 |  IN LOUVERS, GRILLS AND SCREENS
      OUTDOOR OPENING TYPE       |   MEASURED IN ANY DIRECTION
   ------------------------------------------------------------------
    Exhaust, openings            | Not  1/2 inch
   ------------------------------------------------------------------
    Intake openings in           | Not  1/2 inch
    residential occupancies      |
   ------------------------------------------------------------------
    Intake openings in other than|   > 1/4 inch and not > 1 inch
    residential occupancies      |
   ------------------------------------------------------------------
    For SI: 1 inch = 25.4 min.

  401.7  Contaminant  sources.  Stationary   local   sources   producing
air-borne  particulates,  heat,  odors,  fumes,  spray, vapors, smoke or
gases in such quantities as to be  irritating  or  injurious  to  health
shall be provided with an exhaust system in accordance with Chapter 5 or
a  means  of  collection  and  removal of the contaminants. Such-exhaust
shall discharge directly to an approved location at the exterior of  the
building.
                             SECTION MC 402
                           NATURAL VENTILATION
402.1  General.  Natural  ventilation  of an occupied space shall comply
with Chapter 12 of the New York City Building Code.
  402.2 Reserved.
  402.3 Reserved.

  402.4 Reserved.
                             SECTION MC 403
                         MECHANICAL VENTILATION
403.1  Ventilation system. Mechanical ventilation shall be provided by a
method of supply air and return or exhaust air. The amount of supply air
shall be approximately equal to the amount of return  and  exhaust  air.
The  system  shall not be prohibited from producing negative or positive
pressure. The system to convey ventilation air  shall  be  designed  and
installed in accordance with Chapter 6.
  Ventilation  supply  systems shall be designed to deliver the required
rate of supply air to the occupied zone within an  occupied  space.  The
occupied  zone shall have boundaries measured at 3 inches (76 mm) and 72
inches (1829 mm) above the  floor  and  24  inches  (610  mm)  from  the
enclosing walls.
  403.2  Outdoor  air required. The minimum ventilation rate of required
outdoor air shall be determined in accordance with Section 403.3.
  403.2.1 Recirculation of air. The air required by Section 403.3  shall
not  be  recirculated.  Air  in excess of that required by Section 403.3
shall not be prohibited from being recirculated as a component of supply
air to building spaces. except that:
  1. Ventilation air shall not be recirculated from one dwelling unit to
another or to dissimilar occupancies.
  2. Supply air to a swimming pool and associated deck areas  shall  not
be recirculated unless such air is dehumidified to maintain the relative
humidity of the area at 60 percent or less. Air from this area shall not
be recirculated to other spaces.
  3.  Where mechanical exhaust is required by Table 403.3, recirculation
of air from such spaces shall be prohibited. All air  supplied  to  such
spaces  shall be exhausted, including any air in excess of that required
by Table 403.3.
  403.2.2 Transfer air. Except where recirculation from such  spaces  is
prohibited  by  Table 403.3, air transferred from occupied spaces is not
prohibited from serving, as makeup air for required exhaust  systems  in
such  spaces  as  kitchens,  baths,  toilet rooms, elevators and smoking
lounges. The amount of transfer air and exhaust air shall be  sufficient
to  provide  the  flow rates as specified in Sections 403.3 and 403.3.1.
The required outdoor  air  rates  specified  in  Table  403.3  shall  be
introduced  directly  into  such spaces or into the occupied spaces from
which air is transferred or a combination of both.
  403.3 Ventilation rate. Ventilation systems shall be designed to  have
the  capacity  to  supply the minimum outdoor airflow rate determined in
accordance with Table 403.3 based on the occupancy of the space and  the
occupant  load  or  other parameter as stated therein. The occupant load
utilized for design of the ventilation system shall not be less than the
number  determined  from  the  estimated  maximum  occupant  load   rate
indicated   in  Table  403.3.  Ventilation  rates  for  occupancies  not
represented  in  Table  403.3  shall  be  determined  by   an   approved
engineering analysis. The ventilation system shall be designed to supply
the  required rate of ventilation air continuously during the period the
building is occupied, except as otherwise stated in other provisions  of
the code.
  Exception:  The  occupant load is not required to be determined, based
on the estimated maximum occupant load rate indicated  in  Table  403.3,
where  approved  statistical  data document the accuracy of an alternate
anticipated occupant density.

                               TABLE 403.3
                    REQUIRED OUTDOOR VENTILATION AIR

                               ESTIMATED
                               MAXIMUM               OUTDOOR AIR
                               OCCUPANT             (Cubic feet per
                              LOAD, PERSONS          minute (cfm)
                               PER 1,000              per person)
  OCCUPANCY CLASSIFICATION     SQUARE FEET{a}       UNLESS NOTED{e}
________________________________________________________________________
Correctional facilities
 Cells
   without plumbing,
   fixtures                        20                    20
   with plumbing fixtures          20                    20
Dining halls                      100                    15
Guard stations                     40                    15
________________________________________________________________________
Dry cleaners, laundries
 Coin-operated dry cleaner         20                    15
 Coin-operated laundries           20                    15
 Commercial dry cleaner            30                    30
 Commercial laundry                10                    25
 Storage, pick up                  30                    35
________________________________________________________________________
Education
 Auditoriums                      150                    15
 Classrooms                        50                    15
 Corridors                         --               0.10 cfm/ft{2}
 Laboratories                      30                    20
 Libraries                         20                    15
 Locker rooms{b}                   --               0.50 cfm/ft{2}
 Music rooms                       50                    15
 Smoking lounges{bg}               70                    60
 Training shops                    30                   20
________________________________________________________________________
Food and beverage service
 Bars, cocktail lounges           100                    30
 Cafeteria, fast food             100                    70
 Dining rooms                      70                    20
 Kitchens (cooking){fa}            20                    15
________________________________________________________________________
Hospitals, nursing and
convalescent homes
 Autopsy rooms{b}                  --               0.50 cfm/ft{2}
 Medical procedure rooms           20                    15
 Operating rooms                   20                    30
 Patient rooms                     10                    25
 Physical therapy                  20                    15
 Recovery and ICU                  20                    15
________________________________________________________________________
Hotels, motels, resorts and
dormitories
 Assembly rooms                    120                   15
 Bathrooms{bg}                     --               35 cfm per room
 Bedrooms                          --               30 cfm per room
 Conference rooms                  50                    20
 Dormitory sleeping areas          20                    15
 Gambling casinos                 120                    30
 Living rooms                      --               30 cfm per room
 Lobbies                           30                    15

________________________________________________________________________
Laboratories
 Industrial and nonteaching         8               1.0 cfm/ft{2}
 Chemical                           8               1.0 cfm/ft{2}
 Biological                         8               1.0 cfm/ft{2}
 Nonproduction chemical labs  as per NFPA 45        as per NFPA 45

                          TABLE 403.3 Continued
                    REQUIRED OUTDOOR VENTILATION AIR
                               ESTIMATED
                               MAXIMUM               OUTDOOR AIR
                               OCCUPANT             (Cubic feet per
                              LOAD, PERSON           minute (cfm)
                               PER 1,000              per person)
  OCCUPANCY CLASSIFICATION     SQUARE FEET{a}       UNLESS NOTED{e}
________________________________________________________________________
Offices
 Conference rooms                  50                    20
 Office spaces                      7                    20
 Reception areas                   60                    15
 Telecommunication centers
   and data entry                  60                    20
________________________________________________________________________
Private dwellings, single
 and multiple Garages,
 common for multiple
 units{b}                          --               1.5 cfm/ft{2}

 Garages, separate for each
 dwelling                          --               100 cfm per car

 Kitchens{g}                       --               100 cfm
                                                    intermittent or 25
                                                    cfm continuous

 Living areas{c}              Based upon number     0.35 air changes
                              of bedrooms. First    per hour{3} or 15 cfm
                              bedroom: 2; each      per person.
                                additional           whichever is
                                bedroom: 1            greater

 Toilet rooms and
 bathrooms{g}                      --                 Mechanical
                                                    exhaust capacity of
                                                       50 cfm
                                                    intermittent or 20
                                                     cfm continuous

Public spaces
 Corridors and utilities           --               0.05 cfm/ft{2}
 Elevators{g}                      --               1.00 cfm/ft{2}
 Locker rooms{b}                   --               0.5 cfm/ft{2}
 Shower room
 (per shower head){bg}             70                   50cfm
                                                    intermittent or 20
                                                      cfm continuous
 Smoking lounges{bg}                                     60
 Toilet rooms{bg}                                    75 cfm per water

                                                     closet or urinal

Retail stores, sales floors
 and showroom floors
 Basement and street               --               0.30 cfm/ft{2}
 Dressing rooms                    --               0.20 cfm/ft{2}
 Malls and arcades                 --               0.20 cfm/ft{2}
 Shipping and receiving            --               0.15 cfm/ft{2}
 Smoking lounges                   70                    60
 Storage rooms                     --               0.15 cfm/ft{2}
 Upper floors                      --               0.20 cfm/ft{2}
 Warehouses                        --               0.05 cfm/ft{2}

                          TABLE 403.3 Continued
                    REQUIRED OUTDOOR VENTILATION AIR
                               ESTIMATED
                               MAXIMUM               OUTDOOR AIR
                               OCCUPANT             (Cubic feet per
                              LOAD, PERSONS          minute (cfm)
                               PER 1,000              per person)
  OCCUPANCY CLASSIFICATION     SQUARE FEET{a}       UNLESS NOTED{e}
________________________________________________________________________
Specialty shops
 Automotive motorfuel
 -dispensing stations              --               1.5 cfm/ft{2}
 Barber                            25                    15
 Beauty                            25                    25
 Clothiers, furniture              --               0.30 cfm/ft{2}
 Florists                          8                    15
 Hardware, drugs, fabrics           8                    15
 Nail salon{b}                     --                    25
 Pet shops                         --               1.00 cfm/ft{2}
 Reducing salons                   20                    15
 Supermarkets                       8                    15
________________________________________________________________________
Sports and amusement
 Ballrooms and discos             100                    25
 Bowling alleys (seating
   areas)                          70                    25
 Game rooms                        70                    25
 Ice arenas                        --               0.50 cfm/ft{2}-
 Playing floors (gymnasiums)       30                    20
 Spectator areas                 150                     15
 Swimming pools (pool
   and deck area)                  --               0.50 cfm/ft{2}
________________________________________________________________________
Storage
 Repair garages, enclosed
   parking garages{d}              --               1.5 cfm/ft{2}
 Warehouses                        --               0.05 cfm/ft{2}
________________________________________________________________________
Theaters
 Auditoriums                      150                    15
 Lobbies                          150                    20
 Stages, studios                   70                    15
 Ticket booths                     60                   20
________________________________________________________________________
Transportation

 Platforms                        100                    15
 Vehicles                         150                    15
 Waiting rooms                    100                    15
________________________________________________________________________
Workrooms
 Bank vaults                        5                    15
 Darkrooms                         --               0.50 cfm/ft{2}
 Duplicating, printing             --               0.50 cfm/ft{2}
 Meat processing{c}                10                    15
 Pharmacy                          20                    15
 Photo studios                     10                    15
  For SI: 1 cubic foot per minute = 0.0004719 m{3}/s.  1 ton = 908 kg, 1
cubic  foot  per  minute per square foot = 0.00508 m{3}/(s * M{2}). °C =
[(°F)-32]/1.8, 1 square foot = 0.0929 m{2}.
  a. Based upon net floor area.
  b. Mechanical exhaust required and the recirculation of air from  such
spaces  as  permitted  by  Section  403.2.1  is  prohibited (see Section
403.2.11.
  c. Spaces unheated or maintained below 50°F are not covered  by  these
requirements unless the occupancy is continuous.
  d.  Ventilation  systems in enclosed parking garages shall comply with
Section 404. A mechanical ventilation system shall not  be  required  in
garages  having  a floor area not exceeding 850 square feet and used for
the storage of not more than four vehicles or trucks of  1  ton  maximum
capacity.
  e.  Where the ventilation rate is expressed in cfm/ft{2}, such rate is
based upon cubic feet per minute per square foot of the floor area being
ventilated.
  f. The sum of the outdoor and transfer air from adjacent spaces  shall
be sufficient to provide an exhaust rate of not less than 1.5 cfm/ft{2}.
  g. Transfer air permitted in accordance with Section 403.2.2.
  h.  Nonproduction  chemical laboratories subject to Section 419 of the
New York City Building Code.
  403.3.1 System operation. The minimum flow rate of  outdoor  air  that
the  ventilation system must be capable of suppling during its operation
shall be permitted to be based on the rate per person indicated in Table
403.3 and the actual number of occupants present.  Intermittent  exhaust
shall be permitted where an individual exhaust duct and fan are provided
and  the  operation  of  the fan is controlled by occupants of the space
being vented.
  403.3.2 Common  ventilation  system.  Where  spaces  having  different
ventilation  rate  requirements  are  serviced  by  a common ventilation
system, the ratio of outdoor air to total supply air  force  the  system
shall  be  determined  based on the space having the largest outdoor air
requirement or shall be determined  in  accordance  with  the  following
formula:
                              EQUATION 4-1
                           Y =  X/(1 + X - Z)

Where
  Y = V[oc]V[so] = Corrected fraction of outdoor air in system supply.
  X  =  V[on]/V[zl]  =  Uncorrected  fraction  of  outdoor air in system
supply.
  Z = V[oc]/V[zc] = Fraction of  outdoor  air  in  critical  space.  The
critical  space  is  that  space  with the greatest required fraction of
outdoor air in the supply to this space.
  V[oc] = Corrected total outdoor airflow rate.

  V[zl] = Total supply flow rate, i.e., the sum of all  supply  for  all
branches of the system.
  V[ox] = Sum of outdoor airflow rates for all branches on system.
  V[oc] = Outdoor airflow rate required in critical spaces.
  V[zc] = Supply flow rate in critical space.
  403.3.3    Variable air volume system control. Variable air volume air
distribution  systems,  other  than  those  designed  to   supply   only
100-percent outdoor air, shall be provided with controls to regulate the
flow  of outdoor air. Such control systems shall be designed to maintain
the flow of outdoor air at a rate of not  less  than  that  required  by
Section 403 over the entire range of supply  air operating rates.
  403.3.4  Balancing.  Ventilation  systems  shall  be  balanced  by  an
approved method. Such balancing shall verity that the ventilation system
is capable of supplying the airflow rates required by Section 403.
                             SECTION MC 404
                        ENCLOSED PARKING GARAGES
  404.1 Enclosed parking garages.  Mechanical  ventilation  systems  for
enclosed  parking garages are not required to operate continuously where
the system is arranged to operate  automatically  upon  detection  of  a
concentration  of  carbon  monoxide  of  25  parts  per million (ppm) by
approved automatic detection devices.
  404.2 Minimum ventilation. Automatic operation of the system shall not
reduce  the  ventilation  rate  below   0.05   cfm   per   square   foot
(0.00025m{3}/s * m{2}) of the floor area and the system shall be capable
of  producing a ventilation rate of 1.5 cfm per square foot (0.007m{3}/s
* m{2}) of floor area.
  404.3 Occupied spaces accessory to public garages. Connecting offices,
waiting rooms, ticket boots and similar uses that  are  accessory  to  a
public  garage  shall  be maintained at a positive pressure and shall be
provided with ventilation in accordance with Section 403.3.
                             SECTION MC 405
                             SYSTEMS CONTROL
  405.1 General. Mechanical ventilation systems shall be  provided  with
manual or automatic controls that will operate such systems whenever the
spaces  are  occupied.  Air-conditioning  systems  that  supply required
ventilation  air  shall  be   provided   with   controls   designed   to
automatically  maintain  the  required  outdoor  air  supply rate during
occupancy.
  405.2 Manual control. Each air distribution system shall  be  provided
with  not  less  than  one  manual  control to stop the operation of the
supply, return, and exhaust fans(s) in an emergency. The manual  control
shall be provided at an approved location.
  405.2.1  Office buildings. Any building where the main use or dominant
occupancy is classified in occupancy  group  B  having  occupied  floors
located  more  than  75  feet (22 860 mm) above the lowest level of fire
department vehicles access, where a system  serves  a  floor  or  floors
other  than  the  floor  on  which  the  equipment  is located, shall be
provided with the  following  controls,  in  addition  to  the  controls
required by this chapter:
  1. Manual controls for operating individually each air supply and each
exhaust or return fan in the system located as follows:
  1.1. At the Fire Command Center, and
  1.2. In the room containing the affected air-handling fans.
  2. Manual controls for operating individually or in groups each remote
control  reversible  fire  shutter,  when  such shutters are provided in
accordance with the provisions of the New York City  Building  Code,  or
each  smoke damper provided in accordance with the provisions of the New

York City Building Code. Such controls shall  be  located  at  the  Fire
Command Center.
                             SECTION MC 406
                    VENTILATION OF UNINHABITED SPACES
  406.1  General.  Uninhabited  spaces, such as crawl spaces and attics,
shall be provided with natural ventilation openings as required  by  the
New  York  City  Building  Code  or  shall be provided with a mechanical
exhaust and supply air system. The mechanical exhaust rate shall be  not
less  than 0.02 cfm  per square foot (0.00001 m{3} * m{2}) or horizontal
area and shall be automatically controlled to operate when the  relative
humidity in the space served exceeds 60 percent.
                             SECTION MC 407
           VENTILATION OF NON-PRODUCTION CHEMICAL LABORATORIES
  407.1 General. Non-production chemical laboratories complying with the
hazardous  materials quantity limitations of Section 419 of the New York
City Building Code shall provide  a  mechanical  ventilation  system  in
accordance  with this code and NFPA 45, except that ducts constructed of
combustible materials shall not be permitted.
                                CHAPTER 5
                             EXHAUST SYSTEMS
                             SECTION MC 501
                                 GENERAL
  501.1 Scope. This chapter shall govern the  design,  construction  and
installation  of  mechanical  exhaust systems, including dust, stock and
refuse conveyor systems, exhaust systems  servicing  commercial  cooking
appliances and energy recovery ventilation systems.
  501.2  Outdoor  discharge. The air removal by every mechanical exhaust
system shall be discharged outdoors at a point where it will not cause a
nuisance and from which it  cannot  again  be  readily  drawn  in  by  a
ventilating  system.  Air  shall not be exhausted into an attic or crawl
space.
  Exception: Whole-house ventilation-type attic fans that discharge into
the attic space of dwelling units having private attics.
  501.3 Pressure equalization. Mechanical exhaust systems shall be sized
to remove the quantity of air required by this chapter to be  exhausted.
The  system  shall  operate  when air is required to be exhausted. Where
mechanical exhaust is  required  in  a  room  or  space  in  other  than
occupancies  in Group R-3, such space shall be maintained with a neutral
or negative pressure. If a greater quantity of  air  is  supplied  by  a
mechanical  ventilating  supply  system  than is removed by a mechanical
exhaust system for a room, adequate means  shall  be  provided  for  the
natural  exit  of  the excess air supplied. If only a mechanical exhaust
system is installed for a room or  if  a  greater  quantity  of  air  is
removed  by a mechanical exhaust system than is supplied by a mechanical
ventilating supply system for a room, adequate means shall  be  provided
for the natural supply of the deficiency in the air supplied.
  501.4  Ducts. Where exhaust duct construction is not specified in this
chapter, such construction shall comply with Chapter 6 of this code.
  501.5 Independent system required.
  1. Single or combined mechanical exhaust systems  form  bath,  toilet,
urinal,  locker,  service  sink  closets  and  similar  rooms  shall  be
independent of all other exhaust systems, except as permitted in Section
401.5.2.
  2. A separate grease duct system shall be provided  for  each  type  I
hood except as provided in Section 506.3.5.
  3.  Hazardous  exhaust  systems shall be independent of other types of
exhaust systems as provided in Section 510.

                             SECTION MC 502
                            REQUIRED SYSTEMS
  502.1  General.  An  exhaust  system shall be provided, maintained and
operated as specifically required by this section and for  all  occupied
areas  where  machines,  vats,  tanks, furnaces, forges, salamanders and
other appliances, equipment and processes in such areas produce or throw
off dust or particles sufficiently light to float in the air,  or  which
emit  heat,  odors, fumes, spray, gas or smoke, in such quantities so as
to be irritating or injurious to health or safety.
  502.1.1 Exhaust location. The inlet to  an  exhaust  system  shall  be
located in the area of heaviest concentration of contaminants.
  502.1.2  Fuel-dispensing  areas. The bottom of an air inlet or exhaust
opening in fuel-dispensing areas shall  be  located  not  more  than  18
inches (457 mm) above the floor.
  502.1.3  Equipment, appliance and service rooms. Equipment, appliances
and system service rooms that house sources  of  odors,  fumes,  noxious
gases, smoke, steam, dust, spray or other contaminants shall be designed
and constructed so as to prevent spreading of such contaminants to other
occupied parts of the building.
  502.1.4   Hazardous   exhaust.   The   mechanical   exhaust   of  high
concentrations  of  dust  or  hazardous  vapors  shall  conform  to  the
requirements of Section 510.
  502.2  Aircraft  fueling  and  defueling. Compartments housing piping,
pumps,  air  eliminators,  water  separators,  hose  reels  and  similar
equipment  used  in  aircraft  fueling and defueling operations shall be
adequately ventilated at floor level or within the floor itself.
  502.3 Battery-charging areas. Ventilation  shall  be  provided  in  an
approved  manner  in  battery-charging  areas  to  prevent  a  dangerous
accumulation of flammable gases.
  502.4 Stationary  lead-acid  battery  systems.  Ventilation  shall  be
provided  for  stationary  lead-acid  battery systems in accordance with
this chapter and Section 502.4.1 or 502.4.2.
  502.4.1 Hydrogen limit. The ventilation system shall  be  designed  to
limit  the maximum concentration of hydrogen to 1.0 percent of the total
volume of the room.
  502.4.2 Ventilation rate. Continuous ventilation shall be provided  at
a  rate  of  not  less  than  1  cubic  foot  per minute per square foot
(cfm/ft{2}) [0.00508 m{3}/(s  m{2}] of floor area of the room.
  502.5 Valve-regulated lead-acid batteries.  Valve-regulated  lead-acid
battery  systems  as  regulated by the New York City Fire Code, shall be
provided with ventilation in accordance with Section 502.5.1 or  502.5.2
for  rooms  and  in  accordance  with  Section  502.5.3  or  502.5.4 for
cabinets.
  502.5.1 Hydrogen limit in  rooms.  The  ventilation  system  shall  be
designed  to  limit the maximum concentration of hydrogen to 1.0 percent
of the  total  volume  of  the  room  during  the  worst-case  event  of
simultaneous boost charging of all batteries in the room.
  502.5.2  Ventilation  rate  in  rooms. Continuous ventilation shall be
provided at a rate of not less than 1 cubic foot per minute  per  square
foot (cfm/ft{2}) [0.00508 m{3}/(s m{2}) of floor area of the room.
  502.5.3  Hydrogen  limit  in cabinets. The ventilation system shall be
designed to limit the maximum concentration of hydrogen to  1.0  percent
of  the  total  volume  of  the  cabinet  during the worst-case event of
simultaneous boost charging of all batteries in the cabinet.
  502.5.4 Ventilation rate in cabinets. Continuous ventilation shall  be
provided  at  a rate of not less than 1 cubic foot per minute per square
foot (cfm/ft{2}) [0.00508 m{3}/(s m)] of the floor area covered  by  the

cabinet.  The  room  in  which  the  cabinet  is installed shall also be
ventilated as required by Section 502.5.1 or 502.5.2.
  502.6  Dry  cleaning  plants.  Mechanical  ventilation in dry cleaning
plants shall be provided and shall be adequate to protect employees  and
the  public  in  accordance  with  this  section  and  DOL  29  CFR Part
1910.1000, where applicable.
  502.6.1 Type II and Type  III  systems.  Type  II  and  Type  III  dry
cleaning  systems shall be provided with a mechanical ventilation system
that is designed to exhaust 1 cubic foot of  air  per  minute  for  each
square  foot  of floor area (1 cfm/ft{2}) [0.00508 m{3}/(s m{2})] in dry
cleaning rooms and in drying rooms. The ventilation system shall operate
automatically when the dry cleaning equipment is in operation and  shall
have manual controls at an approved location.
  502.6.2  Type  IV  and  V  systems. Type IV and V dry cleaning systems
shall be provided with an automatically  activated  exhaust  ventilation
system  to  maintain  a  minimum  of  100  feet per minute (0.5 m/s) air
velocity through the loading door when the door is opened.
  Exception: Dry cleaning units are not required  to  be  provided  with
exhaust  ventilation  where  an  exhaust  hood  is installed immediately
outside of and above the loading door which operates at an airflow  rate
as follows:
  Q = 100 x A[LD]                                    (Equation 5-1)
  where:
  Q = Flow rate exhausted through the hood, cubic feet per minute.
  A[LD] = Area of the loading door, square feet.
  502.6.3  Spotting  and pretreating. Scrubbing tubs, scouring, brushing
or spotting operations shall be located such  that  solvent  vapors  are
captured and exhausted by the ventilating system.
  502.7   Application  of  flammable  finishes.  Mechanical  exhaust  as
required by this section shall be provided for operations involving  the
application  of  flammable  finishes  and shall comply with the New York
City Fire Code.
  502.7.1  During  construction.  Ventilation  shall  be  provided   for
operations  involving  the application of materials containing flammable
solvents in the course of construction, alteration or  demolition  of  a
structure.
  502.7.2 Limited spraying spaces. Positive mechanical ventilation which
provides  a  minimum  of  six  complete  air  changes  per hour shall be
installed in  limited  spraying  spaces.  Such  system  shall  meet  the
requirements  of  the  New  York  City  Fire Code for handling flammable
vapors. Explosion venting is not required.
  502.7.3 Spraying areas. Mechanical ventilation of spraying  areas  and
resin  application  areas  shall be provided in accordance with Sections
502.7.3.1 through 502.7.3.6.
  502.7.3.1 Operation. Mechanical ventilation shall be kept in operation
at all times while spraying operations are being  conducted  and  for  a
sufficient  time  thereafter to allow vapors from drying coated articles
and finishing material residue to be exhausted. Spraying equipment shall
be interlocked with the ventilation  of  the  spraying  area  such  that
spraying operations cannot be conducted unless the ventilation system is
in operation.
  502.7.3.2  Recirculation. Air exhausted from spraying operations shall
not be recirculated.
  1. Air exhausted from spraying operations shall  be  permitted  to  be
recirculated as makeup air for unmanned spray operations provided that:
  1.1 Solid particulate has been removed.
  1.2  The  vapor  concentration  is  less  than 25 percent of the lower
flammable limit (LFL).

  1.3 Approved equipment is used to monitor the vapor concentration.
  1.4  An  alarm  is sounded and spray operations are automatically shut
down if the vapor concentration exceeds 25 percent of the LFL.
  1.5 The spray booths, spray spaces or  spray  rooms  involved  in  any
recirculation process shall be provided with mechanical ventilation that
shall  automatically  exhaust  100 percent of the required air volume in
the event of shutdown  by  approved  equipment  used  to  monitor  vapor
concentrations.
  2.  Air  exhausted  from  spraying operations shall be permitted to be
recirculated as makeup air to manned spraying operations if all  of  the
conditions  provided in Exception 1 are included in the installation and
documents have been prepared to show  that  the  installation  does  not
present  life  safety hazards to personnel inside the spray booth, spray
space or spray room.
  502.7.3.3  Air  velocity.  Ventilation  systems  shall  be   designed,
installed  and  maintained  such  that the average air velocity over the
open face of the booth, or booth  cross  section  in  the  direction  of
airflow during spraying operations, is not less than 100 feet per minute
(0.51 m/s).
  502.7.3.4  Ventilation  obstruction.  Articles  being sprayed shall be
positioned in a manner that does not obstruct collection of overspray.
  502.7.3.5 Independent ducts. Each spray booth  and  spray  room  shall
have an independent exhaust duct system discharging to the outdoors.
  Exceptions:
  1.  Multiple  spray booths having a combined frontal area of 18 square
feet (1.67 m{2}) or less are allowed to  have  a  common  exhaust  where
identical  spray-finishing  material is used in each booth. If more than
one fan serves one booth, such fans shall be interconnected so that  all
fans operate simultaneously.
  2.  Where  treatment of exhaust is necessary for air pollution control
or energy conservation, ducts shall be allowed to be manifold if all  of
the following conditions are met:
  2.1  The  sprayed  materials used are compatible and will not react or
cause ignition of the residue in the ducts.
  2.2 Nitrocellulose-based finishing material shall not be used.
  2.3 A filtering system shall be  provided  to  reduce  the  amount  of
overspray carried into the duct manifold.
  2.4  Automatic  sprinkler protection shall be provided at the junction
of each booth exhaust with the manifold, in addition to  the  protection
required by this chapter.
  502.7.3.6  Termination  point. The termination point for exhaust ducts
discharging to the  atmosphere  shall  be  located  with  the  following
minimum distances.
  1.  For ducts conveying explosive or flammable vapors, fumes or dusts:
30 feet (9144 mm) from  the  property  line;  10  feet  (3048  mm)  from
openings  into  the  building;  6 feet (1829 mm) from exterior walls and
roofs; 30 feet (9144 mm) from combustible walls and  openings  into  the
building  which  are  in the direction of the exhaust discharge; 10 feet
(3048 mm) above adjoining grade.
  2. For other product-conveying outlets: 10 feet  (3048  mm)  from  the
property  line:  3  feet (914 mm) from exterior walls and roofs; 10 feet
(3048 mm) from openings into the  building:  10  feet  (3048  mm)  above
adjoining grade.
  3.  For  environmental  air  duct  exhaust:  3  feet (914 mm) from the
property line; 3 feet (914 mm) from openings into the building.
  502.7.3.7 Fan motors and belts. Electric motors driving  exhaust  fans
shall  not be placed inside booths or ducts. Fan rotating elements shall
be nonferrous or nonsparking or the casing shall consist of, or be lined

with, such material. Belts shall not enter the duct or booth unless  the
belt and pulley within the duct are tightly enclosed.
  502.7.4  Dipping  operations. Vapor areas of dip tank operations shall
be  provided  with  mechanical  ventilation  adequate  to  prevent   the
dangerous  accumulation of vapors. Required ventilation systems shall be
so arranged that the failure of any ventilating fan  will  automatically
stop the dipping conveyor system.
  502.7.5  Electrostatic apparatus. The spraying area in spray-finishing
operations  involving  electrostatic  apparatus  and  devices  shall  be
ventilated in accordance with Section 502.7.3.
  502.7.6   Powder   coating.  Exhaust  ventilation  for  powder-coating
operations shall be sufficient to maintain the atmosphere below one-half
of the minimum explosive concentration for the material  being  applied.
Nondeposited,  air-suspended  powders  shall  be removed through exhaust
ducts to the powder recovery cyclone or receptacle.
  502.7.7 Floor resurfacing operations. To prevent the  accumulation  of
flammable   vapors   during  floor  resurfacing  operations,  mechanical
ventilation at a minimum rate of 1 cfm/ft{2}[0.00508 m{3}/(s - m{2})] of
area being finished shall be provided.  Such  ventilation  shall  be  by
approved  temporary  or portable means. Vapors shall be exhausted to the
outdoors. Such ventilation equipment shall be kept  in  operation  while
the  floor  finishing  operations  are conducted and until any flammable
vapors have been exhausted.
  502.7.8  Resin  application  areas.  Exhaust  ventilation  for   resin
application areas shall comply with Section 502.7.3.
  Exception:  Mechanical  ventilation is not required for buildings that
are unenclosed for at least 75 percent of the perimeter.
  502.8 Hazardous materials - general requirements. Exhaust  ventilation
systems  for structures containing hazardous materials shall be provided
as required in Sections 502.8.1 through 502.8.5 and  shall  comply  with
the New York City Fire Code.
  502.8.1  Storage in excess of the maximum allowable quantities. Indoor
storage areas and storage buildings for hazardous materials  in  amounts
exceeding  the  maximum  allowable  quantity  per  control area shall be
provided with mechanical  exhaust  ventilation  or  natural  ventilation
where  natural  ventilation  can  be  shown  to  be  acceptable  for the
materials as stored.
  Exception: Storage areas for flammable solids complying with  the  New
York City Fire Code.
  502.8.1.1  System  requirements.  Exhaust  ventilation  systems  shall
comply with all of the following:
  1. The installation shall be in accordance with this code.
  2. Mechanical ventilation shall be provided at a rate of not less than
1 cfm/ft{2} [0.00508 m{3}/(s - m {2})] of floor area  over  the  storage
area.
  3. The systems shall operate continuously unless alternate designs are
approved.
  4. A manual shutoff control shall be provided outside of the room in a
position  adjacent to the access door to the room or in another approved
location. The switch shall be of  the  break-glass  type  and  shall  be
labeled: VENTILATION SYSTEM EMERGENCY SHUTOFF.
  5.  The  exhaust  ventilation system shall be designed to consider the
density of the potential fumes or vapors released. For fumes  or  vapors
that are heavier than air, exhaust shall be taken from a point within 12
inches (304 mm) of the floor.
  6.  The  location  of both the exhaust and inlet air openings shall be
designed to provide air movement across all portions  of  the  floor  or
room to prevent the accumulation of vapors.

  7.  The  exhaust ventilation shall not be recirculated within the room
or building if the materials stored are capable  of  emitting  hazardous
vapors.
  502.8.2   Gas  rooms,  exhausted  enclosures  and  gas  cabinets.  The
ventilation system for gas rooms, exhausted enclosures and gas  cabinets
for any quantity of hazardous material shall be designed to operate at a
negative  pressure in relation to the surrounding area. Highly toxic and
toxic gases shall also comply with  Sections  502.9.7.1,  502.9.7.2  and
502.9.8.4.
  502.8.3 Indoor dispensing and use. Indoor dispensing and use areas for
hazardous  materials in amounts exceeding the maximum allowable quantity
per  control  area  shall  be  provided  with  exhaust  ventilation   in
accordance with Section 502.8.1.
  Exception:  Ventilation  is  not  required  for dispensing- and use of
flammable solids other than finely divided particles.
  502.8.4 Indoor dispensing and use-point sources. Where gases,  liquids
or  solids  in  amounts  exceeding  the  maximum  allowable quantity per
control area and having a hazard ranking of 3 or 4  in  accordance  with
NFPA  704 are dispensed or used, mechanical exhaust ventilation shall be
provided to capture fumes, mists or vapors at the point of generation.
  Exception: Where it can be demonstrated that  the  gases,  liquids  or
solids do not create harmful fumes, mists or vapors.
  502.8.5  Closed systems. Where closed systems for the use of hazardous
materials in  amounts  exceeding  the  maximum  allowable  quantity  per
control  area  are  designed  to be opened as part of normal operations,
ventilation shall be provided in accordance with Section 502.8.4.
  502.9 Hazardous  materials  -  requirements  for  specific  materials.
Exhaust  ventilation  systems  for specific hazardous materials shall be
provided as required in  Section  502.8  and  Sections  502.9.1  through
502.9.11 and shall comply with the New York City Fire Code.
  502.9.1 Compressed gases medical gas systems. Rooms for the storage of
compressed  medical  gases  in  amounts  exceeding the maximum allowable
exempt quantity per control area, and which  do  not  have  an  exterior
wall, shall be exhausted through a duct to the exterior of the building.
Each  space  shall  be separately exhausted, and each exhaust air stream
shall be enclosed in a 1-hour-rated shaft enclosure from the room to the
exterior. Approved mechanical ventilation shall be provided at a minimum
rate of 1 cfm/ft{2} [0.00508 m{3}/(s - m{2})] of the area of the room.
  Gas cabinets for the storage of compressed medical  gases  in  amounts
exceeding  the  maximum  allowable  quantity  per  control area shall be
connected to an exhaust system. The average velocity of  ventilation  at
the  face of access ports or windows shall be not less than 200 feet per
minute (1.02 m/s) with a minimum velocity of 150 feet per  minute  (0.76
m/s) at any point at the access port or window.
  502.9.2 Corrosives. Where corrosive materials in amounts exceeding the
maximum  allowable  quantity  per  control  area  are dispensed or used,
mechanical exhaust ventilation in accordance with Section 502.8.4  shall
be provided.
  502.9.3   Cryogenics.   Storage   areas  for  stationary  or  portable
containers of cryogenic fluids in any quantity shall  be  ventilated  in
accordance  with  Section  502.8. Indoor areas where cryogenic fluids in
any quantity are dispensed shall be ventilated in  accordance  with  the
requirements  of  Section 502.8.4 in a manner that captures any vapor at
the point of generation.
  Exception: Ventilation for indoor dispensing  areas  is  not  required
where  it  can  be  demonstrated that the cryogenic fluids do not create
harmful vapors.

  502.9.4 Explosives. Squirrel  cage  blowers  shall  not  be  used  for
exhausting  hazardous  fumes, vapors or gases in operating buildings and
rooms for the manufacture,  assembly  or  testing  of  explosives.  Only
nonferrous fan blades shall be used for fans located within the ductwork
and  through  which  hazardous  materials are exhausted. Motors shall be
located outside the duct.
  502.9.5 Flammable and combustible liquids. Exhaust ventilation systems
shall be provided as required by Sections  502.9.5.1  through  502.9.5.5
for  the  storage, use, dispensing, mixing and handling of flammable and
combustible liquids. Unless  otherwise  specified,  this  section  shall
apply to any quantity of flammable and combustible liquids.
  Exception:  This  section shall not apply to flammable and combustible
liquids that are exempt from the New York City Fire Code.
  502.9.5.1 Vaults. Vaults that contain tanks of Class I  liquids  shall
be  provided  with  continuous  ventilation at a rate of not less than 1
cfm/ft{2} of floor area [0.00508 m{3}/(s - m{2})], but not less than 150
cfm (4 m{3}/min). Failure of the  exhaust  airflow  shall  automatically
shut down the dispensing system. The exhaust system shall be designed to
provide  air  movement  across  all parts of the vault floor. Supply and
exhaust ducts shall extend to a point not greater than  12  inches  (305
mm)  and  not  less  than  3 inches (76 mm) above the floor. The exhaust
system, shall be installed in accordance with the provisions of NFPA 91.
Means shall be provided to automatically detect any flammable vapors and
to automatically shut down the dispensing system upon detection of  such
flammable vapors in the exhaust duct at a concentration of 25 percent of
the LFL.
  502.9.5.2  Storage  rooms  and  warehouses.  Liquid  storage rooms and
liquid storage warehouses for  quantities  of  liquids  exceeding  those
specified  in  the  New  York  City  Fire  Code  shall  be ventilated in
accordance with Section 502.8.1.
  502.9.5.3 Cleaning machines. Areas containing machines used for  parts
cleaning  in  accordance  with  the  New  York  City  Fire Code shall be
adequately ventilated to prevent accumulation of vapors.
  502.9.5.4  Use,   dispensing   and   mixing.   Continuous   mechanical
ventilation  shall  be  provided  for  the use, dispensing and mixing of
flammable and combustible liquids in open or closed systems  in  amounts
exceeding  the  maximum allowable quantity per control area and for bulk
transfer and process transfer operations. The ventilation rate shall  be
not  less  than  1 cfm/ft{2} [0.00508m{3}/(s - m{2})] of floor area over
the design area.   Provisions shall be  made  for  the  introduction  of
makeup  air  in a manner that will include all floor areas or pits where
vapors can collect.  Local or spot ventilation shall be  provided  where
needed to prevent the accumulation of hazardous vapors.
  502.9.5.5  Bulk plants or terminals. Ventilation shall be provided for
portions of properties  where  flammable  and  combustible  liquids  are
received  by  tank  vessels,  pipelines,  tank cars or tank vehicles and
which are stored or blended in bulk for the purpose of distributing such
liquids  by  tank  vessels,  pipelines,  tank  cars,  tank  vehicles  or
containers as required by Sections 502.9.5.5.1 through 502.9.5.5.3.
  502.9.5.5.1   General.   Ventilation  shall  be  provided  for  rooms,
buildings and enclosures in which Class I liquids are  pumped,  used  or
transferred.      Design  of  ventilation  systems  shall  consider  the
relatively  high  specific  gravity  of  the   vapors.   Where   natural
ventilation  is used. adequate openings in outside walls at floor level,
unobstructed except by louvers or coarse  screens,  shall  be  provided.
Where natural ventilation is inadequate, mechanical ventilation shall be
provided.  The  natural  ventilation  design  shall be approved for each

specific application v the commissioner  prior  to  installation  and/or
use.
  502.9.5.5.2 Basements and pits. Class I liquids shall not be stored or
used  within  a  building  having a basement or pit into which flammable
vapors can  travel,  unless  such  area  is  provided  with  ventilation
designed to prevent the accumulation of flammable vapors therein.
  502.9.5.5.3  Dispensing  of  Class  I  liquids.  Containers of Class I
liquids shall not be drawn from or  filled  within  buildings  unless  a
provision  is  made  to  prevent the accumulation of flammable vapors in
hazardous concentrations. Where mechanical ventilation is  required,  it
shall be kept in operation while flammable vapors could be present.
  502.9.6  Highly  toxic and toxic liquids. Ventilation exhaust shall be
provided for highly toxic and toxic  liquids  as  required  by  Sections
502.9.6.1 and 502.9.6.2.
  502.9.6.1  Treatment  system. This provision shall apply to indoor and
outdoor storage and use of highly Toxic and  toxic  liquids  in  amounts
exceeding  the  maximum  allowable  quantities per control area. Exhaust
scrubbers or other systems for processing vapors of highly toxic liquids
shall be provided where a spill or accidental release  of  such  liquids
can be expected to release highly toxic vapors at normal temperature and
pressure.
  502.9.6.2  Open  and  closed  systems.  Mechanical exhaust ventilation
shall be provided for highly  toxic  and  toxic  liquids  used  in  open
systems   in   accordance   with  Section  502.8.4.  Mechanical  exhaust
ventilation shall be provided for highly toxic and toxic liquids used in
closed systems in accordance with Section 502.8.5.
  Exception: Liquids or solids that do  not  generate  highly  toxic  or
toxic fumes, mists or vapors.
  502.9.7  Highly  toxic  and  toxic  compressed  gases  - any quantity.
Ventilation exhaust  shall  be  provided  for  highly  toxic  and  toxic
compressed  gases  in any quantity as required by Sections 502.9.7.1 and
502.9.7.2.
  502.9.7.1 Gas cabinets. Gas cabinets containing highly toxic or  toxic
compressed  gases  in any quantity shall comply with Section 502.8.2 and
the following requirements:
  1. The average ventilation velocity at the face of gas cabinet  access
ports  or  windows shall be not less than 200 feet per minute (1.02 m/s)
with a minimum velocity of 150 feet per minute (0.76 m/s) at  any  point
at the access port or window.
  2. Gas cabinets shall be connected to an exhaust system.
  3. Gas cabinets shall not be used as the sole means of exhaust for any
room or area.
  502.9.7.2 Exhausted enclosures. Exhausted enclosures containing highly
toxic  or  toxic  compressed  gases  in  any  quantity shall comply with
Section 502.8.2 and the following requirements:
  1. The average ventilation velocity at the face of the enclosure shall
be not less than 200 feet per minute (1.02 m/s) with a minimum  velocity
of 150 feet per minute (0.76 m/s).
  2. Exhausted enclosures shall be connected to an exhaust system.
  3. Exhausted enclosures shall not be used as the sole means of exhaust
for any room or area.
  502.9.8  Highly  toxic and toxic compressed gases quantities exceeding
the maximum allowable per control area.  Ventilation  exhaust  shall  be
provided  for  highly  toxic  and  toxic  compressed  gases  in  amounts
exceeding the maximum allowable quantities per control area as  required
by Sections 502.9.8.1 through 502.9.8.6.
  502.9.8.1  Ventilated  areas.  The  room  or  area in which indoor gas
cabinets or exhausted enclosures are  located  shall  be  provided  with

exhaust  ventilation.  Gas cabinets or exhausted enclosures shall not be
used as the sole means of exhaust for any room or area.
  502.9.8.2  Local  exhaust for portable tanks. A means of local exhaust
shall be provided to capture leakage from indoor  and  outdoor  portable
tanks.  The  local exhaust shall consist of portable ducts or collection
systems designed to be applied to the site of  a  leak  in  a  valve  or
fitting  on the tank. The local exhaust system shall be located in a gas
room. Exhaust shall be directed to a treatment system where required  by
the New York City Fire Code.
  502.9.8.3   Piping   and  controls  -  stationary  tanks.  Filling  or
dispensing connections on indoor stationary tanks shall be provided with
a means of local exhaust. Such exhaust  shall  be  designed  to  capture
fumes  and  vapors.  The exhaust shall be directed to a treatment system
where required by the New York City Fire Code.
  502.9.8.4 Gas rooms. The ventilation system for  gas  rooms  shall  be
designed   to  operate  at  a  negative  pressure  in  relation  to  the
surrounding area. The  exhaust  ventilation  from  gas  rooms  shall  be
directed to an exhaust system.
  502.9.8.5 Treatment system. The exhaust ventilation from gas cabinets,
exhausted  enclosures  and gas rooms, and local exhaust systems required
in Sections 502.8.2 and 502.9.8.3  shall  be  directed  to  a  treatment
system where required by the New York City Fire Code.
  502.9.8.6  Process equipment. Effluent from indoor and outdoor process
equipment containing highly toxic or toxic compressed gases which  could
be  discharged  to  the atmosphere shall be processed through an exhaust
scrubber or other processing system. Such systems shall be in accordance
with the New York City Fire Code.
  502.9.9 Ozone gas generators. Ozone cabinets and  ozone  gas-generator
rooms for systems having a maximum ozone-generating capacity of one-half
pound  (0.23  kg)  or  more  over a 24-hour period shall be mechanically
ventilated at rate of not less  than  six  air  changes  per  hour.  For
cabinets,  the  average  velocity  of ventilation at makeup air openings
with cabinet doors closed shall be not less than  200  feet  per  minute
(1.02 m/s).
  502.9.10   LP-gas   distribution   facilities.   LP-gas   distribution
facilities shall conform to the requirements of the New York  City  Fire
Code.
  502.9.11  Silane  gas.  Exhausted  enclosures and gas cabinets for the
indoor storage of silane gas in amounts exceeded the  maximum  allowable
quantities per control area shall comply with this section.
  1.  Exhausted  enclosures and gas cabinets shall be in accordance with
Section 502.8.2.
  2.  The  velocity  of  ventilation  across   unwelded   fittings   and
connections  on  the  piping  system shall not be less than 200 feet per
minute (1.02 m/s).
  3. The average velocity at the face of the access ports or windows  in
the  gas  cabinet  shall not be less than 200 feet per minute (1.02 m/s)
with a minimum velocity of 150 feet per minute (0.76 m/s) at  any  point
at the access port or window.
  502.10  Hazardous  production  materials  (HPM).  Exhaust  ventilation
systems and materials for ducts utilized for the exhaust  of  HPM  shall
comply  with this section, other applicable provisions of this code, the
New York City Building Code and the New York City Fire Code.
  502.10.1 Where required. Exhaust ventilation systems shall be provided
in the following locations in accordance with the requirements  of  this
section and the New York City Building Code:

  1.  Fabrication areas: Exhaust ventilation for fabrication areas shall
comply with the New York City Building Code. Additional  manual  control
switches shall be provided where required by the commissioner.
  2. Workstations: A ventilation system shall be provided to capture and
exhaust fumes and vapors at workstations.
  3.  Liquid storage rooms: Exhaust ventilation for liquid storage rooms
shall comply with Section 502.8.1.1 and the New York City Building Code.
  4. HPM rooms: Exhaust ventilation for  HPM  rooms  shall  comply  with
Section 502.8.1.1 and the New York City Building Code.
  5.  Gas  cabinets:  Exhaust  ventilation for gas cabinets shall comply
with Section 502.8.2. The gas cabinet ventilation system is  allowed  to
connect to a workstation ventilation system. Exhaust ventilation for gas
cabinets  containing  highly toxic or toxic gases shall also comply with
Sections 502.9.7 and 502.9.8.
  6. Exhausted enclosures: Exhaust ventilation for exhausted  enclosures
shall  comply  with  Section  502.8.2. Exhaust ventilation for exhausted
enclosures containing highly toxic or toxic gases shall also comply with
Sections 502.9.7 and 502.9.8.
  7. Gas rooms: Exhaust ventilation for  gas  rooms  shall  comply  with
Section  502.8.2. Exhaust ventilation for gas cabinets containing highly
toxic or toxic  gases  shall  also  comply  with  Sections  502.9.7  and
502.9.8.
  502.10.2   Penetrations.   Exhaust   ducts  penetrating  fire  barrier
assemblies shall be contained in a shaft  of  equivalent  fire-resistive
construction.    Exhaust  ducts  shall not penetrate building separation
fire walls. Fire dampers shall not be installed in exhaust ducts.
  502.10.3 Treatment systems. Treatment systems  for  highly  toxic  and
toxic gases shall comply with the New York City Fire Code.
  502.11  Motion  picture projectors. Motion picture projectors shall be
exhausted in accordance with Section 502.11.1 or 502.11.2.
  502.11.1 Projectors with an  exhaust  discharge.  Projectors  equipped
with  an  exhaust  discharge shall be directly connected to a mechanical
exhaust system. The exhaust system shall operate at an exhaust  rate  as
indicated by the manufacturer's installation instructions.
  502.11.2  Projectors without exhaust connection. Projectors without an
exhaust  connection  shall  have  contaminants   exhausted   through   a
mechanical  exhaust system. The exhaust rate for electric arc projectors
shall be a minimum of 200 cubic feet per minute (cfm) (0.09 m{3}/s)  per
lamp.  The  exhaust  rate for xenon projectors shall be a minimum of 300
cfm (0.14 m{3}/s) per lamp. Xenon projector exhaust shall be a rate such
that the exterior temperature of the lamp housing does not exceed  130°F
(54°C).   The lamp and projection room exhaust systems, whether combined
or independent, shall not be interconnected with any  other  exhaust  or
return system within the building.
  502.12   Organic  coating  processes.  Enclosed  structures  involving
organic coating processes in which Class  I  liquids  are  processed  or
handled  shall  be  ventilated  at  a  rate of not less than 1 cfm/ft{2}
[0.00508 m{3}/(s   m{2})] of solid  floor  area.  Ventilation  shall  be
accomplished  by  exhaust fans that intake at floor levels and discharge
to a safe location outside the  structure.  Noncontaminated  intake  air
shall  be  introduced  in such a manner that all portions of solid floor
areas are provided with continuous uniformly distributed air movement.
  502.13 Public garages. Mechanical exhaust systems for public  garages,
as  required  in  Chapter 4, shall operate continuously or in accordance
with Section 404.
  502.14 Motor vehicle operation. In areas where motor vehicles operate,
mechanical ventilation shall be provided in accordance with Section 403.
Additionally, areas in which  stationary  motor  vehicles  are  operated

shall be provided with a source capture system that connects directly to
the motor vehicle exhaust systems.
  Exceptions:
  1.  This  section  shall  not  apply  where  the  motor vehicles being
operated or repaired are electrically powered.
  2. This section shall not apply to one- and two-family dwellings.
  3. This section shall not apply to motor vehicle service  areas  where
engines are operated inside the building only for the duration necessary
to move the motor vehicles in and out of the building.
  502.15 Repair garages. Where Class I liquids are stored or used within
a  building  having  a  basement  or  pit wherein flammable vapors could
accumulate, the basement or pit shall be provided with ventilation at  a
minimum  rate  of  1.5 cubic feet per minute per square foot (cfm/ft{2})
[0.009 m{3}/(s  m{2})] to prevent the acculturation of flammable  vapors
therein.
  502.16  Repair  garages for natural gas- and hydrogen-fueled vehicles.
Repair garages used for the repair of natural  gas-  or  hydrogen-fueled
vehicles  shall  be  provided  with  an  approved mechanical ventilation
system. The mechanical ventilation system shall be  in  accordance  with
Sections 502.16.1 and 502.16.2.
  Exception:  Where  approved  by  the commissioner, natural ventilation
shall be permitted in lieu of mechanical ventilation.
  502.16.1 Design. Indoor locations shall be  ventilated  utilizing  air
supply  inlets  and  exhaust  outlets  arranged  to  provide uniform air
movement to the extent practical. Inlets shall be uniformly arranged  on
exterior  walls  near  floor level. Outlets shall be located at the high
point of the room in exterior walls or the roof.
  1. Ventilation shall be by a continuous mechanical ventilation  system
or  by  a  mechanical  ventilation  system  activated  by a continuously
monitoring  natural  gas  detection  systems   activating   at   a   gas
concentration  of not more than 25 percent of the LFL. In all cases, the
system shall shut down the fueling system in the event of failure of the
ventilation system.
  2. The ventilation rate shall be at least 1 cubic foot per minute  per
12 cubic feet [0.00148 m{3}/(s  m{3})] of room volume.
  502.16.2  Operation.  The  mechanical ventilation system shall operate
continuously.
  Exceptions:
  1. Mechanical ventilation systems that  are  interlocked  with  a  gas
detection  system designed in accordance with the New York City Building
Code.
  2. Mechanical ventilation systems in garages that are  used  only  for
the repair of vehicles fueled by liquid fuels or odorized gases, such as
CNG,  where  the ventilation system is electrically interlocked with the
lighting circuit.
  502.17 Tire rebuilding or recapping. Each room where rubber cement  is
used  or  mixed, or where flammable or combustible solvents are applied,
shall be ventilated in accordance with the applicable provisions of NFPA
91.
  502.17.1 Buffing machines. Each buffing machine shall be connected  to
a  dust-collecting  system  that  prevents  the accumulation of the dust
produced by the buffing process.
  502.18 Specific rooms. Specific  rooms,  including  bathrooms,  locker
rooms,   smoking  lounges  and  toilet  rooms,  shall  be  exhausted  in
accordance with the ventilation requirements of Chapter 4.
  502.19 Domestic kitchen exhaust systems. In all group R occupancies  a
minimum of No. 18 Gage galvanized sheet metal shall be used, except that
ductwork  that  complies  with  Section 603.6.1.2 shall be permitted for

independent  apartment  exhaust  systems   providing   general   exhaust
ventilation of kitchen and toilet areas.
  502.20  Nonproduction  chemical  laboratories.  Nonproduction chemical
laboratories shall comply with Section 419 of the New York City Building
Code and NFPA 45.
                             SECTION MC 503
                             MOTORS AND FANS
  503.1 General. Motors and fans shall be sized to provide the  required
air  movement.  Motors  in  areas that contain flammable vapors or dusts
shall be of a type approved for such environments. A  manually  operated
remote  control  installed  at an approved location shall be provided to
shut off fans or blowers in flammable vapor or dust systems.  Electrical
equipment  and  appliances used in operations that generate explosive or
flammable  vapors,  fumes  or  dusts  shall  be  interlocked  with   the
ventilation  system  so  that  the  equipment  and  appliances cannot be
operated unless the ventilation fans are in operation. Motors  for  fans
used  to  convey  flammable vapors or dusts shall be located outside the
duct or shall be  protected  with  approved  shields  and  dustproofing.
Motors  and  fans shall be provided with a means of access for servicing
and maintenance.
  503.2 Fans. Parts of fans  in  contact  with  explosive  or  flammable
vapors,  fumes or dusts shall be of nonferrous or nonsparking materials,
or their casing shall be lined or constructed of such material. When the
size and hardness of materials passing through  a  fan  are  capable  of
producing  a  spark, both the fan and the casing shall be of nonsparking
materials.  When fans are required to be spark resistant, their bearings
shall not be within the airstream, and all parts of  the  fan  shall  be
grounded.    Fans  in  systems-handling  materials  that  are capable of
clogging the blades, and fans in buffing or woodworking exhaust systems,
shall be of the radial-blade or tube-axial type.
  503.3 Equipment and appliances  identification  plate.  Equipment  and
appliances used to exhaust explosive or flammable vapors, fumes or dusts
shall  bear  an  identification  plate  stating the ventilation rate for
which the system was designed.
  503.4 Corrosion-resistant fans.  Fans  located  in  systems  conveying
corrosives  shall be of materials that are resistant to the corrosive or
shall be coated with corrosion-resistant materials.
  503.5 Fan location. Fans  exhausting  noxious,  toxic,  hot  vapor  or
grease  laden  air  shall  be  located  as  close  to  the  terminus  as
practicable,  at  the  roof  or  within  a  mechanical  equipment  room,
immediately below the roof.
  Exception:   Where   the  fan  is  listed  or  approved  for  such  an
application.
                             SECTION MC 504
                          CLOTHES DRYER EXHAUST
  504.1 Installation. Clothes dryers shall be  exhausted  in  accordance
with  the  manufacturer's  instructions.  Dryer exhaust systems shall be
independent of all other systems and shall convey the moisture  and  any
products of combustion to the outside of the building.
  Exception:  This  section  shall  not  apply  to  listed  and  labeled
condensing (ductless) electric clothes dryers.
  504.2 Exhaust penetrations. Ducts that exhaust  clothes  dryers  shall
not  penetrate  or  be located within any fireblocking, draftstopping or
any wall, floor/ceiling or other assembly required by the New York  City
Building   Code  to  be  fire-resistance  rated,  unless  such  duct  is
constructed of galvanized steel or aluminum of the  thickness  specified
in  Section  603.4  and  the  fire-resistance  rating  is  maintained in
accordance  with  the  New  York  City  Building  Code.  Fire   dampers,

combination  fire/smoke  dampers  and  any  similar  devices  that  will
obstruct the exhaust flow, shall be prohibited in clothes dryer  exhaust
ducts.
  504.3 Cleanout. Each vertical riser shall be provided with a means for
cleanout.
  504.4  Exhaust  installation.  Dryer  exhaust ducts for clothes dryers
shall terminate on the outside of the building  and  shall  be  equipped
with  a  backdraft  damper.  Screens  shall not be installed at the duct
termination. Ducts shall not be connected or installed with sheet  metal
screws  or  other fasteners that will obstruct the exhaust flow. Clothes
dryer exhaust ducts shall not be connected to a vent connector, vent  or
chimney.  Clothes  dryer  exhaust ducts shall not extend into or through
ducts or plenums.
  504.5 Makeup air. Installations exhausting more  than  200  cfm  (0.09
m{3}/s)  shall  be  provided with makeup air. Where a closet is designed
for the installation of a clothes dryer, an opening having  an  area  of
not  less  than 100 square inches (0.0645 m{2}) shall be provided in the
closet enclosure.
  504.6 Domestic clothes dryer ducts. Exhaust ducts for domestic clothes
dryers shall be constructed of metal and shall have  a  smooth  interior
finish.  The exhaust duct shall be a minimum nominal size of four inches
(102 mm) in diameter. The entire exhaust system shall be  supported  and
secured  in  place.  The  male end of the duct at overlapped duct joints
shall be supported and secured in place. The male end  of  the  duct  at
overlapped duct joints shall extend in the direction of airflow. Clothes
dryer transition ducts used to connect the appliance to the exhaust duct
system shall be limited to single lengths not to exceed 8 feet (2438 mm)
and  shall  be  listed and labeled for the application. Transition ducts
shall not be concealed within construction.
  504.6.1 Maximum length. The maximum length of a clothes dryer  exhaust
duct  shall  not exceed 25 feet (7620 mm) from the dryer location to the
outlet terminal. The maximum length of duct shall be reduced 2 1/2  feet
(762  mm)  for  each  45-degree (0.79 rad) bend and 5 feet (1524 mm) for
each 90-degree (1.6 rad) bend. The maximum length of  the  exhaust  duct
does not include the transition duct.
  Exception:  Where  the  make  and  model  of  the  clothes dryer to be
installed is known and the manufacturer's installation instructions  for
such  dryer  are  provided,  the  maximum  length  of  the exhaust duct,
including any transition duct, shall be permitted to  be  in  accordance
with the dryer manufacturer's installation instructions.
  504.6.2 Rough-in required. Where a compartment or space for a domestic
clothes  dryer is provided, an exhaust duct system shall be installed in
accordance with Sections 504.6 and 504.6.1.
  504.7 Commercial clothes dryers. The  installation  of  dryer  exhaust
ducts  serving  Type  2  clothes  dryers shall comply with the appliance
manufacturer's installation instructions. Exhaust fan  motors  installed
in  exhaust  systems  shall  be  located  outside  of  the airstream. In
multiple  installations,  the  fan  shall  operate  continuously  or  be
interlocked  to  operate  when  any individual until is operating. Ducts
shall have a minimum clearance of  6  inches  (152  mm)  to  combustible
materials.  Clothes dryer transition ducts used to connect the appliance
to  the  exhaust  duct  system shall be limited to single lengths not to
exceed 8 feet (2438 mm) in length and shall be listed  and  labeled  for
the   application.  Transition  ducts  shall  not  be  concealed  within
construction.
                              SECTION MC 505
                   DOMESTIC KITCHEN EQUIPMENT EXHAUST

  505.1 Domestic  systems.  Where  domestic  range  hoods  and  domestic
appliances  equipped  with downdraft exhaust are located within dwelling
units, such hoods and appliances shall discharge to the outdoors through
ducts constructed of galvanized  steel,  stainless  steel,  aluminum  or
copper.  Such ducts shall have soothe inner walls and shall be air tight
and equipped with a backdraft  damper.  Such  exhaust  system  shall  be
installed i strict compliance with the manufacturer's recommendations as
well as the requirements of the listing.
  Exceptions:
  1.  Where installed in accordance with the manufacturer's instructions
and where mechanical or natural ventilation  is  otherwise  provided  in
accordance with Chapter 4, listed and labeled ductless range hoods shall
not be required to discharge to the outdoors.
  2.  Ducts  for  domestic  kitchen  cooking  appliances  equipped  with
downdraft exhaust systems  shall  be  permitted  to  be  constructed  of
Schedule 40 PVC pipe provided that the installation complies with all of
the following:
  2.1. The duct shall be installed under a concrete slab pure on grade.
  2.2.  The  underfloor  trench  in which the duct is installed shall be
completely backfilled with sand or gravel.
  2.3. The PVC duct shall extend not greater than 1 inch (25  mm)  above
the indoor concrete floor surface.
  2.4.  the  PVC duct shall extend not greater than 1 inch (25 mm) above
grade outside of the building.
  2.5. The PVC ducts shall be solvent cemented.
                             SECTION MC 506
                   COMMERCIAL KITCHEN HOOD VENTILATION
                   SYSTEM DUCTS AND EXHAUST EQUIPMENT
  506.1 General. Commercial kitchen hood ventilation ducts  and  exhaust
equipment shall comply with the requirements of this section. Commercial
kitchen grease ducts shall be designed for the type of cooking appliance
and  hood  served.  All ducts shall lead directly to the exterior of the
building and terminate as required by 506.3.12.
  506.2 Corrosion protection. Ducts exposed to the outside atmosphere or
subject to a corrosive environment shall be protected against  corrosion
in an approved manner.
  1.  The  exterior  portion  of the ductwork shall be vertical wherever
possible and shall be installed and adequately supported on the exterior
of a building. Bolts, screws, rivets,  and  other  mechanical  fasteners
shall  not penetrate duct walls. Clearance of any vertical or horizontal
ducts to any other material or construction shall  comply  with  Section
506.3.6.  and  to  any  additional  clearance  requirements  as  may  be
applicable in accordance with Section 506.5.4.
  2. All exterior ducts shall be constructed of stainless steel not less
than 0.043 inch (1.09 mm) (No. 18 Gage) in thickness.  At  the  base  of
each  duct and at its termination point a clearly identifiable permanent
sign shall be installed identifying the facility  from  which  the  duct
originates.
  1.  No  portion  of  and  exterior  metal duct shall be nearer than 24
inches (610 mm) to any door or window or to any exit, or  located  where
it  would be readily accessible to the public, unless it is insulated or
shielded to avoid injury to any person coming in contact with the duct.
  Exception: Listed and labeled factory-built commercial kitchen  grease
ducts may be used when installed in accordance with Section 304.1.
  506.3  Ducts  serving  Type  I  hoods.  Type  I exhaust ducts shall be
independent of all other exhaust systems except as provided  in  Section
506.3.5.  commercial  kitchen duct systems serving Type I hoods shall be

designed, constructed and installed in accordance with Sections  506.3.1
through 506.3.12.3.
  506.3.1   Duct   materials.  Ducts  serving  Type  I  hoods  shall  be
constructed of materials  in  accordance  with  Sections  506.3.1.1  and
506.3.1.2.
  506.3.1.1  Grease  duct  materials. Grease ducts serving Type I hoods,
and located within buildings, shall be constructed as follows:
  1. Ducts with a cross-sectional area up to and  including  155  square
inches (100 000 mm{2}) shall be constructed of 0.0598 inch (1.52 mm) No.
16 Gage steel;
  2.  Ducts  with  across-sectional area over 155 square inches (100 000
mm{2}), but not  more  than  200  square  inches  (0.129m{2})  shall  be
constructed of 0.074 inch (1.9 mm) No. 14 gage steel; and
  3.  Ducts with a cross-sectional area equal to or more than 200 square
inches (0.129m{2}), shall be constructed of 0.1046 inch (2.66 mm) No. 12
Gage steel.
  If stainless steel is used for ducts of  any  of  the  cross-sectional
areas shown above, the Gage steel may be increased upwards (resulting in
a smaller thickness) by 1 Gage.
  Exception:  Listed and labeled factory-built commercial kitchen grease
ducts shall be installed  in  accordance  with  Section  304.1,  and  as
approved by the commercial.
  506.3.1.2  Makeup air ducts. Make up air ducts connecting to or within
18 inches (457 mm) of a Type I hood shall be constructed  and  installed
in  accordance  with  Sections  603.1,  603.3, 603.4, 603.9, 603.10, and
603.12.  Duct insulation installed within 18 inches (457 mm) of a Type I
hood shall be noncombustible or shall be listed for the application.
  506.3.2 Joints, seams and penetrations of grease ducts. Joints,  seams
and  penetrations  of  grease  ducts  shall  be  made  with a continuous
liquid-tight weld or braze made on the  external  surface  of  the  duct
system.
  Exceptions:
  1.  Penetrations  shall  not  be required to be welded or brazed where
sealed by devices that are listed for the application.
  2. Internal welding or brazing shall not be prohibited  provided  that
the  joint  is formed or ground smooth and is provided with ready access
for inspection.
  3. Listed and labeled factory-built commercial  kitchen  grease  ducts
installed in accordance with Section 304.1.
  506.3.2.1  Duct  joint  types.  Duct  joints  shall  be butt joints or
overlapping  duct  joints  of  either  the  telescoping  or  bell  type.
Overlapping joints shall be installed to prevent ledges and obstructions
from  collecting  grease  or  interfering  with  gravity drainage to the
intended  collection  point.   The   difference   between   the   inside
cross-sectional  dimensions  of  overlapping  sections of duct shall not
exceed 0.25 inch (6mm). The  length  of  overlap  for  overlapping  duct
joints shall not exceed 2 inches (51 mm).
  506.3.2.2  Duct-to-hood joints. Duct-to-hood joints shall be made with
continuous internal or external liquid-tight welded  or  brazed  joints.
Such  joints  shall  be  smooth,  accessible for inspection, and without
grease traps.
  Exceptions: This section shall not apply to:
  1. A vertical duct-to-hood collar connection made in the tip plane  of
the hood in accordance with all of the following:
  1.1.  The  hood  duct  opening  shall have a 1-inch-deep (25 mm), full
perimeter, welded flange turned down into the hood interior at an  angle
of 90 degrees from the plane of the opening.

  1.2. The duct shall have a 1-inch-deep (25 mm) flange made by a 1-inch
by  1-inch  (25  mm by 25 mm) angle iron welded to the full perimeter of
the duct not less than 1 inch (25 mm) above the bottom end of the duct.
  1.3.  A  gasket  rated  for  use  at  not less than 1,500°F (815°C) is
installed between the duct flange and the top of the hood.
  1.4. The duct-to-hood joint shall be secured by stud  bolts  not  less
than  0.25  inch  (6.4 mm) in diameter welded to the hood with a spacing
not greater than 4 inches (102 mm) on center for the full  perimeter  of
the opening. All bolts and nuts are to be secured with lockwashers.
  2.  Listed  and  labeled  duct-to-hood collar connections installed in
accordance with Section 304.1.
  506.3.2.3  Duct-to-exhaust  fan   connections.   Duct-to-exhaust   fan
connections  shall  be  flanged  and gasketed at the base of the fan for
vertical discharge fans; shall be flanged, gasketed and  bolted  to  the
inlet  of  the  fan  for  side-inlet utility fans; and shall be flanged,
gasketed and bolted to the inlet and outlet of the fan for in-line fans.
Approved flexible connectors may be provided.
  506.3.2.4 Vibration  isolation.A  vibration  isolation  connector  for
connecting  a duct to a fan shall consist of noncombustible packing in a
metal sleeve joint of  approved  design  or  shall  be  a  coated-fabric
flexible   duct  connector  listed  and  labeled  for  the  application.
Vibration isolation connectors shall be installed only at the connection
of a duct to a fan inlet or outlet.
  506.3.3 Grease duct supports. Grease duct bracing and supports shall b
of noncombustible  material  securely  attached  to  the  structure  and
designed   to   carry  gravity  and  seismic  loads  within  the  stress
limitations of the New York City building code.  Bolts,  screws,  rivets
and other mechanical fasteners shall not penetrate duct walls.
  506.3.4  Air velocity. Grease duct systems serving a Type I hood shall
be designed and installed to provide an air  velocity  within  the  duct
system of not less than 500 feet per minute (2.54 m/s).
  Exception:  The  velocity  limitations  shall  not  apply  within duct
transitions utilized to connect ducts to  differently  sized  or  shaped
openings in hoods and fans, provided that such transitions do not exceed
3  feet  (914  mm) in length and are designed to prevent the trapping of
grease.
  506.3.5 Separation of grease  duct  system.  A  separate  grease  duct
system shall be provided for each Type I hood.
  Exceptions:
  1.  A  separate  grease  duct  system is not required where all of the
following conditions are met:
  1.1. All interconnected hoods  are  located  within  the  same  story,
provided  that  they are part of the same facility and under the control
of one owner or tenant.
  1.2. All interconnected hoods are located within the same room  or  in
adjoining  rooms,  provided  that they are part of the same facility and
under the control of one owner or tenant.
  1.3. Interconnecting ducts do not penetrate assemblies required to  be
fire-resistance rated.
  1.4.   The   grease  duct  system  does  not  serve  solid  fuel-fired
appliances.
  2. Branch ducts from other equipment in the  same  kitchen  area,  for
which  hoods  and  filters are not required or from registers exhausting
the kitchen space in general, may be connected to the main hood  exhaust
duct if the following requirements are complied with:
  2.1.  A  fusible link fire damper of the same gage as the hood exhaust
duct shall be added at the point of connection of the branch duct to the
exhaust duct.

  2.2. If the branch connection is made to the portion of  the  ductwork
that  will  contain the fire extinguishing medium, then the fire dampers
required in Exception Item 2.1 shall be arranged to close  automatically
upon the operation of the fire extinguishing system.
  2.3  The branch connection shall be made in either the top or sides of
the main duct in a manner to prevent grease from flowing into the branch
duct.
  2.4. The branch ducts shall be  constructed  of  steel,  aluminum,  or
copper of the gages and weights required in Chapter 6, and they shall be
insulated  with  2  inches  (51 mm) of magnesia or other material having
equivalent insulative and fire resistance qualities.
  2.5. All registers in these branches shall have fusible link  actuated
dampers.
  2.6.  Where  branch  ductwork  is  to  be  used to exhaust vapors from
dishwashers, pot sinks, or other similar equipment of a commercial  type
from  which  moisture is emitted, copper or aluminum of the minimum gage
and weights required in Chapter 6 shall be used. Such ductwork shall  be
installed so that condensate cannot leak from it.
  506.3.6  Grease  duct  clearances.  Grease  duct  systems  and exhaust
equipment serving a Type I hood shall have a  clearance  to  combustible
construction  of  not  less  than  18  inches (457 mm), and shall have a
clearance to noncombustible construction and gypsum  wallboard  attached
to noncombustible structures of not less than 3 inches (76 mm).
  Exceptions:
  1.  Listed  and  labeled factory-built commercial kitchen grease ducts
and exhaust equipment installed in accordance with Section 304.1 and the
manufacturer's instructions, and as approved by the commissioner.
  2. Protected with a minimum insulation covering of 2 inches (51 mm) of
magnesium or calcium silicate block,  with  staggered  joints,  attached
with galvanized steel wire or material assembly equivalent in insulating
and  fire  resistant  qualities  which  can not be penetrated by grease,
shall be applied to all ducts inside of the building as approved by  the
commissioner.
  506.3.7  Prevention  of  grease  accumulation  in  grease  ducts. Duct
systems serving a Type I hood shall be constructed and installed so that
grease cannot collect in any portion thereof, and the system shall slope
not less than one-forth unit vertical in 12 units horizontal  (2-percent
slope)  toward  the  hood  or toward an approved grease reservoir. Where
horizontal ducts exceed 75 feet (22 860 mm) in length, the  slope  shall
not  be  less than one unit vertical in 12 units horizontal (8.3-percent
slope). Dampers shall not be  installed  in  the  grease  duct  systems,
except as required by Section 506.3.5 Exception Item 2.
  506.3.7.1  Residue  trap. A residue trap shall be provided at the base
of each vertical riser with provision for cleanout  in  accordance  with
NFPA 96.
  506.3.8  Grease duct cleanouts and other openings. Grease duct systems
shall not have openings therein other than  those  required  for  proper
operation  and  maintenance  of  the  system. Any portion of such system
having sections  not  provided  with  access  from  the  duct  entry  or
discharge  shall  be  provided with cleanout openings. Cleanout openings
shall be provided at every change in direction, within 3 feet  (914  mm)
of  the  exhaust  fan,  and  as required under Section 506.3.9. Cleanout
openings shall be equipped with tight-fitting doors constructed of steel
having a thickness not less than that required for the duct. Doors shall
be equipped with a substantial method of latching,  sufficient  to  hold
the  door  tightly  closed.  Doors  shall  be  designed so that they are
operable without the use of a tool. Door assemblies shall have a  gasket
or  sealant  that is noncombustible and liquid tight, and shall not have

fasteners that penetrate  the  duct.  Listed  and  labeled  access  door
assemblies  shall  be  installed  in  accordance  with  the terms of the
listing. Signage shall be provided at  all  required  access  doors  and
openings in accordance with Section 506.3.11.
  506.3.8.1  Personnel  entry.  Where  ductwork is large enough to allow
entry of personnel, not less than one approved or listed opening  having
dimensions not less than 20 inches by 20 inches (508 mm by 508 mm) shall
be  provided  in  the  horizontal  sections,  and in the top of vertical
risers. Where such entry is provided, the duct and its supports shall be
capable of supporting the additional load and the cleanouts specified in
Section 506.3.8 are not required. Where personnel entry is not possible,
access for cleaning interior vertical ducts shall be  provided  on  each
floor, and for cleaning the base of the vertical riser.
  506.3.9   Grease  duct  horizontal  cleanouts.  Cleanouts  located  on
horizontal sections of ducts shall be spaced not more than 20 feet (6096
mm) apart, unless the opening prescribed by  Section  506.3.8.1  is  not
possible,  in  which  case  openings  large  enough  to  permit thorough
cleaning shall be provided at 12 feet (3658 mm) intervals. The cleanouts
shall be located on the side of the duct with the opening not less  than
1.5  inches  (38  mm)  above the bottom of the duct, and not less than 1
inch (25 mm) below the top of the duct. The opening  minimum  dimensions
shall  be  12  inches (305 mm) on each side. Where the dimensions of the
side of the duct prohibit the cleanout installation  prescribed  herein,
the  openings  shall be on the top of the duct or th bottom of the duct.
Where located on the top of the duct,  the  opening  edges  shall  be  a
minimum  of  1 inch (25 mm) from the edges of the duct. Where located in
the bottom of the duct, cleanout openings shall be designed  to  provide
internal damming around the opening, shall be provided with gasketing to
preclude  grease  leakage, shall provide for drainage of grease down the
duct around the dam, and shall be approved for  the  application.  Where
the  dimensions  of  the  sides,  top or bottom of the duct preclude the
installation  of  the  prescribed  minimum-size  cleanout  opening,  the
cleanout  shall  be  located  on  the duct face that affords the largest
opening dimension and shall be installed with the opening edges  at  the
prescribed distances from the duct edges as previously set forth in this
section.
  506.3.10  Grease  duct  enclosure. A grease duct serving a Type I hood
that penetrates a ceiling, wall or floor  shall  be  enclosed  from  the
first  point  of  penetration  to  the  outlet  terminal.  A  duct shall
penetrate exterior walls only at locations  where  unprotected  openings
are  permitted  by  the  New  York  City  Building  Code. Ducts shall be
enclosed in accordance with the New York City Building Code requirements
for shaft construction. The duct enclosure shall be  sealed  around  the
duct  at  the  point  of  penetration  and  vented to the outside of the
building through the use of weather-protected openings.  Clearance  from
the   duct   to  the  interior  surface  of  enclosures  of  combustible
construction shall be not less than 18 inches (457 mm).  Clearance  from
the  duct  to  the  interior  surface  of  enclosures  of noncombustible
construction or gypsum wallboard attached to  noncombustible  structures
shall be not less than 6 inches (152 mm). The duct enclosure shall serve
a  single  grease  exhaust  duct  system and shall not contain any other
ducts, piping, wiring or systems.
  Exceptions:
  1. The shaft enclosure  provisions  of  this  sections  shall  not  be
required    where    a    duct   penetration   is   protected   with   a
through-penetration firestop system classified in accordance with ASTM E
814 and having an .F. and .T. rating equal to the fire-resistance rating
of the assembly being penetrated and where the surface of  the  duct  is

continuously  covered  on  all  sides  from  the point at which the duct
penetrates a ceiling, wall or  floor  to  the  outlet  terminal  with  a
classified  and  labeled  material,  system,  method  of construction or
product specifically evaluated for such purpose, which material, system,
method  of  construction  or product is approved by the commissioner and
installed according to the  manufacturer's  instructions.  Exposed  duct
wrap systems shall be protected where subject to physical damage.
  2.  As  an  alternative to Exception Item 1 of this section, a minimum
insulation covering of 2 inches (51 mm) of magnesium or calcium silicate
block, with staggered joints, attached with  galvanized  steel  wire  or
material  assembly equivalent in insulating and fire resistant qualities
which  can  not  be  penetrated  by  grease,  and  as  approved  by  the
commissioner, shall be applied to all ducts inside of the building.
  3.  A  duct  enclosure  shall  not  be required for a grease duct that
penetrates only a nonfire-resistance-rated roof/ceiling assembly.
  4. A listed and labeled factory-built commercial kitchen  grease  duct
system,  evaluated  as  an  enclosure  system  for reduced clearances to
combustibles, and approved by the commissioner and  installed  according
to manufacturer's instructions.
  506.3.11  Grease  duct  fire-resistive  access opening. Where cleanout
openings are located in ducts within a fire-resistance-rated  enclosure,
access  openings  shall  be  provided  in the enclosure at each cleanout
point. Access openings hall be equipped with  tight-fitting  sliding  or
hinged  doors that are equal in fire-resistive protection to that of the
shaft or enclosure. An approved sign shall be placed on  access  opening
panels  with  wording  as  follows:  "ACCESS  PANEL.   DO NOT OBSTRUCT."
Cleanout openings provided in ducts that are not located within  a  fire
resistance-rated  enclosure  shall  be  provided  with  signage  at  the
required opening that contains the same wording.
  506.3.12 Exhaust outlets serving Type I  hoods.  Exhaust  outlets  for
grease  ducts  serving Type I hoods shall conform to the requirements of
Sections 506.3.12.1 through 506.3.12.3.
  506.3.12.1 Termination above the roof. Exhaust outlets that  terminate
above the roof shall have the discharge opening located not less than 40
inches  (1016  mm)  above  the  roof  surface. The exhaust flow shall be
directed away from the surface of the roof.
  506.3.12.2 Termination through an exterior wall. Exhaust outlets shall
be permitted to  terminate  through  exterior  walls  where  the  smoke,
grease, gases, vapors, and odors in the discharge from such terminations
do  not  create  a  public  nuisance or a fire hazard. Such terminations
shall not be located where protected openings are required  by  the  New
York  City  Building  Code. Other openings shall not be located within 3
feet (914 mm) of such terminations.
  506.3.12.3 Termination location. Exhaust outlets shall be located  not
less  than  10  feet  (3048  mm)  horizontally from parts of the same or
contiguous buildings, adjacent property lines and  air  intake  openings
into  any  building and shall be located not less than 10 feet (3048 mm)
above the adjoining grade level.
  Exception: Exception: Exhaust outlets shall terminate not less than  5
feet (1524 mm) from an adjacent building, adjacent property line and air
intake  openings  into  a  building  where  air  from the exhaust outlet
discharges away from such locations.
  506.4 Ducts serving Type II hoods. Single or combined Type II  exhaust
systems for food-processing operations shall be independent of all other
exhaust  systems.  Commercial  kitchen  exhaust  systems serving Type II
hoods shall comply with Sections 506.4.1 and 506.4.2.
  506.4.1 Type II exhaust outlets. Exhaust  outlets  for  ducts  serving
Type II hoods shall comply with Sections 401.5 and 401.5.2. Such outlets

shall  be  protected against local weather conditions and shall meet the
provisions for exterior wall opening protectives in accordance with  the
New York City Building Code.
  506.4.2  Ducts.  Ducts  and  plenums  serving  Type  II hoods shall be
constructed   of   rigid   metallic   materials.   Duct    construction,
installation,  bracing  and  supports shall comply with Chapter 6. Ducts
subject to positive  pressure  and  ducts  conveying  moisture-laden  or
waste-heat-laden  air  shall  be  constructed,  joined  and sealed in an
approved manner.
  506.4.2.1  Cooking  spaces.  For  all  buildings  other   than   those
classified  as  residential  occupancy,  a  minimum  of  No. 16 Gage for
galvanized  sheet  duct  shall  be  used  for  nongrease  duct   exhaust
applications.
  506.5  Exhaust equipment. Exhaust equipment, including fans and grease
reservoirs, shall comply with Section 506.5.1 through 506.5.5 and  shall
be of an approved design or shall be listed for the application.
  506.5.1 Exhaust fans. Exhaust fan housings serving a Type I hood shall
be  constructed  as required for grease ducts in accordance with Section
506.3.1.1.
  Exception: Fans listed and labeled in accordance with UL 762.
  506.5.1.1 Fan motor. Exhaust fan motors shall be  located  outside  of
the exhaust airstream.
  506.5.2  Exhaust  fan  discharge.  Exhaust fans shall be positioned so
that the discharge will not impinge on  the  roof,  other  equipment  or
appliances or parts of the structure. A vertical discharge fan serving a
Type  I  hood shall be manufactured with an approved drain outlet at the
lowest point of the housing to permit drainage of grease to an  approved
grease reservoir.
  506.5.3  Exhaust  fan  mounting.  An  upblast  fan shall be hinged and
supplied  with  a  flexible  weatherproof  electrical  cable  to  permit
inspection  and  cleaning.  The  ductwork  shall  extend a minimum of 18
inches (457 mm) above the roof surface.
  506.5.4 Clearances. Exhaust equipment serving a Type I hood shall have
a clearance to combustible construction of not less than 18 inches  (457
mm).
  Exception:  Factory-built  exhaust  equipment  installed in accordance
with Section 304.1 and listed for a lesser clearance.
  506.5.5 Termination location. The outlet of exhaust equipment  serving
Type I hoods, shall be in accordance with Section 506.3.12.3.
  Exception:  The minimum horizontal distance between vertical discharge
fans and parapet-type building structures  shall  be  2  feet  (610  mm)
provided  that  such  structures  are not higher than the top of the fan
discharge opening.
  506.5.6 Exhaust fan operation. The operation of the exhaust fan  shall
be in accordance with the following requirements:
  1.  The  hood  exhaust  fan(s)  shall  continue  to  operate after the
exhausting system has been activated unless fan shutdown is required  by
a  listed  component  of  the ventilation system or by the design of the
extinguishing system.
  2. The hood exhaust fan shall not be required to  start  automatically
upon  activation  of the extinguishing system if the exhaust fan and all
cooking equipment served by the fan have previously been shut down.
  3. The cooking appliances shall be interlocked with the  exhaust  hood
system  to  prevent  appliance operation when the exhaust hood system is
not operating.
  506.6 Exterior duct installations. The installation of exterior  ducts
shall comply with the following requirements:

  1.  The  exterior  portion  of the ductwork shall be vertical wherever
possible and shall be installed and  supported  on  the  exterior  of  a
building.
  2.  Bolts,  screws,  rivets,  and other mechanical fasteners shall not
penetrate duct walls.
  3. Clearance of any ducts shall comply with Section 506.3.6.
  4. All ducts shall be protected on the  exterior  by  paint  or  other
suitable weather-protective coating.
  5.  Ducts constructed of stainless steel shall not be required to have
additional paint or weather-protective coatings.
  6. Ductwork subject to corrosion shall have minimal contact  with  the
building surface.
  506.7  Identification  of  ducts.  All duct systems serving Type I and
Type II  exhaust  equipment  shall  be  permanently  labeled:  "CAUTION:
KITCHEN EXHAUST SYSTEM".
  506.8  Types  I and II hoods. All exhaust ducts serving Type I or Type
II hoods shall have a minimum insulation covering of 2 inches (51 mml of
magnesium or calcium silicate block, attached with galvanized steel wire
or construction equivalent in insulating and fire resistance  qualities,
and shall be applied to all ducts inside of the building. The insulation
shall be applied up to the outer face of the discharge from the building
and  shall  also be applied to the housing of the exhaust fan when it is
located inside of the building. Care shall be taken to insure  that  the
insulation  extends  through  the  walls and roofs to separate the ducts
from the building construction. Masonry  or  concrete  ducts  shall  not
require insulation.
                             SECTION MC 507
                        COMMERCIAL KITCHEN HOODS
507.1  General.  Commercial  kitchen exhaust hoods shall comply with the
requirements of this section. Hoods shall be Type I or Type II and shall
be designed to capture and confine cooking vapors and residues.
  Exceptions:
  1.  Factory-built  commercial  exhaust  hoods  which  are  tested   in
accordance with UL 710, listed, labeled and installed in accordance with
Section  304.1  shall  not  be  required  to comply with Sections 507.4,
507.7, 507.11, 507.12, 507.13, 507.14 and 507.15.
  2. Net exhaust volumes for hoods shall  be  permitted  to  be  reduced
during no-load cooking conditions, where engineered or listed multispeed
or  variable-speed  controls automatically operate the exhaust system to
maintain capture and removal of cooking effluents as  required  by  this
section.
  507.2  Where  required. A Type I or Type II hood shall be installed at
or above all commercial cooking appliances in accordance  with  Sections
507.2.1  and  507.2.2.  Where  any cooking appliance under a single hood
requires a Type I hood, a Type I hood shall be installed. Where  a  Type
II hood is required, a Type I or Type II hood shall be installed.
  507.2.1  Type  I  hoods. Type I hoods shall be installed where cooking
appliances produce grease  or  smoke,  such  as  occurs  with  griddles,
fryers, broilers, ovens, ranges and wok ranges.
  507.2.2  Type II hoods. Type II hoods shall be installed where cooking
or dishwashing appliances produce heat  or  steam  and  do  not  produce
grease   or   smoke,  such  as  steamers,  kettles,  pasta  cookers  and
dishwashing machines.
  Exceptions:
  1. Under-counter-type commercial dishwashing machines.
  2. A Type II hood is not required for dishwashers and potwashers  that
are provided with heat and water vapor exhaust systems that are supplied

by  the  appliance manufacturer and are installed in accordance with the
manufacturer's instructions.
  507.2.3  Domestic  cooking  appliances  used  for commercial purposes.
Domestic cooking appliances utilized for commercial  purposes  shall  be
provided  with  Type  I  or  Type  II  hoods as required for the type of
appliances and processes in accordance with Sections 507.2, 507.2.1  and
507.2.2.
  507.2.4 Solid fuel. Type I  hoods  for  use  over  solid  fuel-burning
cooking  appliances  shall  discharge  to  an  exhaust  system  that  is
independent of other exhaust systems.
  507.3 Fuel-burning appliances. Where  vented  fuel-burning  appliances
are  located  in the same room or space as the hood, provisions shall be
made to prevent the hood system from interfering with  normal  operation
of the appliance vents.
  507.4 Type I materials. Type I hoods shall be constructed of steel not
less  than  0.043 inch (1.09 mm) (No. 18 MSG) in thickness, or stainless
steel not less than 0.037 inch (0.94 mm) (No. 20 MSG) in thickness.
  507.5 Type II hood materials. Type II hoods shall  be  constructed  of
steel  not  less  than  0.030 inch (0.76 mm) (No. 22 Gage) in thickness,
stainless steel not less than 0.024 inch (0.61 mrn)  (No.  24  Gage)  in
thickness,  copper  sheets  weighing  not less than 24 ounces per square
foot (7.3 kg/m{2}), or of other approved material and gage.
  507.6  Supports.  Type  I  hoods  shall  be  secured   in   place   by
noncombustible  supports.  All Type I and Type II hood supports shall be
adequate for the applied load of the hood, the unsupported ductwork, the
effluent loading, and the possible weight of personnel working in or  on
the hood.
  507.7  Hood  joints,  seams  and  penetrations. Hood joints, seams and
penetrations shall comply with Sections 507.7.1 and 507.7.2.
  507.7.1 Type I hoods. External hood joints, seams and penetrations for
Type I hoods shall be made with a continuous external liquid-tight  weld
or  braze  to  the lowest outermost perimeter of the hood. Internal hood
joints, seams, penetrations, filter support frames, and other appendages
attached inside the hood shall not be required to be  welded  or  brazed
but shall be otherwise sealed to be grease tight.
  Exceptions:
  1.  Penetrations  shall  not  be required to be welded or brazed where
sealed by devices that are listed for the application.
  2. Internal welding or brazing of seams, joints, and  penetrations  of
the  hood  shall  not  be  prohibited  provided that the joint is fowled
smooth or ground so as to not trap grease, and is readily cleanable.
  507.7.2 Type II hoods. Joints, seams  and  penetrations  for  Type  II
hoods shall be constructed as set forth in Chapter 6, shall be sealed on
the  interior  of  the  hood  and shall provide a smooth surface that is
readily cleanable and water tight.
  507.8 Cleaning and grease gutters. A hood shall be designed to provide
for thorough cleaning of the entire hood. Grease glitters shall drain to
an approved collection  receptacle  that  is  fabricated,  designed  and
installed to allow access for cleaning.
  507.9  Clearances  for  Type  I hood. A Type I hood shall be installed
with a clearance to combustibles of not less than 18 inches (457 rum).
  Exception: Clearance shall  not  be  required  from  gypsum  wallboard
attached to noncombustible structures provided that a smooth, cleanable,
nonabsorbent  and  noncombustible material is installed between the hood
and the gypsum wallboard over an area extending not less than 18  inches
(457 mm) in all directions from the hood.

  507.10 Hoods A penetrating a ceiling. Type I hoods or portions thereof
penetrating  a  ceiling,  wall or furred space shall comply with all the
requirements of Section 506.3.10.
  507.11  Grease  filters.  Type  I hoods shall be equipped with UL 1046
listed   grease   filters   designed   for   the    specific    purpose.
Grease-collecting  equipment shall be provided with access for cleaning.
The lowest edge of a grease filter located  above  the  cooking  surface
shall be not less than the height specified in Table 507.11.

                              TABLE 507.11
              MINIMUM DISTANCE BETWEEN THE LOWEST EDGE OF A
      GREASE FILTER AND THE COOKING SURFACE OR THE HEATING SURFACE
TYPE OF COOKING                    HEIGHT OF COOKING
APPLIANCE                          SURFACE(feet)
Without exposed flame              0.5
Exposed flame and burners          2
Exposed charcoal and charbroil
type                               4

  For SI: 1 foot = 304.8 mm.
  507.11.1 Criteria. Filters shall be of such size, type and arrangement
as  will  permit the required quantity of air to pass through such units
at rates not exceeding those for which the filter or unit  was  designed
or  approved. Filter units shall be installed in frames or holders so as
to be readily removable  without  the  use  of  separate  tools,  unless
designed and installed to be cleaned in place and the system is equipped
for  such  cleaning  in place. Removable filter units shall be of a size
that will allow them to be cleaned in a dishwashing machine or pot sink.
Filter  units  shall   be   arranged   in   place   or   provided   with
drip-intercepting  devices  to  prevent  grease or other condensate from
dripping into food or on food preparation surfaces.
  507.11.2 Mounting position. Filters shall be installed at an angle  of
not  less  than  45  degrees (0.79 rad) from the horizontal and shall be
equipped with a drip tray beneath the lower edge of the filters.
  507.11.3 Filter servicing. Filters  shall  be  serviced  and  replaced
regularly by qualified employees of the owner or by a cleaning agency. A
record indicating the name of the person or firm doing the servicing and
the  dates  when filters were cleaned or replaced shall be available for
inspection by the commissioner. They shall be  cleaned  or  replaced  as
frequently as necessary, but at least every three months, and no exhaust
system  shall  be operated while cooking is being carried on without the
filters installed in place.
  507.12 Canopy size and location. The inside lower edge of  canopy-type
commercial  cooking hoods shall overhang or extend a horizontal distance
of not less than 6 inches (152  mm)  beyond  the  edge  of  the  cooking
surface,  on  all  open  sides.  The vertical distance between the front
lower lip of the hood and the cooking surface shall not  exceed  4  feet
(1219 mm).
  Exception: The hood shall be permitted to be flush with the outer edge
of the cooking surface where the hood is closed to the appliance side by
a noncombustible wall or panel.
  507.13  Capacity of hoods. Commercial food service hoods shall exhaust
a minimum net quantity of air determined in accordance with this section
and Sections 507.13.1 through 507.13.4. The net quantity of exhaust  air
shall  be  calculated  by subtracting any airflow supplied directly to a
hood cavity from the total exhaust  flow  rate  of  a  hood.  Where  any
combination of extra-heavy-duty, heavy-duty, medium-duty, and light-duty

cooking appliances are utilized under a single hood, the highest exhaust
rate required by this section shall be used for the entire hood.
  507.13.1  Extra-heavy-duty cooking appliances. The minimum net airflow
for Type I hoods used for extra-heavy-duty cooking appliances  shall  be
determined as follows:

Type of Hood                       CFM Per linear foot of hood
Wall-mounted canopy                550
Single island canopy               700
Double island canopy (per side)    550
Backshelf/pass-over                Not allowed
Eyebrow                            Not allowed
  For SI: 1 cfm per linear foot = 1.55 L/s per linear meter.
  507.13.2  Heavy-duty  cooking  appliances. The minimum net airflow for
Type I hoods used for heavy-duty cooking appliances shall be  determined
as follows:
Type of Hood                       CFM per linear foot of hood
Wall-mounted canopy                400
Single island canopy               600
Double island canopy (per side)    400
Backshelf/pass-over                400
Eyebrow                            Not allowed
  For SI: 1 cfm pr linear foot = 1.55 L/s per linear meter.
  507.13.3  Medium-duty  cooking appliances. The minimum net airflow for
Type I hoods used for medium-duty cooking appliances shall be determined
as follows:
Type of Hood                       CFM per linear foot of hood
Wall-mounted canopy                300
Single island canopy               500
Double island canopy (per side)    300
Backshelf/pass-over                300
Eyebrow                            250
  For SI: 1 cfm per linear foot = 1.55 L/s per linear meter.
  507.13.4 Light-duty cooking appliances. The minimum  net  airflow  for
Type  I  hoods  used  for light duty cooking appliances and food service
preparation and cooking operations approved for use under a Type II hood
shall be determined as follows:
Type of Hood                       CFM per linear foot of hood
Wall-mounted canopy                200
Single island canopy               400
Double island canopy (per side)    250
Backshelf/pass-over                250
Eyebrow                            250
  For SI: 1 cfm per linear foot = 1.55 L/s per linear meter.
  507.14 Noncanopy size and  location.  Noncanopy-type  hoods  shall  be
located a maximum of 3 feet (914 mm) above the cooking surface. The edge
of the hood shall be set back a maximum of 1 foot (305 mm) from the edge
of the cooking surface.
  507.15  Exhaust outlets. Exhaust outlets located within the hood shall
be located so as to optimize the capture  of  particulate  matter.  Each
outlet shall serve not more than a 12-foot (3658 mm) section of hood.
  507.16  Performance  test.  A performance test shall be conducted upon
completion and witnessed by a  representative  of  the  Fire  Department
before  final  approval  of  the  installation  of  a ventilation system
serving commercial cooking appliances. The test shall verify the rate of
exhaust airflow required by Section 507.13, makeup airflow  required  by
Section  508,  and  proper  operation  as specified in this chapter. The

permit holder shall furnish the necessary  test  equipment  and  devices
required to perform the tests.
                             SECTION MC 508
                      COMMERCIAL KITCHEN MAKEUP AIR
508.1  Makeup  air. Makeup air shall be supplied during the operation of
commercial kitchen exhaust systems  that  are  provided  for  commercial
cooking   appliances.  The  amount  of  makeup  air  supplied  shall  be
approximately equal to the amount of exhaust air. The makeup  air  shall
not  reduce the effectiveness of the exhaust system. Makeup air shall be
provided by gravity or mechanical means or both. For  mechanical  makeup
air  systems,  the  exhaust and makeup air systems shall be electrically
interlocked to ensure that makeup air is provided whenever  the  exhaust
system is in operation. Makeup air intake opening locations shall comply
with Sections 401.5 and 401.5.1.
  508.1.1  Makeup  air temperature. The temperature differential between
makeup air and the air in the conditioned space shall  not  exceed  10°F
(6°C).
  Exceptions:
  1. Makeup air that is part of the air-conditioning system.
  2.  Makeup  air  that  does not increase the comfort conditions of the
occupied space.
  508.2 Compensating hoods. Manufacturers of  compensating  hoods  shall
provide  a  label  indicating minimum exhaust flow and/or maximum makeup
airflow that provides capture and containment of the exhaust effluent.
                             SECTION MC 509
                        FIRE SUPPRESSION SYSTEMS
509.1 Where required. Commercial cooking appliances required by  Section
507.2.1  to  have  a  Type  I  hood  shall  be provided with an approved
automatic fire suppression system  complying  with  the  New  York  City
Building Code and the New York City Fire Code.
                              SECTION MC 510
                        HAZARDOUS EXHAUST SYSTEMS
510.1  General. This section shall govern the design and construction of
duct systems for  hazardous  exhaust  and  shall  determine  where  such
systems  are required. Hazardous exhaust systems are systems designed to
capture and control hazardous emissions generated from product  handling
or  processes,  and  convey  those  emissions to the outdoors. Hazardous
emissions include flammable vapors, gases, fumes, mists  or  dusts,  and
volatile   or   air-borne   materials,  including  but  not  limited  to
perchloroethylene, posing a health hazard, such as  toxic  or  corrosive
materials. For the purposes of this section, the health hazard rating of
materials shall be specified in NFPA 704.
  510.2  Where  required.  A  hazardous exhaust system shall be required
wherever operations involving the handling or  processing  of  hazardous
materials,  in  the  absence  of  such  exhaust systems and under normal
operating conditions, have the potential to create one of the  following
conditions.
  1.  A  flammable  vapor,  gas,  fume,  mist  or  dust  is  present  in
concentrations exceeding 25 percent of the lower flammability  limit  of
the substance for the expected room temperature.
  2.  A  vapor, gas, fume, mist or dust with a health-hazard rating of 4
is present in any concentration.
  3. A vapor, gas, fume, mist or dust with a health-hazard rating of  1,
2  or  3  is present in concentrations exceeding 1 percent of the median
lethal concentration of the substance for acute inhalation toxicity.
  510.2.1  Lumber  yards  and  woodworking  facilities.   Equipment   or
machinery  located  inside  buildings  at  lumber  yards and woodworking
facilities which generates or emits combustible dust shall  be  provided

with  an  approved  dust-collection  and  exhaust  system  installed  in
conformance with this section and the New York City Fire Code. Equipment
and systems that are used to  collect,  process  or  convey  combustible
dusts shall be provided with an approved explosion-control system.
  510.2.2  Combustible  fibers. Equipment or machinery within a building
which generates or emits combustible fibers shall be  provided  with  an
approved  dust-collecting  and exhaust system. Such systems shall comply
with this code and the New York City Fire Code.
  510.3 Design and operation. The design and operation  of  the  exhaust
system  shall  be  such  that  flammable  contaminants  are  diluted  in
noncontaminated air to maintain concentrations in the exhaust flow below
25 percent of the contaminant's lower flammability limit.
  510.4  Independent  system.  Hazardous  exhaust   systems   shall   be
independent  of  other types of exhaust systems. Incompatible materials,
as defined in the New York  City  Fire  Code,  shall  not  be  exhausted
through  the  same  hazardous  exhaust system. Hazardous exhaust systems
shall not share common shafts with other duct systems, except where such
systems are hazardous exhaust systems originating in the same fire area.
  Contaminated air shall not be recirculated to  occupied  areas  unless
the  contaminants  have been removed. Air contaminated with explosive or
flammable  vapors,  fumes  or  dusts;  flammable  or  toxic  gases;   or
radioactive material shall not be recirculated.
  510.5  Design. Systems for removal of vapors, gases and smoke shall be
designed by the constant velocity or  equal  friction  methods.  Systems
conveying  particulate  matter  shall be designed employing the constant
velocity method.
  510.5.1  Balancing.  Systems  conveying   explosive   or   radioactive
materials  shall  be  prebalanced by duct sizing. Other systems shall be
balanced by duct sizing with balancing devices, such as dampers. Dampers
provide to balance  air-flow  shall  be  provided  with  securely  fixed
minimum-position  blocking devices to prevent restricting flow below the
required volume or velocity.
  510.5.2 Emission control. The design of the system shall be such  that
the  emissions  are  confined to the area in which they are generated by
air currents, hoods or enclosures and  shall  be  exhausted  by  a  duct
system to a safe location or treated by removing contaminants.
  510.5.3  Hoods  required.  Hoods  or  enclosures  shall  be used where
contaminants originate in a limited area of a space. The design  of  the
hood or enclosure shall be such that air currents created by the exhaust
systems will capture the contaminants and transport them directly to the
exhaust duct.
  510.5.4 Contaminant capture and dilution. The velocity and circulation
of air in work areas shall be such that contaminants are captured by and
airstream  at  the  area  where the emissions are generated and conveyed
into a product-conveying duct system. Contaminated air from  work  areas
where  hazardous  contaminates  are generated shall be diluted below the
thresholds specified in Section 510.2 with air  that  does  not  contain
other hazardous contaminants.
  510.5.5   Makeup   air.  Makeup  air  shall  be  provided  at  a  rate
approximately equal to the rate that air is exhausted by  the  hazardous
exhaust  system.    Makeup-air  intakes  shall be located so as to avoid
recirculation of contaminated air.
  510.5.6  Clearances.  The  minimum   clearance   between   hoods   and
combustible  construction  shall  be  the clearance required by the duct
system.
  510.5.7 Ducts. Hazardous exhaust duct systems shall extend directly to
the exterior of the building and shall not extend into or through  ducts
and plenums.

  510.6 Penetrations. Penetrations of structural elements by a hazardous
exhaust system shall conform to Sections 510.6.1 through 510.6.3.
  Exception:  Duct penetrations within H-5 occupancies as allowed by the
New York City Building Code.
  510.6.1  Floors.  Hazardous   exhaust   systems   that   penetrate   a
floor/ceiling  assembly  shall  be  enclosed  in a fire-resistance-rated
shaft constructed in accordance with the New York City Building Code.
  510.6.2 Wall assemblies. Hazardous exhaust duct systems that penetrate
fire-resistance-rated   wall   assemblies   shall   be    enclosed    in
fire-resistance-rated  construction  from the first point of penetration
to the outlet terminal,  except  where  the  interior  of  the  duct  is
equipped with an approved automatic fire suppression system. Ducts shall
be  enclosed  in  accordance  with  the  New  York  City  Building  Code
requirements for shaft construction and  such  enclosure  shall  have  a
minimum   fire-resistance-rating   of   not   less   than   the  highest
fire-resistance-rated wall assembly penetrated.
  510.6.3 Fire walls. Ducts shall not penetrate a fire wall.
  510.7 Suppression required. Ducts shall be protected with an  approved
automatic  fire  suppression system installed in accordance with the New
York City Building Code.
  Exceptions:
  1. An approved automatic fire suppression system shall not be required
in  ducts  conveying  materials,  fumes,  mists  and  vapors  that  area
nonflammable   and  noncombustible  under  all  conditions  and  at  any
concentrations.
  2. An approved automatic fire suppression system shall not be required
in ducts where the largest cross-sectional diameter of the duct is  less
than 10 inches (254 mm).
  510.8  Duct  construction.  Ducts utilized to convey hazardous exhaust
shall be constructed of approved G90  galvanized  sheet  steel,  with  a
minimum nominal thickness as specified in Table 510.8.
  Nonmetallic   ducts   utilized   in  systems  exhausting  nonflammable
corrosive fumes or vapors shall be listed and labeled. Nonmetallic  duct
shall  have  a  flame  spread  index of 25 or less and a smoke-developed
index of 50 or less, when tested in accordance with  ASTM  E  84.  Ducts
shall be approved for installation in such an exhaust system.
  Where  the  products  being  exhausted  are  detrimental  to  the duct
material, the ducts shall be constructed of alternative  materials  that
are compatible with the exhaust.
                               TABLE 510.8
                         MINIMUM DUCT THICKNESS
                             MINIMUM NOMINAL THICKNESS
DIAMETER OF
DUCT                               Nonabrasive/
OR MAXIMUM SIDE     Nonabrasive      Abrasive        Abrasive
DIMENSION           materials        materials       materials
                    0.028 inch     0.034 inch        0.040 inch
0-8 inches          (No. 24        (No. 22           (No. 20
                    Gage)          Gage)             Gage)
                    0.034 inch     0.040 inch        0.052 inch
9-18 inches         (No. 22        (No. 20           (No. 18
                    Gage)          Gage)             Gage)
                    0.040 inch     0.052 inch        0.064 inch
19-30 inches        (No. 20        (No. 18           (No. 16
                    Gage)          Gage)             Gage)
510.8.1  Duct joints. Ducts shall be made tight with lap joints having a
minimum lap of 1 inch (25 mm).

  510.8.2 Clearance to combustibles. Ducts shall  have  a  clearance  to
combustibles  in  accordance  with  Table  510.8.2. Exhaust gases having
temperatures in excess of 600°F (316°C) shall be exhausted to a  chimney
in accordance with Section 511.2.

                              TABLE 510.8.2
                        CLEARANCE TO COMBUSTIBLES
--------------------------------------------------------------------------
    TYPE OF EXHAUST OR                      CLEARANCE   TO  COMBUSTIBLES
TEMPERATURE OF EXHAUST (°F)                         (inches)
--------------------------------------------------------------------------
    Less than 100                                       1
--------------------------------------------------------------------------
     100-600                                           12
--------------------------------------------------------------------------
  Flammable vapors                                      6
--------------------------------------------------------------------------
For SI: 1 inch = 25.44 mm. °C = {(°F - 32)}/1.8
  510.8.3 Explosion relief.  Systems  exhausting  potentially  explosive
mixtures  shall be protected with an approved explosion relief system or
by an approved explosion prevention system  designed  and  installed  in
accordance with NFPA 69. An explosion relief system shall be designed to
minimize   and  structural  and  mechanical  damage  resulting  from  an
explosion or  deflagration  within  the  exhaust  system.  An  explosion
prevention   system  shall  be  designed  to  prevent  an  explosion  or
deflagration from occurring.
  510.9 Supports. Ducts shall be supported at intervals not exceeding 10
feet  (3048  mm).  Supports  shall  be  constructed  of   noncombustible
material.
                             SECTION MC 511
                         DUST, STOCK AND REFUSE
                            CONVEYING SYSTEMS
  511.1 Dust, stock and refuse conveying systems. Dust, stock and refuse
conveying  systems  shall  comply with the provisions of Section 510 and
Sections 511.1.1 through 511.2.
  511.1.1 Collectors and separators. Cyclone collectors  and  separators
and associated supports shall be constructed of noncombustible materials
and  shall  be  located  on the exterior of the building or structure. A
collector or separator shall not be located nearer than  10  feet  (3048
mm)  to  combustible  construction  or  to  an unprotected wall or floor
opening, unless the collector is provided with a metal  vent  pipe  that
extends  above  the  highest  part of any roof within the distance of 30
feet (9144 mm).
  511.1.2  Discharge  pipe.  Discharge  piping  shall  conform  to   the
requirements  for  ducts,  including  clearances  required for high-heat
appliances, as contained in this code. A delivery pipe  from  a  cyclone
collector shall not convey refuse directly into the firebox of a boiler,
furnace, dutch oven, refuse burner, incinerator or other appliance.
  511.1.3  Conveying  system  exhaust discharge. An exhaust system shall
discharge to the outside of the building either  directly  by  flue,  or
indirectly  through  the  separator,  bin or vault into which the system
discharges.
  511.1.4 Spark protection. The outlet of an open-air  exhaust  terminal
shall be protected with an approved metal or other noncombustible screen
to prevent the entry of sparks.
  511.1.5  Explosion  relief  vents.  A  safety or explosion relief vent
shall be provided ion all systems  that  convey  combustible  refuse  or

stock of an explosive nature, in accordance with the requirements of the
New York City Building Code.
  511.1.5.1  Screens.  Where  a  screen  is installed in a safety relief
vent, the screen shall be attached so as to permit ready  release  under
the explosion pressure.
  511.1.5.2  Hoods.  The  relief vent shall be provided with an approved
noncombustible cowl or hood, or with a counterbalanced relief  valve  or
cover  arranged  to  prevent the escape of hazardous materials, gases or
liquids.
  511.2 Exhaust outlets. Outlets for exhaust that exceed  600°F  (315°C)
shall be designed in accordance with Table 511.2.
  The  termination point for exhaust ducts discharging to the atmosphere
shall not be less than the following
  1. Ducts conveying explosive or flammable vapors, fumes or  dusts:  30
feet  (9144 mm) from property line; 10 feet (3048 mm) from openings into
the building; 6 feet (1829 mm) from exterior walls  or  roofs;  30  feet
(9144 mm) from combustible walls or openings into the building which are
in  the  direction of the exhaust discharge; and 10 feet (3048 mm) above
adjoining grade.
  2. Other product-conveying outlets: 10 feet (3048  mm)  from  property
line; 3 feet (914 mm) from exterior wall or roof; 10 feet (3048 mm) from
openings into the building; and 10 feet (3048 mm) above adjoining grade.
  3. Environmental air duct exhaust: 3 feet (914 mm) from property line;
and 3 feet (914 mm) from openings into the building.
                                TABLE 511.2
  CONSTRUCTION, CLEARANCE AND TERMINATION REQUIREMENTS FOR SINGLE-WALL
             METAL DUST, STOCK AND REFUSE CONVEYING SYSTEMS
------------------------------------------------------------------------
                  |MINIMUM THICKNESS|  TERMINATION  |  CLEARANCE
                  ------------------------------------------------------
                  |      |          |    |          |Combustib|Noncombu-
                  |      |          |Abo-|Above any |le constr|stible
                  |      |          |ve  |part of   |uction   |constru-
                  |      |          |roof|building  |(inches) |ction
                  |      |          |ope-|within    |Int-|Ext-|Int-|Ext-
    SERVING       |      |          |ning|(feet)    |eri-|eri-|eri-|eri-
  TEMPERATURE     |Walls |          |(fe-|          |or  |r   |or  |r
     RANGE        |(inch)|  Lining  |et) |10 |25|50 |inst|inst|inst|inst.
------------------------------------------------------------------------
Low-heat applian- | 0.27 |          |    |   |  |   |    |    |
ces (1,000° F no- |(No.  |   None   | 3  | 2 |--|-- | 18 |  6 |
rmal operation)   |10 MSG|          |    |   |  |   |    |    |
--------------------------------------------------------------
Medium-heat appl- |0.127 |Up to 18"-|    |   |  |   |    |    |Up to 18"
iances (2,000° F  |10 MSG|  2 1/2"  |    |   |  |   |    |    |diameter,
maximum) {bo}     |      |Over 18"- | 10 |-- |10|-- | 36 | 24 |    2"
                  |      |  4 1/2"  |    |   |  |   |    |    |Over 18"
                  |      |On 4 1/2" |    |   |  |   |    |    |diameter,
                  |      |bed       |    |   |  |   |    |    |    4"
------------------------------------------------------------------------
High-heat applia- |0.127 |4 1/2"    |    |   |  |   |
nces (Over        |(No.  |laid on   | 20 |-- |--|20 |    See Note c
2,000° F){a}      |10 MSG|4 1/2"    |    |   |  |   |
                  |      |bed       |    |   |  |   |
------------------------------------------------------------------------
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, °C = [(°F)-32]/1.8.
  a. Lining shall extend from bottom to top of outlet.

  b.  Lining  shall  extend  from  24  inches below connector to 24 feet
above.
  c.  Clearance  shall  be as specified by the design engineer and shall
have  sufficient  clearance  from  buildings  and  structures  to  avoid
overheating combustible materials (maximum 160°F).
                             SECTION MC 512
                      SUBSLAB SOIL EXHAUST SYSTEMS
  512.1  General.  When  a  subslab soil exhaust system is provided, the
duct shall conform to the requirements of this section.
  512.2 Materials. Subslab soil exhaust system duct  material  shall  be
air  duct  material listed and labeled to the requirements of UL 181 for
Class 0 air ducts, or any of the following piping materials that  comply
with  the  New York City Plumbing Code as building sanitary drainage and
vent pipe: cast iron; galvanized steel; brass  or  copper  pipe;  copper
tube  of  a weight not less than that of copper drainage tube, Type DWV;
and plastic piping.
  512.3 Grade. Exhaust system ducts shall not be trapped and shall  have
a  minimum  slope  of  one-eight  unit  vertical  in 12 units horizontal
(1-percent slope).
  512.4 Termination. Subslab solid exhaust  system  ducts  shall  extend
through the roof and terminate at least 6 inches (152 mm) above the roof
and at least 10 feet (3048 mm) from any operable openings or air intake.
  512.5  Identification. Subslab soil exhaust ducts shall be permanently
identified within each floor level by means of a tag, stencil  or  other
approved marking.
                             SECTION MC 513
                          SMOKE CONTROL SYSTEMS
  513.1  Scope  and  purpose.  This  section  applies  to mechanical and
passive smoke control systems that are required by  the  New  York  City
Building  Code.  The  purpose  of  this  section is to establish minimum
requirements for the design,  installation  and  acceptance  testing  of
smoke control systems that are intended to provide a tenable environment
for  the evacuation or relocation of occupants. These provisions are not
intended for the preservation of contents,  the  timely  restoration  of
operations,   or   for   assistance  in  fire  suppression  or  overhaul
activities. Smoke control systems regulated  by  this  section  serve  a
different  purpose  than the smoke- and heat-venting provisions found in
Section 910 of the New York Building Code.
  513.2 General design requirements.  Buildings,  structures,  or  parts
thereof  required by this code to have a smoke control system or systems
shall have such systems  designed  in  accordance  with  the  applicable
requirements  of  Section 909 of the New York City Building Code and the
generally  accepted  and  well-established  principles  of   engineering
relevant  to  the  design.  The  construction  documents  shall  include
sufficient information and detail to describe adequately the elements of
the design necessary for the proper implementation of the smoke  control
systems.   These   documents   shall   be  accompanied  with  sufficient
information  and  analysis  to   demonstrate   compliance   with   these
provisions.
  513.3  Special  inspection  and  test requirements. In addition to the
ordinary inspection and test requirements  which  buildings,  structures
and parts thereof are required to undergo, smoke control systems subject
to  the  provisions  of  Section  909 of the New York City Building Code
shall undergo special inspections and tests  sufficient  to  verify  the
proper  commissioning of the smoke control design in its final installed
condition. The design submission accompanying the construction documents
shall clearly detail procedures and methods to be  used  and  the  items
subject  to  such  inspections and tests. Such commissioning shall be in

accordance with  generally  accepted  engineering  practice  and,  where
possible,  based  on  published  standards  for  the  particular testing
involved. The special inspections and tests  required  by  this  section
shall  be conducted under the same terms as found in Section 1704 of the
New York City Building Code.
  513.4 Analysis. A rational analysis  supporting  the  types  of  smoke
control  systems to be employed, their methods of operation, the systems
supporting them, and the methods of construction to  be  utilized  shall
accompany  the  submitted  construction documents and shall include, but
not be limited to, the  items  indicated  in  Sections  513.4.1  through
513.4.6.
  513.4.1  Stack  effect.  The  system  shall  be designed such that the
maximum probable normal or reverse  stack  effects  will  not  adversely
interfere  with  the  system's  capabilities. In determining the maximum
probable  stack  effects,  altitude,  elevation,  weather  history   and
interior temperatures shall be used.
  513.4.2  Temperature  effect of fire. Buoyancy and expansion caused by
the design fire in accordance with Section 513.9 shall be analyzed.  The
system  shall  be  designed  such  that  these  effects do not adversely
interfere with its capabilities.
  513.4.3 Wind effect. The design shall consider the adverse effects  of
wind.  Such  consideration  shall  be  consisted  with  the wind-loading
provisions of the New York City Building Code.
  513.4.4 HVAC systems. The design shall consider  the  effects  of  the
heating,  ventilating  and air-conditioning (HVAC) systems on both smoke
and fire transport. The  analysis  shall  include  all  permutations  of
system's  status.  The  design shall consider the effects of fire on the
HVAC systems.
  513.4.5  Climate.  The  design  shall  consider  the  effects  of  low
temperatures on systems, property and occupants. Air inlets and exhausts
shall be located so as to prevent snow or ice blockage.
  513.4.6 Duration of operation. All portions of active or passive smoke
control  system  shall be capable of continued operation after detection
of the fire event for not less than 20 minutes.
  513.5 Smoke barrier construction. Smoke barriers shall comply with the
New York City Building Code. Smoke barriers  shall  be  constructed  and
sealed  to  limit  leakage  areas  exclusive  of protected openings. The
maximum allowable leakage area shall be the  aggregate  area  calculated
using the following leakage area ratios:
  1. Walls: A/A[w] = 0.00100
  2. Exit enclosures: A/A[w] = 0.00035
  3. All other shafts: A/A[w] = 0.00150
  4. Floors and roofs: A/A[F} = 0.00050
  where:
  A = Total leakage area, square feet (m{2}).
  A[F}] = Unit floor or roof area of barrier, square feet (m{2}).
  A[w] = Unit wall area of barrier, square feet (m{2}).
  The  leakage  area  ratios shown do not include openings due to doors,
operable windows or similar gaps. These shall be included in calculating
the total leakage area.
  513.5.1 Leakage area. Total leakage area of the barrier is the product
of the smoke barrier gross area times the allowable leakage area  ratio,
plus  the area of such as gaps and operable windows. Compliance shall be
determined by achieving the minimum air pressure difference  across  the
barrier  with  the system in the smoke control mode for mechanical smoke
control systems.  Passive  smoke  control  systems  tested  using  other
approved  means  such  as  door  fan testing shall be as approved by the
commissioner.

  513.5.2 Opening  protection.  Openings  in  smoke  barriers  shall  be
protected by automatic-closing devices actuated by the required controls
for  the  mechanical  smoke  control  system.  Door  openings  shall  be
protected by door assemblies complying with the requirements of the  New
York Building Code for doors in smoke barriers.
  Exceptions:
  1.  Passive  smoke  control  systems  with  automatic-closing  devices
actuated by spot-type  smoke  detectors  listed  for  releasing  service
installed in accordance with the New York City Building Code.
  2.  Fixed  openings  between smoke zones which are protected utilizing
the airflow method.
  3. In Group I-2 where such doors are  installed  across  corridors,  a
pair  of  opposite-swinging  doors  without  a  center  mullion shall be
installed  having  vision  panels  with  approved   fire-rated   glazing
materials  in  approved  fire-rated  frames, the area of which shall not
exceed that tested. The doors shall be close-fitting within  operational
tolerances,  and shall not have undercuts, louvers or grilles. The doors
shall have head and jamb stops, astragals or rabbets  at  meeting  edges
and   automatic-closing  devices.  Positive  latching  devices  are  not
required.
  4. Group I-3.
  5. Openings between smoke zones with clear ceiling heights of 14  feet
(4267  mm)  or greater and bank down capacity of greater than 20 minutes
as determined by the design fire size.
  513.5.2.1 Ducts and air transfer  openings.  Ducts  and  air  transfer
openings  are  required  to  be protected with a minimum Class II, 250°F
(121°C) smoke damper complying with the New York City Building Code.
  513.6  Pressurization  method.  The  primary   mechanical   means   of
controlling   smoke  shall  be  by  pressure  differences  across  smoke
barriers.  Maintenance of a tenable environment is not required  in  the
smoke control zone of fire origin.
  513.6.1  Minimum  pressure difference. The minimum pressure difference
across a smoke barrier shall be 0.05-inch water Gage (12.4 Pa) in  fully
sprinklered buildings.
  In  buildings  permitted to be other than fully sprinklered, the smoke
control system shall be designed  to  achieve  pressure  differences  at
least  two  times the maximum calculated pressure difference produced by
the design fire.
  513.6.2  Maximum  pressure  difference.  The  maximum   air   pressure
difference  across  a  smoke  barrier  shall  be  determined by required
door-opening or closing forces. The actual force required to  open  exit
doors  when  the  system  is  in  the  smoke  control  mode  shall be in
accordance with the New York City Building  Code.  Opening  and  closing
forces  for  other  doors  shall  be  determined by standard engineering
methods for the resolution of forces and reactions. The calculated force
to set a side-hinged, swinging door in motion shall be determined by:

  F = F[dc]+K(WA/\P)/2(W-d)                     (Equation 5-2)
  where:
  A = Door area, square feet (m{2}).
  d = Distance from door handle to latch edge of door, feet (m).
  F = total door opening force, pounds (N).
  F[dc] = Force required to overcome closing device, pounds (N).
  K = Coefficient 5.2 (1.0).
  W = Door width, feet (m).
  /\P = Design pressure difference, inches (Pa) water gauge.

  513.7 Airflow design method. When approved by the commissioner,  smoke
migration  through  openings fixed in a permanently open position, which
are located between smoke control  zones  by  the  use  of  the  airflow
method,  shall  be permitted. The design airflows shall be in accordance
with  this  section. Air-flow shall be directed to limit smoke migration
from the fire zone. The geometry of  openings  shall  be  considered  to
prevent flow reversal from turbulent effects.
  513.7.1 Velocity. The minimum average velocity through a fixed opening
shall not be less than:

  v = 217.2 [h(T[f]-T[o])/T[f]+460)]{1/2}              (Equation 5-3)
  For SI: v = 119.9 [h(T[f]-T[o])/T[f]]{1/2}
  where:
  H = Height of opening, feet (m).
  T[f] = Temperature of smoke, °F (K).
  T[o] = Temperature of ambient air, °F (K).
  v = Air velocity, feet per minute (m/minute).

  513.7.2 Prohibited conditions. This method shall not be employed where
either the quantity of air or the velocity of the airflow will adversely
affect  other portions of the smoke control system, unduly intensify the
dire, disrupt plume dynamics or interfere with exiting. In no case shall
airflow toward the fire exceed 200 feet per minute (1.02 m/s). Where the
formula in Section 513.7.1 requires airflow to exceed  this  limit,  the
airflow method shall not be used.
  513.8  Exhaust  method.  When approved by the commissioner, mechanical
smoke control for large enclosed volumes, such as  in  atria  or  malls,
shall  be  permitted  to  utilize the exhaust method. The design exhaust
volumes shall be in accordance with this section.
  513.8.1 Exhaust rate. The height of the lowest horizontal  surface  of
the  accumulating smoke layer shall be maintained at least 10 feet (3048
mm) above any walking surface which forms a portion of a required egress
system within the smoke zone. The required exhaust  rate  for  the  zone
shall  be  the  largest  of the calculated plume mass flow rates for the
possible plume configurations. Provisions shall be made for  natural  or
mechanical supply of outside air from outside or adjacent smoke zones to
make  up  for  the air exhausted. Makeup airflow rates, when measured at
the potential fire location, shall not exceed 200 feet per minute  (1.02
m/s)  toward  the  fire. The temperature of the makeup air shall be such
that it does not expose  temperature-sensitive  fire-protection  systems
beyond their limits.
  513.8.2  Axisymmetric  plumes.  The  plume  mass  flow rate (m[p]), in
pounds per second (kg/s), shall be determined by placing the design fire
center on the axis of the  space  being  analyzed.  The  limiting  flame
height shall be determined by:

  z[l] = 0.533Q[c]{2/5}                               (Equation 5-4)
  For SI; z[l] = 0.166Q[c]{2/5}
  where:
  M[p] = Plume mass flow rate, pounds per second (kg/s).
  Q = Total heat output.
  Q[c] = Convective heat output, British thermal units per second (kW).
         (The value of Q[c] shall not be taken as less than 0.70Q).
  z = Height from top of fuel surface to bottom of smoke layer, feet (m).
  z[l] = Limiting flame height, feet (m). The z[l] value must be greater
         than the fuel equivalent diameter (see Section 513.9).
  for z > z[l]
  m[p] = 0.022Q[c]{1/3}[z]{5/3}+0.0042Q[c]

  For SI: m[p] = 0.071Q[c]{1/3}z{5/3}+0.0018Q[c]
  for z = z[l]
  M[p} = 0.011 Q[c]
  For SI: m[p] = 0.035Q[c]
  for z l]
  M[p] = 0.0208Q[c]{3/5}z
  For SI: m[p] = 0.032Q[c]{3/5}z
    To convert m[p] from pounds per seccond of mass flow to a volumetric
    rate, the following formula shall be used:
  V = 60m[p]/p                                      (Equation 5-5)
  where:
  V = Volumetric flow rate, cubic feet per minute (m{3}/s).
  R = Density of air at the temperature of the smoke layer, pounds per
      cubic feet (T: in °F)[kg/m{3}(T: in °C)]

  513.8.3  Balcony  spill  plumes.  The  plume mass flow rate (m[p]) for
spill plumes shall be determined using the geometrically probable  width
based  on  architectural  elements  and  projections  in  the  following
formula:

  M[p] = 0.124(QW{2}){1/3}(z[b]+0.25H)                (Equation 5-6)
  For SI: m]p] = 0.36(QW[2}){1/3}(z[b]+0.25H)
  where:
  H = Height above fire to underside of balcony, feet (m).
  M[p] = Plume mass flow rate, pounds pwer second (kg/s).
  Q = Total heat output.
  W = Plume width at point of spill, feet (m).

  513.8.4 Window plumes. The  plume  mass  flow  rate  (m[p])  shall  be
determined from:

m[p] = 0.077(A[w]H[w]{1/2})[1/3(z[w]+a){5/3}+0.18A[w]H[w]{1/2}
                                                      (Equation 5-7)
  For SI: m[p] = 0.68(A[w]H[w]}1/2})(z[w]+a){5/3}+1.5A[w]H[w]{1/2}
  where:
  A[w] = Area of the opening, square feet (m[2]).
  H[w] = Height of the opening, feet (m).
  M[p] = Plume mass flow rate, pounds per second (kg/s).
  Z[w]  =  Height from the top of the window or opening to the bottom of
the smoke layer, feet (m).
  a = 2.4A[w]{2/5}H[w]1/5-2.1H[w]

513.8.5 Plume contact with walls. When a plume contacts one or  more  of
the  surrounding  walls,  the  mass  flow rate shall be adjusted for the
reduced entrainment resulting from the contact provided that the contact
remains constant. Use of this  provision  requires  calculation  of  the
plume diameter, that shall be calculated by:

  d = 0.48 [(T[c]+460)/(T[a]+460)]{1/2}z              (Equation 5-8)
  For SI: d = 0.48(T[c]/T[a]){1/2}z
  where:
  d = Plume diameter, feet (m).
  T[a] = Ambient air temperature, °F (°K).
  T[c] = Plume centerline temperature, °F (°K)
       = 0.6 (T[a]+460)Q[c]{2/3}Z{-5/3}+T[a]
  z = Height at which T[c] is determined, feet (m).
  For SI: T[c] = 0.08 T[a]Q[c]{2/3}Z{-5/3}+T[a]

  513.9  Design  fire. The design fire shall be based on a Q of not less
than 5,000 Btu per second  (5275  kW)  unless  a  rational  analysis  is
performed  by  the  registered  design  professional and approved by the
commissioner. The  design  fire  shall  be  based  on  the  analysis  in
accordance with Section 513.4 and this section.
  513.9.1 Factors considered. The engineering analysis shall include the
characteristics  of  the  fuel, fuel load, effects included by the fire,
and whether the fire is likely to be steady or unsteady.
  513.9.2 Separation distance. Determination of the  design  fire  shall
include   consideration   of   the   type  of  fuel,  fuel  spacing  and
configuration.  The  ratio  of  the  separation  distance  to  the  fuel
equivalent  radius  shall not be less than 4. The fuel equivalent radius
shall be the radius of a circle of equal area to floor area of the  fuel
package.  The  design  fire shall be increased if other combustibles are
within the separation distance as determined by:

  R = [Q/(12piq{"})]{1/2}                            (Equation 5-9)
  where:
  Q{"} = Incident radiant heat flux required for nonpiloted ignition,
          Btu/ft{2} x s (W/m{2}).
  Q = Heat release from fire, Btu/s (kW).
  R = Separation distance from target to center of fuel package, feet
      (m).

  513.9.3 Heat-release assumptions. The analysis shall make use  of  the
best  available  data  from  approved sources and shall  not be based on
excessively stringent limitations of combustible material.
  513.9.4 Sprinkler effectiveness assumptions. A documented  engineering
analysis  shall  be  provided  for conditions that assume fire growth is
halted at the time of sprinkler activation.
  513.10 Equipment. Equipment such as, but not limited to, fans,  ducts,
automatic  dampers  and  balance  dampers  shall  be  suitable for their
intended use, suitable for the probable exposure temperatures  that  the
rational analysis indicates, and as approved by the commissioner.
  513.10.1  Exhaust  fans. Components of exhaust fans shall be rated and
certified by the manufacturer for the probable temperature rise to which
the components will be exposed. This temperature rise shall be  computed
by:

  T[s] = (Q[c],c)+(T[a])                          (Equation 5-10)
  where:
  C = Specific heat of smoke at smoke-layer temperature, Btu/lb°F
      (kJ/kg x K).
  m = Exhaust rate, pounds per second (kg/s).
  Q[c] = Convective heat output of fire, Btu/s (kW).
  T[a] = Ambient temperature, °F (K).
  T[s] = Smoke temperature, °F (K).
  Exception: Reduced T[s] as calculated based on the assurance of
  adequate dilution air.

  513.10.2  Ducts.  Duct  materials  and  joints  shall  be  capable  of
withstanding the probable temperatures and pressures to which  they  are
exposed  as  determined in accordance with Section 513.10.1. Ducts shall
be constructed and supported in accordance with Chapter 6.  Ducts  shall
be  leak  tested  to  1.5 times the maximum design operating pressure in
accordance with nationally accepted practices.  Measured  leakage  shall
not  exceed 5 percent of design flow. Results of such testing shall be a
part of the documentation procedure. Ducts shall be  supported  directly

from  fire-resistance-rated  structural  elements  of  the  building  by
substantial, noncombustible supports.
  Exception:   Flexible   connections,  for  the  purpose  of  vibration
isolation,  that  are  constructed  of  approved   fire-resistance-rated
materials.
  513.10.3  Equipment, inlets and outlets. Equipment shall be located so
as to not expose uninvolved portions of the building  to  an  additional
fire  hazard.  Outdoor air inlets shall be located so as to minimize the
potential for introducing smoke or  flame  into  the  building.  Exhaust
outlets  shall be so located as to minimize reintroduction of smoke into
the building and to limit exposure of the building or adjacent buildings
to an additional fire hazard.
  513.10.4 Automatic  dampers.  Automatic  dampers,  regardless  of  the
purpose  for  which  they are installed within the smoke control system,
shall be listed and conform to the requirements of  approved  recognized
standards.
  513.10.5  Fans.  In  addition  to other requirements, belt-driven fans
shall have 1.5 times the number of belts required for  the  design  duty
with  the  minimum number of belts being two. Fans shall be selected for
stable performance based on normal temperature  and,  where  applicable,
elevated  temperature.  Calculations and manufacturer's fan curves shall
be part of the documentation procedures. Fans  shall  be  supported  and
restrained  by  noncombustible devices in accordance with the structural
design requirements of the New York City Building Code.  Motors  driving
fans   shall   not   be  operating  beyond  their  nameplate  horsepower
(kilowatts) as determined  from  measurement  of  actual  current  draw.
Motors driving fans shall have a minimum service factor of 1.15.
  513.11  Power systems. The smoke control system shall be supplied with
two sources of power. Primary power shall be the normal  building  power
systems.  Secondary  power  shall  be  from an approved emergency source
complying with the New York City Electrical Code.  The  emergency  power
source  and  its  transfer switches shall be in a separate room from the
normal power transformers and switch gear and shall  be  enclosed  in  a
room  constructed  of  not  less  than 1-hour fire-resistance-rated fire
barriers,  ventilated  directly  to  and  from   the   exterior.   Power
distribution  from  the  two  sources  shall  be  by independent routes.
Transfer to full emergency  power  shall  be  automatic  and  within  60
seconds  of  failure of the primary power. The systems shall comply with
the New York City Electrical Code.
  513.11.1 Power  sources  and  power  surges.  Elements  of  the  smoke
management  system  relying  on  volatile  memories or the like shall be
supplies  with  integral  interruptible  power  sources  of   sufficient
duration  to  span 15-minute primary power interruption. Elements of the
Smoke management system susceptible to power surges  shall  be  suitably
protected by conditioners, suppressors or other approved means.
  513.12 Detection and control systems. Fire detection systems providing
control  input  or output signals to mechanical smoke control systems or
elements thereof shall comply wit the requirements of Chapter 9  of  the
New  York  City  Building  Code.  Such  systems shall be equipped with a
control  unit  complying  with  UL  864  and  listed  as  smoke  control
equipment.
  513.12.1  Wiring.  In  addition to meeting the requirements of the New
York City Electrical Code, all wiring, regardless of voltage,  shall  be
fully enclosed within continuous raceways.
  513.12.2  Activation.  Smoke  control  systems  shall  be activated in
accordance with the New York City Building Code.
  513.12.3 Automatic control.  Where  completely  automatic  control  is
required  or  used,  the  automatic control sequences shall be initiated

from an appropriately zoned automatic sprinkler  system  complying  with
Chapter  9  of  the  New York City Building Code or from manual controls
that are readily accessible  to  the  Fire  Department,  and  any  smoke
detectors required by engineering analysis.
  513.13  Control-air  tubing. Control-air tubing shall be of sufficient
size to meet the required response times. Tubing shall be flushed  clean
and dry prior to final connections. Tubing shall be adequately supported
and  protected  from  damage. Tubing passing through concrete or masonry
shall be sleeved and protected from abrasion and electrolytic action.
  513.13.1 Materials. Control-air tubing  shall  be  hard-drawn  copper,
Type  L,  ACR  in  accordance with ASTM B 42, ASTM B 43, ASTM B 68, ASTM
B88, ASTM B 251 and ASTM 280. Fittings shall be wrought copper or brass,
solder type in accordance with ASME B 16.18 or ASME B 16.22. Changes  in
direction   shall   be   made   with   appropriate   tool  bends.  Brass
compression-type fittings shall be used at final connection to  devices;
other  joints  shall  be  brazed using a BCuP5 brazing alloy with solids
above 1, 100 °F (593°C) and liquids below 1,500°F (816°C). Brazing  flux
shall be used on copper-to-brass joints only.
  Exception:  Nonmetallic  tubing  used within control panels and at the
final connection to devices provided all of the following conditions are
met:
  1. Tubing shall be listed by an approved agency for  flame  and  smoke
characteristics.
  2.  Tubing  and connected device shall be completely enclosed within a
galvanized or paint-grade steel enclosure of not less  than  0.030  inch
(0.76  mm)  (No.  22  galvanized  sheet  Gage)  thickness.  Entry to the
enclosure shall be  by  copper  tubing  with  a  protective  grommet  of
neoprene  or  teflon  or  by  suitable  brass compression to male barbed
adapter.
  3. Tubing shall be identified by appropriately documented coding.
  4. Tubing shall be neatly tied and  supported  within  the  enclosure.
Tubing  bridging  cabinets  and  doors  or  moveable devices shall be of
sufficient length to avoid tension and excessive stress. Tubing shall be
protected against abrasion. Tubing serving devices  on  doors  shall  be
fastened along hinges.
  513.13.2  Isolation from other functions. Control tubing serving other
than smoke control functions shall be isolated  by  automatic  isolation
valves or shall be an independent system.
  513.13.3 Testing. Test control-air tubing at three times the operating
pressure  for  not  less  than 30 minutes without any noticeable loss in
gauge pressure prior to final connection to devices.
  513.14 Marking and identification. The detection and  control  systems
shall be clearly marked at all junctions, accesses and terminations.
  513.15  Control diagrams. Identical control diagrams shall be provided
and maintained as required by the New York City Fire Code.
  513.16 Fire fighter's smoke control  panel.  A  fire  fighter's  smoke
control panel for Fire Department emergency response purposes only shall
be provided in accordance with the New York City Fire Code.
  513.17  System  response  time.  Smoke control system activation shall
comply with the New York City Fire Code.
  513.18  Acceptance  testing.  Devices,   equipment,   components   and
sequences shall be tested in accordance with New York City Fire Code.
  513.19 System acceptance. Acceptance of the smoke control system shall
be in accordance with the New York City Fire Code.
  513.20  Underground  building  smoke exhaust system. Where required by
the New York City Building  Code  for  underground  buildings,  a  smoke
exhaust system shall be provided in accordance with this section.

  513.20.1  Exhaust capability. Where compartmentation is required, each
compartment shall have an independent smoke exhaust  system  capable  of
manual  operation. The system shall have an air supply and smoke exhaust
capability that will provide a minimum of six air changes per hour.
  513.20.2  Operation.  The  smoke  exhaust  system shall be operated in
accordance with Section 909 of the New York City Building Code.
  513.20.3 Alarm required. Activation of the smoke exhaust system  shall
activate   an  audible  alarm  at  a  constantly  attended  location  in
accordance with the New York City Fire Code.
                              SECTION MC 514
                   ENERGY RECOVERY VENTILATION SYSTEMS
  514.1 General. Energy recovery ventilation systems shall be  installed
in  accordance  with this section. Where required for purposes of energy
conservation, energy recovery ventilation systems shall also comply with
the New York City Energy Conservation Code.
  514.2 Prohibited applications.  Energy  recovery  ventilation  systems
shall not be used in the following systems, unless specifically designed
and/or listed for the specific applications and as part of an engineered
system.
  1. Hazardous exhaust systems covered in Section 510.
  2.  Dust,  stock and refuse systems that convey explosive or flammable
vapors, fumes or dust covered in Section 511.
  3. Smoke control systems covered in Section 513.
  4. Commercial kitchen exhaust systems serving Type I and Type II hoods
covered in Section 506.
  5. Clothes dryer exhaust systems covered in Section 504.
  514.3 Access. A  means  of  access  shall  be  provided  to  the  heat
exchanger  and  other  components of the system as required for service,
maintenance, repair or replacement.
                             SECTION MC 515
                      POST-FIRE SMOKE PURGE SYSTEMS
  515.1 General. Post-fire smoke purge  systems  shall  be  provided  as
required by Chapter 9 of the New York City Building Code.
                                CHAPTER 6
                              DUCT SYSTEMS

                             SECTION MC 601
                                 GENERAL
601.1   Scope.   Duct   systems   used   for  the  movement  of  air  in
air-conditioning, heating, ventilating and exhaust systems shall conform
to the provisions of this  chapter  except  as  otherwise  specified  in
Chapters 5 and 7.
  Exception:  Ducts  discharging  combustible material directly into any
combustion chamber shall conform to the requirements of NFPA 82.
  601.2 Air movement in corridors. Corridors shall  not  be  used  as  a
portion  of  direct  supply,  return,  or  exhaust  air  system  serving
adjoining areas.   Air transfer opening(s) shall  not  be  permitted  in
walls or in doors separating public corridors from adjoining areas.
  Exceptions:
  1  Where  located  within  dwelling  units,  the  use of corridors for
conveying return air shall not be prohibited.
  2. Where located within tenant spaces of 1.000 square feet  (93  m{2})
or  less  in  area, utilization of corridors for conveying return air is
permitted.
  3. Corridors in Group B office buildings equipped throughout  with  an
automatic  sprinkler  system in accordance with Section 903.3.1.1 of the
New York City Building Code.

  4. Air transfer  openings  serving  toilet  rooms,  bathrooms,  shower
rooms,  sink  closets,  and  similar  auxiliary  spaces opening onto the
public corridor.
  5.  Group  1-3  detention  and  correctional occupancies with corridor
separations  of  open  construction  (e.g.  grating  doors  or   grating
partitions).
  6.  Air transfer in openings because of pressure differential in Group
1-2 health care occupancies from corridors is permitted.
  7. Where door clearances do not exceed those specified for fire  doors
in  the  New  York  City  Building Code, air transfer caused by pressure
differentials shall be permitted.
  8. Use of egress corridors as  part  of  an  engineered  smoke-control
system is permitted.
  601.2.1  Corridor  ceiling.  Use  of  the  space  between the corridor
ceiling and the floor or roof structure above as a return air plenum  is
permitted for one or more of the following conditions:
  1.  The  corridor  is  not  required  to  be  of fire-resistance-rated
construction;
  2. The corridor is separated from the plenum by  fire-resistance-rated
construction;
  3.  The  air-handling  system  serving  the corridor is shut down upon
activation of the air-handling unit smoke  detectors  required  by  this
code;
  4.  The  air-handling  system  serving  the corridor is shut down upon
detection  of  sprinkler  waterflow  where  the  building  is   equipped
throughout with an automatic sprinkler system; or
  5.  The  space  between  the  corridor  ceiling  and the floor or roof
structure above the corridor is used  as  a  component  of  an  approved
engineered smoke control system.
  601.3 Contamination prevention. Exhaust ducts under positive pressure,
chimneys,  and  vents  shall  not  extend  into or pass through ducts or
plenums.
                             SECTION MC 602
                                 PLENUMS
602.1 General. Supply,  return,  exhaust,  relief  and  ventilation  air
plenums  shall  be  limited  to  uninhabited crawl spaces, areas above a
finished ceiling, or  below  the  finished  floor,  attic  spaces    and
mechanical  equipment  rooms. Plenums shall be limited to one fire area.
Fuel-fired appliances shall not be installed within a plenum.
  602.2  Construction.  Plenum  enclosures  shall  be   constructed   of
materials  permitted  for the type of construction classification of the
building.  The temperature of air delivered to or through these  plenums
shall not exceed  250°F  (121°C),  except  where  used  as  part  of  an
engineered smoke control system.
  The  use  of gypsum boards to form plenums shall be limited to systems
where the air temperatures do not exceed 125°F (52°C) and  the  building
and  mechanical  system design conditions are such that the gypsum board
surface temperature will be maintained above the  air  stream  dew-point
temperature.   Air   plenums  formed  by  gypsum  boards  shall  not  be
incorporated in air-handling systems utilizing evaporative coolers.
  602.2.1 Materials  exposed  within  plenums.  Except  as  required  by
Sections  602.2.1.1  through 602.2.1.5, materials exposed within plenums
shall be noncombustible or shall have a flame spread index of  not  more
than  25  and a smoke-developed index of not more than 50 when tested in
accordance with ASTM E 84.
  Exceptions:
  1. Rigid and flexible ducts and connectors shall  conform  to  Section
603.

  2.  Duct  coverings,  linings,  tape  and  connectors shall conform to
Sections 603 and 604.
  3. This section shall not apply to materials exposed within plenums in
one- and two-family dwellings.
  4. This section shall not apply to smoke detectors.
  5.  Combustible materials enclosed in approved gypsum board assemblies
or enclosed in materials listed and labeled for such application.
  602.2.1.1 Wiring. Combustible electrical or electronic wiring  methods
and  materials,  optical  fiber cable, and optical fiber raceway exposed
within a plenum shall have a peak optical density not greater than 0.50,
an average optical density not greater than 0.15, and a flame spread not
greater than 5 feet (1524 mm) when tested in accordance with  NFPA  262.
Only type OFNP (plenum rated nonconductive optical fiber cable) shall be
installed  in  plenum-  rated optical fiber raceways. Wiring, cable, and
raceways addressed in this section shall be listed and labeled as plenum
rated and shall be installed in accordance with New York City Electrical
Code.
  602.2.1.2 Fire sprinkler piping. Plastic fire sprinkler piping exposed
within a plenum shall be used only in wet pipe systems and shall have  a
peak  optical  density not greater than 0.50, an average optical density
not greater than 0.15, and a flame spread of not  greater  than  5  feet
(1524 mm) when tested in accordance with UL 1887. Piping shall be listed
and labeled.
  602.2.1.3  Pneumatic  tubing.  Combustible  pneumatic  tubing  exposed
within a plenum shall have a peak optical density not greater than 0.50,
an average optical density not greater than 0.15, and a flame spread  of
not  greater  than  5  feet  (1524 mm) when tested in accordance with UL
1820.  Combustible pneumatic tubing shall be listed and labeled.
  602.2.1.4 Combustible  electrical  equipment.  Combustible  electrical
equipment exposed within a plenum shall have a peak rate of heat release
not  greater than 100 kilowatts, a peak optical density not greater than
0.50 and an average optical density not greater than 0.15 when tested in
accordance with UL  2043.  Combustible  electrical  equipment  shall  be
listed and labeled.
  602.2.1.5  Foam  plastic  insulation.  Foam plastic insulation used as
wall or ceiling finish in plenums shall exhibit a flame spread index  of
75  or  less  and  a smoke developed index of 450 or less when tested in
accordance  with  ASTM  E  84  and  shall  also  comply   with   Section
602.2.1.5.1, 602.2.1.5.2 or 602.2.1.5.3.
  602.2.1.5.1  Separation required. The foam plastic insulation shall be
separated from the plenum by a thermal barrier  complying  with  Section
2603.4 of the New York City Building Code.
  602.2.1.5.2  Approval.  The  foam plastic insulation shall be approved
based on tests conducted in accordance with Section 2603.8  of  the  New
York City Building Code.
  602.2.1.5.3  Covering. The foam plastic insulation shall be covered by
corrosion-resistant steel having a base metal thickness of not less than
0.0160 inch (0.4 mm).
  602.3 Stud cavity and joist space plenums. Stud wall cavities and  the
spaces  between  solid  floor joists to be utilized as air plenums shall
comply with the following conditions:
  1. Such cavities or spaces shall not  be  utilized  as  a  plenum  for
supply air.
  2.   Such  cavities  or  spaces  shall  not  be  part  of  a  required
fire-resistance-rated assembly.
  3. Stud wall cavities shall not convey air from more  than  one  floor
level.

  4.  Stud  wall  cavities and joist space plenums shall comply with the
floor penetration protection requirements of the New York City  Building
Code.
  5.  Stud  wall cavities and joist space plenums shall be isolated from
adjacent concealed spaces by approved fireblocking as  required  in  the
New York City Building Code.
  602.4  Flood  hazard. For structures located in areas of special flood
hazard, plenum spaces shall comply with Appendix G of the New York  City
Building Code.
  602.5 Fire-stopping. Where required by the New York City Building Code
through penetrations shall be firestopped in accordance with Section 712
of the New York City Building Code.
  602.6  Materials. Materials used in the construction of a plenum shall
be suitable for continuous exposure  to  the  temperature  and  humidity
conditions of the environmental air in the plenum.
                             SECTION MC 603
                   DUCT CONSTRUCTION AND INSTALLATION
603.1  General.  An  air  distribution  system  shall  be  designed  and
installed to supply the required distribution of air.  The  installation
of  an  air  distribution  system  shall  not affect the fire protection
requirements specified in the New York City Building Code.  Ducts  shall
be  constructed.  braced, reinforced and installed to provide structural
strength and durability.
  603.2 Duct sizing. Ducts installed within a single dwelling unit shall
be sized in accordance with ACCA Manual D  or  other  approved  methods.
Ducts  installed within all other buildings shall be sized in accordance
with the ASHRAE Handbook of Fundamentals or other equivalent computation
procedure.
  603.3 Duct classification. Ducts shall  be  classified  based  on  the
maximum  operating  pressure  of  the  duct  at pressures of positive or
negative 0.5, 1.0, 2.0, 3.0, 4.0, 6.0 or 10.0 inches  of  water  column.
The  pressure  classification  of ducts shall equal or exceed the design
pressure of the air distribution in which the ducts are utilized.
  603.4 Metallic ducts. All  metallic  ducts  shall  be  constructed  as
specified  in  the  SMACNA  HVAC  Duct  Construction Standards Metal and
Flexible.
  Exception: Ducts installed within single dwelling units shall  have  a
minimum thickness as specified in Table 603.4.
                               TABLE 603.4
                  DUCT CONSTRUCTION MINIMUM SHEET METAL
                  THICKNESSES FOR SINGLE DWELLING UNITS
     ------------------------------------------------------------
                                |     GALVANIZED     |
                                |Minimum  |Equivalent|APPROXIMATE
                                |thickness|Galvanized| ALUMINUM
           DUCT SIZE            |(inches) |Gage No.  | B GAGE
     ------------------------------------------------------------
      Round ducts and enclosed  |         |          |
      Rectangular ducts         |         |          |
        14" or less             |  0.013  |    30    |    26
        Over 14"                |  0.016  |    28    |    24
     ------------------------------------------------------------
      Exposed rectangular ducts |         |          |
        14" or less             |  0.016  |    28    |    24
        Over 14"                |  0.019  |    26    |    22
     ------------------------------------------------------------
      For SI: 1 inch = 23.4 mm

  603.5  Nonmetallic  ducts. Nonmetallic ducts shall be constructed with
Class 0 or Class 1 duct material in accordance with UT 181. Fibrous duct
construction shall conform to the SMACNA Fibrous Glass Duct Construction
Standards or  NALMA  Fibrous  Glass  Duct  Construction  Standards.  The
maximum  air temperature within nonmetallic ducts shall not exceed 250°F
(121°C).
  603.6 Air ducts and air  connectors.  Air  ducts.  both  metallic  and
nonmetallic,  shall  comply  with  Sections  603.6.1  and 603.6.1.1. Air
connectors, both metallic and nonmetallic, shall  comply  with  Sections
606.6.2 and 603.6.3.
  603.6.1  Air  ducts.  Air  ducts  shall  be  permitted  to be rigid or
flexible and shall be constructed of materials that are  reinforced  and
sealed  to  satisfy the requirements for the use of the air duct system,
such as the supply air system, the return or exhaust  air  systems,  and
the variable volume/pressure air system.
  603.6.1.1  Materials.  All  air  duct  materials shall be suitable for
continuous exposure to the temperature and humidity  conditions  of  the
environmental air in the air duct. Air ducts shall be constructed of any
of the following materials:
  1. Iron, steel, aluminum, copper, concrete, masonry, or clay tile.
  2. Class 0 or Class 1 rigid or flexible air ducts tested in accordance
with  UL  181  and  installed  in conformance with the conditions of the
listing.
  Exceptions:
  1. Class 0 or Class 1 rigid or flexible air duct shall not be used  as
a vertical air duct that is more than two stories in height.
  2.  Class  0  or Class 1 rigid or flexible air ducts shall not be used
for air ducts containing air at temperatures in excess of 250°F (121°C)
  3. Where the temperature of the conveyed air  does  not  exceed  125°F
(52°C)  in normal service, negative pressure exhaust or return air ducts
shall be permitted to be constructed of gypsum board  having  a  maximum
flame   spread   index/rating   of  25  without  evidence  of  continued
progressive combustion and a maximum smoke developed index/rating of 50.
Air ducts formed by gypsum  boards  shall  have  a  surface  temperature
maintained  above the air stream dew-point temperature, and shall not be
used in air-handling systems utilizing evaporative coolers.
  Exception: The maximum conveyed air temperature of 125°F (52°C)  shall
not  apply to gypsum board material used for emergency smoke exhaust air
ducts.
  603.6.1.2. Installation. The materials, thickness,  construction,  and
installation  of  ducts shall provide structural strength and durability
in conformance  with  recognized  good  practice.  Air  ducts  shall  be
considered  to  be in compliance with this requirement where constructed
and installed in accordance with the New York City Building Code.  Where
no  standard  exists  for  the  construction of air ducts, they shall be
constructed to withstand both the positive and negative pressures of the
system.
  603.6.2 Air Connectors. Air connectors are limited-use,  flexible  air
ducts that are required to conform to other provisions applicable to air
ducts and shall meet the following requirements:
  1.  Air  connectors  shall  conform to the requirements for Class 0 or
Class 1 connectors when tested and approved in accordance with UL 181.
  2. Class 0 or Class 1 air connectors  shall  not  be  used  for  ducts
containing air at temperatures in excess of 250°F (121°C).
  3. Air connector runs shall not exceed 14 feet (4267 mm) in length.
  4.  Air  connectors  shall not penetrate any rated wall, partition, or
shaft that is required to have a fire resistance rating  of  1  hour  or
more.

  5. Air connectors shall not pass through floors.
  603.6.3  Flexible  air  duct and air connector clearance. Flexible air
ducts and air connectors shall be installed with a minimum clearance  to
an  appliance  as specified in the appliance manufacturer's installation
instructions.
  603.7 Rigid duct penetrations.  Duct  system  penetrations  of  walls,
floors,  ceilings  and  roofs and air transfer openings in such building
components shall be protected as required by Section 607.
  603.8 Underground ducts.  Ducts  shall  be  approved  for  underground
installation.  Metallic  ducts not having an approved protective coating
shall be completely encased  in  a  minimum  of  2  inches  (51  mm)  of
concrete.
  603.8.1 Slope. Ducts shall slope to allow drainage to a point provided
with access.
  603.8.2  Sealing.  Ducts  shall be sealed and secured prior to pouring
the concrete encasement.
  603.8.3 Plastic ducts and fittings. Plastic ducts shall be constructed
of PVC having a minimum pipe stiffness of 8 psi (55  kPa)  at  5-percent
deflection  when  tested  in  accordance  with ASTM D 2412. Plastic duct
fittings  shall  be  constructed   of   either   PVC   or   high-density
polyethylene. Plastic duct and fittings shall be utilized in underground
installations only. The maximum design temperature for systems utilizing
plastic duct and fittings shall be 150`F (66°C).
  603.9  Joints,  seams and connections. All longitudinal and transverse
joints, seams and connections in metallic and nonmetallic ducts shall be
constructed   as   specified   in   SMACNA   HVAC   Duct    Construction
Standards-Metal  and Flexible and SMACNA Fibrous Glass Duct Construction
Standards or  NAIMA  Fibrous  Glass  Duct  Construction  Standards.  All
longitudinal  and  transverse  joints,  seams  and  connections shall be
sealed in accordance with the New York City Energy Conservation Code.
  603.10 Supports. Ducts shall be supported  with  approved  hangers  at
intervals  not  exceeding  10  feet  (3048 mm) or by other approved duct
support systems designed in accordance with the New York  City  Building
Code.  Flexible  and  other  factory-made  ducts  shall  be supported in
accordance with  the  manufacturer's  installation  instructions.  Ducts
shall not be hung from or supported by suspended ceilings.
  603.11 Furnace connections. Ducts connecting to a furnace shall have a
clearance  to combustibles in accordance with the furnace manufacturer's
installation instructions.
  603.11.1 Air duct at heat sources. Where heat sources from  electrical
equipment,  fossil  fuel-burning  equipment,  or solar energy collection
equipment are installed in air ducts, the installation shall  avoid  the
creation of a fire hazard. Air ducts rated as Class 1 in accordance with
UL  181,  air  duct  coverings,  and linings shall be interrupted at the
immediate area of operation of such heat sources in order  to  meet  the
clearances specified in the equipment listing.
  Exceptions:
  1.  Appliances  listed  for  zero  clearance  from  combustibles where
installed with the conditions of their listings.
  2. Insulation specifically suitable for the maximum  temperature  that
reasonably  can be anticipated on the duct surface shall be permitted to
be installed at the immediate area of operation of such appliances.
  603.12 Condensation. Provisions shall be made to prevent the formation
of condensation on the exterior of any duct.
  603.13 Flood hazard areas. For structures in areas  of  special  flood
hazard, ducts shall comply with Appendix G of the New York City Building
Code.

  603.14  Location.  Ducts  shall not be installed in or within 4 inches
(102 mm) of the earth, except  where  such  ducts  comply  with  Section
603.8.
  603.15  Mechanical protection. Ducts installed in locations where they
are exposed to mechanical damage by vehicles or from other causes  shall
be  protected  by approved vehicle barriers and required by the New York
City Building Code.
  603.16 Weather protection. All ducts including linings, coverings  and
vibration isolation connectors installed on the exterior of the building
shall be adequately protected against the elements.
  603.17  Registers,  grilles and diffusers. Duct registers, grilles and
diffusers shall be  installed  in  accordance  with  the  manufacturer's
installation  instructions.  Balancing  dampers or other means of supply
air adjustment shall  be  provided  in  the  branch  ducts  or  at  each
individual duct register, grille or diffuser.
  603.17.1  Floor  registers.  Floor  registers  shall  resist,  without
structural failure,  a  200-pound  (90.8  kg)  concentrated  load  on  a
2-inch-diameter  (51  mm)  disc applied to the most critical area of the
exposed face.
  603.18 Vibration Isolation Connectors. Vibration isolation  connectors
in  duct  systems shall be made of an approved flame-retardant fabric or
shall consist of sleeve joints with packing of approved  material,  each
having  a    maximum flame spread index/rating of 25 and a maximum smoke
developed rating of 50. The fabric shall have a  maximum  length  of  10
inches (254 mm) in the direction of air flow.
                             SECTION MC 604
                               INSULATION
  604.1  General.  Duct  insulation shall conform to the requirements of
Sections 604.2 through 604.13 and the New York City Energy  Conservation
Code.
  604.2   Surface   temperature.  Ducts  that  operate  at  temperatures
exceeding 120°F (49°C) shall have sufficient thermal insulation to limit
the exposed surface temperature to 120°F (49°C).
  604.3  Coverings  and  linings.  Coverings  and   linings,   including
adhesives  when  used,  shall have a flame spread index not more than 25
and a smoke-developed index not more than 50, when tested in  accordance
with  ASTM  E  84.  Duct  coverings  and  linings shall not flame, glow,
smolder or smoke when tested in  accordance  with  ASTM  C  411  at  the
temperature  to  which they are exposed in service. The test temperature
shall not fall below 250°F (121°C).
  604.4 Foam plastic insulation. Foam plastic used as duct coverings and
linings shall conform to the requirements of Section 604.
  604.5 Appliance insulation. Listed and  labeled  appliances  that  are
internally   insulated   shall   be  considered  as  conforming  to  the
requirements of Section 604.
  604.6 Penetration of assemblies. Duct coverings shall not penetrate  a
wall  or  floor required to have a fire-resistance rating or required to
be fireblocked.
  604.7 Identification. External duct insulation  and  factory-insulated
flexible  duct  shall  be legibly printed or identified at intervals not
greater than 36 inches (914 mm) with the name of the  manufacturer,  the
thermal  resistance R-value at the specified installed thickness and the
flame spread and smoke-developed indexes of the composite materials. All
duct insulation product R-values shall  be  based  on  insulation  only,
excluding air films, vapor retarders or other duct components, and shall
be  based  on  tested  C-values  at  75°F (24°C) mean temperature at the
installed thickness, in accordance with recognized industry  procedures.

The  installed  thickness  of  duct  insulation  used  to  determine its
R-values shall be determined as follows:
  1.  For  duct  board,  duct  liner  and  factory-made  rigid ducts not
normally subjected to compression, the normal insulation thickness shall
be used.
  2. For duct wrap, the installed thickness shall be assumed  to  be  75
percent (25-percent compression) of nominal thickness.
  3.  For factory-made flexible air ducts, the installed thickness shall
be determined by dividing the  difference  between  the  actual  outside
diameter and nominal inside diameter by two.
  604.8 Lining installation. Linings shall be interrupted at the area of
operation  of  a  fire  damper  and  at  a  minimum of 6 inches (152 mm)
upstream of and 6 inches (152 mm) downstream of electric-resistance  and
fuel-burning heaters in a duct system. Metal nosings or sleeves shall be
installed over exposed duct liner edges that face opposite the direction
of airflow.
  604.9  Thermal  continuity. Where a duct liner has been interrupted, a
duct covering of equal thermal performance shall be installed.
  604.10 Service openings. Service openings shall not  be  concealed  by
duct  coverings  unless  the  exact  location of the opening is properly
identified.
  604.11 Vapor retarders. Where ducts used for  cooling  are  externally
insulated,  the insulation shall be covered with a vapor retarder having
a maximum permeance of 0.05 perm [2.87 ng/(PA * s *  m{2}]  or  aluminum
foil having a minimum thickness of 2 mils (0.051 mm). Insulations having
a  permeance  of  0.05 perm [2.87 ng/(P * s* m{2})] or less shall not be
required to be covered. All joints and seams shall be sealed to maintain
the continuity of the vapor retarder.
  604.12  Weatherproof  barriers.  Insulated  exterior  ducts  shall  be
protected with an approved weatherproof barrier.
  604.13  Internal insulation. Materials used as internal insulation and
exposed to the airstream in ducts shall be  shown  to  be  durable  when
tested  in  accordance  with UL 181. Exposed internal insulation that is
not impermeable to water shall not be used to line ducts or plenums from
the exit of a cooling coil to the downstream end of the drain pan.
                             SECTION MC 605
                               AIR FILTERS
  605.1 General. Heating and air-conditioning  systems  of  the  central
type  shall  be  provided  with  approved  air filters. Filters shall be
installed in the return air system, upstream from any heat exchanger  or
coil,  in an approved convenient location. Liquid adhesive coatings used
on filters shall have a flash point not lower than 325°F (163°C).
  605.2 Standards. Media-type and electrostatic-type air  filters  shall
be  listed and labeled. Media-type air filters shall comply with UL 900.
High-efficiency particulate  air  filters  shall  comply  with  UL  586.
Electrostatic-type  air  filters  shall  comply with UL 867. Air filters
utilized within dwelling  units  shall  be  designed  for  the  intended
application and shall not be required to be listed and labeled.
  605.2.1  Standards  for  air-handling  units.  Air-handling  units  of
mechanical ventilation systems, any portion of which provide outdoor air
ventilation, shall be equipped  with  a  particulate  matter  filtration
system  in  accordance  with ASHRAE 62.1 or ASHRAE 62.2 and shall have a
minimum efficiency reporting value (MERV) of 11 or greater in accordance
with ASHRAE 52.2.
  Exceptions:
  1. This section shall not apply to  the  alteration  or  repair  of  a
mechanical  ventilation  system  that  was installed prior to January 1,

2013 unless such  alteration  or  repair  includes  the  replacement  or
addition of an air-handling unit in such system.
  2.  This section shall not apply to the replacement of an air handling
unit in a mechanical ventilation system installed prior  to  January  1,
2013  if  the  department determines that the design of such replacement
air-handling unit cannot be made to comply with the allowable fan system
power limitations of the New  York  City  Energy  Conservation  Code  or
ASHRAE 90.1.
  3. This section shall not apply to any air-handling unit with a design
capacity of less than 5,000 cfm.
  605.3  Airflow over the filter. Ducts shall be constructed to allow an
even distribution of air over the entire filter.
  605.4 Liquid adhesive tanks. Tanks for liquid  adhesives,  into  which
removable  filters  are  dipped,  shall  be  located  either outside the
building or, if such a location is not available,  in  a  separate  fire
resistive  room  and stored in accordance with NFPA 30. Such tanks shall
be metal, equipped with tight-fitting covers and shall be  kept  tightly
covered when not in actual use.
  605.5 Filter maintenance. All air filters shall be kept free of excess
dust  and combustible material. Unit filters shall be renewed or cleaned
when the resistance to airflow has increased to two times  the  original
resistance  or  when  the  resistance has reached a value of recommended
replacement by the manufacturer. A  permanently  installed  draft  gauge
shall  be  provided  for  this  purpose.  Where  the  filters are of the
automatic liquid adhesive type, sludge shall be removed from the  liquid
adhesive reservoir regularly.
                             SECTION MC 606
                     SMOKE DETECTION SYSTEMS CONTROL
  606.1  Controls  required.  Air distribution systems shall be equipped
with  smoke  detectors  listed  and  labeled  for  installation  in  air
distribution systems, as required by this section.
  606.2  Where  required.  Smoke  detectors  shall  be  installed  where
indicated in Sections 606.2.1 through 606.2.4.
  Exceptions:  Smoke  detectors  shall  not  be   required   where   air
distribution  systems  are  incapable  of  spreading  smoke  beyond  the
enclosing walls, floors and ceilings of the room or space in  which  the
smoke is generated.
  606.2.1  Return  air  systems.  Smoke  detectors shall be installed in
return air systems with a design capacity greater than  2,000  cfm  (0.9
m{3}/s),  in  the  return  air  duct  or plenum upstream of any filters,
exhaust air connections, outdoor  air  connections,  or  decontamination
equipment and appliances.
  Exception:  Smoke  detectors are not required in the return air system
where all portions of the building served by the air distribution system
are protected by area smoke detectors connected to a fire  alarm  system
in accordance with the New York City Fire Code. The area smoke detection
system shall comply with Section 606.4.
  606.2.2   Common   supply  and  return  air  systems.  Where  multiple
air-handling systems share common supply or return air ducts or  plenums
with a combined design capacity greater than 2,000 cfm (0.9 m{3}/s), the
return  air  system shall be provided with smoke detectors in accordance
with Section 606.2.1.
  Exception: Individual smoke detectors shall not be required  for  each
fan-powered  terminal  unit,  provided  that  such  units do not have an
individual design capacity greater than 2,000 cfm (0.9 m{3}/s) and  will
be shut down by activation of one of the following:
  1. Smoke detectors required by Sections 606.2.1 and 606.2.3.

  2.  An  approved  area smoke detector system located in the return air
plenum serving such units.
  3.  An  area  smoke  detector system as prescribed in the exception to
Section 606.2.1.
  In all cases, the smoke detectors shall comply with Sections 606.4 and
606.4.1.
  606.2.3 Return air risers. Where return air risers serve two  or  more
stories  and  serve  any  portion of a return air system having a design
capacity greater than 15,000 cfm (7.1 m{3}/s), smoke detectors shall  be
installed at each story. Such smoke detectors shall be located up stream
of  the  connection  between  the  return air riser and any air ducts or
plenums.
  606.2.4 Supply air systems. Smoke detectors  listed  for  use  in  air
distribution  systems  shall  be installed downstream of the air filters
and ahead of any branch connections  in  air  supply  systems  having  a
capacity greater than 2,000 cfm (0.9 m{3}/s).
  606.3 Installations. Smoke detectors required by this section shall be
installed  in  accordance  with  the  New York City Electrical Code. The
required smoke detectors  shall  be  installed  to  monitor  the  entire
airflow  conveyed  by  the  system  including supply air, return air and
exhaust or relief air. Access shall be provided to smoke  detectors  for
inspection and maintenance.
  606.4  Controls  operation. Upon activation, the smoke detectors shall
automatically shut down their respective air distribution system(s). Air
distribution systems that are part  of  a  smoke  control  system  shall
switch to the smoke control mode upon activation of a detector.
  606.4.1  Supervision. The duct smoke detectors shall be connected to a
fire alarm system. The actuation of a duct smoke detector shall activate
a visible and  audible  supervisory  signal  at  a  constantly  attended
location.
  Exceptions:
  1.  The  supervisory  signal  at a constantly attended location is not
required  where  the  duct  smoke  detector  activates  the   building's
alarm-indicating appliances.
  2.  In  occupancies  not  required  to  be  equipped with a fire alarm
system, actuation of either area or duct smoke detector shall activate a
visible and an audible signal in  an  approved  location.  Additionally,
duct  smoke  detector  trouble  conditions  shall  activate a visible or
audible signal in an approved location and shall be  identified  as  air
duct detector trouble.
  606.4.2  Fan  shutdown. When any building or floor is provided with an
air system utilizing recirculated air and is protected by  an  automatic
sprinkler  system or an automatic fire alarm system, provisions shall be
made to automatically stop the fans serving the affected area  when  the
sprinkler  system  or  fire  alarm  system are installed in the area, it
shall be required to have only one of these systems arranged to stop the
fans.
  Exceptions:
  1. Activation of a manual  pull  station  shall  not  be  required  to
automatically stop the fans.
  2.  Systems  having  a  capacity  of 2,000 cfm (0.2 m{3}/s) or less or
serving not more than one floor.
  606.4.3 Manual restart of fans after automatic fire  detecting  device
or  fire  alarm  system  shutdown.  Fans  or  fan system which have been
automatically shut down on activation of  an  automatic  dire  detecting
device  or fire alarm system shall be arranged and equipped so that they
do not automatically restart when either the  automatic  fire  detecting
device or fire alarm system is reset. The manual means of restarting the

fans  or  fan  system  shall  function  independently  from  the  manual
resetting of either the automatic fire detecting device  or  fire  alarm
system.
                             SECTION MC 607
                     DUCTS AND AIR TRANSFER OPENINGS
  607.1  General.  The  provisions  of  this  section  shall  govern the
protection  of  duct  penetrations  and   air   transfer   openings   in
fire-resistance-rated assemblies.
  607.1.1 Ducts and air transfer openings without dampers. Ducts and air
transfer  openings  that  penetrate fire-resistance-rated assemblies and
are not required to have dampers by this section shall comply  with  the
requirements of Section 712 of the New York City Building Code.
  607.2   Installation.   fire   dampers,   smoke  dampers,  combination
fire/smoke dampers and ceiling dampers located within  air  distribution
and  smoke  control  systems  shall  be installed in accordance with the
requirements  of  this  section,  and  the  manufacturer's  installation
instructions and listing.
  607.2.1  Smoke control system .Where the installation of a fire damper
will interfere with the operation of a required smoke control system  in
accordance  with  Section  513, approved alternative protection shall be
utilized.
  607.2.1.1 Remote operation. Combination fire and smoke  dampers  shall
be  operable  by remote controls where necessary for smoke removal. Such
dampers shall have provisions that allow them to re-close  automatically
upon  reaching  the  damper's  maximum  degradation  test temperature in
accordance with UL 555S.
  607.2.2 Hazardous exhaust ducts. Fire dampers  for  hazardous  exhaust
duct systems shall comply with Section 510.
  607.2.3  Supply  air  systems.  Smoke  dampers  listed  for use in air
distribution systems shall be installed both upstream and downstream  of
filters  and  ahead  of  any  branch  connections in supply air-handling
apparatus and systems having a capacity equal to or greater than  15,000
cfm (7.1 m{3}/s).
  Exceptions:
  1.  Where the air-handling unit is located on the floor that it serves
and serves only that floor.
  2. Where the air-handling unit is located on the roof and serves  only
the floor immediately below the roof.
  3.  Existing  buildings  using  only  UL  90D Class 1 filters shall be
exempt from this subdivision provided the control system is arranged  to
shut down the fresh air intake, return air, and exhaust air dampers, and
fan  shutdown and smoke detection is provided in accordance with Section
606.
  607.3 Damper testing and ratings. Dampers shall be listed and bear the
label of an approved  testing  agency  indicating  compliance  with  the
standards   in   this  section.  Fire  dampers  shall  comply  with  the
requirements of UL 555. Only fire dampers labeled  for  use  in  dynamic
systems  shall be installed in heating, ventilation and air-conditioning
systems designed to operate with fans on during a  fire.  Smoke  dampers
shall  comply  with  the requirements of UL 555S. Combination fire/smoke
dampers shall comply with the requirements of both UL 555 and  UL  555S.
Ceiling radiation dampers shall comply with the requirements of UL 555C.
  607.3.1  Fire  protection  rating. Fire dampers shall have the minimum
fire protection rating specified  in  Table  607.3.1  for  the  type  of
penetration.
                              TABLE 607.3.1
                           FIRE DAMPER RATING
          ---------------------------------------------

                                 |   MINIMUM DAMPER
           TYPE OF PENETRATION   |    RATING (hour)
          ---------------------------------------------
           Less than 3-hour      |
           fire-resistance-rated |       1 1/2
           assemblies            |
          ---------------------------------------------
           3-hour or greater     |
           fire-resistance-rated |         3
           assemblies            |
          ---------------------------------------------
  607.3.1.1  Fire  damper  actuating  device.  The fire damper actuating
device shall meet one of the following requirements:
  1. The operating temperature  shall  be  approximately  50°F  (27.8°C)
above  the  normal temperature within the duct system, but not less than
160°F (71°C).
  2. The operating temperature shall be  not  more  than  286°F  (141°C)
where located in a smoke control system complying with Section 513.
  3. Where a combination fire/smoke damper is located in a smoke control
system  complying  with  Section  513,  the operating temperature rating
shall be approximately 50°F (27.8°C) above  the  maximum  smoke  control
system designed operating temperature, or a maximum temperature of 350°F
(177°C).  The  temperature shall not exceed the UL 555S degradation test
temperature rating for a combination fire/smoke damper.
  607.3.2 Smoke damper ratings. Smoke damper leakage ratings  shall  not
be  less  than  Class II. Elevated temperature ratings shall be not less
than 250°F (121°C).
  607.3.2.1 Smoke damper actuation methods. The smoke damper shall close
upon actuation of a listed smoke  detector  or  detectors  installed  in
accordance  with Section 606 of this code and Sections 907.10 and 907.11
of the New York City Building code and one of the following methods,  as
applicable:
  1.  Where  a damper is installed within a duct, a smoke detector shall
be installed in the duct within 5 feet (1524 mm) of the damper  with  no
air  outlets or inlets between the detector and the damper. The detector
shall  be  listed  for  the  air  velocity,  temperature  and   humidity
anticipated at the point where it is installed. Other than in mechanical
smoke  control  systems, dampers shall be closed upon fan shutdown where
local smoke detectors require a minimum velocity to operate.
  2. Where a damper is installed above smoke barrier doors  in  a  smoke
barrier,  a  spot-type  detector  listed  for releasing service shall be
installed on either side of the smoke barrier door opening.
  3. Where a damper is installed within an inducted opening in a wall, a
spot-type detector listed  for  releasing  service  shall  be  installed
within 5 feet (1524 mm) horizontally of the damper.
  4. Where a damper is installed in a corridor wall, the damper shall be
permitted  to be controlled by a smoke detection system installed in the
corridor.
  5. Where a total-coverage smoke detector  system  is  provided  within
areas  served  by  an  HVAC  system,  dampers  shall  be permitted to be
controlled by the smoke detection system.
  6. Smoke dampers that are part of an engineered smoke  control  system
shall  be  capable  of being positioned manually from a command station.
Such positioning devices shall be provided for supply and return/exhaust
dampers grouped by floor and by  type.  Damper  switch  positions  shall
indicate  whether the related dampers are commanded to be either open or
closed. Smoke damper positioning switches shall be located at  the  Fire

Command  Station, or in a Mechanical Control Center in buildings without
a Fire Command Station.
  607.4  Access  and  identification.  Fore  and  smoke dampers shall be
provided with an approved  means  of  access,  large  enough  to  permit
inspection  and  maintenance  of the damper and its operating parts. The
access  shall  not  affect  the   integrity   of   fire-resistance-rated
assemblies.  The  access  openings  shall not reduce the fire-resistance
rating of the assembly. Access points shall be permanently identified on
the exterior by a label having letters not less than 0.5  inch  (12.7mm)
in  height  reading:  SMOKE  DAMPER  or  FIRE  DAMPER,  followed  by  an
identification marking that is unique to  the  damper  accessed.  Access
doors  in ducts hall be tight fitting and suitable for the required duct
construction.
  607.5  Where  required.  Fire  dampers,  smoke  dampers,   combination
fire/smoke  dampers  and  ceiling radiation dampers shall be provided at
the locations prescribed in this section. Where an assembly is  required
to  have  both  fire  dampers  and smoke dampers, combination fire/smoke
dampers or a fire damper and a smoke damper shall be required.
  Exceptions:
  1. Smoke dampers shall not be required on air systems other than where
necessary for the proper function of that system  where  the  system  is
designed specifically to:
  1.1.  Function  as  an  engineered smoke-control system, including the
provision of continuous air movement with the air-handling system; or
  1.2. Provide air  to  other  areas  of  the  building  during  a  fire
emergency; or
  1.3. Provide pressure differentials during a fire emergency.
  2.  Smoke  dampers  shall  not  be  required  to  be  located within a
prescribed distance of a fire  rated  enclosure  where  isolation  smoke
dampers are used in air-handling equipment (Refer to Section 607.2.3).
  3.  Smoke  dampers  shall  not  be  required  in  ducts  where the air
continues to move and the air-handling system installed is  arranged  to
prevent  recirculation  of  exhaust  or  return air under fire emergency
conditions.
  607.5.1 Fire walls. ducts  and  air  transfer  openings  permitted  in
firewalls  in  accordance  with  Section  705.11  of there New York City
Building code shall be protected with approved fire  dampers  and  smoke
dampers installed in accordance with their listing.
  607.5.2  Fire barriers. duct penetrations and air transfer openings in
fire barriers shall be protected with approved fire dampers installed in
accordance with their listing.  In  addition,  smoke  dampers  shall  be
installed  in  penetrations  of public corridor walls in accordance with
Section 607.5.2.1.
  Exceptions: Fire dampers are not  required  at  penetrations  of  fire
barriers where any of the following apply:
  1.  Penetrations  are  tested in accordance with ASTM E 119 as part of
the fire-resistance-rated assembly.
  2. Where permitted  under  Section  513  and  ducts  are  part  of  an
engineered smoke control system.
  3.  Such  walls are penetrated by ducted HVAC systems, have a required
fire resistance rating of 1 hour or less, are in  areas  of  other  than
Group  H  and  are  in  buildings  equipped throughout with an automatic
sprinkler system in accordance with Section 903.3.1.1  or  903.3.1.2  of
the  New  York City Building code. For the purposes of this exception, a
ducted HVAC system shall be a  duct  system  for  the  structure's  HVAC
system.  Such a duct system shall be constructed of sheet metal not less
than 26-Gage (0.0217-inch) [0.55 mm)] thickness and hall  be  continuous

from the air-handling appliance or equipment to the air outlet and inlet
terminals.
  607.5.2.1  Public  corridors. A listed smoke damper designed to resist
the passage of smoke shall be provided at  each  point  a  duct  or  air
transfer opening penetrates a public corridor wall constructed as a fire
barrier.
  Exceptions:
  1.  Smoke  dampers  are  not  required  where the building is equipped
throughout with an approved smoke  control  system  in  accordance  with
Section  909,  and smoke dampers are not necessary for the operation and
control of the system.
  2. Smoke dampers are not required in corridor  penetrations  where  th
duct  is  constructed  of  steel  not  less than 0.019-inch (0.48 mm) in
thickness and there are no openings serving the corridor.
  3. Smoke dampers are not required in corridor  penetrations  in  Group
R-2 buildings and spaces.
  607.5.3 Fire partitions. Duct penetrations in fire partitions shall be
protected  with approved fire dampers installed in accordance with their
listing.
  Exceptions: In occupancies other than Group H, fire  dampers  are  not
required where any of the following apply:
  1.  The  partitions  are  tenant  separation  and  corridor  walls  in
buildings equipped throughout with  an  automatic  sprinkler  system  in
accordance  with  Section  903.3.1.1  or  903.3.1.2 of the New York City
Building Code and the duct is protected  as  a  through  penetration  in
accordance with the New York City Building Code.
  2.  The duct system is constructed of approved materials in accordance
with this code and the duct  penetrating  the  wall  meets  all  of  the
following minimum requirements.
  2.1 The duct shall not exceed 100 square inches (0.06 m{2}).
  2.2.  The  duct shall be constructed of steel a minimum of 0.0217-inch
(0.55 mm) in thickness.
  2.3. The duct shall not have openings that  communicate  the  corridor
with adjacent spaces or rooms.
  2.4. The duct shall be installed above a ceiling.
  2.5.  The  duct  shall  not  terminate  at  a  wall  register  in  the
fire-resistance-rated wall.
  2.6. A minimum 12-inch-long (304.8 mm) by 0.060-inch-thick  (1.52  mm)
steel sleeve shall be centered in each duct opening. The sleeve shall be
secured  to both sides of the wall and all four sides of the sleeve with
minimum 1 1/2-inch by 1 1/2-inch by 0.060-inch (38 mm by 38 mm  by  1.52
mm) steel retaining angles. The retaining angles shall be secured to the
sleeve  and  the wall with No. 10 (M5) screws. The annular space between
the steel sleeve  and  the  wall  opening  shall  be  filled  with  rock
(mineral) wool batting or approved equivalent on all sides.
  607.5.4  Smoke  barriers. A listed smoke damper designed to resist the
passage of smoke shall be provided at each point where a duct or an  air
transfer  opening  penetrates a smoke barrier wall enclosure required to
have smoke and draft control doors in accordance with the New York  City
Building  Code.  Smoke  dampers and smoke damper actuation methods shall
comply with Section 607.5.4.1.
  Exception:  Smoke  dampers  are  not   required   in   smoke   barrier
penetrations  where  the openings in ducts are limited to a single smoke
compartment and the ducts are constructed of steel.
  607.5.4.1 Smoke damper. The smoke damper shall close upon actuation of
a listed smoke detector or detectors installed in  accordance  with  the
New York City Building Code and Section 607.3.2.1.

  607.5.5  Shaft  enclosures.  Ducts and air transfer openings shall not
penetrate a shaft serving as an exit enclosure except  as  permitted  by
Section 1019.1.2 of the New York City Building Code.
  607.5.5.1  Penetrations of shaft enclosures. Shaft enclosures that are
permitted to be penetrated by ducts and air transfer openings  shall  be
protected  with  approved fire and smoke dampers installed in accordance
with their listing.
  Exceptions:
  1. Fire dampers are not required at penetrations of shafts where:
  1.1. Steel exhaust  subducts  extend  at  least  22  inches  (559  mm)
vertically  in  exhaust  shafts  provided  there is a continuous airflow
upward tot he outside, or
  1.2. Penetrations are tested in accordance with ASTM E 119 as part  of
the fire-resistance-rated assembly, or
  1.3.  Ducts  are  used  as  part  of  an approved smoke control system
designed and installed in accordance with Section 513 of this code,  and
where  the  fire  damper  will interfere with the operation of the smoke
control system, or
  1.4. The penetrations are in parking garage exhaust or  supply  shafts
that  are  separated  from other building shafts by not less than 2-hour
fire-resistance-rated construction.
  2. In Group B  occupancies,  equipped  throughout  with  an  automatic
sprinkler  system  in  accordance with Section 903.3.1.1 of the New York
City Building Code, smoke dampers are not required  at  penetrations  of
shafts where:
  2.1.  Bathroom  and  toilet  room  exhaust openings with steel exhaust
subducts, having a wall thickness of  at  least  0.019  inch  (0.48  mm)
extend  at least 22 inches (559 mm) vertically and where the exhaust fan
at the upper terminus is powered continuously  in  accordance  with  the
provisions  of  Section  909.11  of the New York City Building Code, and
maintains airflow upward to the outside, or
  2.2. Ducts are used as  part  of  an  approved  smoke  control  system
designed  and  installed  in accordance with Section 909 of the New York
City Building Code, and where the smoke damper will interfere  with  the
operation of the smoke control system.
  3.  Smoke dampers are not required at penetration of exhaust or supply
shafts in ;parking garages that are separated from other building shafts
by not less than 2-hour fire-resistance-rated construction.
  4. Fire dampers and/or smoke dampers shall not be required at a  shaft
where  the  shaft  is acting as an extension of the mechanical equipment
room that it serves and the shaft and mechanical equipment room maintain
fire and smoke separation required by the greater of the two spaces from
the occupied portions of the  building  and  meet  the  requirements  of
Section 707.11 of the New York City Building Code.
  5.  Smoke  dampers  shall  not  be  required  to  be  located within a
prescribed distance of a fire  rated  enclosure  where  isolation  smoke
dampers are used in air-handling equipment.
  6.  Smoke  dampers  shall  not  be  required  in  ducts  where the air
continues to move and the air-handling system installed is  arranged  to
prevent  recirculation  of  exhaust  or  return air under fire emergency
conditions.
  607.5.5.2 Limitations.  Shafts  that  constitute  air  ducts  or  that
enclose  air  ducts used for the movement of environmental air shall not
enclose:
  1. Exhaust ducts used for the removal of smoke and grease-laden vapors
from cooking equipment;
  2. Ducts used for removal of flammable vapors;

  3. Ducts used for moving, conveying, or transporting stock,  vapor  or
dust;
  4.  Ducts  used  for  the  removal of nonflammable corrosive fumes and
vapors;
  5. Refuse and linen chutes; or
  6. Piping.
  Exception: Shafts that constitute air ducts or that enclose air  ducts
used  for  the  movement of environmental air may enclose noncombustible
piping conveying water or other nonhazardous or nontoxic materials.
  607.6 Horizontal assemblies. Penetrations by air  ducts  of  a  floor,
floor/ceiling  assembly  or  the  ceiling  membrane  of  a  roof/ceiling
assembly shall be protected by a shaft enclosure that complies with  the
New York City Building Code or shall comply with this section.
  607.6.1 Through penetrations. In occupancies other than Groups I-2 and
I-3,  a  duct  and  air  transfer opening system constructed of approved
materials   in   accordance   with   this   code   that   penetrates   a
fire-resistance-rated floor/ceiling assembly that connects not more than
two  stories  is permitted without shaft enclosure protection provided a
fire damper is installed at  the  floor  line  and  the  penetration  is
firestopped.
  Exception:  A  duct  serving a dwelling unit is permitted to penetrate
three floors or less without a fire damper at  each  floor  provided  it
meets all of the following requirements.
  1. The duct shall be contained and located within the cavity of a wall
and  shall be constructed of steel not less than 0.019 inch (0.48 mm)(26
gauge) in thickness.
  2. The duct shall open into only one dwelling unit and the duct system
shall be continuous from the unit to the exterior of the building.
  3. The duct shall not exceed 5-inch (127 mm) nominal diameter and  the
total  area  of  such  ducts  shall not exceed 100 square inches (64 516
mm{2}) for any 100 square feet (9.3 m{2}) of the floor area.
  4. The annular space around the duct is protected with materials  that
prevent  the  passage of flame and hot gases sufficient to ignite cotton
waste where subjected to ASTM E 119 time-temperature conditions under  a
minimum  positive  pressure differential of 0.01 inch (2.49 Pa) of water
at the location of the penetration for the time period equivalent to the
fire-resistance rating of the construction penetrated.
  5. Grille openings located in a  ceiling  of  a  fire-resistance-rated
floor/ceiling or roof/ceiling assembly shall be protected with a ceiling
radiation damper in accordance with Section 607.6.2.
  607.6.2  Membrane  penetrations.  Where  duct  systems  constructed of
approved materials in accordance with this code penetrate a ceiling of a
fire-resistance-rated  floor/ceiling  or  roof/ceiling  assembly,  shaft
enclosure  protection  is  not  required  provided  an  approved ceiling
radiation damper and the firestopping is installed at the ceiling  line.
Where  a duct is not attached to a diffuser that penetrates a ceiling of
a fire-resistance-rated floor/ceiling or  roof/ceiling  assembly,  shaft
enclosure  protection  is  not  required  provided  an  approved ceiling
radiation damper and firestopping is  installed  at  the  ceiling  line.
Ceiling  radiation dampers shall be installed in accordance with UL 555C
and  constructed  in  accordance  with   the   details   listed   in   a
fire-resistance-rated assembly or shall be labeled to function as a heat
barrier  for  air-handling outlet/inlet penetrations in the ceiling of a
fire-resistance-rated assembly. Ceiling radiation dampers shall  not  be
required  where  ASTM E 119 fire tests have shown that ceiling radiation
dampers are not necessary  in  order  to  maintain  the  dire-resistance
rating  of  the assembly. Ceiling radiation damper shall not be required
where exhaust duct penetrations are protected in accordance with Section

712.4.2 of the New York City Building code and  the  exhaust  ducts  are
located  within  the  cavity  of a wall, and do not pass through another
dwelling unit or tenant space.
  607.6.3  Nonfire-resistance-rated assemblies. Duct systems constructed
of approved materials  in  accordance  with  this  code  that  penetrate
nonfire-resistance-rated floor assemblies that connect not more than two
stories  are  permitted without shaft enclosure protection provided that
the annular space between the  assembly  and  the  penetrating  duct  is
filled  with  an  approved  noncombustible  material  to resist the free
passage  of  flame  and  the  products  of  combustion.   Duct   systems
constructed  of  approved  materials  in  accordance with this code that
penetrate nonrated floor assemblies that connect  not  more  than  three
stories  are  permitted without shaft enclosure protection provided that
the annular space between the  assembly  and  the  penetrating  duct  is
filled  with  an  approved  noncombustible  material  to resist the free
passage of flame and the products of combustion, and a  fire  damper  is
installed at each floor line.
  Exception:  Fire  dampers  are not required in ducts within individual
residential dwelling units.
  607.7 Flexible ducts  and  air  connectors.  Flexible  ducts  and  air
connectors shall not pass through any fire-resistance-rated assembly.
                             SECTION MC 608
                       AIR OUTLETS AND AIR INLETS
608.1  Air  Outlets.  Air  outlets  shall  comply  with sections 608.1.1
through 608.1.3.
  608.1.1 General. Air supplied to any space shall not contain flammable
vapors, flyings, or dust in quantities  and  concentrations  that  would
introduce a hazardous condition.
  608.1.2  Construction of air outlets. Air outlets shall be constructed
of noncombustible material or  a  material  that  has  a  maximum  smoke
developed  index/rating of 50 and a maximum flame spread index/rating of
25.
  608.1.3 Location of air outlets. The location  of  air  outlets  shall
comply with the following requirements:
  1.  Air  outlets  shall be located at least 3 inches (76 mm) above the
floor.
  Exception: Air outlets may be located less than 3 inches (76 mm) above
the floor where provisions have been  made  to  prevent  dirt  and  dust
accumulations from entering the system.
  2.  Where  located  less than 7 feet (2134 mm) above the floor, outlet
openings shall be protected  by  a  grille  or  screen  having  openings
through which a 1/2-inch (12.7 mm) sphere cannot pass.
  3.  Grilles  may  be  located in floors provided they are installed so
that they may be removed for cleaning purposes  and  provided  they  are
constructed as follows:
  3.1.  Grilles up to 3 square feet (0.2787 m{2}) in gross area shall be
designed to support a concentrated live load of 250 pounds (114  kg)  on
any 4 square inches (2580mm{2}) of surface.
  3.2  Grilles  over  3 square feet (0.2787 m{2}) in gross area shall be
designed to support the same loads as the floor in the area where used.
  3.3 If located where they may be walked upon, the opening  in  grilles
shall reject a 1/2-inch (12.7 mm) sphere.
  608.2 Air inlets 9return or exhaust or return and exhaust). Air inlets
shall be constructed in accordance with 608.2.1 through 608.2.3.
  608.2.1 General. Air shall not be recirculated from any space in which
flammable  vapors,  flyings,  or  dust  is  present  in  quantities  and
concentrations that would  introduce  a  hazardous  condition  into  the
return air system.

  608.2.2 Construction of air inlets. Air inlets shall be constructed of
noncombustible  material  or  a material that has a maximum flame spread
index/rating or 25 and a maximum smoke developed index/rating of 50.
  608.2.3  Location  of  air  inlets.  The  location of air inlets shall
comply with the following requirements.
  1. Air inlets shall be located at least 3 inches  (76  mm)  above  the
floor.
  Exception:  Air inlets may be located less than 3 inches (76 mm) above
the floor where provisions have been  made  to  prevent  dirt  and  dust
accumulations from entering the system.
  2.  Where  located  less  than 7 feet (2134 mm) above the floor, inlet
openings shall be protected by  a  grille  or  screens  having  openings
through which a 1/2-inch (12,7 mm) sphere cannot pass.
  3.  Grilles  may  be  located in floors provided they are installed so
that they may be removed for cleaning purposes  and  provided  they  are
constructed as follows:
  3.1.  Grilles up to 3 square feet (0.2787 m{2}) in gross area shall be
designed to support a concentrated live load of 250 pounds 9114  kg)  on
any 4 square inches (2580 mm{2}) of surface.
  3.2.  Grilles  over 3 square feet (0.2787 m{2}) in gross area shall be
designed to support the same loads as the floor in the area where used.
  3.3 If located where they may be walked upon, the opening  in  grilles
shall reject a 1/2-inch (12.7 mm) sphere.
                             SECTION MC 609
                            SERVICE OPENINGS
  609.1 General. Horizontal air ducts and plenums shall be provided with
service  openings to facilitate the removal of accumulations of dust and
combustible  materials.   Service   openings   shall   be   located   at
approximately  20 feet (6096 mm) intervals along the air duct and at the
base of each vertical riser.
  Exceptions:
  1. Removable air outlet or air inlet devices of adequate size shall be
permitted in lieu of service openings.
  2. Service openings shall not be required in supply  ducts  where  the
supply  air has previously passed through an air filter, air cleaner, or
water spray. Such  air  filters  and  air  cleaners  shall  be  properly
maintained and replaced when needed.
  3.  Service  openings shall not be required where all of the following
conditions exist:
  3.1. The occupancy has no process producing combustible material  such
as  dust,  or  greasy  vapors.  Such  occupancies  include banks, office
buildings, houses of worship, hotels, and health  care  facilities  (but
not kitchens, laundries, and manufacturing portions of such facilities).
  3.2.  The  air inlets are at least 7 feet (2134 mm) above the floor or
are protected by corrosion-resistant metal screens of at least  14  mesh
(0.07  inches)  (1.8  mm)  that are installed at the inlets so that they
cannot draw papers, refuse, or other combustible solids into the  return
air duct.
  3.3. The minimum design velocity in the return duct for the particular
occupancy is 1000 feet/minute (5.080 m/s).
                                CHAPTER 7
                             COMBUSTION AIR
                             SECTION MC 701
                                 GENERAL
  701.1   Scope.  The  provisions  of  this  chapter  shall  govern  the
requirements for combustion and dilution air for fuel-burning appliances
other than gas-fired appliances. The  requirements  for  combustion  and

dilution  air  for  gas-fired appliances shall be in accordance with the
New York City Fuel Gas Code.
  701.2  Combustion  and  dilution  air  required.  Every  room or space
containing fuel-burning appliances shall be provided with combustion and
dilution air as required by this code. Combustion and dilution air shall
be provided in accordance with Section 702, 703, 704, 705, 706  or  707.
Direct vent appliances or equipment that do not draw combustion air from
inside  of  the  building  are  not  required  to  be  considered in the
determination  of  the  combustion  and   dilution   air   requirements.
Combustion   air   requirements   shall   be  determined  based  on  the
simultaneous operation of all fuel-burning appliances drawing combustion
and dilution air from the room or space. The combustion air system shall
maintain the room in which the equipment is located at  a  pressure  not
less than the outdoor atmosphere pressure.
  701.3  Circulation  of  air. The equipment and appliances within every
room containing fuel-burning appliances shall  be  installed  so  as  to
allow free circulation of air. Provisions shall be made to allow for the
simultaneous  operation  of  mechanical  exhaust  systems, fireplaces or
other equipment and appliances operating in the same room or space  from
which  combustion and dilution air is being drawn. Such provisions shall
prevent the operation of such appliances,  equipment  and  systems  from
affecting the supply of combustion and dilution air.
  701.4  Crawl  space and attic space. For the purposes of this chapter,
an opening to a naturally ventilated crawl space or attic space shall be
considered equivalent to an opening to the outdoors.
  701.4.1 Crawl space. Where lower combustion air openings connect  with
crawl  spaces,  such  spaces  shall  have  unobstructed  openings to the
outdoors at least twice that required for the combustion  air  openings.
The  height of the crawl space shall comply with the requirements of the
New York City Building Code and shall be without obstruction to the free
flow of air.
  701.4.2 Attic space. Where combustion air is obtained  from  an  attic
area, the attic ventilating openings shall not be subject to ice or snow
blockage,  and  the  attic  shall  have not less than 30 inches (762 mm)
vertical clear height at its maximum point. Attic  ventilation  openings
shall be sufficient to provide the required volume of combustion air and
the  attic  ventilation required by the New York City Building Code. The
combustion air openings shall be provided with a sleeve of not less than
0.019 inch (0.48 mm) (No. 26 Gage) galvanized steel  or  other  approved
material  extending  from  the  appliance enclosure to at least 6 inches
(152 mm) above the top of the ceiling joists and insulation.
  701.5  Prohibited  sources.  Openings  and  ducts  shall  not  connect
appliance  enclosures  with a space in which the operation of a fan will
adversely affect the flow of the combustion air.  Combustion  air  shall
not  be  obtained from a hazardous location, except where the fuel-fired
appliances are located within the hazardous location and  are  installed
in  accordance  with this code. Combustion air shall not be taken from a
refrigeration machinery room, except where a refrigerant vapor  detector
system  is installed to automatically shut off the combustion process in
the event of refrigerant leakage. For structures  in  areas  of  special
flood  hazard,  air  shall  be  obtained  from a location complying with
Appendix G of the New York City Building Code. Combustion air  shall  be
obtained solely from the outdoors for a boiler room.
                             SECTION MC 702
                               INSIDE AIR
  702.1  All  air  from  indoors.  Combustion  and dilution air shall be
permitted to be obtained entirely from the indoors in buildings that are
not of unusually tight construction. In  buildings  of  unusually  tight

construction,  combustion  air  shall  be  obtained from the outdoors in
accordance with Section 703, 705, 706 or 707.
  702.2  Air  from  the same room or space. The room or space containing
fuel-burning appliances shall be  an  unconfined  space  as  defined  in
Section 202.
  702.3  Air from adjacent spaces. Where the volume of the room in which
the fuel-burning appliances are located does  not  comply  with  Section
702.2,  additional  inside combustion and dilution air shall be obtained
by opening the room to adjacent spaces so that the  combined  volume  of
all  communicating  spaces  meet  the  volumetric requirement of Section
702.2.  Openings  connecting  the  spaces  shall  comply  with  Sections
702.3.1, 702.3.2 and Figure A-1 of Appendix A of this code.
  702.3.1  Number  and  location  of  openings.  Two  openings  shall be
provided, one within 1 foot (305 mm) of the ceiling of the room and  one
within 1 foot (305 mm) of the floor.
  702.3.2  Size  of  openings.  The  net  free  area  of  each  opening,
calculated in accordance with Section 708,  shall  be  a  minimum  of  1
square  inch  per  1,000  Btue/h  (2201  mm{2}kW) of input rating of the
fuel-burning appliances drawing combustion and  dilution  air  from  the
communicating  spaces  and  shall be not less than 100 square inches (64
516 mm{2}).
                             SECTION MC 703
                               OUTDOOR AIR
  703.1 All air from the outdoors. Where all combustion and dilution air
is to be provided by outdoor air, the required combustion  and  dilution
air  shall  be  obtained  by  opening the room to the outdoors. Openings
connecting the room to  the  outdoor  air  shall  comply  with  Sections
703.1.1  through  703.1.4, and Figures A-2, A-3 and A-4 of Appendix A of
this code. The size of the openings connecting the room to  the  outdoor
air  supply  shall also comply with any applicable rules of the New York
City Department of Environmental Protection.
  703.1.1 Number  and  location  of  openings.  Two  openings  shall  be
provided,  one within 1 foot (305 mm) of the ceiling of the room and one
within 1 foot (305 mm) of the floor.
  703.1.2 Size of direct openings. The net  free  area  of  each  direct
opening  to  the  outdoors,  calculated  in accordance with Section 709,
shall be a minimum of 1 square inch per 4,000 Btu/h  (550  mm{2}/kW)  of
combined  input rating of the fuel-burning appliances drawing combustion
and dilution air from the room.
  703.1.3 Size of  horizontal  openings.  The  net  free  area  of  each
opening,  calculated in accordance with Section 709 and connected to the
outdoors through a horizontal duct, shall be a minimum of 1 square  inch
per  2,000  Btu/h  (1100  mm{2}/kW)  of  combined  input  rating  of the
fuel-burning appliances drawing combustion and  dilution  air  from  the
room.  The cross-sectional area of the duct shall be equal to or greater
than the required size of the opening.
                             SECTION MC 704
          COMBINED USE OF INSIDE AND OUTDOOR AIR (CONDITION 1)
  704.1 Combination of air from inside and outdoors. This section  shall
apply  only to appliances located in confined spaces in buildings not of
unusually tight construction. Where the volumes of rooms and spaces  are
combined  for the purpose of providing indoor combustion air, such rooms
and spaces shall communicate through permanent  openings  in  compliance
with  Sections 702.3.1 and 702.3.2. The required combustion and dilution
air shall be obtained by opening  the  room  to  the  outdoors  using  a
combination  of  inside  and  outdoor  air,  prorated in accordance with
Section 704.1.6. The ratio of interior spaces shall comply with  Section
704.1.5.  The  number,  location  and  ratios of openings connecting the

space with the outdoor air shall comply with  Sections  704.1.1  through
704.1.4.
  704.1.1  Number  and location of openings. At least two openings shall
be provided, one within 1 foot (305 mm) of the ceiling of the  room  and
one within 1 foot (305 mm) of the floor.
  704.1.2  Ratio  of  direct  openings.  Where  direct  openings  to the
outdoors are provided in accordance with Section  703.1,  the  ratio  of
direct  openings  shall  be the sum of the net free areas of both direct
openings to the outdoors, divided by the sum of the required  areas  for
both such openings as determined in accordance with Section 703.1.2.
  704.1.3  Ratio of horizontal openings. Where openings connected to the
outdoors through  horizontal  ducts  are  provided  in  accordance  with
Section  703.1, the ratio of horizontal openings shall be the sum of the
net free areas of both such openings, divided by the sum of the required
areas for both such openings as determined in  accordance  with  Section
703.1.3.
  704.1.4  Ratio  of  vertical openings. Where openings connected to the
outdoors through vertical ducts are provided in accordance with  Section
703.1,  the  ratio of vertical openings shall be the sum of the net free
areas of both such openings, divided by the sum of  the  required  areas
for both such openings as determined in accordance with Section 703.1.4.
  704.1.5  Ratio  of interior spaces. The ratio of interior spaces shall
be the available volume of all  communicating  spaces,  divided  by  the
required  volume  as  determined  in  accordance with Sections 702.2 and
702.3.
  704.1.6 Prorating of inside and outdoor air. In spaces that utilize  a
combination  of  inside  and  outdoor  air, the sum of the ratios of all
direct openings, horizontal openings,  vertical  openings  and  interior
spaces shall equal or exceed 1.
                             SECTION MC 705
          COMBINED USE OF INSIDE AND OUTDOOR AID (CONDITION 2)
  705.1  General. This section shall apply only to appliances located in
unconfined  spaces  in  buildings  of  unusually   tight   construction.
Combustion  air  supplied  by  a  combined use of indoor and outdoor air
shall be supplied through openings and ducts extending to the  appliance
room or to the vicinity of the appliance.
  705.1.1 Openings and supply ducts. Openings shall be provided, located
and sized in accordance with Sections 702.3.1 and 702.3.2; additionally,
there  shall  be  one  opening  to the outdoors having a free area of at
least 1 square inch per 5,000 Btu/h (440 mm{2}/kW) of total input of all
appliances in the space.
                             SECTION MC 706
                      FORCED COMBUSTION AIR SUPPLY
  706.1 Rate of air supplied. Where all combustion air and dilution  air
is  provided  by  a mechanical forced-air system, the combustion air and
dilution air shall be supplied at the minimum rate of 1  cfm  per  2,400
Btu/h  [0.00067  m{3}/(s    kW)]  of  combined  input  rating of all the
fuel-burning appliances served. Combustion air rates shall  also  comply
with   any   applicable  rules  of  the  New  York  City  Department  of
Environmental Protection.
                             SECTION MC 707
                            DIRECT CONNECTION
  707.1 General. Fuel-burning appliances that are listed and labeled for
direct combustion air connection to the outdoors shall be  installed  in
accordance with the manufacturer's installation instructions.
                             SECTION MC 708
                          COMBUSTION AIR DUCTS
  708.1 General. Combustion air ducts shall:

  1.  Be  of  galvanized steel complying with Chapter 6 or of equivalent
corrosion-resistant material approved for this application.
  Exception:  Within  dwelling units, unobstructed stud and joist spaces
shall not be prohibited from conveying combustion air, provided that not
more than one required fireblock is removed.
  2. Have a minimum cross-sectional dimension of 3 inches (76 mm).
  3. Terminate in  an  unobstructed  space  allowing  free  movement  of
combustion air to the appliances.
  4.  Have  the  same  cross-sectional  areas  as  the  free area of the
openings to which they connect.
  5. Serve a single appliance enclosure.
  6. not serve both upper and lower combustion air openings  where  both
such  openings  are used. The separation between ducts serving upper and
lower combustion air opening  shall  be  maintained  to  the  source  of
combustion air.
  7. Not be screened where terminating in an attic space.
  8.  Not  slope  downward  toward  the  source of combustion air, where
serving the upper required combustion air opening.
                             SECTION MC 709
                          OPENING OBSTRUCTIONS
  709.1 General. The  required  size  of  openings  for  combustion  and
dilution  air  shall  be based on the net free area of each opening. The
net free area of an opening shall be that specified by the  manufacturer
of  the  opening  covering. In the absence of such information, openings
covered with metal louvers shall be deemed to have a net free  areas  of
60  percent  of  the area of the opening, and openings covered with wood
louvers shall be deemed to have net free area of 10 percent of the  area
of the opening. Louvers and grills shall be fixed in the open position.
  Exception:  Louvers  interlocked  with  the appliance so that they are
proven to be in the full open position prior to main burner ignition and
during main burner operation. Means shall be  provided  to  prevent  the
main  burner  from  igniting  if  the louvers fail to open during burner
startup and to shut down the main burner if  the  louvers  close  during
operation.
  709.2  Dampered  openings.  Where  the  combustion  air  openings  are
provided with volume, smoke  or  fire  dampers,  the  dampers  shall  be
electrically interlocked with the firing cycle of the appliances served,
so  as  to  prevent operation of any appliance that draws combustion and
dilution air from the room when any of the dampers are closed.  Manually
operated dampers shall not be installed in combustion air openings.
                             SECTION MC 710
                     OPENING LOCATION AND PROTECTION
710.1 General. Combustion air openings to the outdoors shall comply with
the  location  and  protection  provisions  of  Sections 401.5 and 401.6
applicable to outside air intake openings.
                                CHAPTER 8
                           CHIMNEYS AND VENTS
                             SECTION MC 801
                                 GENERAL
801.1 Scope. This chapter shall govern  the  installation,  maintenance,
design,   minimum   safety   requirements,   repair   and   approval  of
factory-built chimneys, chimney liners, vents and connectors, and  field
built  chimneys  and  connectors.  This  chapter  shall  also govern the
utilization of masonry chimneys. Gas-fired appliances shall be vented in
accordance with the New York City Fuel Gas Code.
  801.1.1 Adjoining chimneys and vents.  Adjoining  chimneys  and  vents
shall be in accordance with Sections 801.1.1.1 through 801.1.1.8.

  801.1.1.1  Responsibility  of  owner  of  taller  building. Whenever a
building is erected, enlarged,  or  increased  in  height  so  that  any
portion  of such building, except chimneys or vents, extends higher than
the top of any previously constructed chimneys or vents within 100  feet
(30  480  mm),  the owner of such new or altered building shall have the
responsibility of altering such chimneys or vents to make  them  conform
with  the  requirements  of  this  chapter. A chimney or vent that is no
longer connected with a fireplace or combustion or other  equipment  for
which  a  chimney  or  vent  was  required,  shall  be  exempt from this
requirement. Such alterations  shall  be  accomplished  by  one  of  the
following means or a combination thereof:
  1. Carry up the previously constructed chimneys or vents to the height
required  in  this  chapter. Offset such chimneys or vents to a distance
beyond that required in Chapter 5 of this code from the new  or  altered
building  provided  that  the  new  location of the outlet of the offset
chimney or vent shall otherwise comply with  the  requirements  of  this
chapter.
  Such  requirements  shall  not  dispense with or modify any additional
requirements that may be applicable pursuant to rules of  the  New  York
City Department of Environmental Protection.
  801.1.1.2  Protection  of  draft. After the alteration of a chimney or
vent as required by this section, it shall be the responsibility of  the
owner of the new or altered building to provide any mechanical equipment
or devices necessary to maintain the proper draft in the equipment.
  801.1.1.3  Written  notification.  The  owner  of  the  new or altered
building shall notify the owner of the building affected in  writing  at
least  forty-five  days  before  starting  the work required and request
written consent to do such work. Such notice shall be companied by plans
indicating the manner in which the proposed alterations are to be made.
  801.1.1.4 Approval. The  plans  and  method  of  alteration  shall  be
subject to the approval of the commissioner.
  801.1.1.5  Refusal  of consent. If consent is not granted by the owner
of the  previously  constructed  building  to  do  the  alteration  work
required by this section, such owner shall signify her or her refusal in
writing  to  the  owner  of  the  new  or  altered  building  and to the
commissioner; and the owner  of  the  new  or  altered  building  having
submitted  plans that conform to the requirements of this section, shall
thereupon be released from any responsibility for the  proper  operation
of  the  equipment  due  to  loss  of draft and for any health hazard or
nuisance that may occur as a result of the new or altered building. Such
responsibilities shall then be assumed by the owner  of  the  previously
constructed  building.    Similarly,  should  such  owner  fail to grant
consent within forty-five days from the date of written request or  fail
to  signify  his  or  her  refusal,  he  or  she  shall  then assume all
responsibilities as prescribed above.
  801.1.1.6 Procedure. It shall be the obligation of the  owner  of  the
new or altered building to:
  1.  Schedule this work so as to create a minimum of disturbance to the
occupants of the affected building; and
  2. Provide such essential services as are  normally  supplied  by  the
equipment while it is out of service; and
  3.   Where  necessary,  support  such  extended  chimneys,  vents  and
equipment from this building or to  carry  up  such  chimneys  or  vents
within his or her building; and
  4.  Provide  for  the  maintenance, repair, and/or replacement of such
extensions and added equipment; and
  5. Make such alterations of the same material as the original  chimney
or  vent so as to maintain the same quality and appearance, except where

the affected owner of the chimney or vent shall give his or her  consent
to  do  otherwise. All work shall be done in such fashion as to maintain
the architectural aesthetics of the existing building.  Where  there  is
practical  difficulty  in complying strictly with the provisions of this
Item, the commissioner may permit an equally safe alternative.
  801.1.1.7  Existing  violations.  Any  existing  violations   on   the
previously  constructed equipment shall be corrected by the owner of the
equipment before any equipment is  added  or  alterations  made  at  the
expense of the owner of the new or altered building.
  801.1.1.8   Variance.   The  commissioner  may  grant  a  variance  in
accordance with the provisions of this code.
  801.2  General.  Every  fuel-burning  appliance  shall  discharge  the
products  of  combustion  to  a  vent,  factory-built chimney or masonry
chimney, except for appliances vented in accordance  with  Section  804.
The  chimney  or  vent shall be designed for the type of appliance being
vented.
  801.2.1 Design. Chimneys and vents shall be designed  and  constructed
so  as  to  provide  the necessary draft and capacity for each appliance
connected to completely  exhaust  the  products  of  combustion  to  the
outside  air. The temperature on adjacent combustible surfaces shall not
be raised above 160°F (71°C). Condensation shall not be developed to  an
extent that can cause deterioration of the chimney or vent.
  801.2.2  Outlets. The outlet shall be arranged that the flue gases are
not directed  so  that  they  jeopardize  people,  overheat  combustible
structures, or enter building openings in the vicinity of the outlet.
  801.2.3  Support.  Chimneys  and  vents  shall not be supported by the
equipment  they  serve  unless  such  equipment  has  been  specifically
designed for such loads.
  801.2.4  Oil-fired appliances. Oil-fired appliances shall be vented in
accordance with this code and NFPA 31.
  801.2.5 Gas fired appliances. Gas fired appliances shall be vented  in
accordance with the New York City Fuel Gas Code.
  801.3  Masonry  chimneys.  Masonry  chimneys  shall  be constructed in
accordance with the New York City Building Code.
  801.4 Positive flow. Venting systems shall be designed and constructed
so as to develop a positive  flow  adequate  to  convey  all  combustion
products to the outside atmosphere.
  801.5  Design.  Venting  systems  shall be designed in accordance with
this chapter and comply with the requirements of the New York  City  Air
Pollution Control Code.
  801.6  Minimum  size  of chimney or vent. Except as otherwise provided
for in this chapter, the size of the chimney or vent, serving  a  single
appliance, except engineered systems, shall have a minimum area equal to
the area of the appliance connection.
  801.7  Solid  fuel appliance flues. The cross-sectional area of a flue
serving a solid fuel-burning appliance shall be not greater  than  three
times  the  cross-sectional  area  of  the appliance flue collar or flue
outlet.
  801.8 Abandoned inlet openings. Abandoned inlet openings  in  chimneys
and  vents  shall  be closed by an approved method, sealed air-tight and
permanently labeled as abandoned.
  801.9 Positive pressure. Where an appliance equipped with a forced  or
induced  draft system creates a positive pressure in the venting system,
the venting system shall be designed and listed  for  positive  pressure
applications.
  801.10  Connection  to  fireplace. Connection of appliances to chimney
flues serving fireplaces shall be in accordance with  Sections  801.10.1
through 801.10.3.

  801.10.1  Closure  and access. A noncombustible seal shall be provided
below the point of connection to prevent entry  of  room  air  into  the
flue.  Means shall be provided for access to the flue for inspection and
cleaning.
  801.10.2  Connection  to  factory-built  fireplace  flue. An appliance
shall not be connected to  a  flue  serving  a  factory-built  fireplace
unless  the  appliance  is specifically listed for such installation The
connection shall be made in accordance with the appliance manufacturer's
installation instructions.
  801.10.3 Connection t masonry fireplace flue. A connector shall extend
from the appliance to the flue serving a masonry fireplace such that the
flue gases are exhausted directly into the flue. The connector shall  be
provided  with  access or shall be removable for inspection and cleaning
of both the connector and the flue.  Listed  direct  connection  devices
shall be installed in accordance with their listing.
  801.11  Multiple solid fuel prohibited. A solid fuel-burning appliance
of fireplace shall not connect to a chimney passageway  venting  another
fireplace.
  801.12 Chimney entrance. Connectors shall connect to a chimney flue at
a point not less than 12 inches (305 mm) above the lowest portion of the
interior of the chimney flue.
  801.13  Cleanouts.  Masonry  chimney  flues  shall  be provided with a
cleanout opening having a minimum height of 6 inches (152 mm). The upper
edge of the opening shall be located not less than  6  inches  (152  mm)
below  the  lowest chimney inlet opening. The cleanout shall be provided
with a tight-fitting, noncombustible cover of a minimum size of 8 inches
(203 mm by 203 mm).
  Exception: Cleanouts shall not be required for chimney  flues  serving
masonry  fireplaces,  if such flues are provided with access through the
fireplace opening.
  801.14 Connections  to  exhauster.  All  appliance  connections  to  a
chimney  or  vent  equipped  with a power exhauster shall be made on the
inlet side of the exhauster. All  joints  and  piping  on  the  positive
pressure  side  of  the  exhauster shall be listed for positive pressure
applications   as   specified   by   the   manufacturer's   installation
instructions for the exhauster.
  801.15  Fuel-fired  appliances.  Masonry  chimneys  utilized  to  vent
fuel-fired  appliances  shall  be  located,  constructed  and  sized  as
specified  in  the  manufacturer's  installation  instructions  for  the
appliances being vented.
  801.16 Flue lining.  Masonry  chimneys  shall  be  lined.  The  lining
material  shall  be  compatible with the type of appliance connected, in
accordance  with  the   appliance   listing   and   the   manufacturer's
installation  instructions.  Listed materials used as flue linings shall
be installed in accordance with their listings  and  the  manufacturer's
installation instructions.
  801.16.1  Residential  and  low-heat appliances (general). Flue lining
systems for use with residential-type and low-heat appliances  shall  be
limited to the following:
  1.  Clay  flue lining complying with the requirements of ASTM C 315 or
equivalent. Clay flue lining shall be installed in accordance  with  the
New York City Building Code.
  2. Listed chimney lining systems complying with UL 1777.
  3.  Other  approved  materials  that  will  resist,  without cracking,
softening or corrosion, flue gases and condensate at temperatures up  to
1,800°F (982°C).
  801.17 Space around lining. The space surrounding a flue lining system
or  other  vent  installed within a masonry chimney shall not be used to

vent any other appliance. This shall not prevent the installation  of  a
separate  flue lining in accordance with the manufacturer's installation
instructions and this code.
  801.18  Existing chimneys and vents. Where an appliance is permanently
disconnected from an existing chimney or vent, or where an appliance  is
connected  to  an  existing  chimney or vent during the process of a new
installation, the chimney or vent shall comply  with  Sections  801.18.1
through 801.18.4.
  801.18.1  Size.  The  chimney or vent shall be resized as necessary to
control flue gas condensation in the interior of the chimney or vent and
to provide the appliance or appliances served with the  required  draft.
For  the  venting  of  oil-fired  appliances  to  masonry  chimneys, the
resizing shall be in accordance with NFPA 31.
  801.18.2 Flue passageways. The flue gas passageway shall  be  free  of
obstructions and combustible deposits and shall be cleaned if previously
used  for venting a solid or liquid fuel-burning appliance or fireplace.
The flue liner, chimney innerwall or vent innerwall shall be  continuous
and  shall  be  free  of  cracks,  gaps, perforations or other damage or
deterioration which would  allow  the  escape  of  combustion  products,
including gases, moisture and creosote.
  Where  an  oil-fired  appliance  is  connected  to an existing masonry
chimney, such chimney flue shall be repaired or  relined  in  accordance
with NFPA 31.
  801.18.3  Cleanout. Masonry chimneys shall be provided with a cleanout
opening complying with Section 801.13.
  801.18.4 Clearance. Chimneys and vents shall have air-space  clearance
to  combustibles  in accordance with the New York City Building Code and
the chimney or vent manufacturer's installation instructions.
  Exception: Masonry chimneys equipped  with  a  chimney  lining  system
tested   and  listed  for  installation  in  chimneys  in  contact  with
combustibles in accordance with US 1777,  and  installed  in  accordance
with  the  manufacturer's  instructions,  shall  not be required to have
clearance between combustible materials and  exterior  surfaces  of  the
masonry  chimney.  Noncombustible  fireblocking  shall  be  provided  in
accordance with the New York City Building Code.
  801.19 Multistory prohibited. Common venting  systems  for  appliances
located  on  more than one floor level shall be prohibited, except where
all of the appliances served by the common vent are located in rooms  or
spaces   that  are  accessed  only  from  the  outdoors.  The  appliance
enclosures shall not  communicate  with  the  occupiable  areas  of  the
building.
  801.20 Reserved.
                             SECTION MC 802
                                  VENTS
802.1  General.  All  vent  systems shall be listed and labeled or field
fabricated in accordance with NFPA 211. Type L vents shall be tested  in
accordance with UL 641.
  802.2   Vent  application.  The  application  of  vents  shall  be  in
accordance with Table 802.2.

                               TABLE 802.2
                            VENT APPLICATION
------------------------------------------------------------------------
   VENT TYPES       |     APPLIANCE TYPES
------------------------------------------------------------------------
 Type L oil vents   | Oil-burning appliances listed and labeled for
                    | venting with Type L vents; gas appliances listed
                    | and labeled for venting with Type B vents.

------------------------------------------------------------------------

  802.3  Installation.  Vent  systems  shall  be  sized,  installed  and
terminated in accordance with  the  vent  and  appliance  manufacturer's
installation instructions.
  802.4  Vent  termination  caps.  Vent  termination  caps  shall not be
permitted and a 2 1/2-inch (64 mm) minimum drain  installed  to  receive
condensed water shall be required. A positive means shall be provided to
prevent water from entering the appliance.
  802.5  Type L vent terminations. Type L vents shall terminate not less
than 2 feet (610 mm) above the highest point of the roof penetration and
not less than 2 feet (610 mm) higher than  any  portion  of  a  building
within  10  feet  (3048 mm). Chimneys serving appliances less than 600°F
(316°C) shall extend  at  least  3  feet  (914  mm)  above  the  highest
construction,  such  as a roof ridge, parapet wall, or penthouse, within
10 feet (3048 mm) of the chimney outlet, whether the construction is  on
the  same  buildings  as the chimney or on another building. Any chimney
located in an area that is  more  than  10  feet  (3048  mm)  from  such
construction  but  not more than the distance determined by Equation 8-1
and Table 8032.5, shall be at least as high as the highest  construction
in  such  area.  For  purposes of determining the required height of the
chimney, such construction does not include other  chimneys,  vents,  or
open structural framing.
  D = F x -vA                              (Equation 8-1)
  where:  D = Distance, in feet, measured from the center of the chimney
outlet to the nearest edge of the construction.
  F = Value determined from Table 802.5.
  A = Free area, in square inches, of chimney flue space.

                               TABLE 802.5
               "F" FACTOR FOR DETERMINING CHIMNEY DISTANCE
------------------------------------------------------------------------
               "F" FACTOR FOR DETERMINING CHIMNEY DISTANCE
------------------------------------------------------------------------
   Type of Fuel   |                  "F" Factor
------------------------------------------------------------------------
                  |600°F (316°C) and| 600°F (316°C) to|  Greater than
                  |       less      |  1000°F (538°C) | (538°C) 1000°F
------------------------------------------------------------------------
No. 2 Fuel Oil    |       2.5       |       2.5       |        3
------------------------------------------------------------------------
No. 4, 6 Fuel Oil |        3        |        3        |        3
------------------------------------------------------------------------

  802.6 Minimum vent heights. Vents shall terminate not less than 5 feet
(1524 mm) in vertical height above the highest connected appliance  flue
collar.
  Exceptions:
  1.  Venting  systems  of  direct  vent appliance shall be installed in
accordance with the appliance and the vent manufacturer's instructions.
  2. Appliances listed for outdoor installations incorporating  integral
venting  means  shall be installed in accordance with their listings and
the manufacturer's installation instructions.
  802.7 Support of vents. All portions  of  vents  shall  be  adequately
supported for the design and weight of the materials employed.
  802.8   Insulation   shield.   Where   vents  pass  through  insulated
assemblies, an insulation shield constructed of not  less  than  No.  26
Gage  sheet  metal  shall  be installed to provide clearance between the

vent and the insulation material. The clearance shall be not  less  than
the  clearance  to  combustibles  specified  by  the vent manufacturer's
installation instructions. Where vents pass  through  attic  space,  the
shield  shall  terminate  not  less  than  2  inches  (51  mm) above the
insulation  materials  and  shall  be  secured  in  place   to   prevent
displacement.  Insulation  shields  provided  as  part  of a listed vent
system  shall  be  installed  in  accordance  with  the   manufacturer's
installation instructions.
                             SECTION MC 803
                               CONNECTORS
  803.1  Connectors  required.  Connectors  shall  be  used  to  connect
appliances to the vertical chimney or vent, except where the chimney  or
vent is attached directly to the appliance.
  803.2  Location.  Connectors shall be located entirely within the room
in which the connecting appliance is located, except as provided for  in
Section  803.10.4.  Where passing through an unheated space, a connector
shall not be constructed of single-wall pipe.
  803.3 Size. The connector shall not be smaller than the  size  of  the
flue  collar  supplied  by  the manufacturer of the appliance. Where the
appliance has more than on flue  outlet,  and  in  the  absence  of  the
manufacturer's  specific  instructions,  the connector area shall be not
less than the combined are of the flue outlets for which it  acts  as  a
common connector.
  803.4 Branch connections. All branch connections to the vent connector
shall be made in accordance with the vent manufacturer's instructions.
  803.5  Manual  dampers.  Manual  dampers  shall  not  be  installed in
connectors except in  chimney  connectors  servings  solid  fuel-burning
appliances.
  803.6 Automatic dampers. Automatic dampers shall be listed and labeled
in  accordance  with UL 17 for oil-fired heating appliances. The dampers
shall be installed in accordance with  the  manufacturer's  installation
instructions.  An automatic vent damper device shall not be installed on
an existing appliance unless the appliance is listed and labeled and the
device is installed in accordance with the terms  of  its  listing.  The
name  of  the  installer  and  date of installation shall be marked on a
label affixed to the damper device.
  803.7 Connectors serving two or more appliances.  Where  two  or  more
connectors  enter  a common vent or chimney, the smaller connector shall
enter at  the  highest  level  consistent  with  available  headroom  or
clearance to combustible material.
  803.8  Vent connector construction. Vent connectors shall be construed
of metal. The minimum nominal thickness of the connector shall be  0.019
inch  (0.5  mm)  (No. 28 Gage) for galvanized steel, 0.022 inch (0.6 mm)
(No.  26 B & S Gage) for copper, and 0.020 inch (0.5 mm) No. 24  B  &  S
Gage) for aluminum.
  803.9  Chimney connector construction. Chimney connectors for low-heat
appliances shall be of sheet steel pipe having resistance  to  corrosion
and  heat  not  less  than  that  of galvanized steel specified in Table
803.9(1). Connectors for medium-heat appliance and high-heat  appliances
shall  be  of sheet steel not less than the thickness specified in Table
803.9(2).
                             TABLE 803.9(1)
                 MINIMUM CHIMNEY CONNECTOR THICKNESS FOR
                           LOW-HEAT APPLIANCES
     -----------------------------------------------------------
                                   | MINIMUM NOMINAL THICKNESS
        DIAMETER OF CONNECTOR      |        (galvanized)
                (inches)           |          (inches)

     -----------------------------------------------------------
          5 and smaller            |    0.022 (No. 26 Gage)
     -----------------------------------------------------------
      Larger than 5 and up to 10   |    0.028 (No. 24 Gage)
     -----------------------------------------------------------
      Larger than 10 and up to 16  |    0.034 (No. 22 Gage)
     -----------------------------------------------------------
         Larger than 16            |    0.064 (No. 16 Gage)
     -----------------------------------------------------------
  For SI: 1 inch = 25.4 mm.
                             TABLE 803.9(2)
                 MINIMUM CHIMNEY CONNECTOR THICKNESS FOR
                    MEDIUM- AND HIGH-HEAT APPLIANCES
 ---------------------------------------------------------------------
                      |   EQUIVALENT ROUND    |    MINIMUM NOMINAL
         AREA         |        DIAMETER       |      THICKNESS
   (square inches)    |        (inches)       |       (inches)
 ---------------------------------------------------------------------
        0-154         |         0-14          | 0.060 (No. 16 Gage)
 ---------------------------------------------------------------------
        155-201       |         15-16         | 0.075 (No. 14 Gage)
 ---------------------------------------------------------------------
        202-254       |         17-18         | 0.105 (No. 12 Gage)
 ---------------------------------------------------------------------
   Greater than 254   |     Greater than 18   | 0.135 (No. 10 Gage)
 ---------------------------------------------------------------------
  For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm{2}.
  803.10  Installation. Connectors shall be installed in accordance with
Sections 803.10.1 through 803.10.6.
  803.10.1 Supports and joints. Connectors  shall  be  supported  in  an
approved  manner,  and joints shall be fastened with sheet metal screws,
rivets or other approved means.
  803.10.2 Length.  The  maximum  horizontal  length  of  a  single-wall
connector  shall  not  affect  the  capability  of the system to produce
adequate draft.
  803.10.3 Connection. The connector shall extend to the inner  face  of
the  chimney  or  vent  liner,  but  not  beyond. A connector entering a
masonry chimney shall be cemented to  masonry  in  an  approved  manner.
Where thimbles are installed to facilitate removal of the connector from
the  masonry chimney, the thimble shall be permanently cemented in place
with high-temperature cement.
  803.10.4 Connector pass-through. Chimney  connectors  shall  not  pass
through  any  floor or ceiling, nor through a fire-resistance-rated wall
assembly. Chimney connectors for domestic-type appliances shall not pass
through walls or partitions constructed of combustible material to reach
a masonry chimney unless:
  1. The connector is labeled for wall pass-through and is installed  in
accordance with the manufacturer's instructions; or
  2.   The   connector   is  put  through  a  device  labeled  for  wall
pass-through; or
  3. The connector has a diameter not larger than 10 inches (254 mm) and
is installed in accordance with one of the methods  in  Table  830.10.4.
Concealed  metal  parts  of the pass-through system in contact with flue
gases shall be of stainless steel or  equivalent  material  that  resist
corrosion, softening or cracking up to 1,800°F (980°C).
                             TABLE 803.10.4
                CHIMNEY CONNECTOR SYSTEMS AND CLEARANCES

                    TO COMBUSTIBLE WALL MATERIALS FOR
                 DOMESTIC HEATING APPLIANCES{a, b, c, d}
 -----------------------------------------------------------------------
                    | A 3.5-inch-thick brick wall shall be framed into
                    | the combustible wall. A 0.625-inch-thick fire-
                    | clay liner (ASTM C 315 or equivalent){e} shall be
    System A        | firmly cemented in the center of the brick wall
    (12-inch        | maintaining a 12-inch clearance to combustibles.
    clearance)      | The clay liner shall run from the outer surface
                    | of the bricks to the inner surface of the chimney
                    | liner.
 -----------------------------------------------------------------------
                    | A labeled solid-insulated factory-built chimney
                    | section (1-inch insulation) the same inside
                    | diameter as the connector shall be utilized. Sheet
                    | metal supports cut to maintain a 9-inch clearance
    System B        | to combustibles shall be fastened to the wall
    (9-inch         | surface and to the chimney section. Fasteners
    clearance)      | shall not penetrate the chimney flue liner. The
                    | chimney length shall be flush with the masonry
                    | chimney liner and sealed to the masonry with
                    | water-insolvable refractory cement. Chimney
                    | manufacturers' parts shall be utilized to
                    | securely fasten the chimney connector to
                    | the chimney connector to the chimney section.
 -----------------------------------------------------------------------
                    | A sheet metal (minimum number 24 Gage)
                    | ventilated thirable having two 1-inch air
                    | channels shall be installed with a sheet
    System C        | steel chimney connector (minimum number 24
    (6-inch         | Gage). Sheet steel supports (minimum number
    clearance)      | 24 Gage) shall be cut to maintain a 6-inch
                    | clearance between the thimble and combustibles.
                    | One side of the support shall be fastened to
                    |3the wall on all sides. Glass-fiber insulation
                    |3shall fill the 6-inch space between the thimble
                    | and the supports.
                    | A labeled solid-insulated factory-built
                    | chimney section (1-inch insulation) with a
                    | diameter 2 inches larger than the chimney
                    | connector shall be installed with a sheet
                    | steel chimney connector (minimum number 24
    System D        | Gage). Sheet metal supports shall be positioned
    (2-inch         | to maintain a 2-inch clearance to combustibles
    clearance)      | and to hold the chimney connector to ensure
                    | that a 1-inch airspace surrounds the chimney
                    | connector through the chimney section. The
                    | steel support shall be fastened to the wall on
                    | all sides and the chimney section shall be
                    | fastened to the supports. Fasteners shall not
                    | penetrate the liner of the chimney section.
 -----------------------------------------------------------------------
  For  SI:  1 inch = 25.4 mm. 1.0 Btu x in/fr{2} * h °F = 0.144 W/m{2} *
K.
  a. Insulation material that is part of the  wall  pass-through  system
shall  be  noncombustible  and  shall have a thermal conductivity of 1.0
Btuxin/ft{2}*h * °F or less.
  b. All clearances and thicknesses are minimums.

  803.10.5 Pitch. Connectors shall rise vertically  to  the  chimney  or
vent  with a minimum pitch equal to one-fourth unit vertical in 12 units
horizontal (2-percent slope).
  803.10.6  Clearances.  Connectors  shall  have  a minimum clearance to
combustibles in accordance with Table 803.10.6. The clearances specified
in Table 803.10.6 apply, except where the listing  and  labeling  of  an
appliance  specifies  a  different  clearance, in which case the labeled
clearance shall apply. The  clearance  to  combustibles  for  connectors
shall be reduced only in accordance with Section 308 or via the use of a
listed chimney or vent connector system.
                             TABLE 803.10.6
                  CONNECTOR CLEARANCES TO COMBUSTIBLES
   -----------------------------------------------------------------
                                                | MINIMUM CLEARANCE
            TYPE OF APPLIANCE                   |     (inches)
   -----------------------------------------------------------------
                        Domestic-type appliances
   -----------------------------------------------------------------
      Chimney and vent connectors               |
        Electric and oil incinerators           |        18
        Oil and solid fuel appliances           |        18
        Oil appliances labeled for venting      |
          with with Type L vents                |        9
   -----------------------------------------------------------------
                     Commercial, industrial-type appliance
   -----------------------------------------------------------------
      Low-heat appliances                       |
      Chimney connectors                        |
        Oil and solid fuel boilers, fumaces     |
          and water heaters                     |       18
        Oil unit heaters                        |       18
        Other low-heat industrial appliances    |       18
   -----------------------------------------------------------------
      Medium-heat appliances                    |
      Chimney connectors                        |
        All oil and solid fuel appliances       |       36
   -----------------------------------------------------------------
      High-heat appliances                      | In accordance
      Masonry or metal connectors               | with NFPA211
        All oil and solid fuel appliances       |
   -----------------------------------------------------------------
                              SECTION MC 804
                     DIRECT-VENT, INTEGRAL VENT AND
                        MECHANICAL, DRAFT SYSTEMS
  804.1   Direct-vent   terminations.  Vent  terminals  for  direct-vent
appliances shall be installed  in  accordance  with  the  manufacturer's
installation  instructions.  Horizontal venting shall be allowed only if
approved by the commissioner and only if in a nonhazardous location  and
if the appliance has a sealed combustion chamber.
  804.2   Appliances   with  integral  vents.  Appliances  incorporating
integral venting means shall  be  installed  in  accordance  with  their
listings  and  the  manufacturer's installation instructions. Horizontal
venting shall be allowed only if in a non hazardous location and if  the
appliance has a sealed combustion chamber.
  804.2.1  Terminal  clearances.  Appliances  designed for natural draft
venting and-incorporating integral venting, means shall  be  located  so
that a minimum clearance of 9 inches (229 mm) is maintained between vent
terminals and from any openings through which combustion products  enter

the  building. Appliances using forced draft venting shall be located so
that a minimum clearance of 12 inches (305  mm)  is  maintained  between
vent  terminals  and from any openings through which combustion products
enter the building.
  804.3  Mechanical  draft  systems.  Mechanical draft systems of either
forced or induced  draft  design  shall  comply  with  Sections  804.3.1
through 804.3.7.
  804.3.1 Forced draft systems. Forced draft systems and all portions of
induced draft systems, under positive pressure during operation shall be
designed  and  installed  so  as  to  be gas tight to prevent leakage of
combustion products into a building.
  804.3.2    Automatic     shutoff.     Power     exhausters     serving
automatically-fired  appliances  shall be electrically connected to each
appliance to prevent operation of the appliance when the power exhauster
is not in operation.
  804.3.3 Termination. The termination of  chimneys  or  vents  equipped
with  power  exhausters  shall be located a minimum of 10 feet (3048 mm)
from the lot line or from  adjacent  buildings.  The  exhaust  shall  be
directed away from the building.
  804.3.4 Horizontal terminations. Horizontal terminations shall only be
allowed  if  approved by the commissioner, if they are in a nonhazardous
location and if the appliance has a sealed  combustion  chamber  (direct
vent)  in  accordance  with  the  appliance  listing  and  manufacturers
instructions. In addition, horizontal terminations shall comply with the
following requirements:
  1. Where located adjacent to walkways, the termination  of  mechanical
draft systems shall be not less than 7 feet (2134 mm) above the level of
the walkway.
  2. Vents shall terminate at least 3 feet (914 mm) above any forced air
inlet located within 10 feet (3048 mm).
  3.  The vent system shall terminate at least 4 feet (1219 mm) below, 4
feet (1219 mm) horizontally from or 1 foot  (305  mm)  above  any  door,
window or gravity air inlet into the building.
  4. The vent termination point shall not be located closer than 3 feet
  (914  mm)  to  an  interior comer formed by two walls perpendicular to
each other.
  5. The vent termination shall not be mounted directly above or  within
3  feet  (914  mm)  horizontally  from  any  gas  or  electric metering,
regulating, venting relief equipment or other building opening.
  6. The bottom of the vent termination shall be  located  at  least  24
inches (610 mm) above finished grade.
  804.3.5 Vertical terminations. Vertical terminations shall comply with
the  following requirements and in accordance with the appliance listing
and manufacturers instructions:
  1. Chimneys serving appliances less than 600°F (316°C) shall extend at
least 3 feet (914 mm) above the highest construction,  such  as  a  roof
ridge,  parapet  wall,  or  penthouse,  within  10 feet (3048 mm) of the
chimney outlet, whether the construction is on the same building as  the
chimney  or  on another building. Any chimney located in an area that is
more than 10 feet (3048 mm) from such construction, but  not  more  than
the distance determined by Equation 8-2 shall be at least as high as the
highest  construction in such area. However, for purposes of determining
the required height of a chimney, such  construction  does  not  include
other chimneys, vents, or open structural framing.
  2.  Chimneys  serving  appliances  between  600°F  (316°C)  and 1000°F
(538°C) shall extend at least  10  feet  (3048  mm)  above  the  highest
construction.  such as a roof ridge, or parapet wall or penthouse within
20  feet (6096 mm) of the chimney outlet, whether the construction is on

the same building as the chimney or on  another  building.  Any  chimney
located  in  an area more than 20 feet (6096 mm) from such construction,
but not more than the distance determined from Equation 8-2 shall be  at
least  as  high  as  the highest construction in such area. However, for
purposes of  determining  the  required  height  of  the  chimney,  such
construction  does  not include other chimneys, vents or open structural
framing.
  3. Chimneys serving  appliances  greater  than  1000°F  (538°C)  shall
extend  at  least 20 feet (6096 mm) above the highest construction, such
as roof ridge, parapet wall, penthouse, or other obstruction  within  50
feet  (15 240 mm) of the chimney outlet, whether the  construction is on
the same building as the chimney or in  another  building.  Any  chimney
located  in  an  area  that  is  more than 50 feet (15 240 mm) from such
construction, but not more than the distance  determined  from  Equation
8-2  shall  be  at  least as high as the highest construction located in
such area. However, for purposes of determining the required  height  of
the  chimney,  such construction does not include other chimneys, vents,
or open structural framing.
  4. Vent termination caps shall not be permitted and a 3-inch  (76  mm)
minimum  drain installed to receive condensed water shall be required. A
positive means shall be provided to  prevent  water  from  entering  the
appliance.
  5.  The  following  formula  shall  be  used in order to determine the
distance referred to in Items 1, 2 and 3 of this section:

   ______________________________________________________________
   1                                                            |
   2                                                            |
   3          COPY OF EQUATION 8-2                              |
   4          MAY BE OBTAINED FROM:                             |
   5          NYS LEGISLATIVE BILL DRAFTING COMMISSION          |
   6          CONTACT: LEGISLATIVE RETRIEVAL SYSTEM'S HELPLINE  |
   7                                                            |
   8                                                            |
   9____________________________________________________________|

  804.3.6 Exhauster connections. An appliance vented  by  natural  draft
shall  not  be  connected  into a vent, chimney or vent connector on the
discharge side of a mechanical flue exhauster.
  804.3.7 Exhauster sizing. Mechanical  flue  exhausters  and  the  vent
system  served  shall  be  sized  and  installed  in accordance with the
manufacturer's installation instructions.
  804.3.8 Mechanical draft systems for  manually  fired  appliances  and
fireplaces. A mechanical draft system shall be permitted to be used with
manually fired appliances and fireplaces where such system complies with
all of the following requirements:
  1.  The  mechanical  draft  device  shall  be  listed and installed in
accordance with the manufacturer's installation instructions.
  2. A device shall be  installed  that  produces  visible  and  audible
warning  upon  failure  of  the  mechanical  draft  device  or  loss  of
electrical power, at any time that the mechanical draft device is turned
on. This device shall be equipped with a battery backup if  it  receives
power from the building wiring.
  3.  A smoke detector shall be installed in the room with the appliance
or fireplace. This device shall be equipped with a battery backup if  it
receives power from the building wiring.
                             SECTION MC 805
                         FACTORY-BUILT CHIMNEYS

805.1  Listing.  Factory-built  chimneys shall be listed and labeled and
shall be installed and terminated in accordance with this code  and  the
manufacturer's installation instructions.
  805.2 Solid fuel appliances. Factory-built chimneys for use with solid
fuel-burning appliances shall comply with the Type HT requirements of UL
103.
  Exception:  Chimneys  for  use with fireplace stoves listed only to UL
737 shall comply with the requirements of UL 103.
  805.3 Factory-built fireplaces. Chimneys for  use  with  factory-built
fireplaces shall comply with the requirements of UL 127.
  805.4   Support.   Where   factory-built  chimneys  are  supported  by
structural members, such as joists and rafters, such  members  shall  be
designed to support the additional load.
  805.5  Medium-heat  appliances. Factory-built chimneys for medium-heat
appliances producing flue  gases  having  a  temperature  above  1,000°F
(538°C),  measured  at the entrance to the chimney, shall comply with UL
959.
  805.6 Decorative shrouds. Decorative, shrouds shall not  be  installed
at  the  termination of factory-built chimneys except where such shrouds
are listed and labeled for use with the specific  factory-built  chimney
system and are installed in accordance with Section 304.1.
                             SECTION MC 806
                             METAL CHIMNEYS
806.1  General.  Metal  chimneys  shall  be constructed and installed in
accordance with NFPA 211.
  806.2 Exterior  metal  chimneys.  Exterior  metal  chimneys  shall  be
galvanized,  painted on the exterior surface with a heat resisting paint
or constructed of equal corrosion resistive alloys.
                             SECTION MC 807
                       CHANGES IN APPLIANCE FUELS
807.1 Changes in appliance fuels. Conversion from gas to fuel oil for  a
heating appliances shall be made only if:
  1.  The  chimney design meets the requirements of this chapter for the
conversion fuel; and
  2. The chimney size is adequate to vent the combustion  products  from
the new fuel. Conversion from solid or liquid fuels to natural gas fuels
for heating appliances shall be made only if:
  2.1  The chimney design meets the requirements of this chapter for the
conversion fuel and the New York City Fuel Gas Code;
  2.2 The chimney is thoroughly  cleaned  prior  to  the  conversion  to
remove  collected flue deposits, which can spill off when gas is used as
a fuel;
  2.3 Chimney provides adequate draft the new fuel;
  2.4 Drains are installed to remove condensed water; and
  2.5 Gas vents are installed within the chimney for  venting,  purposes
if required by the appliance listing.
                             SECTION MC 808
                         REDUCTION OF FLUE SIZE
808.1 Reduction of flue size. Conversion from one fuel to another or the
use  of  an  existing  chimney  to  service  a fireplace or wood-burning
appliance may require a flue size change for proper operation. This  may
be  done  if  the  redesigned  flue  meets the criteria for the fuel and
chimney type to be used as set forth in this chapter.
                             SECTION MC 809
                    CHIMNEY SUPPORTED FROM EQUIPMENT
809.1 Chimney support. Chimneys shall not be supported by the  equipment
they  serve,  unless  such  equipment has been specifically designed for
such loads.

                             SECTION MC 810
                         TEST RUN AND SMOKE TEST
810.1  Test  run.  All  new  chimneys  shall be test run under operating
conditions to demonstrate fire safety and  the  complete  exhausting  of
smoke  and  the  products  of  combustion to the outer air. The test run
shall be conducted by a registered design professional  responsible  for
the test, and the results of such test run shall be certified as correct
by such professional and submitted in writing to the department.
  810.2  Requirement  of  a  smoke  test.  A smoke test shall be made as
outlined in Section 810.3. Any faults or leaks found shall be corrected.
Such  smoke  test  shall  be  witnessed  by  a  representative  of   the
commissioner.  In  lieu  thereof,  the  commissioner may accept the test
report of a registered design  professional  responsible  for  the  test
which shall be submitted in writing to the department.
  810.3  Smoke test. To determine the tightness of chimney construction,
a smoke test shall be made in accordance with the  following  conditions
and requirements:
  1.  The  equipment, materials, power and labor necessary for such test
shall be furnished by, and at the expense of, the owner or holder of the
work permit.
  2. If the test shows any evidence of leakage or  other  defects,  such
defects  shall  be corrected in accordance with the requirements of this
chapter,  and  the  test  shall  be  repeated  until  the  results   are
satisfactory.
  3. The chimney shall be filled with a thick penetrating smoke produced
by  one  or  more  smoke  machines,  or smoke bombs, or other equivalent
method.  As the smoke appears at the stack opening  on  the  roof,  such
opening  shall  be  tightly closed and a pressure equivalent to 1/2 inch
(13 mm) column of water measured at the base  of  the  stack,  shall  be
applied.  The  test  shall be applied for a length of time sufficient to
permit the inspection of the chimney.
                             SECTION MC 811
             EXHAUST GASES FROM INTERNAL COMBUSTION ENGINES
811.1  Exhaust  pipe  construction.  The  exhaust  pipe  from   internal
combustion   engines   shall  be  constructed  in  accordance  with  the
requirements for metal chimneys in this chapter. NFPA 211  and  NFPA  37
based  on the temperature of the gases entering the exhaust pipe, and in
accordance with the following:
  1. The exhaust pipe, if factory fabricated  shall  be  constructed  in
accordance with their listing and manufacturers instructions.
  2.  The  exhaust pipe, if field fabricated, shall be constructed of at
least 1/16-inch (5 mm) steel, or of other equivalent  metal  of  similar
strength  and  resistance to the temperature and corrosive action of the
exhaust gases.
  3. No lining shall be required.
  4. Where the  exhaust  pipe  runs  inside  a  building,  it  shall  be
insulated  with  insulation adequate for the temperature of the pipe, so
that the surface temperature shall be not more than 200°F (93°C).
  5. All joints shall be constructed so as to be  gas  tight  under  all
operating conditions.
  811.2  Discharge  openings.  The  location  of  discharge openings for
emergency and standby internal combustion engines shall comply with  the
requirements  of  NFPA  37  so  that  the flue gases are not directed to
jeopardize  the  health  or  safety  of  people,  overheat   combustible
structures,  nor  enter building openings in the vicinity of the outlet,
nor shall the location of such openings cause the condensate leaving the
outlet to come into contact with people.

  811.2.1 Interference.  No  discharge  opening  shall  be  located  and
constructed  so  as  to  interfere  with the proper functioning of other
openings in the same  building  or  adjoining  buildings,  to  interfere
unreasonably  with  the  occupants  of  the  same  building or adjoining
buildings,  or  with  the  general public, or to create a fire or health
hazard.
  811.2.2 Chimneys. The exhaust pipe may be connected to a chimney  used
for  other equipment, provided that the operation of the engine does not
adversely affect the operation of the other equipment so that it  is  in
violation of the New York City Air Pollution Control Code.
  811.3 Vertical termination requirements. The location of the discharge
outlet from all other engines shall comply with the vertical termination
requirements  of at least a 600°F (316°C) to 1000°F (538°C) chimney or a
greater than 1000°F (538°C) chimney based  on  the  temperature  of  the
gases entering the exhaust pipe.
                                CHAPTER 9
                   SPECIFIC APPLIANCES, FIREPLACES AND
                      SOLID FUEL-BURNING EQUIPMENT

                             SECTION MC 901
                                 GENERAL
901.1   Scope.   This   chapter   shall  govern  the  approval,  design,
installation, construction, maintenance, alteration and  repair  of  the
appliances    and   equipment   specifically   identified   herein   and
factory-built   fireplaces.   The   approval,   design,    installation,
construction, maintenance, alteration and repair of gas-fired appliances
shall be regulated by the New York City Fuel Gas Code.
  901.2  General.  The  requirements  of this chapter shall apply to the
mechanical equipment  and  appliances  regulated  by  this  chapter,  in
addition  to  the  other  requirements  of  this  code, and installed in
accordance with the requirements of NFPA 31, NFPA 54 and NFPA 211.
  901.3  Hazardous  locations.   Fireplaces   and   solid   fuel-burning
appliances shall not be installed in hazardous locations.
  901.4  Fireplace  accessories.  Listed  fireplace accessories shall be
installed in accordance with the  conditions  of  the  listing  and  the
manufacturer's installation instructions.
  901.5  Inspection  of  solid fuel-burning heating appliances, chimneys
and  flues.  Inspections  of  solid  fuel  burning  heating  appliances,
chimneys  and  flues  shall  be  in  accordance  with  the New York City
Building Code.
  901.6 Fireplaces. Fireplaces (solid-fuel-type or ANSI Z21.50) shall be
installed with tight-fitting noncombustible fireplace doors  to  control
infiltration losses in construction types listed here:
  1. Masonry or factory-built fireplaces designed to allow an open burn.
  2. Decorative appliances (ANSI Z21.60 gas-log style unit) installed in
a vented solid fuel fireplace.
  3.  Vented  decorative  gas  fireplace  appliances (ANSI Z21.50 unit).
Fireplaces shall be provided with a source of combustion air as required
by the fireplace construction provisions of the New York  City  Building
Code and Chapter 7 of this code.
                             SECTION MC 902
                           MASONRY FIREPLACES
902.1  General.  Masonry  fireplaces  shall be constructed in accordance
with the New York City Building Code.
                             SECTION MC 903
                        FACTORY-BUILT FIREPLACES

903.1 General. Factory-built fireplaces shall be listed and labeled  and
shall  be  installed  in  accordance with the conditions of the listing.
Factory-built fireplaces shall be tested in accordance with UL 127.
  903.2  Hearth  extensions. Hearth extensions of approved factory-built
fireplaces and fireplace stoves shall be installed  in  accordance  with
the  listing  of  the  fireplace.  The hearth extension shall be readily
distinguishable from the surrounding floor area.
  903.3 Unvented gas lob heaters. The installation of unvented gas fired
space heaters, gas stoves, gas logs, gas fireplaces  and  gas  fireplace
inserts is prohibited.
  903.4  Flues. Separate flues shall be provided for every fireplace and
fireplace stove.
  903.5  Combustion  air  supply.  All  installations  of  factory-built
fireplaces  shall  comply  with  the  requirements  of the New York City
Energy Conservation Code concerning combustion air supply.
                              SECTION MC 904
                     PELLET FUEL-BURNING APPLIANCES
  904.1 General. Pellet fuel-burning  appliances  shall  be  listed  and
labeled  and  shall  be  installed  in  accordance with the teems of the
listing. If permitted, such appliances shall be operated  in  accordance
with the New York City Air Pollution Control Code.
                              SECTION MC 905
                    FIREPLACE STOVES AND ROOM HEATERS
  905.1 General. Fireplace stoves and solid-fuel-type room heaters shall
be  listed  and  labeled  and  shall be installed in accordance with the
conditions  of  the  listing.  Fireplace  stoves  shall  be  tested   in
accordance  with UL 737. Solid-fuel-type room heaters shall be tested in
accordance with UL 1482. Fireplace inserts intended for installation  in
fireplaces   shall   be  listed  and  labeled  in  accordance  with  the
requirements of UL 1482 and shall be installed in  accordance  with  the
manufacturer's installation instructions.
  905.2     Connection  to  fireplace.  The  connection  of  solid  fuel
appliances  to  chimney  flues  serving  fireplaces  shall  comply  with
Sections 801.7 and 801.10.
  905.3  Air  pollution.  All  fireplace  stoves  and room heaters shall
comply with the requirements of the New York City Air Pollution  Control
Code.
  905.4  Combustion  air  supply.  All fireplace stoves and room heaters
shall  comply  with  the  requirements  of  the  New  York  City  Energy
Conservation Code concerning combustion air supply.
  905.5  Flues.  Separate  flues  and  independent combustion air source
shall be provided for every fireplace stove and room heater.  Combustion
air   shall   be   provided   in   accordance  with  the  manufacturer's
recommendations and Chapter 7.
                              SECTION MC 906
                    FACTORY-BUILT BARBECUE APPLIANCES
  906.1 General.  Factory-built  barbecue  appliances  shall  be  of  an
approved   type   and   shall   be  installed  in  accordance  with  the
manufacturer's installation instructions, this chapter and  Chapters  3,
5,  7,  8  and  the  New York City Fuel Gas Code. All provisions for the
construction and installation of fireplaces shall be complied within the
construction and installation of barbecue grills.
                             SECTION MC 907
                      INCINERATORS AND CREMATORIES
907.1 General. Incinerators and crematories shall be listed and  labeled
in  accordance  with  UL  791  and  NFPA  82  and  shall be installed in
accordance with the manufacturer's installation instructions.

  907.2 Compliance. All incinerators and crematories shall be installed,
altered and maintained in buildings in conformity  with  the  applicable
provisions  of  the  Administrative  Code  and  the  New  York  City Air
Pollution Control Code.
                             SECTION MC 908
                       COOLING TOWERS, EVAPORATIVE
                      CONDENSERS AND FLUID COOLERS
908.1   General.   A   cooling   tower   used  in  conjunction  with  an
air-conditioning appliance shall be installed  in  accordance  with  the
manufacturer's installation instructions.
  908.2 Access. Cooling towers, evaporative condensers and fluid coolers
shall be provided with ready access.
  908.3  Location.  Cooling  towers  evaporative  condensers  and  fluid
coolers shall be located to prevent  the  discharge  vapor  plumes  from
entering occupied spaces. Plume discharges shall be not less than 5 feet
(1524  mm) above or 20 feet (6096 mm) away from any ventilation inlet to
a building. Location on the property shall be as required for  buildings
in accordance with the New York City Building Code.
  908.3.1  Indoor.  Cooling  towers,  evaporative  condensers  and fluid
coolers  located  inside  of   buildings   shall   be   constructed   of
noncombustible materials including fill and drift eliminators.
  908.3.2 Outside. Cooling towers shall be constructed of noncombustible
materials.
  Exception:   Fill  and  drift  eliminators  may  be  made  of  limited
combustibility materials provided all the following conditions are met:
  1. The cooling tower is located on a building  in  construction  group
1-A or 1-B of the New York City Building Code.
  2.  The cooling tower. fill and drift eliminators are located at least
30 feet (9144 mm) away from windows or fresh air intakes which are at an
elevation above the roof on which the cooling tower is located,  whether
in the same building or in an adjoining building.
  3.  The  cooling tower is located not less than 15 feet (4572 mm) from
the lot line.
  4. The cooling tower is located not less than 10 feet (3048  mm)  from
any  chimney,  except  that  the distance shall not be less than 20 feet
(6096 mm) from a chimney venting products of combustion other than  from
gas  or  oil-fired  appliances,  whether  on  the  same  or an adjoining
building.
  908.4 Support and anchorage. Supports for cooling towers,  evaporative
condensers  and  fluid  coolers shall be designed in accordance with the
New York City Building Code. Seismic restraints shall be as required  by
the  New  York City Building Code. Adequate vibration isolation shall be
provided in accordance with the manufacturer's  installation  guidelines
and as required for the supporting structure, and in accordance with the
following:
  908.4.1  Cooling towers. All moving parts of cooling towers located on
a roof or floor other than a  floor  on  grade  shall  be  installed  on
vibration  isolators  providing  a  minimum  isolation  efficiency of 85
percent at fan rotor rpm with a maximum static deflection  of  4  inches
(102  mm).  Each  isolator  shall  incorporate  a  leveling device and a
resilient pad having a minimum thickness of 1/4 inch (6 mm).
  908.4.2 Evaporative condensers. Evaporative and air cooled  condensers
located  on a roof or floor other than a floor on grade shall be mounted
on vibration isolators providing a minimum isolation  efficiency  of  85
percent  at  fan  rotor rpm with a maximum static deflection of 4 inches
(102 mm). Each isolator  shall  incorporate  a  leveling  device  and  a
resilient pad having a minimum thickness of 1/4 inch (6 mm).

  908.5 Water supply. Water supplies and protection shall be as required
by the New York City Plumbing Code.
  908.6  Drainage.  Drains,  overflows  and blowdown provisions shall be
indirectly connected to an  approved  disposal  location.  Discharge  of
chemical   waste   shall  be  approved  by  the  appropriate  regulatory
authority.
  908.7 Refrigerants and hazardous fluids. Heat exchange equipment  that
contains a refrigerant and that is part of a closed refrigeration system
shall  comply  with  Chapter 11. Heat exchange equipment containing heat
transfer fluids which are combustible or hazardous shall comely with the
New York City Fire Code. Flammable heat transfer fluids are prohibited.
                             SECTION MC 909
                          VENTED WALL FURNACES
  909.1 General. Vented wall furnaces shall be installed  in  accordance
with  their  listing  and  the manufacturer's installation instructions.
Oil-fired furnaces shall be tested in accordance with UL 730.
  909.2 Location. Vented wall furnaces shall be located  so  as  not  to
cause  a fire hazard to walls, floors, combustible furnishings or doors.
Vented wall furnaces installed between  bathrooms  and  adjoining  rooms
shall not circulate air from bathrooms to other parts of the building.
  909.3 Door swing. Vented wall furnaces shall be located so that a door
cannot  swing within 12 inches (305 mm) of an air inlet or air outlet of
such furnace measured at right angles to the opening. Doorstops or  door
closers shall not be installed to obtain this clearance.
  909.4  Ducts prohibited. Ducts shall not be attached to wall furnaces.
Casing extension boots shall not be installed unless listed as  part  of
the appliance.
  909.5  Manual shutoff valve. A manual shutoff valve shall be installed
ahead of all controls.
  909.6 Access. Vented wall furnaces shall be provided with  access  for
cleaning  of  heating  surfaces,  removal  of  burners,  replacement  of
sections, motors, controls, filters and other  working  parts,  and  for
adjustments  and  lubrication of parts requiring such attention. Panels,
grilles and access doors that  must  be  removed  for  normal  servicing
operations shall not be attached to the building construction.
                             SECTION MC 910
                             FLOOR FURNACES
  910.1  General.  Floor  furnaces shall be installed in accordance with
their  listing  and  the   manufacturer's   installation   instructions.
Oil-fired  furnaces  shall be tested in accordance with UL 729. Unvented
floor furnaces are prohibited.
  910.2  Placement.  Floor  furnaces  shall  not  be  installed  in  any
corridor,  in  the  floor  of any aisle or passageway of any auditorium,
public hall, place of assembly, or in any egress element from  any  such
room or space.
  With  the exception of wall register models, a floor furnace shall not
be placed closer than 6 inches (152 mm) to the nearest  wall,  and  wall
register  models  shall not be placed closer than 6 inches (152 mm) to a
corner.
  The furnace shall be placed such that a drapery or similar combustible
object will not be nearer than 12 inches (305 mm) to any portion of  the
register  of  the  furnace.  Floor  furnaces  shall  not be installed in
concrete floor construction built on grade. The  controlling  thermostat
for  a  floor  furnace shall be located within the same room or space as
the floor furnace or shall be located in an adjacent room or space  that
is  permanently  open to the room or space containing the floor furnace.
Floor furnaces shall be located so as to be accessible.  Floor  furnaces
shall  be installed only in floors of noncombustible construction having

at least a 2-hour fire rating, except as where  required  for  one-  and
two-family dwellings.
  910.3 Bracing. The floor around the furnace shall be braced and headed
with  a  support  framework  design in accordance with the New York City
Building Code.
  910.4 Clearance. The lowest portion of the floor  furnace  shall  have
not  less  than a 6-inch (152 mm) clearance from the grade level; except
where the lower 6-inch (152 mm) portion of the floor furnace  is  sealed
by  the manufacturer to prevent entrance of water, the minimum clearance
shall be reduced to  not  less  than  2  inches  (51  mm).  Where  these
clearances  are  not present, the ground below and to the sides shall be
excavated to form a pit under the furnace so that the required clearance
is provided beneath the lowest portion of the furnace.  A  12-inch  (305
mm)  minimum clearance shall be provided on all sides except the control
side, which shall have an 18-inch (457 mm) minimum clearance.
  910.5 Enclosures. Enclosures of floor furnaces  shall  be  constructed
entirely of noncombustible materials with a fire-resistance rating of at
least  1  hour and shall be provided with adequate outdoor air to ensure
proper combustion. The enclosure shall be provided with  adequate  means
of access for servicing the furnace.
  910.6  Duct  temperature.  The  outlet  duct  temperature  of warm air
heating furnaces shall not be greater than 250°F (121°C).
  910.7 One- and two- family dwellings. Floor furnace  enclosures  shall
be constructed of noncombustible materials with a fire-resistance rating
of  at  least 1 hour. Means shall be provided for supporting the furnace
when the grille is removed. Clearances shall be provided as per NFPA 54.
                             SECTION MC 911
                              DUCT FURNACES
  911.1 General. Duct furnaces shall be installed in accordance with the
manufacturer's installation instructions.  Electric  furnaces  shall  be
tested in accordance with UL 1995. Unvented furnaces are prohibited.
  911.2  Access  panels.  Ducts  connected  to  duct furnaces shall have
removable access panels on both the upstream and downstream sides of the
furnace.
  911.3 Location of draft hood and controls.  The  controls,  combustion
air inlets and draft hoods for duct furnaces shall be located outside of
the  ducts.  The  draft hood shall be located in the same enclosure from
which combustion air is taken.
  911.4 Circulating air. Where a  duct  furnace  is  installed  so  that
supply  ducts  convey  air  to  areas  outside  the space containing the
furnace, the return air shall also be conveyed by a  duct(s)  sealed  to
the  furnace  casing  and  terminating  outside the space containing the
furnace.The duct furnace shall be installed  on  the  positive  pressure
side of the circulating air blower.
  911.5  Duct  Temperature. The outlet duct temperature of duct furnaces
shall not be greater than 20°F (121°C).
                             SECTION MC 912
                        INFRARED RADIANT HEATERS
  912.1 Support. Infrared radiant heaters shall be safely and adequately
fixed in an approved position independent of fuel  and  electric  supply
lines. Hangers and brackets shall be noncombustible material.
  912.2  Clearance.  Heaters  shall  be  installed  with clearances from
combustible material in accordance with the manufacturer's  installation
instructions.
                             SECTION MC 913
                             CLOTHES DRYERS
  913.1  General.  Clothes  dryers shall be installed in accordance with
the  manufacturer's  installation  instructions.   Electric   commercial

clothes  dryers  shall  be  tested  in accordance with UL 1240. Electric
residential  and  coin-operated  clothes  dryers  shall  be  tested   in
accordance with UL 2158.
  913.2   Exhaust   required.  Clothes  dryers  shall  be  exhausted  in
accordance with Section 504.
  Exception: Electric clothes dryers provided with a condensate drain.
  913.3 Clearances. Clothes dryers shall be installed with clearance  to
combustibles in accordance with the manufacturer's instructions.
                             SECTION MC 913
                              SAUNA HEATERS
  914.1 Location and protection. Sauna heaters shall be located so as to
minimize the possibility of accidental contact by a person in the room.
  914.1.1  Guards.  Sauna  heaters  shall  be  protected from accidental
contact by an approved  guard  or  barrier  of  material  having  a  low
coefficient  of  thermal conductivity. The guard shall not substantially
affect the transfer of heat from the heater to the room.
  914.2 Installation. Sauna heaters shall  be  listed  and  labeled  and
shall   be   installed   in   accordance  with  their  listing  and  the
manufacturer's installation instructions.
  914.3 Access. Panels, grilles and access doors that are required to be
removed for normal servicing operations shall not  be  attached  to  the
building.
  914.4  Heat  and time controls. Sauna heaters shall be equipped with a
thermostat that will limit room temperature  to  194°F  (90°C).  If  the
thermostat   is   not  an  integrate  part  of  the  sauna  heater,  the
heat-sensing element shall be located within 6 inches (152  mm)  of  the
ceiling.  If  the heat-sensing element is a capillary tube and bulb, the
assembly shall be attached to the wall or other support,  and  shall  be
protected against physical damage.
  914.4.1 Timers. A timer, if provided to control main burner operation,
shall have a maximum operating time of 1 hour. The control for the timer
shall be located outside the sauna room.
  914.5  Sauna  room. A ventilation opening into the sauna room shall be
provided. The opening shall be not less than 4 inches by 8  inches  (102
mm by 203 mm) located near the top of the door into the sauna room.
  914.5.1 Warning notice. The following permanent notice, constructed of
approved  material,  shall be mechanically attached to the sauna room on
the outside:
  WARNING: DO NOT EXCEED 30 MINUTES IN SAUNA. EXCESSIVE EXPOSURE CAN  BE
HARMFUL  TO  HEALTH.  ANY  PERSON  WITH  POOR  HEALTH  SHOULD  CONSULT A
PHYSICIAN BEFORE USING SAUNA.
  The words shall contrast with the background and the wording shall  be
in letters not less than 0.25-inch (6.4 mm) high.
  Exception:  This  section  shall  not  apply  to  one-  and two-family
dwellings.
                             SECTION MC 915
                     ENGINE AND GAS TURBINE-POWERED
                        EQUIPMENT AND APPLIANCES
  915.1 General. The installation of liquid-fueled  stationary  internal
combustion  engines and gas turbines, including fuel storage and piping,
shall meet the requirements of NFPA 37 and Chapter 13 of this code.
  915.2  Powered  equipment  and   appliances.   Permanently   installed
equipment  and  appliances  powered  by  internal combustion engines and
turbines shall  be  installed  in  accordance  with  the  manufacturer's
installation instructions and NFPA 37.
                             SECTION MC 916
                          POOL AND SPA HEATERS

  916.1  General.  Pool and spa heaters shall be installed in accordance
with the manufacturer's installation instructions.  Oil-fired  pool  and
spa heaters shall be tested in accordance with UL 726. Electric pool and
spa heaters shall be tested in accordance with UL 1261.
                             SECTION MC 917
                           COOKING APPLIANCES
  917.1  Cooking  appliances.  Cooking  appliances that are designed for
permanent  installation,  including  ranges,  ovens,  stoves,  broilers,
grills,  fryers,  griddles  and  barbecues, shall be listed, labeled and
installed   in   accordance   with   the   manufacturer's   installation
instructions.   Oil-fired   cooking  appliances  are  prohibited.  Solid
fuel-fired ovens shall be tested in accordance with UL 2162.
  917.2 Prohibited location. Cooking appliances designed, tested, listed
and labeled for use in commercial occupancies  shall  not  be  installed
within  dwelling  units  or  within  any  area  where  domestic  cooking
operations occur.
  917.3  Domestic  appliances.  Cooking  appliances   installed   within
dwelling  units and within areas where domestic cooking operations occur
shall be listed and labeled as household-type  appliances  for  domestic
use.
  917.4  Domestic  range  installation.  Domestic  ranges  installed  on
combustible floors shall be set on their own bases or legs and shall  be
installed with clearances of not less than that shown on the label.
  917.5  Open-top  broiler  unit  hoods.  A  ventilating  hood  shall be
provided above a domestic open-top broiler unit, unless otherwise listed
for forced down draft ventilation.
  917.5.1 Clearances. A minimum clearance of 24 inches (610 mm) shall be
maintained between the cooking top and combustible  material  above  the
hood.  The  hood  shall be at least as wide as the open-top broiler unit
and be centered over the unit.
  917.6  Commercial  cooking  appliance  venting.   Commercial   cooking
appliances,  other  than those exempted by Section 501.8 of the New York
City Fuel Gas Code, shall be vented by connecting  the  appliance  to  a
vent  or  chimney  in  accordance  with  this  code  and  the  appliance
manufacturer's  instructions  or  the  appliance  shall  be  vented   in
accordance with Section 505.1.1 of the New York City Fuel Gas Code.
  917.7  Domestic  ventilation.  When  a  hood  is  required  for proper
ventilation of a domestic cooking appliance, the exhaust and make-up air
systems shall be properly engineered and  designed  in  accordance  with
Chapter 5.
                             SECTION MC 918
                      FORCED-AIR WARM-AIR FURNACES
  918.1  Forced-air  furnaces.  Oil-fired  furnaces  shall  be tested in
accordance with UL 727. Electric furnaces shall be tested in  accordance
with  UL 1995. Solid fuel furnaces shall be tested in accordance with UL
391. Forced-air furnaces shall  be  installed  in  accordance  with  the
listings  and  the  manufacturer's installation instructions. Forced-air
warm-air furnaces shall be installed in accordance with the requirements
of NFPA 31 and the New York City Fuel Gas Code.  Unvented  furnaces  are
prohibited.
  918.2  Minimum  duct sizes. The minimum unobstructed total area of the
outside and return air  ducts  or  openings  to  a  forced-air  warm-air
furnace  shall  be  not  less than 2 square inches per 1,000 Btu/h (4402
mm{2}kW) output rating capacity of the furnace and not  less  than  that
specified  in  the furnace manufacturer's installation instructions. The
minimum unobstructed total  area  of  supply  ducts  from  a  forced-air
warm-air  furnace  shall not be less than 2 square inches for each 1,000
Btu/h (4402mm{2}/kW) output rating capacity of the furnace and not  less

than   that   specified   in  the  furnace  manufacturer's  installation
instructions.
  Exception:  The  total  area  of  the supply air ducts and outside and
return air ducts shall not be required to be  larger  than  the  minimum
size  required  by  the furnace manufacturer's installation instructions
and in accordance with NFPA 54.
  918.3 Heat pumps. The minimum unobstructed total area of  the  outside
and return air ducts or openings to a heat pump shall be not less than 6
square  inches  per  1,000  Btu/h  (13 208 mm{2}/kW) output rating or as
indicated by the conditions of listing of the heat pump.  Electric  heat
pumps shall be tested in accordance with UL 1995.
  918.4  Dampers. Volume dampers shall not be placed in the air inlet to
a furnace in a manner that will  reduce  the  required  to  air  to  the
furnace.
  918.5   Circulating   air  ducts  for  forced-air  warm-air  furnaces.
Circulating air for  fuel-burning,  forced-air-type,  warm-air  furnaces
shall  be  conducted  into  the  blower housing from outside the furnace
enclosure by continuous air-tight ducts.
  918.6 Prohibited sources. Outside  or  return  air  for  a  forced-air
heating system shall not be taken from the following locations:
  1. Closer than 10 feet (3048 mm) from an appliance vent outlet, a vent
opening  from  a  plumbing drainage system or the discharge outlet of an
exhaust fan, unless the outlet is 3 feet (914 mm) above the outside  air
inlet.
  2.  Where  the  is  the  presence  of  objectionable  odors,  fumes or
flammable vapors; or where located less than 10 feet (3048 mm) above the
surface of any abutting public way or  driveway;  or  where  located  at
grade level by a sidewalk, street, alley or driveway.
  3.  A  hazardous  or  unsanitary location or a refrigeration machinery
room as defined in this code.
  4. A room or space, the volume of which is less than 25 percent of the
entire volume served by such system.  Where  connected  by  a  permanent
opening having an area sized in accordance with Sections 918.2 and 918.3
adjoining  rooms or spaces shall be considered as a single room or space
for the purpose of determining the volume of such rooms or spaces.
  Exception: The minimum volume requirement shall not  apply  where  the
amount of return air taken from a room or space is less than or equal to
the amount of supply air delivered to such room or space.
  5.  A closet, bathroom, toilet room, kitchen, garage, mechanical room,
boiler room or furnace room.
  6. A room or space containing a fuel-burning appliance where such room
or space serves as the sole source of return air.
  Exceptions:
  1. This  shall  not  apply  where  the  fuel-burning  appliance  is  a
direct-vent appliance.
  2.  This  shall  not  apply  where the room or space complies with the
following requirements:
  2.1 The return air shall be taken from a room or space having a volume
exceeding 1 cubic foot for each 10 Btu/h (9.6  L/W)  of  combined  input
rating of all fuel-burning appliances therein.
  2.2.  The  volume  of  supply  air discharged back into the same space
shall be approximately equal to the volume of return air taken from  the
space.
  2.3.  Return-air  inlets shall not be located within 10 feet (3048 mm)
of any appliance firebox or draft hood in the same room or space.
  3.  This  shall  not  apply  to  rooms  or  spaces  containing   solid
fuel-burning appliances, provided that return-air inlets are located not
less than 10 feet (3048 mm) from the firebox of such appliances.

  918.7 Outside opening protection. Outdoor air intake openings shall be
protected in accordance with Section 401.6.
  918.8  Return-air  limitation. Return air from one dwelling unit shall
not be discharged into another dwelling unit.
                             SECTION MC 919
                           CONVERSION BURNERS
919.1 Conversion burners. The installation of conversion  burners  shall
conform to ANSI Z21.8.
                             SECTION MC 920
                              UNIT HEATERS
920.1  General.  Unit  heaters shall be installed in accordance with the
listing and the manufacturer's installation instructions. Oil-fired unit
heaters shall be tested in accordance with UL 731.
  920.2 Support. Suspended-type  unit  heaters  shall  be  supported  by
elements that are designed and constructed to accommodate the weight and
dynamic loads. Hangers and brackets shall be of noncombustible material.
Suspended-type  oil-fired  unit heaters shall be installed in accordance
with NFPA 31.
  920.3 Ductwork. A unit heater shall not be attached to a warm-air duct
system unless listed for such installation.
                             SECTION MC 921
                           VENTED ROOM HEATERS
921.1 General. Vented room heaters shall be listed and labeled and shall
be installed in accordance with the conditions of the  listing  and  the
manufacturer's instructions.
                             SECTION MC 922
                      KEROSENE AND OIL-FIRED STOVES
922.1  General.  The  installation  of  kerosene and oil-fired stoves is
prohibited.
                             SECTION MC 923
                           SMALL CERAMIC KILNS
923.1 General. The provisions of this section shall apply to kilns  that
are  used  for ceramics, have a maximum interior volume of 20 cubic feet
(0.566 m{3}) and are used for hobby and noncommercial purposes.
  923.1.1 Installation. Kilns shall be installed in accordance with  the
manufacturer's  installation  instructions  and  the  provisions of this
code.
                             SECTION MC 924
                    STATIONARY FUEL CELL POWER PLANTS
  924.1 General. Stationary fuel cell power plants having a power output
not exceeding 1,000 kW, shall be tested in accordance with  ANSI  Z21.83
and  shall  be  installed in accordance with manufacturer's installation
instructions and NFPA 853. Such fuel cell plants  shall  be  powered  by
hydrogen  derived  on-site  from  piped  natural  gas,  except where the
storage, handling  and  use  of  hydrogen  or  other  flammable  gas  is
authorized  by  the Fire Code for such purposes and approved by the fire
commissioner.
                              SECTION MC 925
                             MASONRY HEATERS
  925.1 General. Masonry heaters shall be constructed in accordance with
the New York City Building Code.
                              SECTION MC 926
                       NOISE CONTROL REQUIREMENTS
  926.1 Minimum air-borne noise insulation requirements.
  926.1.1 Exterior  mechanical  equipment.  Mechanical  equipment  in  a
building in any occupancy group, when located outside of the building in
a  yard  or  court  or  on  a  roof, or where the equipment opens to the
exterior  of  the  building,  shall  be  subject  to  the  noise  output

limitations given in Table 926.1 where one or more windows of a dwelling
unit  in any building in occupancy groups R-1, R-2, and R-3, are located
within a sphere of 100 foot radius (30 480 mm) whose center is any  part
of  the  equipment or its housing, unless it can be shown that the sound
pressure levels, in octave bands, of the exterior  mechanical  equipment
as  measured  within the dwelling unit do not exceed the levels given in
Table 926.1(2).
                             TABLE 926.1(1)
 MAXIMUM SOUND POWER LEVELS PERMITTED FOR EXTERIOR MECHANICAL EQUIPMENT
                           ADJOINING BUILDINGS
                  |           Maximum Sound Power Levels in
                  |        Octave Bands - db re 10{-13} Watts{a}
------------------------------------------------------------------------
     Minimum      |         Octave Bands c.p.s. Mid Frequency
  distance from   |      |      |      |     |     |      |      |
  equipment to    |  63  | 125  | 250  | 500 |1000 | 2000 | 4000 |8000
 exterior window  |      |      |      |     |     |      |      |
    (ft.){a}      |      |      |      |     |     |      |      |
------------------------------------------------------------------------
     12           |  97  |  90  |  83  |  78 |  75 |  73  |  72  |  71
------------------------------------------------------------------------
     25           | 104  |  96  |  89  |  84 |  81 |  79  |  78  |  77
------------------------------------------------------------------------
     50           | 110  | 102  |  95  |  90 |  87 |  85  |  84  |  83
------------------------------------------------------------------------
    100           | 116  | 108  | 101  |  96 |  93 |  91  |  90  |  89
------------------------------------------------------------------------
                  |           Octave Bands - db re 10{-12} Watts
------------------------------------------------------------------------
     12           |  87  |  80  |  73  |  68 |  65 |  63  |  62  |  61
------------------------------------------------------------------------
     25           |  94  |  86  |  79  |  74 |  71 |  69  |  68  |  67
------------------------------------------------------------------------
     50           | 100  |  92  |  85  |  80 |  77 |  75  |  74  |  73
------------------------------------------------------------------------
    100           | 106  |  98  |  91  |  86 |  83 |  81  |  80  |  79
------------------------------------------------------------------------
  Notes:
  a.  The  minimum  distance  shall  be  measured  in  a  straight  line
regardless   of  obstructions.  Interpolated  levels  may  be  used  for
distances between those given in this table. See note a, at end of Table
1207.2.1 in the New York City Building Code.
  1. In the event sound power level data  for  the  exterior  mechanical
equipment  is  not available, the sound pressure levels in octave bands,
of the exterior mechanical equipment shall be measured.
  2. The measurements shall be  obtained  with  the  microphone  of  the
measuring  equipment  located  at  the  interior  of  the  dwelling unit
affected in a line with  the  window  nearest  the  exterior  mechanical
equipment.  The  window  shall be fully open and the microphone shall be
located 3 feet away from the open portion of the window.
  3. Measurements shall be obtained during times when the ambient  sound
pressure  levels, in octave bands, are at least 6 db lower at all octave
bands  than  the  sound  pressure  levels  measured  with  the  exterior
equipment  operating.  By  ambient  sound  pressure  levels is meant the
measured  sound  pressure  levels,  at  the  above  described  measuring
location, with the exterior equipment not in operation.
                             TABLE 926.1(2)
            NOISE OUTPUT LIMITATIONS FOR EXTERIOR MECHANICAL

                EQUIPMENT MAXIMUM SOUND PRESSURE LEVEL{a}
                (NOT TO BE EXCEEDED IN ANY OCTAVE BANDS)
              ---------------------------------------------
                    Octave Bands      |     Decibels
               Center Frequency (cps) |  Re .0002 Microbar
              ---------------------------------------------
                          63          |        61
              ---------------------------------------------
                         125          |        53
              ---------------------------------------------
                         250          |        46
              ---------------------------------------------
                         500          |        40
              ---------------------------------------------
                        1000          |        36
              ---------------------------------------------
                        2000          |        34
              ---------------------------------------------
                        4000          |        33
              ---------------------------------------------
                        8000          |        32
              ---------------------------------------------
Note:
  a.  Measurements shall be obtained with a sound level meter and octave
band analyzer, calibrated both electronically  and  acoustically  before
and after the measurements are made.
  926.1.2  Noise  Control Code. Sound sources shall also comply with any
applicable requirements of Section 24-323 of  the  Administrative  Code,
also known as the New York City Noise Control Code.
  926.2   Minimum   structure-borne   noise   and   vibration  isolation
requirements. All  isolators  shall  comply  with  the  requirements  of
Section 926.1 through 926.2.9.
  926.2.1 Boiler rooms.
  926.2.1.1  Boilers.  All  boilers  supported  on  floors above a story
having dwelling units shall be supported on resilient isolators having a
minimum static deflection of 1 inch (25  mm).  The  isolators  shall  be
installed directly under the structural frame of the boiler.
  926.2.1.2  Boiler breeching and piping. When boilers are equipped with
mechanical  draft  fans,  the  boiler  breeching  and  piping  that  are
supported  from  or on slabs, floors or walls that are contiguous to the
dwelling unit shall be supported for a distance of 50 pipe diameters  on
or  from  resilient isolators. Each isolator shall have a minimum static
deflection of 1 inch (25 mm).
  926.2.2 Incinerator charging chutes.
  926.2.2.1 Metal chutes. Metal chutes,  metal  chute  supports,  and/or
metal  chute  bracing  shall  be  free  of direct contact with the shaft
enclosure and the openings provided in  the  floor  construction.  Metal
chutes  shall  be  resiliently  supported  at  each  structural  support
location. Isolators shall provide a minimum static  deflection  of  0.30
inches (7.62 mm). All chutes shall be plumb.
  926.2.2.2  Masonry  chutes. The interior chute wall shall be plumb and
without obstructions for the full height of the shaft and shall  have  a
smooth interior finish.
  926.2.3 Piping. Equipment piping shall be installed as follows:
  1.   Metal  piping  connected  to  power  driven  equipment  shall  be
resiliently supported from or on the building structure for  a  distance
of  50  pipe  diameters  from  the power driven equipment. The resilient
isolators shall have a minimum static deflection of 1 inch (25  mm)  for

all  piping  with  a 4 inch (25 mm) or larger in actual outside diameter
and 1/2 inch (12.7 mm) for piping with less than 4  inches  (25  mm)  in
actual  outside  diameter.  Piping  connected to fluid pressure-reducing
valves shall be resiliently isolated for a distance of 50 pipe diameters
from  pressure  reducing  valves  and  isolators shall provide a minimum
static deflection of 1/2 inch (12.7 mm).
  2.  Equipment  shall  as  heat  exchangers,  absorption  refrigeration
machines,  or  similar  equipment,  that is located on any floor or roof
other than a floor on grade,  and  that  is  not  power  driven  but  is
connected   by   metal  piping  to  power  driven  equipment,  shall  be
resiliently supported from or on the building structure, for a  distance
of  50  pipe  diameters  from  the power driven equipment. The resilient
supports shall be vibration isolators having a minimum static deflection
of 1 inch (25 mm) and shall incorporate approved resilient pads having a
minimum thickness of 1/4 inch (6.4 mm).
  926.2.4 Fans. All fan equipment located on any  roof  or  floor  other
than  a  floor on grade shall be mounted on or from vibration isolators.
Fan equipment with motor drives separated from the fan  equipment  shall
be  supported  on  an isolated integral rigid structural base supporting
both the fan and motor. Fan equipment with motor drives  supported  from
the fan equipment shall be mounted directly on vibration isolators. Each
isolator  shall have provision for leveling. Isolators shall incorporate
resilient pads having a minimum thickness of  1/4  inch  (6.4  mm).  The
vibration  insulators shall provide a minimum isolation efficiency of 90
percent at fan rotor rpm with a maximum deflection of 2 inches (51  mm).
Fans  and  compressors  of  3  horsepower (2.25 kW) or less assembled in
unitary containers may meet this requirement with isolators internal  to
the  container  providing  the isolators meet the above minimum isolator
efficiencies.
  926.2.5 Pumps. All pumps of 3 horsepower (2.25 kW) or more located  on
any  floor  other  than a floor on grade shall be supported on vibration
isolators having a minimum isolation efficiency of  85  percent  at  the
lowest  disturbing frequency. Each isolator shall incorporate a leveling
device and a resilient pad having a minimum thickness of 1/4  inch  (6.4
mm).
  926.2.6  Compressors.  Compressors and drives located on a floor other
than a floor on grade shall be mounted on vibration isolators  having  a
minimum  isolation  efficiency  of  85  percent at the lowest disturbing
frequency. Each isolator shall  incorporate  a  leveling  device  and  a
resilient pad having a minimum thickness of 1/4 inch (6.4 mm).
  926.2.7  Cooling towers. All moving parts of cooling towers located on
a roof or floor other than a  floor  on  grade  shall  be  installed  on
vibration  isolators  providing  a  minimum  isolation  efficiency of 85
percent at fan rotor rpm with a maximum static deflection  of  4  inches
(102  mm).  Each  isolator  shall  incorporate  a  leveling device and a
resilient pad having a minimum thickness of 1/4 inch (6.4 mm).
  926.2.8 Evaporative condensers. Evaporative and air cooled  condensers
located  on a roof or floor other than a floor on grade shall be mounted
on vibration isolators providing a minimum isolation  efficiency  of  85
percent  at  fan  rotor rpm with a maximum static deflection of 4 inches
(102 mm). Each isolator  shall  incorporate  a  leveling  device  and  a
resilient pad having a minimum thickness of 1/4 inch (6.4 mm).
  926.2.8  Evaporative condensers. Evaporative and air cooled condensers
located on a roof or floor other than a floor on grade shall be  mounted
on  vibration  isolators  providing a minimum isolation efficiency of 85
percent at fan rotor rpm with a maximum static deflection  of  4  inches
(102  mm).  Each  isolator  shall  incorporate  a  leveling device and a
resilient pad having a minimum thickness of 1/4 inch (6.4 mm).

  926.2.9 Duct connections to fan equipment. Flexible connections  shall
be installed between fan equipment and connecting ductwork.
                                CHAPTER 10
                       BOILERS, WATER HEATERS AND
                            PRESSURE VESSELS
                             SECTION MC 1001
                                 GENERAL
  1001.1   Scope.  This  chapter  shall  establish  the  minimum  safety
requirements for and  shall  govern  the  installation,  alteration  and
repair of boilers, water heaters and pressure vessels.
  Exceptions:
  1. Pressure vessels used for unheated water supply.
  2.   Portable   unfired   pressure  vessels  and  Interstate  Commerce
Commission containers.
  3. Containers for bulk oxygen and medical gas.
  4. Unfired pressure vessels having a volume  of  5  cubic  feet  (0.14
m{3}) or less operating at pressures not exceeding 250 pounds per square
inch  (psi)(1724  kPa) and located within occupancies of Groups B, F, H,
M, R, S and U.
  5. Pressure vessels used in refrigeration systems that  are  regulated
by Chapter 11 of this code.
  6.  Pressure  tanks used in conjunction with coaxial cables, telephone
cables, power cables and other similar humidity control systems.
                              SECTION MC 1002
                              WATER HEATERS
  1002.1 General. Portable water heaters and  hot  water  storage  tanks
shall  be  listed  and  labeled  and  installed  in  accordance with the
manufacturer's installation instructions, the  New  York  City  Plumbing
Code  and this code. All water heaters shall be capable of being removed
without first removing a permanent portion of  the  building  structure.
The  potable  water  connections and relief valves for all water heaters
shall conform to the requirements of the New York  City  Plumbing  Code.
Domestic  electric  water  heaters  shall comply with UL 174 or UL 1453.
Commercial electric water heaters shall comply with UL  1453.  Oil-fired
water heaters shall comply with UL 732.
  1002.2  Water  heaters  utilized  for  space  heating.  Water  heaters
utilized both to supply potable hot water  and  provide  hot  water  for
space-heating   applications  shall  be  listed  and  labeled  for  such
applications by the manufacturer, and shall be built in accordance  with
Section  IV of the ASME Boiler and Pressure Vessel Code with an "H" code
stamp. They shall be installed in  accordance  with  the  manufacturer's
installation  instructions, the ASME Code and the New York City Plumbing
Code.
  1002.2.1 Sizing. Water heaters utilized for both potable water heating
and  space-heating  applications  shall  be   sized   to   prevent   the
space-heating  load  from diminishing the required potable water-heating
capacity.
  1002.2.2 Scald protection. Where a combination  potable  water-heating
and   space-heating   system   requires   water  for  space  heating  at
temperatures higher than  140°F  (60°C),  a  tempering  valve  shall  be
provided  to  temper  the  water  supplied  to  the  potable  hot  water
distribution system to a temperature of 140°F (60°C) or less.
  1002.3  Supplemental  water-heating  devices.  Potable   water-heating
devices  that  utilize  refrigerant-to-water  heat  exchangers  shall be
approved and installed in accordance with the  New  York  City  Plumbing
Code and the manufacturer's installation instructions.
                              SECTION MC 1003
                            PRESSURE VESSELS

  1003.1  General.  All  pressure  vessels  shall  bear  the label of an
approved  agency  and  shall  be  installed  in  accordance   with   the
manufacturer's  installation  instructions. The requirements for unfired
pressure vessels shall be the same as required for boilers designed  for
the same operating temperatures.
  1003.2 Piping. All piping materials, fittings, joints, connections and
devices  associated  with  systems utilized in conjunction with pressure
vessels shall be designed for the  specific  application  and  shall  be
approved.
  1003.3  Welding.  Welding  on  pressure  vessels shall be performed by
approved certified welders  in  compliance  with  nationally  recognized
standards, ASME Boiler and Pressure Vessel Code Sections VIII and IX, 12
NYCRR 4-6.2, and 12 NYCRR 14-3.3 through 14-3.18.
                              SECTION MC 1004
                                 BOILERS
  1004.1 Standards. Oil-fired boilers and their control systems shall be
listed and labeled in accordance with UL 726. Electric boilers and their
control  systems  shall be listed and labeled in accordance with UL 834.
Boilers shall  be  designed  and  constructed  in  accordance  with  the
requirements  of  ASME  CSD-1  and  as  applicable:  the ASME Boiler and
Pressure Vessel Code, Sections I, II, IV, V, VI, VII  and  IX;  12  NYCR
Parts 4 and 14; NFPA 8501; NFPA 8502; and NFPA 8504.
  1004.2 Installation. In addition to the requirements of this code, the
installation   of   boilers   shall   conform   to   the  manufacturer's
instructions. Operating  instructions  of  a  permanent  type  shall  be
attached  to  the  boiler. Boilers shall have all controls set, adjusted
and tested by the installer. The  manufacturer's  rating  data  and  the
nameplate shall be attached to the boiler.
  1004.3  Working  clearance.  Clearances  shall  be  maintained  around
boilers, generators, heaters, tanks and related equipment and appliances
so  as  to  permit  inspection,  servicing,  repair,   replacement   and
visibility  of  all  gauges.  When  boilers  are  installed or replaced,
clearance shall be provided to allow access for inspection,  maintenance
and  repair.    Passageways  around  all  sides of boilers shall have an
unobstructed width of not less than 18 inches (457 mm), unless otherwise
approved, by the commissioner.
  1004.3.1  Top  clearance.  High-pressure  steam   boilers   having   a
steam-generating capacity in excess of 5,000 pounds per hour (2268 kg/h)
or  having a heating surface in excess of 1,000 square feet (93 m{2}) or
input in excess of 5,000,000  Btu/h  (1465  kW)  shall  have  a  minimum
clearance of 7 feet (2134 mm) from the top of the boiler to the ceiling.
Steam-heating  boilers  and hot-water-heating boilers that exceed one of
the following limits: 5,000,000 Btu/h input (1465 kW); 5,000  pounds  of
steam  per  hour  (2268  kg/h) capacity or a 1,000-square-foot (93 m{2})
heating surface; and high-pressure steam boilers that do not exceed  one
of  the  following limits: 5,000,000 Btu/h input (1465 kW); 5,000 pounds
of steam per hour (2268 kg/h) capacity or a 1,000-square-foot (93  m{2})
heating  surface;  and  all  boilers with manholes on top of the boiler,
shall have a minimum clearance of 3 feet (914 mm) from the  top  of  the
boiler  to  the  ceiling.  Package  boilers,  steam-heating  boilers and
hot-water-heating boilers without manholes on top of the shell  and  not
exceeding  one  of  the  limits  of  this  section  shall have a minimum
clearance of 2 feet (610 mm) from the ceiling.
  1004.4 Mounting. Equipment and appliances shall be set or mounted on a
level base capable of supporting and distributing the  weight  contained
thereon.  Boilers, tanks and equipment shall be securely anchored to the
structure. Equipment and appliances requiring vibration isolation  shall

be  installed  as  designed  by  a  registered  design  professional  in
accordance with the manufacturer's installation instructions.
  1004.5  Floors.  Boilers  shall be mounted on floors of noncombustible
construction, unless listed for mounting on combustible flooring.
  1004.6 Boiler rooms and enclosures. Boiler rooms  and  enclosures  and
access  thereto  shall  comply  with the New York City Building Code and
Chapter 3 of this code. Boiler rooms shall  be  equipped  with  a  floor
drain or other approved means for disposing of liquid waste.
  1004.7  Operating  adjustments  and  instructions. Hot water and steam
boilers  shall  have  all  operating  and  safety   controls   set   and
operationally  tested  by  the installing contractor. A complete control
diagram and boiler operating instructions  shall  be  furnished  by  the
installer for each installation.
  1004.8  Burner  controls.  Gas  and  oil  modulating  burners shall be
provided with burner  controls  (oil  and  gas  equivalent  ratings)  in
accordance with Table 1004.8.
                               TABLE 1004.8
                      MINIMUM CONTROL REQUIREMENTS
------------------------------------------------------------------------
                        | Gross Output Firing Rate of the Boiler or the
                        |         Burner Oil Delivery Rate (gph),
  Type of Control       |             Whichever is Greater
------------------------------------------------------------------------
  Combustion Controls   |    #6 Oil     |    #4 Oil     |    #2 Oil
------------------------------------------------------------------------
  On-Off                |       -       |       -       |       -
------------------------------------------------------------------------
  Low-High-Off with     |               |               |
  low fire start        |   20 to 50       |     >50       |     >50
------------------------------------------------------------------------
  Full Modulation with  |               |               |
  proven low fire start |               |               |
  as well as            |     >350      |     >350      |     >350
  Cross-Limited Oxygen  |               |               |
  Trim (dry cell        |               |               |
  electrochemical type) |               |               |
------------------------------------------------------------------------
                              SECTION MC 1005
                           BOILER CONNECTIONS
  1005.1  Valves.  Every  boiler  or modular boiler shall have a shutoff
valve in the supply and return piping. For multiple boiler  or  multiple
modular  boiler  installations, each boiler or modular boiler shall have
individual shutoff valves in the supply and return piping.
  Exception: Shutoff valves are not required in a system having a single
low-pressure steam boiler of 350,000 Btu/h (103 kW) output or less.
  1005.2 Potable water supply. The water supply to all boilers shall  be
connected in accordance with the New York City Plumbing Code.
                             SECTION MC 1006
                    SAFETY AND PRESSURE RELIEF VALVES
                              AND CONTROLS

  1006.1  Safety  valves  for  steam boilers. All steam boilers shall be
protected with a safety valve.
  1006.2  Safety  relief valves for hot water boilers. Hot water boilers
shall be protected with a safety relief valve.
  1006.3 Pressure relief for  pressure  vessels.  All  pressure  vessels
shall  be  protected  with  a pressure relief valve or pressure-limiting
device as required by the manufacturer's installation  instructions  for
the pressure vessel.
  1006.4 Standards of safety and safety relief valves. Safety and safety
relief  valves  shall  be  listed  and labeled, and shall have a minimum
rated capacity for the equipment or appliances served. Safety and safety
relief valves shall be set at a maximum of the nameplate pressure rating
of the boiler or pressure vessel.
  1006.5 Installation.  Safety  or  relief  valves  shall  be  installed
directly  into  the  safety  or  relief  valve  opening on the boiler or
pressure vessel. Valves shall not be located on either side of a  safety
or relief valve connection. The relief valve shall discharge by gravity.
  1006.6  Safety  and  relief  valve  discharge. Safety and relief valve
discharge pipes shall  be  of  rigid  pipe  that  is  approved  for  the
temperature of the system. The discharge pipe shall be the same diameter
as the safety or relief valve outlet. Safety and relief valves shall not
discharge so as to be a hazard, a potential cause of damage or otherwise
a  nuisance.  High-pressure-steam  safety  valves shall be vented to the
outside of the structure. Where a low-pressure safety valve or a  relief
valve  discharges to the drainage system, the installation shall conform
to the New York City Plumbing Code.
  1006.7 Boiler safety devices. Boilers shall be equipped with  controls
and  limit  devices  as  required  by  the  manufacturer's  installation
instructions and the conditions of the listing.
  1006.8 Electrical requirements. The power  supply  to  the  electrical
control  system  shall  be  from  a  two-wire  branch circuit that has a
grounded conductor, or from an isolation  transformer  with  a  two-wire
secondary.  Where an isolation transformer is provided, one conductor of
the secondary winding shall  be  grounded.  Control  voltage  shall  not
exceed  150 volts nominal, line to line. Control and limit devices shall
interrupt the ungrounded side  of  the  circuit.  A  means  of  manually
disconnecting  the  control circuit shall be provided and controls shall
be arranged so that when deenergized, the burner shall  be  inoperative.
Such  disconnecting  means  shall  be capable of being locked in the off
position and shall be provided with ready access.
  1006.8.1 Remote control (shutdown). A remote control shall be provided
to stop the flow of oil and/or gas and combustion air to any  burner  or
fuel  burning  internal  combustion  equipment.  Such  control  shall be
located outside all means of egress to the room in which the  burner  or
equipment  is  located  and  as  close to such entrances as practicable,
except that when an outside location is impracticable, such control  may
be  located immediately inside the room in which the burner or equipment
is located, provided such location is accessible at all times. All  such
controls shall be labeled: "REMOTE CONTROL FOR BURNER".
                             SECTION MC 1007
                         BOILER LOW-WATER CUTOFF
1007.1  General. All steam and hot water boilers shall be protected with
dual low-water cutoff control.
  1007.1.1 High-Pressure boiler. If the low-water cut  off  devices  are
mounted  externally  to the boiler, the main and auxiliary low-water cut
offs shall be connected to the boiler  using  isolated  steam  side  and
water side connection. No other control devices, gauges or valves except

for  the  water  column  drain shall be connected to the tappings on the
boiler used for low-water cut offs.
  1007.2  Operation.  The  low-water cutoff shall automatically stop the
combustion operation of the appliance when the water level  drops  below
the  lowest  safe  water level as established by the manufacturer and in
accordance with ASME CSD-1.
                             SECTION MC 1008
                     BOILER BLOWOFF/BLOWDOWN VALVES
1008.1 General. Every boiler shall  be  equipped  with  blowoff/blowdown
valve(s).  The  valve(s)  shall be installed in the openings provided on
the boiler. The minimum quantity and size of each  valve  shall  be  the
quantity  and  size specified by the boiler manufacturer or the quantity
and size of the boiler blowoff/blowdown valve opening.
  1008.2 Discharge. Blowoff/blowdown valves shall discharge  to  a  safe
place  of  disposal.  Where  discharging  to  the  drainage  system, the
installation shall conform to the New York City Plumbing Code.
                             SECTION MC 1009
                     HOT WATER BOILER EXPANSION TANK
1009.1 Where required. An expansion tank shall be installed in every hot
water system. For  multiple  boiler  installations,  a  minimum  of  one
expansion  tank  is  required. Expansion tanks shall be of the closed or
open type. Tanks shall be rated  for  the  pressure  of  the  hot  water
system.
  1009.2  Closed-type expansion tanks. Closed-type expansion tanks shall
be installed in accordance with  the  manufacturer's  instructions.  The
size of the tank shall be based on the capacity of the hot-water-heating
system.  The  minimum size of the tank shall be determined in accordance
with the following equation:

         (0.000041T - 0.0466)V[3]                   (Equation 10-1)
  V[t] = -------------------------
             (P[a])     (P[a])
             ------  -  ------
             (P[f]      (P[a])

  For SI:

         (0.0000738T - 0.03348)V[3]
  V[t] = ---------------------------
             (P[a])     (P[a])
             ------  -  ------
             (P[f])     (P[a])

  where:
  V[t] = Minimum volume of tanks (gallons) (L).
  V[3] = Volume of system, not including expansion tanks (gallons) (L).
  T = Average operating temperature (°F) (°C).
  P[a] = Atmospheric pressure (psi) (kPa).
  P[f] = Fill pressure (psi) (kPa).
  P[o] = Maximum operating pressure (psi) (kPa).

  1009.3 Open-type expansion tanks. Open-type expansion tanks  shall  be
located  at  a  minimum  of  4  feet (1219 mm) above the highest heating
element. The tank shall be adequately sized for the hot water system. An
overflow with a minimum diameter of 1 inch (25 mm) shall be installed at
the top of the tank. The overflow shall discharge to the drainage system
in accordance with the New York City Plumbing Code.

                              SECTION MC 1010
                                 GAUGES
  1010.1  Hot  water  boiler gauges. Every hot water boiler shall have a
pressure gauge and a temperature gauge, or a  combination  pressure  and
temperature  gauge.  The  gauges  shall  indicate  the  temperature  and
pressure within normal range of the system's operation.
  1010.2  Steam  boiler  gauges.  Every  steam  boiler  shall   have   a
water-gauge  glass  and  a  pressure gauge. The pressure gauge installed
with a siphon shall indicate the pressure within the normal range of the
system's operation.
  1010.2.1 Water-gauge glass. The gauge glass shall be installed so that
the midpoint is at the normal boiler water level.
                             SECTION MC 1011
                                  TESTS
  1011.1 Tests. Upon completion of  the  assembly  and  installation  of
boilers  and  pressure  vessels,  acceptance tests shall be conducted in
accordance with the requirements of the ASME Boiler and Pressure  Vessel
Code.  Boilers  shall  not  be  placed  in  operation upon completion of
construction until they have been inspected and tested and a certificate
of compliance has been issued by the commissioner. All final inspections
and tests for boilers shall be made by a qualified boiler  inspector  in
the  employ  of the department or a duly authorized insurance company as
provided in Section 204 of the Labor Law  of  the  State  of  New  York.
Equipment  having  a  Btu input of not more than 350,000 Btu/la (103 kW)
shall be exempt from this requirement. Where field assembly of  pressure
vessels  or boilers is required, a copy of the completed H-2, P-2 or U-1
Manufacturer's Data Report required by  the  ASME  Boiler  and  Pressure
Vessel Code shall be submitted to the department.
  1011.2  Test  gauges.  An  indicating  test  gauge  shall be connected
directly to the boiler or pressure vessel where it  is  visible  to  the
operator  throughout  the duration of the test. The pressure gauge scale
shall be graduated over a range of not less than one and one-half  times
and  not  greater  than four times the maximum test pressure. All gauges
utilized for testing shall be  calibrated  and  certified  by  the  test
operator.
  1011.3  Periodic boiler inspections. Periodic boiler inspections shall
be performed in accordance with Section  28-303  of  the  Administrative
Code.
                                CHAPTER 11
                              REFRIGERATION
                             SECTION MC 1101
                                 GENERAL
  1101.1  Scope.  This  chapter  shall  govern the design, installation,
construction and repair  of  refrigeration  systems  that  vaporize  and
liquefy  a  fluid  during  the  refrigeration  cycle. Refrigerant piping
design and installation, including pressure vessels and pressure  relief
devices,  shall  conform to this code. Permanently installed refrigerant
storage systems and other components shall be considered as part of  the
refrigeration system to which they are attached.
  1101.2  Factory-built  equipment  and  appliances.  Listed and labeled
self-contained, factory-built equipment and appliances shall  be  tested
in  accordance  with  UL  207,  412,  471  or  1995.  Such equipment and
appliances are deemed to meet the design, manufacture and  factory  test
requirements  of this code if installed in accordance with their listing
and the manufacturer's installation instructions.
  1101.3 Protection. Any portion  of  a  refrigeration  system  that  is
subject to physical damage shall be protected in an approved manner.

  1101.4  Water  connection.  Water  supply  and  discharge  connections
associated with refrigeration systems shall be made in  accordance  with
this code and the New York City Plumbing Code.
  1101.5 Fuel-oil and fuel-gas connection. Refrigeration system devices,
equipment  and  appliances utilizing fuel oil or fuel gas for combustion
shall be installed in accordance with the applicable provisions  of  the
New York City Fuel Gas Code and this code.
  1101.6   General.   Refrigeration   systems   shall  comply  with  the
requirements of this code and, except as modified by this  code,  ASHRAE
15.    Ammonia-refrigerating  systems  shall  comply with this code and,
except as modified by this code, ASHRA 15 and IIAR 2.
  1101.7  Maintenance.  Mechanical  refrigeration   systems   shall   be
maintained  in  proper  operating  condition, free from accumulations of
oil, dirt, waste, excessive corrosion, other debris and leaks.
  1101.8  Change  in  refrigerant  type.  The  type  of  refrigerant  in
refrigeration  systems having a refrigerant circuit containing more than
220 pounds (100 kg) of Group A1 or 30 pounds  (13.6  kg)  of  any  other
group refrigerant shall not be changed without prior notification to the
commissioner  and compliance with the applicable code provisions for the
new  refrigerant  type.  The  refrigerant  being  considered  shall   be
evaluated for suitability by an engineer. Whenever change in the type of
refrigerant  is  to  be  done,  consideration  shall  be  given  to  the
following:
  1. The effects of the  substitute  refrigerant  on  materials  in  the
system;
  2.  The  possibility  of over loading the liquid receiver, which shall
not be more than 80 percent full of liquid;
  3. The possibility of exceeding motor rating, design working pressure,
or other requirements that would violate any of the provisions  of  this
code;
  4. The proper size of refrigerant controls;
  5. The effect of the operation and setting of safety devices;
  6.  The  possible  hazards  created by mixture of the original and the
substituted refrigerant; and
  7. The effect of the classification of the refrigerant as provided.
  1101.9 Refrigerant discharge. Notification  of  refrigerant  discharge
shall be provided in accordance with the New York City Fire Code.
  1101.10  Gas  and  oil fired absorption systems. Refrigeration systems
utilizing fuel oil or fuel gas for  combustion  shall  be  installed  in
accordance  with the applicable provisions of the New York City Fuel Gas
Code and this code.
  1101.11  Signs,  nameplates,  and  operation  and  emergency  shutdown
instructions.  Signs,  nameplates,  and operation and emergency shutdown
instructions for refrigeration systems shall comply with the following:
  1. Sections 9.15, 11.2.1, 11.2.2, 11.2.4, and 11.7 of ASHRAE 15.
  2. Each  refrigeration  unit  or  system  shall  be  provided  with  a
nameplate indicating the horsepower of the prime mover or compressor and
the equivalent of such horsepower in kilowatts.
  3. Section 1105.10 of this code.
                             SECTION MC 1102
                           SYSTEM REQUIREMENTS
1102.1  General.  The  system  classification,  allowable  refrigerants,
maximum quantity,  enclosure  requirements,  location  limitations,  and
field pressure test requirements shall be determined as follows:
  1.  Determine  the refrigeration systems classification, in accordance
with Section 1103.3.
  2. Determine the refrigerant classification in accordance with Section
1103.1.

  3.  Determine  the  maximum  allowable  quantity  of  refrigerant   in
accordance  with  Section  1104,  based  on  type of refrigerant, system
classification, and occupancy.
  4.  Determine  the  system  enclosure  requirements in accordance with
section 1104.
  5. Refrigeration equipment and  appliance  location  and  installation
shall be subject to the limitations of Chapter 3.
  6.  Nonfactory-tested, field-erected equipment and appliances shall be
pressure tested in accordance with Section 1108.
  1102.2 Refrigerants. The refrigerant shall be that which the equipment
or  appliance  was  designed  to  utilize  or  converted   to   utilize.
Refrigerants  not  identified  in  Table 1103.1 shall be approved before
use.
  1102.2.1 Mixing.  Refrigerants,  including  refrigerant  blends,  with
different designations in ASHRAE 34 shall not be mixed in a system.
  Exception: Addition of a second refrigerant is allowed where permitted
by  the equipment or appliance manufacturer to improve oil return at low
temperatures. The refrigerant and amount added shall  be  in  accordance
with the manufacturer's instructions.
  1102.2.2  Purity.  Refrigerants used in refrigeration systems shall be
new, recovered or reclaimed  refrigerants  in  accordance  with  Section
1102.2.2.1, 1102.2.2.2 or 1102.2.2.3. Where required by the equipment or
appliance  owner,  the installer shall furnish a signed declaration that
the refrigerant used  meets  the  requirements  of  Section  1102.2.2.1,
1102.2.2.2 or 1102.2.2.3.
  Exception:  The  refrigerant used shall meet the purity specifications
set by the manufacturer of the equipment  or  appliance  in  which  such
refrigerant  is  used  where such specifications are different from that
specified in Sections 1102.2.2.1, 1102.2.2.2 and 1102.2.2.3.
  1102.2.2.1 New refrigerants. Refrigerants shall be of a  purity  level
specified by the equipment or appliance manufacturer.
  1102.2.2.2  Recovered  refrigerants.  Refrigerants  that are recovered
from refrigeration and air-conditioning systems shall not be  reused  in
other  than  the  system  from  which  they  were recovered and in other
systems of the same owner. Recovered refrigerants shall be filtered  and
dried  before  reuse.  Recovered  refrigerants  that show clear signs of
contamination shall not be reused unless reclaimed  in  accordance  with
Section 1102.2.23.
  1102.2.2.3  Reclaimed  refrigerants.  Used  refrigerants  shall not be
reused in a different owner's equipment or appliances unless tested  and
found   to  meet  the  purity  requirements  of  ARI  700.  Contaminated
refrigerants shall not be used unless reclaimed and found  to  meet  the
purity requirements of ARI 700.
                             SECTION MC 1103
                   REFRIGERATION SYSTEM CLASSIFICATION
1103.1  Refrigerant  classification. Refrigerants shall be classified in
accordance with ASHRAE 34 as listed in Table 1103.1.

   ______________________________________________________________
   1                                                            |
   2                                                            |
   3          COPY OF TABLE 1103.1                              |
   4          MAY BE OBTAINED FROM:                             |
   5          NYS LEGISLATIVE BILL DRAFTING COMMISSION          |
   6          CONTACT: LEGISLATIVE RETRIEVAL SYSTEM'S HELPLINE  |
   7                                                            |
   8                                                            |
   9____________________________________________________________|

  1103.2 Occupancy classification. Locations  of  refrigerating  systems
are  described by occupancy classifications that consider the ability of
people  to  respond  to  potential  exposure  to  refrigerants.    Where
equipment  or  appliances,  other  than  piping,  are  located outside a
building  and  within  20  feet  (6096 mm) of any building opening, such
equipment  or  appliances   shall   be   governed   by   the   occupancy
classification  of  the  building.  Occupancy  classifications  shall be
defined as follows:
  1. Institutional occupancy is that portion  of  premises  from  which,
because  they  are  disabled,  debilitated or confined, occupants cannot
readily  leave  without  the   assistance   of   others.   Institutional
occupancies include, among others, hospitals, nursing homes, asylums and
spaces containing locked cells.
  2.  Public  assembly occupancy is that portion of premises where large
numbers of people congregate and from  which  occupants  cannot  quickly
vacate  the  space.  Public  assembly occupancies include, among others,
auditoriums, ballrooms, classrooms, passenger  depots,  restaurants  and
theaters.
  3. Residential occupancy is that portion of premises that provides the
occupants   with   complete  independent  living  facilities,  including
permanent  provisions  for  living,  sleeping,   eating,   cooking   and
sanitation. Residential occupancies include, among others,  dormitories,
hotels, multi-unit apartments and private residences.
  4.  Commercial  occupancy  is  that  portion  of premises where people
transact business, receive personal service or purchase food  and  other
goods.    Commercial  occupancies  include,    among  others, office and
professional buildings, markets (but not large  mercantile  occupancies)
and work or storage areas that do not qualify as industrial occupancies.
  5.  Large  mercantile occupancy is that portion of premises where more
than 100 persons congregate on levels above or  below  street  level  to
purchase personal merchandise.
  6.  Industrial  occupancy is that portion of premises that is not open
to the public, where access by authorized  persons  is  controlled,  and
that  is  used to manufacture, process or store goods such as chemicals,
food, ice, meat or petroleum.
  7. Mixed occupancy occurs when two or  more  occupancies  are  located
within  the same building. When each occupancy is isolated from the rest
of the building by tight walls, floors and ceilings and by  self-closing
doors, the requirements for each occupancy shall apply to its portion of
the  building.  When  the  various  occupancies are not so isolated, the
occupancy having the most stringent requirements shall be the  governing
occupancy.
  1103.3   System   classification.   Refrigeration   systems  shall  be
classified according to  the  degree  of  probability  that  refrigerant
leaked  from  a  failed  connection,  seal,  or component could enter an
occupied area. The distinction is based on the basic design or  location
of the components.
  1103.3.1  Low-probability systems. Double-indirect open-spray systems,
indirect closed systems and indirect  vented  closed  systems  shall  be
classified    as    low-probability    systems,    provided   that   all
refrigerant-containing  piping  and  fittings  are  isolated  when   the
quantities in Table 1103.1 are exceeded.
  1103.3.2   High-probability   systems.  Direct  systems  and  indirect
open-spray systems shall be classified as high-probability systems.
  Exception: An indirect open-spray system shall not be required  to  be
classified as a high-probability system if the pressure of the secondary
coolant  is  at  all  times  (operating  and  standby)  greater than the
pressure of the refrigerant.

                             SECTION MC 1104
                     SYSTEM APPLICATION REQUIREMENTS
  1104.1  General.  The refrigerant, occupancy and system classification
cited in this section shall be determined in  accordance  with  Sections
1103.1, 1103.2 and 1103.3, respectively. For refrigerant blends assigned
dual   classification,   as   formulated  and  for  the  worst  case  of
fractionation, the classifications for the worst case  of  fractionation
shall  be used. Use of a Group A3 or Group B3 refrigerant is prohibited.
In an industrial occupancy, a Group A3 or Group B3  refrigerant  may  be
used  in  high  or  low-probability  systems  only  when approved by the
commissioner and the Commissioner of the Fire Department. Such use  will
be approved only if the applicant can demonstrate to the satisfaction of
the  commissioner  and  the Commissioner of the Fire Department that the
use of  the  refrigerant  is  a  necessity  and  does  not  represent  a
substantial risk to life, limb, health or property.
  1104.2  Machinery  room.  Except  as provided in Sections 1104.2.1 and
1104.2.2, all components containing the  refrigerant  shall  be  located
either outdoors or in a machinery room where the quantity of refrigerant
in an independent circuit of a system exceeds the amounts shown in Table
1103.1.  For  refrigerant  blends  not  listed in Table 1103.1, the same
requirement shall apply when the amount for any blend component  exceeds
that  indicated  in  Table  1103.1  for that component. This requirement
shall also apply when  the  combined  amount  of  the  blend  components
exceeds  a  limit of 69,100 parts per million (ppm) by volume. Machinery
rooms required by this section shall be constructed  and  maintained  in
accordance  with  Section  1105  for Group A1 and B1 refrigerants and in
accordance with Sections 1105 and 1106 for  Group  A2,  B2,  A3  and  B3
refrigerants.  Nothing  in  this section shall be construed to allow the
use of Group A3 and B3 refrigerants if otherwise prohibited.
  Exceptions:
  1.  Machinery  rooms  are  not  required  for  listed  equipment   and
appliances  containing  not  more than 6.6 pounds (3 kg) of refrigerant,
regardless of the refrigerant's safety classification,  where  installed
in  accordance  with  the  equipment's  or  appliance's  listing and the
equipment or appliance manufacturer's installation instructions.
  2. Piping in conformance with Section 1107 of this chapter and Section
8.10 of ASHRAE 15 is allowed in other locations  to  connect  components
installed in a machinery room with those installed outdoors.
  1104.2.1  Institutional occupancies. The amounts shown in Table 1103.1
shall  be  reduced  by  50  percent  for  all  areas  of   institutional
occupancies  except kitchens, laboratories, and mortuaries. The total of
all Group A2, B2, A3 and B3 refrigerants shall  not  exceed  550  pounds
(250  kg)  in occupied areas or machinery rooms. Nothing in this section
shall be construed to allow the use of Group A3 and B3  refrigerants  if
otherwise prohibited.
  1104.2.2  Industrial  occupancies and refrigerated rooms. This section
applies only  to  industrial  occupancies  and  refrigerated  rooms  for
manufacturing,  food  and  beverage  preparation,  meat  cutting,  other
processes and storage. Machinery rooms are not required where all of the
following conditions are met:
  1.  The  space  containing  the  machinery  is  separated  from  other
occupancies by tight construction with tight-fitting doors.
  2. Access is restricted to authorized personnel.
  3.  The  floor area per occupant is not less than 100 square feet (9.3
m{2}). Where provided with egress  directly  to  the  outdoors  or  into
building  exits  meeting  the requirements of the New York City Building
Code, the minimum floor area shall not apply.

  4. Refrigerant detectors are installed as required for machinery rooms
in accordance with section 1105.3.
  5.  Surfaces  having  temperatures  exceeding  800°F  (427°C) and open
flames are not present where any Group A2, B2, A3 or B3  refrigerant  is
used  (see Section 1104.3.4). Nothing in this section shall be construed
to  allow  the  use  of  Group  A3  and  B3  refrigerants  of  otherwise
prohibited.
  6.  All  electrical  equipment  and  appliances  conform  to  Class 1,
Division 2, hazardous location classification requirements  of  NFPA  70
where the quantity of any Group A2, B2, A3 or B3 refrigerant in a single
independent  circuit  would  exceed 25 percent of the lower flammability
limit (LFL) upon release to the space. Nothing in this section shall  be
construed  to allow the use of Group A3 and B3 refrigerants if otherwise
prohibited.
  7. All refrigerant-containing parts in systems exceeding 100 hp  (74.6
kW)   drive   power,   except  evaporators  used  for  refrigeration  or
dehumidification; condensers used  for  heating;  control  and  pressure
relief valves for either; and connecting piping, shall be located either
outdoors or in a machinery room.
  1104.3  Refrigerant  restrictions.  Refrigerant  applications, maximum
quantities and use shall  be  restricted  in  accordance  with  Sections
1104.3.1 through 1104.3.4.
  1104.3.1  Air-conditioning for human comfort. In other than industrial
occupancies where the quantity in a single independent circuit does  not
exceed  the  amount  in  Table  1103.1, Group B1, B2 and B3 refrigerants
shall not be used in high-probability systems for  air-conditioning  for
human  comfort.  Nothing in this section shall be construed to allow the
use of Group A3 and B3 refrigerants if otherwise prohibited.
  1104.3.2 Nonindustrial occupancies. Group A2 and B2 refrigerants shall
not  be  used  in  high-probability  systems  where  the   quantity   or
refrigerant  in  any  independent refrigerant circuit exceeds the amount
shown in Table 1104.3.2.

                             TABLE 1104.3.2
             MAXIMUM PERMISSIBLE QUANTITIES OF REFRIGERANTS
------------------------------------------------------------------------
                |     MAXIMUM POUNDS(kg) FOR VARIOUS OCCUPANCIES
    TYPE OF     |             |             |             |
 REFRIGERATION  |Institutional|   Assembly  | Residential |  All other
    SYSTEM      |             |             |             | occupancies
------------------------------------------------------------------------
Sealed absorpt- |             |             |             |
ion system      |             |             |             |
  In exit access|     0(0)    |     0(0)    |  3.3(1.5)   |  3.3(1.5)
  In adjacent   |             |             |             |
  outdoor       |             |             |             |
  locations     |     0(0)    |     0(0)    |   22(10)    |   22(10)
  In other than |             |             |             |
  exit access   |     0(0)    |   6.3(3)    |   6.6(3)    |   6.6(3)
------------------------------------------------------------------------
Unit Systems    |             |             |             |
  In other than |             |             |             |
  exit access   |     0(0)    |     0(0)    |   6.6(3)    |   6.6(3)
------------------------------------------------------------------------

  For SI: 1 pound = 0.454 kg.

  1104.3.3 All occupancies. The total of all Group A2,  B2,  A3  and  B3
refrigerants  other  than  R-717, ammonia, shall not exceed 1,100 pounds
(499 kg) except  where  approved.  Nothing  in  this  section  shall  be
construed  to allow the use of Group A3 and B3 refrigerants if otherwise
prohibited.
  1104.3.4  Protection  from refrigerant decomposition. Where any device
having an open flame or surface temperature greater than  800°F  (427°C)
is  used in a room containing more than 6.6 pounds (3 kg) of refrigerant
in a single independent circuit, a hood  and  exhaust  system  shall  be
provided  in  accordance  with  Section  510.  Such exhaust system shall
exhaust combustion products to the outdoors.
  Exception: A hood and exhaust system shall not be required:
  1. Where the refrigerant is R-717, R-718, or R-744;
  2. Where the combustion air is ducted from the outdoors  in  a  manner
that prevents leaked refrigerant from being combusted; or
  3.  Where  refrigerant  detector is used to stop the combustion in the
event of a refrigerant leak (see Sections 1105.3 and 1105.5)
  1104.4 Volume calculations. Volume calculations shall be in accordance
with Sections 1104.4.1 through 1104.4.3.
  1104.4.1 Noncommunicating  spaces.  Where  the  refrigerant-containing
parts  of  a  system  are  located  on  one  or  more spaces that do not
communicate through permanent openings or HVAC ducts, the volume of  the
smallest,  enclosed  occupied  space  shall  be  used  to  determine the
permissible quantity of refrigerant in the system.
  1104.4.2 Communicating spaces. Where an  evaporator  or  condenser  is
located  in  an  air  duct  system, the volume of the smallest, enclosed
occupied space  served by the duct system shall be used to determine the
maximum allowable quantity of refrigerant in the system.
  Exception: If airflow to any enclosed space cannot  be  reduced  below
one-quarter  of  its  maximum,  the  entire space served by the air duct
system shall be used to determine  the  maximum  allowable  quantity  of
refrigerant in the system.
  1104.4.3  Plenums.  Where  the  space  above  a  suspended  ceiling is
continuous and part of the supply or  return  air  plenum  system,  this
space shall be included in calculating the volume of the enclosed space.
                              SECTION MC 1105
                  MACHINERY ROOM, GENERAL REQUIREMENTS
  1105.1  Design and construction. Machinery rooms shall be designed and
constructed in accordance with the New York City Building Code and  this
section.
  1105.2  Openings.  Ducts  and  air handlers in the machinery room that
operate at a lower pressure than the room shall be sealed to prevent any
refrigerant leakage from entering the airstream.
  1105.3 Refrigerant detector. Refrigerant detectors in machinery  rooms
shall be provided as required by ASHRAE 15.
  1105.4  Tests.  Periodic  tests  of  the mechanical ventilating system
shall be performed in accordance with manufacturer's specifications  and
as required by the Commissioner of the Fire Department.
  1105.5  Fuel-burning  appliances.  Open flames that use combustion air
from the machinery room shall not be installed in a machinery room.
  Exceptions:
  1. Matches, lighters, halide leak detectors and similar devices.
  2. Where th refrigerant is carbon dioxide or water.
  3. Fuel-burning  appliances  shall  not  be  prohibited  in  the  same
machinery room with refrigerant-containing equipment or appliances where
combustion  air  is ducted from outside the machinery room and sealed in
such a manner as to prevent any refrigerant leakage  from  entering  the
combustion chamber, or where a refrigerant vapor detector is employed to

automatically   shut   off  the  combustion  process  in  the  event  of
refrigerant leakage.
  1105.6  Ventilation.  Machinery rooms shall be mechanically ventilated
to the outdoors. Mechanical ventilation shall be capable  of  exhausting
the  minimum  quantity  of  air  both  at normal operating and emergency
conditions. Multiple fans or multispeed fans shall be allowed  in  order
to  produce  the  emergency  ventilation  rate  and  to obtain a reduced
airflow for normal ventilation. Location of the  mechanical  ventilation
openings  shall  be  based on the relative density of the refrigerant to
air. When compressors or self-contained unit  system  are  housed  in  a
machinery  space,  other  than  in a machinery room or plenum, the space
shall be ventilated in  accordance  with  the  requirements  of  Section
1105.6.3.
  Exception:  Where a refrigerating system is located outdoors more than
20 feet (6096 mm) from  any  building  opening  and  is  enclosed  by  a
penthouse,  lean-to  or other open structure, natural ventilation may be
provided in lieu of mechanical  ventilation.  Location  of  the  natural
ventilation  openings  shall  be  based  on  the relative density of the
refrigerant to air. The free-aperture cross section for the  ventilation
of the machinery room shall not less than:

  F = Square root of G                              (Equation 11-1)
  For SI: F = 0.138 Square root of G
  where:
  F = The free opening area in square feet (m{2})
  G  = The mass of refrigerant in pounds (kg) in the largest system, any
part of which is located in the machinery room.

  1105.6.1 Discharge location. The discharge of the air shall be to  the
outdoors   in   accordance  with  Chapter  5.  Exhaust  from  mechanical
ventilation systems shall be discharged not less than 20 feet (6096  mm)
from  outdoor  air  intake or openings and 10 feet (3048 mm) from a fire
escape or exterior stair.
  1105.6.2 Make-up air. Provisions shall be  made  for  make-up  air  to
replace  that being exhausted. Openings for make-up air shall be located
to avoid intake  of  exhaust  air.  Supply  and  exhaust  ducts  to  the
machinery  room  shall  serve  no  other  area,  shall be constructed in
accordance with Chapter 5 and shall be covered with  corrosion-resistant
screen of not less than 1/4-inch (6.4 mm) mesh.
  Exception:  The  requirement  for  supply  and  exhaust  ducts  to the
machinery room to serve no other area shall not apply to a change in the
type of refrigerant  in  a  lawfully  installed  existing  refrigerating
system  being  maintained and operated in accordance with these approved
installation requirements:
  1. Where the replacement refrigerant has a  safety  classification  of
Group A1; or
  2.  Where  the  replacement  refrigerant  is  R123 and the engineer or
architect demonstrates to the  satisfaction  of  the  commissioner  that
providing  such  air  supply and exhaust ducts represents a hardship and
that the proposed alternative provides an equivalent level of safety.
  1105.6.3 Quantity-normal ventilation. During occupied conditions,  the
mechanical ventilation system shall exhaust the larger of the following:
  1.  Not  less  than  0.5  cfm  per square foot (0.0025 m{3}/s m{2}) of
machinery room area or 20 cfm (0.009 m{3}/s) per person; or
  2. A volume required to limit the room temperature rise to 18°F (10°C)
taking into account the ambient heating effect of all machinery  in  the
room but not above a maximum temperature of 122°F (50°C).

  1105.6.4   Quantity-emergency   conditions.   Upon  actuation  of  the
refrigerant  detector  required  in  Section  1105.3,   the   mechanical
ventilation  system  shall  exhaust  air  from the machinery room in the
following quantity:

  Q = 100 x square root of G                          (Equation 11-2)
  For SI: Q = 0.07 x square root of G
  where:
  Q = The airflow in cubic feet per minute (m{3/s})
  G  =  The  design  mass  of  refrigerant in pounds (kg) in the largest
system, any part of which is located in the machinery room.

  1105.7 Termination of relief devices. In addition to the  requirements
of  Section  9.7.8  of ASHRAE 15, pressure relief devices, fusible plugs
and purge systems located within  the  machinery  room  shall  terminate
outside  of  the structure at a location not less than 15 feet (4572 mm)
above the adjoining grade level and not less than 20 feet (6096 mm) from
any window, ventilation opening or exit.
  1105.7.1 Discharge of Group A2, B2, A3 and B3 refrigerants.  Discharge
of systems containing Group A2 or B2 refrigerants shall be acceptable to
the  commissioner.  Discharge  of  systems  containing  Group  A3  or B3
refrigerants shall be subject to the approval of  the  commissioner  and
the  Commissioner  of the Fire Department. Nothing in this section shall
be construed to approve the use of  Group  A3  and  B3  refrigerants  if
otherwise prohibited.
  1105.7.2  Certificate  of  qualification. Discharge of pressure relief
devices, fusible plugs  and  purge  systems  for  refrigerating  systems
containing  flammable,  toxic  and highly toxic refrigerants and ammonia
shall comply with Section 606 of the New York City Fire Code.
  1105.8 Ammonia discharge. Pressure relief valves for  ammonia  systems
shall discharge in accordance with ASHRAE 15.
  1105.9  Remote control. A clearly identified switch of the break-glass
type shall provide off-only control of the compressors in the  machinery
room.  A  second clearly identified switch of the break-glass type shall
provide on-only control of the machinery  room  ventilation  fans.  Such
switches  shall  be  located outside each entrance to the machinery room
and as close to the entrance as practicable, except that when an outside
location is impracticable, such  switches  may  be  located  immediately
inside  the  machinery  room provided such location is accessible at all
times.
  1105.10 Emergency signs. Signs shall comply with the following:
  1. Sections 8.11.8 and 11.2.4 of ASHRAE 15.
  2.  Refrigeration  units  or  systems  having  a  refrigerant  circuit
containing  more  than  220 pounds (100 kg) of Group A1 or 30 pounds (14
kg) of any  the  group  refrigerant  shall  be  provided  with  approved
emergency signs, charts, and labels in accordance with NFPA 704.
                             SECTION MC 1106
                  MACHINERY ROOM, SPECIAL REQUIREMENTS
  1106.1  General.  Where required by Section 1104.2, the machinery room
shall  meet  the  requirements  of  this  section  in  addition  to  the
requirements of Section 1105.
  1106.2   Elevated   temperature.   There   shall   not   be   an  open
flame-producing device or continuously operating hot surface over  800°F
(427°C) permanently installed in the room.
  1106.3  Ammonia  room  ventilation.  Ventilation  systems  in  ammonia
machinery rooms shall be operated continuously.
  Exceptions:

  1.  Machinery  rooms  equipped  with  a  vapor  detector   that   will
automatically  start  the  ventilation  system and actuate an alarm at a
detection level not to exceed 1,000 ppm; or
  2.  Machinery  rooms  conforming to the Class 1, Division 2, hazardous
location classification requirements of the  New  York  City  Electrical
Code.
  1106.4 Flammable refrigerants. Where refrigerants of Groups A2, A3, B2
and  B3  are  used,  the  machinery  room  shall conform to the Class 1,
Division 2, hazardous location classification requirements  of  the  New
York City Electrical Code.
  Exception:  Ammonia  machinery rooms. Nothing in this section shall be
construed to approve  the  use  of  Group  A3  and  B3  refrigerants  if
otherwise prohibited.
  1106.5 Remote controls. Remote control of the mechanical equipment and
appliances  located  in  the  machinery  room  shall  be  provided at an
accessible location immediately outside the machinery room and  adjacent
to its principal entrance.
  1106.5.1  Refrigeration  system.  A  clearly  identified switch of the
break-glass type shall provide  off-only  control  of  all  electrically
energized  equipment  and  appliances  in the machinery room, other than
refrigerant leak detectors and machinery room ventilation.
  1106.6 Reserved.
                             SECTION MC 1107
                           REFRIGERANT PIPING
  1107.1 General. All refrigerant piping shall be installed, tested  and
placed in operation in accordance with this chapter.
  1107.2  Pipe  enclosures.  Rigid  or flexible metal enclosures or pipe
ducts shall be provided for  soft,  annealed  copper  tubings  used  for
refrigerant  piping  erected  on  the premises and containing other than
Group A1 refrigerant. Enclosures shall not be required  for  connections
between  condensing  units  and the nearest riser box(es), provided such
connections do not exceed 6 feet (1829 mm) in length.
  1107.3 Condensation. All  refrigerating  piping  and  fittings,  brine
piping  and fittings that, during normal operation, will reach a surface
temperature below the dew point of the surrounding air, and are  located
in  spaces or areas where condensation will cause a safety hazard to the
building  occupants,  structure,  electrical  equipment  or  any   other
equipment  or  appliances,  shall  be protected in an approved manner to
prevent such damage.
  1107.4 Materials for refrigerant pipe  and  tubing.  Piping  materials
shall be as set forth in Sections 1107.4.1 through 1107.4.6.
  1107.4.1  Steel pipe. Carbon steel pipe with a wall thickness not less
than Schedule 80 shall be used for Group A2, A3, B2  or  B3  refrigerant
liquid lines for sizes 1.5 inches (38 mm) and smaller. Carbon steel pipe
with  a wall thickness not less than Schedule 40 shall be used for Group
A1 or B1 refrigerant liquid lines 6 inches (152 mm) and  smaller,  Group
A2, A3, B2 or B3 refrigerant liquid lines sizes 2 inches (51 mm) through
6  inches  (152  mm)  and  all refrigerant suction and discharge lines 6
inches (152 mm) and smaller. Type F steel pipe shall  not  be  used  for
refrigerant  lines  having  an  operating  temperature  less  than -20°F
(-29°C).
  1107.4.2  Copper and brass pipe. Standard iron-pipe size,  copper  and
red brass (not less than 80-percent copper) pipe shall conform to ASTM B
42 and ASTM B 43.
  1107.4.3  Copper tube. Copper tube used for refrigerant piping erected
on the premises shall be seamless copper  tube  of  Type  ACR  (hard  or
annealed)  complying  with  ASTM  B 280. Where approved, copper tube for
refrigerant piping erected on the premises shall be seamless copper tube

of Type K or L (drawn  or  annealed)  in  accordance  with  ASTM  B  88.
Annealed  temper  copper  tube  shall not be used in sizes larger than a
2-inch (51 mm) nominal size. Mechanical joints  shall  not  be  used  on
annealed  temper  copper tube in sizes larger than 7/8-inch (22.2) mm OD
size.
  1107.4.4  Copper  tubing  joints.  Copper  tubing   joints   used   in
refrigeration systems containing Group A2, A3, B1, B2 or B3 refrigerants
shall be brazed. Soldered joints shall not be used in such refrigerating
systems.
  1107.4.5 Aluminum tube. Type 3003-0 aluminum tubing with high-pressure
fittings  shall  not be used with methyl chloride and other refrigerants
known to attack aluminum.
  1107.4.6 Insulation.  Pipe  and  chiller  insulation  shall  meet  the
requirements of Section 1204.1 of this code.
  1107.5  Joints  and  refrigerant-containing parts in air ducts. Joints
and all refrigerant-containing parts of a refrigerating  system  located
in an air duct of an air-conditioning system carrying conditioned air to
and from human-occupied space shall be constructed to withstand, without
leakage,  a pressure of 150 percent of the higher of the design pressure
or pressure relief device setting.
  1107.6 Exposure of refrigerant pipe joints.  Refrigerant  pipe  joints
erected  on the premises shall be exposed for visual inspection prior to
be being covered or enclosed.
  1107.7 Stop valves. All systems containing more than 6.6 pounds (3 kg)
of a refrigerant  in  systems  using  positive-displacement  compressors
shall have stop valves installed ass follows:
  1.  At  the  inlet  of  each compressor, compressor unit or condensing
unit.
  2. At the discharge outlet of  each  compressor,  compressor  unit  or
condensing unit and of each liquid receiver.
  Exceptions:
  1. Systems that have a refrigerant pumpout function capable of storing
the entire refrigerant charge in a receiver or heat exchanger.
  2.  Systems  that  are  equipped  with  provisions  for pumpout of the
refrigerant using either  portable  or  permanently  installed  recovery
equipment.
  3. Self-contained systems.
  1107.7.1  Liquid  receivers. All systems containing 100 pounds (45 kg)
or more of a  refrigerant,  other  than  systems  utilizing  nonpositive
displacement  compressors,  shall have stop valves, in addition to those
required by Section 1107.7, on each inlet of each liquid receiver.  Stop
valves  shall not be required on the inlet of a receiver in a condensing
unit, nor on the inlet of a receiver which is an integral  part  of  the
condenser.
  1107.7.2  Copper  tubing.  Stop  valves used with soft annealed copper
tubing or hard-drawn copper tubing 7/8-inch (22.2 mm) OD  standard  size
or  smaller  shall be securely mounted, independent of tubing fastenings
or supports.
  1107.7.3 Identification. Stoop valves shall be identified where  their
intended  purpose  is not obvious. Numbers hall not be used to label the
valves, unless a key to the numbers is located near the valves.
                             SECTION MC 1108
                               FIELD TEST
  1108.1 General. Every refrigerant-containing part of every system that
is erected on the premises,  except  compressors,  condensers,  vessels,
evaporators, safety devices, pressure gauges and control mechanisms that
are  listed  and  factory tested, shall be tested and proved tight after
complete installation, and before operation. Tests  shall  include  both

the  high-  and  low-pressure  sides of each system at not less than the
lower of the design pressures or the  setting  of  the  pressure  relief
device(s). the design pressures for testing shall be those listed on the
condensing  unit,  compressor or compressor unit name-plate, as required
by ASHRAE 15.
  Exceptions:
  1. Gas bulk storage tanks that are  not  permanently  connected  to  a
refrigeration system.
  2. Systems using an A1 refrigerant erected on the premises with copper
tubing  not  exceeding  5/8-inch  (15.8  mm)  OD, with wall thickness as
required by ASHRAE 15,  shall  be  tested  in  accordance  with  Section
1108.1,  or  by  means  of  refrigerant  charged  into the system at the
saturated vapor pressure of the refrigerant at 70°F (21°C) or higher.
  3. Limited-charge systems equipped  with  a  pressure  relief  device,
erected on the premises, shall be tested at a pressure not less than one
and  one-half  times  the  pressure setting of the relief device. If the
equipment or appliance has been tested by the manufacturer  at  one  and
one-half  times  the  design  pressure,  the  test after erection on the
premises shall be conducted at the design pressure.
  1108.1.1 Booster compressor. Where a compressor is used as  a  booster
to  obtain an intermediate pressure and discharges into the suction side
of another compressor, the booster compressor shall be considered a part
of the low side, provided that it is  protected  by  a  pressure  relief
device.
  1108.1.2    Centrifugal/nonpositive   displacement   compressors.   In
field-testing   systems   using   centrifugal   or   other   nonpositive
displacement  compressors,  the entire system shall be considered as the
low-side pressure for field test purposes.
  1108.2 Test gases. Tests shall be performed with  an  inert-dried  gas
including, but not limited to, nitrogen and carbon dioxide. Oxygen, air,
flammable gases and mixtures containing such gases shall not be used.
  Exceptions:
  1.  The use of air is allowed to test R-717, ammonia, systems provided
that they are subsequently evacuated before charging with refrigerant.
  2. Mixtures of dry nitrogen, inert gases, or  a  combination  of  them
with nonflammable refrigerants in concentrations of a refrigerant weight
fraction (mass fraction) not exceeding 5 are allowed for tests.
  1108.3  Test  apparatus.  The means used to build up the test pressure
shall have either a  pressure-limiting  device  or  a  pressure-reducing
device and a gauge on the outlet side.
  1108.4  Declaration.  A  certificate of test shall be provided for all
systems containing 55  pounds  (25  kg)  or  more  of  refrigerant.  The
certificate  shall  give  the name of the refrigerant and the field test
pressure applied to the high-side and the low side of  the  system.  The
certification of test shall be signed by the installer and shall be made
part of the public record.
                             SECTION MC 1109
                            PERIODIC TESTING
  1109.1  Testing  required. The following emergency devices and systems
shall be periodically tested and the results logged in  accordance  with
the  manufacture's  instructions  and as required by the Commissioner of
the Fire Department:
  1. Treatment and flaring systems.
  2. Valves and appurtenances necessary to the  operation  of  emergency
refrigeration control boxes.
  3.  Fans  and associated equipment intended to operate emergency purge
ventilation systems.
  4. Detection and alarm systems.

  1109.2 Operation. Operating permits and qualification of operators for
refrigeration systems shall comply with the requirements of the New York
City Fire Code and the rules of the Fire Department.
                       CHAPTER 12 HYDRONIC PIPING
                             SECTION MC 1201
                                 GENERAL
  1201.1  Scope.  The  provisions  of  this  chapter  shall  govern  the
construction, installation, alteration and  repair  of  hydronic  piping
systems.  This  chapter  shall apply to hydronic piping systems that are
part of heating, ventilation and air-conditioning systems.  Such  piping
systems  hall  include steam, hot water, chilled water, condenser water,
cooling coil condensate drain, steam condensate and ground  source  heat
pump loop systems. Potable cold and hot water distribution systems shall
be installed in accordance with the New York City Plumbing Code.
  1201.2  Pipe  sizing.  Piping for hyudronic systems shall be sized for
the demand of the system.
                             SECTION MC 1202
                                MATERIAL
  1202.1 Piping. Piping material shall conform to the standards cited in
this section.
  Exception: Embedded piping regulated by Section 1209.
  12.2.2 Used existing materials. Reused pipe, fittings, valves or other
materials shall be clean and free of foreign materials.
  1202.3 Material rating. Materials shall be  rated  for  the  operating
temperature  and  pressure  of  the  hydronic system. Materials shall be
suitable for the type of fluid in the hydronic system.
  1202.4 Piping materials standards. Hydronic pipe shall conform to  the
standards  listed  in  Table  1202.4.  the exterior of the pipe shall be
protected from corrosion and degradation.
                              TABLE 1202.4
                              HYDRONIC PIPE
------------------------------------------------------------------------
          MATERIAL                  |    STANDARD (see Chapter 15)
------------------------------------------------------------------------
  Acrylonitrile butadiene styrene   |
  (ABS) plastic pipe                |  ASTM D 1227; ASTM D 2282
------------------------------------------------------------------------
  Brass pipe                        |  ASTM B 43
------------------------------------------------------------------------
  Brass tubing                      |  ASTM B 135
------------------------------------------------------------------------
  Copper or copper-alloy pipe       |  ASTM B 42; ASTM B 302
------------------------------------------------------------------------
  Copper or copper-alloy tube       |  ASTM B 75; ASTM B 88
  (Type K, L or M)                  |  ASTM B 251
------------------------------------------------------------------------
  Chlorinated polyvinyl chloride    |  ASTM D 2846; ASTM F 441;
  (CPVC) plastic pipe               |  ASTM F 442
------------------------------------------------------------------------
  Cross-linked polyethylene/        |
  aluminum/cross-linked             |
  polyethylene                      |  ASTM F 1281;
  (PEX-AL-PEX) pressure pipe        |  CSA CAN/CSA-B-137.10
------------------------------------------------------------------------
  Cross-linked polyethylene         |
  (PEX) tubing                      |  ASTM F 876; ASTM F 877
------------------------------------------------------------------------
  Polyethylene (PE) pipe,           |  ASTM D 2513; ASTM D 3035;

  tubing and fittings (for          |  ASTM D 2447; ASTM D 2683;
  ground source heat pump           |  ASTM F 1055; ASTM D 2837;
  loop systems)                     |  ASTM D 3350; ASTM D 1693
------------------------------------------------------------------------
  Polyvinyl chloride (PVC)          |
  plastic pipe                      |  ASTM D 1785; ASTM D 2241
------------------------------------------------------------------------
  Steel pipe                        |  ASTM A 53; ASTM A 106
------------------------------------------------------------------------
  Steel tubing                      |  ASTM A 254
------------------------------------------------------------------------
  Cross-linked polyethylene         |
  (PEX) tubing                      |  ASTM F 876; ASTM F 877
------------------------------------------------------------------------
  Lead pipe                         |  FS WW-P-325B
------------------------------------------------------------------------
  Polybutylene (PB) plastic pipe    |
  and tubing                        |  ASTM D 3309
------------------------------------------------------------------------
  Polyethylene (PE) pipe,           |  ASTM D 2513; ASTM D 3035;
  tubing and fittings (for          |  ASTM D 2447; ASTM D 2683;
  ground source heat pump           |  ASTM F 1055; ASTM D 2837;
  loop systems)                     |  ASTM D 3350; ASTM D 1693
------------------------------------------------------------------------
  Polyvinyl chloride (PVC) plastic  |
  pipe                              |  ASTM D 1785; ASTM D 2241
------------------------------------------------------------------------
  Steel pipe                        |  ASTM A 53; ASTM A 106
------------------------------------------------------------------------
  Steel tubing                      |  ASTM A 254
------------------------------------------------------------------------
  1202.5  Pipe  fittings.  Hydronic  pipe fittings shall be approved for
installation with the  piping  materials  to  be  installed,  and  shall
conform  to  the respective pipe standards or to the standards listed in
Table 1202.5.
                              TABLE 1202.5
                         HYDRONIC PIPE FITTINGS
------------------------------------------------------------------------
         MATERIAL                   |     STANDARD (see Chapter 15)
------------------------------------------------------------------------
  Bronze                            |  ASME B16.24
------------------------------------------------------------------------
                                    |  ASME B16.15; ASME B16.18;
  Copper and copper alloys          |  ASME B16.22; ASME B16.23;
                                    |  ASME B16.26; ASME B16.29
------------------------------------------------------------------------
  Gray Iron                         |  ASTM A 126
------------------------------------------------------------------------
  Malleable iron                    |  ASME B16.3
------------------------------------------------------------------------
                                    |  ASTM D 2466; ASTM D 2467;
  Plastic                           |  ASTM D 2468; ASTM F 438;
                                    |  ASTM F 439; ASTM F 877
------------------------------------------------------------------------
                                    |  ASME B16.5; ASME B16.9;
  Steel                             |  ASME B16.11; ASME B16.28;
                                    |  ASTM A 420
------------------------------------------------------------------------

  Brass                             |  ASTM F 1974
------------------------------------------------------------------------
  1202.6  Valves.  Valves  shall  be  constructed  of materials that are
compatible with the type of piping material and fluids  in  the  system.
Valves  shall be rated for the temperatures and pressures of the systems
in which the valves are installed.
  1202.7 Flexible  connectors,  expansion  and  vibration  compensators.
Flexible   connectors,  expansion  and  vibration  control  devices  and
fittings shall be of an approved type.
                             SECTION MC 1203
                         JOINTS AND CONNECTIONS
  1203.1 Approval. Joints and connections shall be of an approved  type.
Joints  and  connections shall be tight for the pressure of the hydronic
system.
  1203.1.1 Joints between different  piping  materials.  Joints  between
different piping materials shall be made with approved adapter fittings.
Joints  between  different  metallic piping materials shall be made with
approved dielectric fittings or brass converter fittings.
  1203.2 Preparation of pipe ends. Pipe shall be cut square, reamed  and
chamfered,  and shall be free of burrs and obstructions. Pipe ends shall
have full-bore openings and shall not be undercut.
  1203.3 Joint preparation and installation. When  required  by  Section
1203.4  through  1203.14,  the  preparation  and installation of brazed,
mechanical, soldered, solvent-cemented, threaded and welded joints shall
comply with Sections 1203.3.1 through 1203.3.7.
  1203.3.1 Brazed joints. Joint surfaces shall be cleaned.  An  approved
flux  shall  be applied where required. The joint shall be brazed with a
filler metal conforming to AWS A 5.8.
  1203.3.2 Mechanical joints. Mechanical joints shall  be  installed  in
accordance with the manufacturer's instructions.
  1203.3.3  Soldered  joints.  Joint  surfaces  shall be cleaned. A flux
conforming to ASTM B 813 shall be applied. The joint shall  be  soldered
with a solder conforming to ASTM B 32.
  1203.3.4  Solvent-cemented  joints.  CPVC  joints  shall  be  made  in
accordance with ASTM D 2846. Joint surfaces shall be clean and  free  of
moisture. An approved primer shall be applied to CPVC and PVC pipe-joint
surfaces.  Joints  shall be made while the cement is wet. Solvent cement
conforming to the following standards shall  be  applied  to  all  joint
surfaces:
  1. ASTM D 2235 for ABS joints.
  2. ASTM F 493 for CPVC joints.
  3. ASTM D 2564 for PVC joints.
  1203.3.5  Threaded  joints.  Threads  shall  conform to ASME B 1.20.1.
Schedule 80  or  heavier  plastic  pipe  shall  be  threaded  with  dies
specifically  designed  for  plastic  pipe. Thread lubricant, pipe-joint
compound or tape shall be applied on the male threads only and shall  be
approved for application on the piping material.
  1203.3.6 Welded joints. Joint surfaces shall be cleaned by an approved
procedure. Joints shall be welded with an approved filler metal.
  1203.3.7  Grooved and shouldered joints. Grooved and shouldered joints
shall be approved and installed in accordance  with  the  manufacturer's
installation instructions.
  1203.3.8  Mechanically  formed  tee  fittings.  Mechanically extracted
outlets shall have a height not less than three times the  thickness  of
the branch tube wall.
  1203.3.8.1  Full  flow assurance. Branch tubes shall not restrict flow
in the run tube. A dimple/depth stop shall be formed in the branch  tube
to  ensure that penetration into the outlet is of the correct depth. For

inspection purposes, a second dimple shall be placed 0.25 inch (6.4  mm)
above the first dimple. Dimples shall be aligned with the tube run.
  1203.3.8.2  Brazed  joints.  Mechanically formed tee fittings shall be
brazed in accordance with Section 1203.3.1.
  1203.4 ABS plastic pipe. Joints between ABS plastic pipe  or  fittings
shall  be  solvent-cemented  or  threaded  joints  conforming to Section
1203.3.
  1203.5 Brass pipe. Joints between brass  pipe  or  fittings  shall  be
brazed,  mechanical,  threaded  or  welded  joints conforming to Section
1203.3.
  1203.6 Brass tubing. Joints between brass tubing or fittings shall  be
brazed, mechanical or soldered joints conforming to Section 1203.3.
  1203.7   Copper   or  copper-alloy  pipe.  Joints  between  copper  or
copper-alloy pipe or fittings shall  be  brazed,  mechanical,  soldered,
threaded or welded joints conforming to Section 1203.3.
  1203.8  Copper  or  copper-alloy  tubing.  Joints  between  copper  or
copper-alloy tubing or fittings shall be brazed, mechanical or  soldered
joints  conforming  to  Section  1203.3  or  flared joints conforming to
Section 1203.8.1.
  1203.8.1 Flared joints. Flared joints shall be made by a  tool  design
for that operation.
  1203.9 CPVC plastic pipe. Joints between CPVC plastic pipe or fittings
shall  be  solvent-cemented  or  threaded  joints  conforming to Section
1203.3.
  1203.10 Reserved.
  1203.11 Cross-linked polyethylene (PEX) plastic tubing. Joints between
cross-linked polyethylene plastic tubing and fittings shall  conform  to
Section  1203.11.1  and  1203.11.2.  Mechanical  joints shall conform to
Section 1203.3.
  1203.11.1 Compression-type fittings.  When  compression-type  fittings
include inserts and ferrules or O-rings, the fittings shall be installed
without omitting the inserts and ferrules or O-rings.
  1203.11.2 Plastic-to-metal connections. Soldering on the metal portion
of  the  system  shall  be  performed at least 18 inches (457 mm) from a
plastic-to-metal adapter in the same water line.
  1203.12 PVC plastic pipe. Joints between PVC plastic pipe and fittings
shall be solvent-cemented  or  threaded  joints  conforming  to  Section
1203.3.
  1203.13  Steel  pipe.  Joints  between steel pipe or fittings shall be
mechanical joints that are made with an approved  elastomeric  seal,  or
shall be treated or welded joints conforming to Section 1203.3.
  1203.14 Steel tubing. Joints between steel tubing or fittings shall be
mechanical or welded joints conforming to Section 1203.3.
  1203.15  Polyethylene  plastic  pipe  or tubing for ground source heat
pump loop systems. Joints between polyethylene plastic pipe  and  tubing
or  fittings  for  ground  source  heat  pump loop systems shall be heat
fusion joints conforming  to  Section  1203.15.1,  electrofusion  joints
conforming   to   Section   1203.15.2,  or  stab-type  insertion  joints
conforming to Section 1203.15.3.
  1203.15.1 Heat-fusion joints. Joints shall be  of  the  socket-fusion,
saddle-fusion  or  butt-fusion  type,  fabricated in accordance with the
piping manufacturer's instructions. Joint surfaces shall  be  clean  and
free  of  moisture.  Joint surfaces shall be heated to melt temperatures
and joined. The joint shall be undisturbed until cool. Fittings shall be
manufactured in accordance with ASTM D 2683.
  1203.15.2 Electrofusion joints. Joints shall be of  the  electrofusion
type. Joint surfaces shall be clean and free of moisture, and scoured to
expose virgin resin. Joint surfaces shall be heated to melt temperatures

for the period of time specified by the manufacturer. The joint shall be
undisturbed  until  cool.  Fittings  shall be manufactured in accordance
with ASTM F 1055.
  1203.15.3 Stab-type insert fittings. Joint surfaces shall be clean and
free  of  moisture.  Pipe  ends shall be chamfered and inserted into the
fittings to full depth. Fittings shall  be  manufactured  in  accordance
with ASTM D 2513.
                             SECTION MC 1204
                             PIPE INSULATION
  1204.1   Insulation  characteristics.  Pipe  insulation  installed  in
buildings shall conform to the requirements of the New York City  Energy
Conservation  Code,  shall  be  tested  in accordance with ASTM E 84 and
shall have a maximum flame spread index  of  25  and  a  smoke-developed
index  not  exceeding  450.  Insulation installed in an air plenum shall
comply with Section 602.2.1.
  1204.2 Required thickness. Hydronic piping shall be insulated  to  the
thickness required by the New York City Energy Conservation Code.
                              SECTION MC 1205
                                 VALVES.
  1205.1  Where  required. Shutoff valves shall be installed in hydronic
piping systems in the locations indicated in Sections  1205.1.1  through
1205.1.5.
  1205.1.1  Heat  exchangers.  Shutoff  valves shall be installed on the
supply and return side of a heat exchanger.
  Exception: Shutoff valves shall not be required when  heat  exchangers
are  integral  with  a  boiler;  or  are a component of a manufacturer's
boiler and heat  exchanger  packaged  unit  and  are  capable  of  being
isolated  from  the  hydronic  system  by  the  supply and return valves
required by Section 1005.1.
  1205.1.2 Central systems. Shutoff valves shall  be  installed  on  the
building  supply  and  return  of  central utility systems, and district
heating and cooling systems.
  1205.1.3 Pressure vessels. Shutoff valves shall be  installed  on  the
connection to any pressure vessel.
  1205.1.4  Pressure-reducing  valves. Shutoff valves shall be installed
on both sides of a pressure-reducing valve.
  1205.1.5 Equipment and appliances. Shutoff valves shall  be  installed
on  connections to mechanical equipment and appliances. This requirement
does not apply to components of a hydronic system  such  as  pumps,  air
separators, metering devices and similar equipment.
  1205.2 Reduced pressure. A pressure relief valve shall be installed on
the  low-pressure side of a hydronic piping system that has been reduced
in pressure. The relief valve shall be set at the  maximum  pressure  of
the  system  design.  The  valve  shall  be installed in accordance with
Section 1006.
                             SECTION MC 1206
                           PIPING INSTALLATION
  1206.1 General. Piping, valves,  fittings  and  connections  shall  be
installed in accordance with the conditions of approval.
  1206.1.1  Prohibited  tee  applications. Fluid in the supply side of a
hydronic system shall  not  enter  a  tee  fitting  through  the  branch
opening.
  1206.2  System  drain  down. Hydronic piping systems shall be designed
and installed to permit the system  to  be  drained.  Where  the  system
drains  to  the plumbing drainage system, the installation shall conform
to the requirements of the New York City Plumbing Code.

  1206.3 Protection of potable water. The potable water system shall  be
protected  from  backflow  in accordance with the New York City Plumbing
Code.
  1206.4  Pipe  penetrations.  Openings  for pipe penetrations in walls,
floors or ceilings shall be larger than the penetrating  pipe.  Openings
through  concrete  or  masonry  building  elements shall be sleeved. The
annular space  surrounding  pipe  penetrations  shall  be  protected  in
accordance with the New York City Building Code.
  1206.5  Clearance  to combustibles. A pipe in a hydronic piping system
in which the exterior temperature exceeds 250°F  (121°C)  shall  have  a
minimum clearance of 1 inch ( 25 mm) to combustible materials.
  1206.6  Contact with building material. A hydronic piping system shall
not be in direct contact with building materials that cause  the  piping
material  to degrade or corrode, or that interfere with the operation of
the system.
  1206.7 Water hammer. The flow velocity of the hydronic  piping  system
shall  be  controlled to reduce the possibility of water hammer. Where a
quick-closing valve  creates  water  hammer,  an  approved  water-hammer
arrestor  shall  be  installed.  The  arrestor shall be located within a
range as specified by the manufacturer of the quick-closing valve.
  1206.8 Steam piping pitch. Steam piping shall be installed to drain to
the boiler or the steam trap. Steam systems shall not have drip  pockets
that reduce the capacity of the steam piping.
  1206.9  Strains  and  stresses.  Piping  shall  be  installed so as to
prevent detrimental strains and stresses in the pipe.  Provisions  shall
be  made  to  protect  piping  from  damage  resulting  from  expansion,
contraction and structural settlement. Piping shall be installed  so  as
to avoid structural stresses or strains within building components.
  1206.9.1 Flood hazard. Piping located in areas of special flood hazard
shall comply with Appendix G of the New York City Building Code.
  1206.10  Pipe  support.  Pipe  shall  be  supported in accordance with
Section 305. Seismic supports shall be provided where  required  by  the
New York City Building Code.
  1206.11   Condensation.  Provisions  shall  be  made  to  prevent  the
formation of condensation on the exterior of piping.
                             SECTION MC 1207
                             TRANSFER FLUID
  1207.1 Flash point. The flash point of transfer fluid in the  hydronic
piping system shall be a minimum of 50°F (28°C) above the maximum system
operating temperature.
  1207.2  Makeup  water. The transfer fluid shall be compatible with the
makeup water supplied to the system.
                             SECTION MC 1208
                                  TESTS
  1208.1 General. Hydronic piping systems other than ground-source  heat
pump  loop  systems  shall be tested hydrostatically at one and one half
times the system design operating pressure, but not less  than  100  psi
(689  kPa).  The  duration  of each test shall be not less than 2 hours.
Ground-source heat pump loop systems shall be tested in accordance  with
Section 1208.1.1.
  1208.1.1  Ground  source  heat  pump  look  systems. Before connection
(header) trenches are backfilled, the assembled  loop  system  shall  be
pressure  tested  with water at 100 psi (689 kPa) for 30 minutes with no
observed leaks. Flow and pressure loss testing shall  be  performed  and
the  actual  flow  rates  and  pressure  drops  shall be compared to the
calculated design values. If actual flow rate or  pressure  drop  values
differ  from  calculated  design  values  by  more  than 10 percent, the
problem shall be identified and corrected.

                             SECTION MC 1209
                             EMBEDDED PIPING
  1209.1  Materials  Piping  for heating panels shall be standard-weight
steel pipe. Type L copper tubing, or approved  plastic  pipe  or  tubing
rated at 100 psi (689 kPa) at 180°F (82°C).
  1209.2  Pressurizing  during  installation.  Piping  to be embedded in
concrete shall be pressure tested  prior  to  pouring  concrete.  During
pouring,  the  pipe  shall  be  maintained  at  the  proposed  operating
pressure.
  1209.3 Embedded joints. Joints of pipe or tubing that are embedded  in
a  portion  of  the  building,  such as concrete or plaster, shall be in
accordance with the requirements of Sections 1209.3.1 and 1209.2.
  1209.3.1 Steep pipe joints. Steep pipe shall be welded  by  electrical
arc or oxygen/acetylene method.
  1209.3.2  Copper  tubing  joints.  Copper  tubing  shall  be joined by
brazing with filler metals having a  melting  point  of  not  less  than
1,000°f (538°C).
  1209.4 Reserved.
                            SECTION MC 12010
                   HIGH-PRESSURE STEAM PIPING SYSTEMS.
  1210.1   Scope.   The  provisions  of  this  section  shall  apply  to
high-pressure steam piping system which is defined as a system operating
at a steam pressure of more than 15 psi (103 kPa). For purposes of  this
section,  loops,  bends or offsets of the piping shall not be considered
expansion joints.
  1210.2 New systems. For purposes of this section, the  replacement  of
existing  steam  piping  systems,  the  installation  of a new system in
existing buildings, as well  as  installations  in  buildings  hereafter
constructed,  shall  be  considered  to  be  a  new high-pressure piping
systems. The following requirements are applicable:
  1210.2.1 Design. The design of  new  steam  piping  systems  shall  be
conducted as follows:
  1.  The  system  shall  be designed by an engineer. An application and
plans shall be filed and the approval of the  department  obtained.  The
plans  and  application  shall  contain,  but  not  be  limited  to, the
following information:
  1.1. Size and location of all steam piping.
  1.2. The operating pressures and temperatures.
  1.3. The location, type, specifications and details of  all  expansion
joints.
  1.4.  The  design,  size, material and location of all anchors, guides
and auxiliary steel, and the stresses thereon.
  2. Systems using utility street steam shall be designed for a pressure
of 200 psig (1379 kPa) and 413°F (212°C) up to and including  the  steam
pressure  reducing  valve or valves which reduce the pressure of 90 psig
(621 kPa) or below. For steam pressures between 90 psig (621 kPa) and 16
psig (110 kPa), the system shall be designed for 125 psig (108 kPa).
  1210.2.2 Installation. The installation of new system  piping  systems
shall be conducted as follows:
  1.   Installations,   including  any  welding,  shall  be  by  special
inspection by the engineer responsible for the design, or by an engineer
acceptable to him or her.
  2. Welders shall be  qualified  for  all  required  pipe  sizes,  wall
thicknesses  and  positions  in  accordance  with  the  ASME  Boiler and
Pressure Vessel Code, Section  IX.  Requalification  is  required  every
three years or sooner if the commissioner has a specific reason to doubt
a welder's ability to make sound welds.

  3. Welder qualification testing shall be performed by an agency listed
with  the  department,  and  if  the  testing  is  by  radiography,  the
inspection shall have a minimum radiography qualification of Level II in
accordance with the ASNT, Document No. SNT-TC-1A.
  4.  Copies  of  the  certified  welder, qualification reports shall be
maintained by the responsible welding agency and the company  performing
the welding, and shall be made available upon request to the department.
  5.  No  reports  from  any welding inspection agency shall be accepted
unless such agency has first requested and obtained  approval  from  the
department in accordance with rules of the department.
  6. Pipe welding shall conform to the following:
  6.1  Piping  over  2  inches  (51 mm) shall be butt-welded.   Piping 2
inches (76 mm) and under may be socket-welded or threaded.
  6.2 Threaded piping may continue to be used for existing  construction
in sizes of 6 inches (152 mm) and under.
  6.3  Where  welding  is  not  feasible,  the commissioner may allow an
acceptable alternative.
  7. Radiographic examination, when  required,  shall  be  performed  on
butt-welds  in  accordance  with ASME B31.1 based on the piping pressure
and shall be as follows:
          Piping Pressure                              Percentage
          90 psig (621 kPa) or below                   Not required
          91 psig (627 kPa) to 150 psig (1034 kPa)     10 at Random
          Over 150 psig (1034 kPa)                     100
  However, if, in the opinion of the engineer  responsible  for  special
inspection,  radiographic  examination  is  not  required  for piping at
pressure between 90 psig (621 kPa) and 150 psig (1034 kPa), the engineer
shall so specify in writing, and the final report  on  the  installation
may  omit  the  foregoing,  and  be  predicated  on  all  of  the  other
requirements noted in this section, and a hydrostatic test.
  1210.2.3 Testing.  Hydrostatic  testing  shall  be  conducted  on  the
completed  installation  at  150  percent of the design pressure for all
piping pressure. Where the changes in an existing steam  system  involve
less  than 30 percent of the piping in the system, the testing may be in
accordance with the ASME B31.1.
  1210.2.4 Relocation. The commissioner, where deemed  necessary,  shall
require  the replacement or relocation of any joints, guides or anchors.
The  commissioner  shall  cause  the  joints  in  potentially  hazardous
locations,  such  as  those that are located adjacent to tenant occupied
spaces, to  be  relocated,  unless  means  exist  or  are  provided  for
eliminating the hazard.
  1210.3  Existing  systems.  Existing  steam  piping systems hall be in
accordance with Sections 1210.3.1 through 1210.3.3. Upon the  completion
of  a  new  high-pressure steam piping system and department approval of
same, the rules relating to maintenance requirements and the keeping  of
records for existing high-pressure steam piping systems shall apply.
  1210.3.1  Maintenance  inspections.  Expansion  joints,  anchorage and
guides shall be inspected as follows:
  1. Expansion joints shall be inspected weekly.
  2. The anchorage and guides shall be inspected annually.  Exposure  of
the  structural attachments to the buildings of the anchorages or guides
shall not be required.
  3. A record of such inspections shall be  kept by the person in charge
of  the  mechanical  equipment  of  the  building  or  qualified  person
designated  by the owner and acceptable to the commissioner. The records
shall be available at the premises and  subject  to  inspection  by  the
commissioner.

  1210.3.2  Work  approval.  No  joint,  anchorage  or  guides  shall be
repaired, replaced or relocated without a  work  permit  issued  by  the
department.   The application for the permit shall contain all pertinent
information and shall be filed  by  the  engineer  knowledgeable  as  to
high-pressure  steam  piping  systems. The engineer shall be responsible
for the inspection of the proposed work in accordance with the  approved
application.  This  provision shall not apply to the repacking of a slip
or ball joint; however, records of such repacking shall be kept  in  the
inspections records as provided in Section 12103.1, Item 3. When, in the
opinion  of  the engineer, the requirement for prior department approval
would create an imminent health or  safety  hazard,  the  engineers  may
permit  the  work  to proceed without prior approval. In such cases, the
engineer shall, prior the repair, replacement or relocation,  notify  by
telephone  the borough commissioner of the borough in which the building
is located; and, if the emergency occurs at other  than  normal  working
hours, he or she shall notify the department in the manner prescribed by
the  commissioner.  This  shall  be  following  by  the  filing  of  the
application for department approval as specified in  Section  28-105.4.1
of the Administrative Code.
                                CHAPTER 13
                       FUEL-OIL PIPING AND STORAGE
                             SECTION MC 1301
                                 GENERAL
  1301.1  Scope.  This  chapter  shall  govern the design, installation,
construction and repair of fuel-oil  storage  and  piping  systems.  The
storage  of  flammable  and  combustible  liquids  not addressed in this
chapter shall be in accordance with the New York City Fire Code.
  1301.2 Storage and piping systems. Fuel-oil storage and piping systems
shall comply with the requirements of Chapter 13 and, to the extend  not
otherwise  provided for in this code, shall comply with the requirements
of NFPA 31. All aboveground and underground storage  facilities  with  a
combined  storage  capacity  of  over  1,100 gallons (4160 L) shall also
comply with the  requirements  of  the  New  York  State  Department  of
Environmental  Conservation's Petroleum Bulk Storage Code; 6 NYCRR Parts
612, 613, and 614.
  1301.3 Fuel type. An appliance shall be designed for use with the type
of fuel to which it will be  connected.  Such  appliance  shall  not  be
converted  from  the  fuel  specified on the rating plate for use with a
different fuel without securing reapproval from the commissioner.
  1301.4 Fuel tanks, piping and valves. The tank, piping and valves  for
appliances  burning  oil  shall  be  installed  in  accordance  with the
requirements of this chapter. When oil burning equipment is served by  a
tank  located  such  that any part of the tank is above the level of the
burner inlet connection and where the fuel supply line is taken from the
top of the tank, an approved anti-siphon valve or other  siphon-breaking
devices  hall  be  installed.  The  anti-siphon valve or siphon-breaking
device shall be located at the highest point in the supply line.
  Exceptions: An anti-siphon valve or other siphon-breaking device shall
not be required where either:
  1. An approved foot valve is used in the tank, or
  2. No. 6 fuel oil is used.
  1301.5 Out of  service  system.  Fuel-oil  storage  systems  that  are
temporarily  or  permanently  taken out of service shall comply with the
requirements of the Fire  Code.
  1301.6 Fuel-oil spill and overfill  prevention  equipment.    Fuel-oil
spill  and  overfill  prevention  equipment shall comply with EPA 40 CFR
Parts 280, and Section 1305.6.6.

  1301.7 Portable fire extinguishers. Portable fire extinguishers with a
minimum weight of 30 pounds (13.64 kg) shall be provided as required  by
the Fire Code and NFPA 10.
  1301.8  Absorbent  materials.  The  building  owner  shall  maintain a
sufficient quantity of absorbent materials near fuel-oil storage  tanks,
pumps, and related equipment to control leaks and slipping hazards.
  1301.9  Certificate  of fitness. Where fuel-oil piping systems utilize
pumps to transfer fuel-oil to equipment at levels above the lowest floor
or to storage tanks at levels above the lowest  floor  in  buildings,  a
qualified  employee  or contracted general company holding a certificate
of fitness from the Fire Department shall maintain the fuel-oil system.
                              SECTION MC 1302
                                MATERIAL
  1302.1 General. Piping materials shall conform to the standards  cited
in this section.
  1302.2  Rated  for  system.  All  materials  shall  be  rated  for the
operating temperatures and  pressures  of  the  systems,  and  shall  be
compatible with the type of liquid being handled by the systems.
  1302.3  Pipe  standards. Fuel-oil pipe shall comply with the standards
listed in Table 1302.3.
  Exception: Piping for fuel-oil systems utilizing a  transfer  pump  to
equipment at levels above the lowest floor or to storage tanks at levels
above  the  lowest floor in buildings shall comply with the requirements
of Section 1305.9.5.

                              TABLE 1302.3
                             FUEL OIL PIPING
     -------------------------------------------------------------
         MATERIAL                    |   STANDARD (see Chapter 15)
     -------------------------------------------------------------
       Brass pipe                    | ASTM B 43
     -------------------------------------------------------------
       Copper or copper-alloy pipe   | ASTM B 42; ASTM B 302
     -------------------------------------------------------------
       Cooper or Copper-alloy tubing | ASTM B 75; ASTM B 88;
       (Type K)                      | ASTM B 280
     -------------------------------------------------------------
       Labeled pipe                  | (See Section 1302.4)
     -------------------------------------------------------------
       Nonmetallic pipe              | ASTM D 2996
     -------------------------------------------------------------
       Steel pipe                    | ASTM A 53; ASTM A 106
     -------------------------------------------------------------

a. Brass tubing, steel  tubing  and  cooper  tubing,  L  or  M  are  not
permitted.
  1302.4  Nonmetallic  pipe.  All  nonmetallic  pipe shall be listed and
labeled as being acceptable for the intended application  for  flammable
and  combustible  liquids.  Nonmetallic  pipe  shall  be  installed only
outside, underground.
  1302.5 Fittings and valves. Fittings and valves shall be approved  for
the  piping  systems,  and  shall be compatible with, or shall be of the
same material as, the pipe or tubing.
  1302.6 Bending of pipe. Pipe shall be approved for bending. Pipe bends
shall be made with approved equipment. The bend  shall  not  exceed  the
structural limitations of the pipe.
  1302.7  Pumps.  Pumps  that are not part of an appliance shall be of a
positive-displacement type. The pump shall automatically  shut  off  the

supply  when  not  in  operation.  Pumps  shall be listed and labeled in
accordance with UL 343.
  1302.8  Flexible  connectors  and hoses. Flexible metal connectors and
hoses used where rigid connections are  impractical  or  to  reduce  the
effect  of  jarring  and  vibrating  shall  be  listed  and  labeled  in
accordance with UL 536 and shall be installed  in  compliance  with  its
label  and the manufacturer's installation instructions. Connectors made
from combustible materials shall not be used inside buildings  or  above
ground outside of buildings.
                              SECTION MC 1303
                         JOINTS AND CONNECTIONS
  1303.1  Approval.  Joints  and  connections shall be approved and of a
type a approved for fuel-oil piping systems.  All  threaded  joints  and
connections  shall  be  made  tight  with  suitable  lubricant  or  pipe
compound.    Unions  requiring  gaskets  or  packings,  right  or   left
couplings,  and  sweat  fittings  employing  brazing  material  having a
melting point of less than 1,000°F (538°C) shall  not  be  used  in  oil
lines.  Cast-iron  fittings  shall  not  be used. Joints and connections
shall be tight for the pressure required by test.
  1303.1.1 Joints between different  piping  materials.  Joints  between
different piping materials shall be made with approved adapter fittings.
Joints  between  different  metallic piping materials shall be made with
approved dielectric fittings or brass converter fittings.
  1303.2 Reserved.
  1303.3 Joint preparation and installation. Where required by  Sections
1303.4  through  1303.10,  the  preparation  and installation of brazed,
threaded and welded joints shall comply with Sections  1303.3.1  through
1303.3.4.
  1303.3.1  Brazed  joints.  All  joint  surfaces  shall  be cleaned. An
approved flux shall be applied where required.    The  joints  shall  be
brazed with a filler meter conforming to AWS A5.8.
  1303.3.2   Mechanical   joints.   Mechanical   joints   utilizing   an
elastromeric and/or compression seal are not permitted.
  1303.3.3 Threaded joints.  Threads  shall  conform  to  ASME  B1.20.1.
Pipe-joint compound or tape shall be applied on the male threads only.
  1303.3.4  Welded  joints.  All  joint  surfaces  shall  be  cleaned by
approved procedure. The joint shall be welded with  an  approved  filler
metal.
  1303.4  Brass  pipe.  Joints  between  brass pipe of fittings shall be
brazed, mechanical, threaded or welded  joints  complying  with  Section
1303.3.
  1303.5 Reserved.
  1303.6   Copper   or  copper-alloy  pipe.  Joints  between  copper  or
copper-alloy pipe or fittings shall be brazed, mechanical,  threaded  or
welded joints complying with Section 1303.3.
  1303.7  Cooper  or  copper-alloy  tubing.  Joints  between  copper  or
copper-alloy tubing or fittings shall be  brazed  or  mechanical  joints
complying  with  Section 1303.3 or flared joints. Flared joints shall be
made by as tool designed for that operation.
  1303.8 Nonmetallic pipe. Joints between nonmetallic pipe  or  fittings
shall  be  installed  in accordance with the manufacturer's instructions
for the labeled pipe and fittings.
  1303.9 Steel pipe. Joints between steel  pipe  of  fittings  shall  be
threaded or welded joints complying with Section 1303.3.
  1303.10 Reserved.
  1303.11   Piping  protection.  Proper  allowance  shall  be  made  for
expansion, contraction, jarring and vibration. Piping other than tubing,
connected to underground tanks, except  straight  full  lines  and  test

wells,  shall  be  provided  with  flexible  connectors,  or  other wise
arranged to permit the tanks to settle without impairing  the  tightness
of  the piping connections. Piping serving equipment at levels above the
lowest  floor  or  storage  tanks  at  levels  above the lowest floor in
buildings shall also comply with the requirements  of  Section  1305.9.6
and 1305.9.7.
                              SECTION MC 1304
                             PIPING SUPPORT
  1304.1 General. Pipe supports shall be in accordance with Section 305.
Piping  serving  equipment  at  levels above the lowest floor or storage
tanks at levels above the lowest floor in buildings  shall  also  comply
with the requirements of Section 1305.9.6 and 1305.9.7.
                              SECTION MC 1305
                      FUEL-OIL SYSTEM INSTALLATION
  1305.1   General.  Fuel-oil  piping  systems  shall  be  installed  in
accordance with this section.
  1305.2 Protection of pipe,  equipment  and  appliances.  All  fuel-oil
pipe,  equipment and appliances shall be protected from physical damage.
Piping serving equipment at levels above the  lowest  floor  or  storage
tanks  at  levels  above the lowest floor in buildings shall also comply
with the requirements of Section 1305.9.
  1305.2.1  Floor  hazard.  All  fuel-oil  pipe,  tanks,  equipment  and
appliances  located  in  areas of special flood hazard shall comply with
Appendix G of the New York City Building Code.
  1305.3 Supply piping. Supply piping shall comply with the requirements
of Sections 1305.3.1 through 1305.3.7.
  1305.3.1 Size. The fuel-oil system shall  be  sized  for  the  maximum
capacity  of  fuel oil required. The minimum size of a supply line shall
be 3/8-inch (9.5 mm) inside diameter nominal pipe or 3/8-inch  (9.5  mm)
OD tubing.
  1305.3.2  Connections  to tank. Supply piping shall connect to the tip
of the fuel-oil tank.
  Exception: Storage tanks in buildings that  comply  with  all  of  the
following conditions:
  1. The tank is located above ground on the lowest floor;
  2. The tank does not exceed 330 gallons (1250 L); and
  3.  The tank is provided with a 3/4-inch (19.1 mm) opening for gravity
discharge and a 1-inch (25 mm) opening in the bottom  for  cleaning  and
protection against corrosion.
  1305.3.3  Pumps.  Fuel  oil  shall  be  supplied by a transfer pump or
automatic pump or by other approved means.
  1305.3.4 Smoke detectors. Appropriate safeties shall  be  provided  so
that  detection  of smoke or heat within the generator or equipment room
shall provost additional fuel oil from  being  pumped  into  the  piping
system  within  such  room, including a fusible link operated lever gate
valve in the supply pipe at the wall of the generator room.
  1305.3.5 Horizontal runouts. Horizontal runouts  from  risers  to  the
generator   or  equipment  room  shall  follow  as  direct  a  route  as
practicable.
  1305.3.6 Direct feed. Systems where day  tanks  are  absent  (such  as
generator installations where fuel oil is taken directly from a fuel-oil
pipe or header into the engine) shall comply with Section 1305.9.12.
  1305.3.7 Piping from transfer pump to equipment or storage tanks above
the  lowest  floor.  Supply  piping from a transfer pump to equipment at
levels above the lowest floor or  storage  tanks  at  levels  above  the
lowest  floor  in  buildings  shall also comply with the requirements of
Section 1305.9.

  1305.4 Return piping. Return piping shall connect to the  top  of  the
fuel-oil  tank. The minimum size of a return line shall be 1/4-inch (6.4
mm) inside diameter nominal pipe or 5/16-inch (7.9 mm) outside  diameter
tubing. Valves shall not be installed on return piping unless a means of
relieving  overpressure  is provided. Return piping serving equipment at
levels above the lowest floor or  storage  tanks  at  levels  above  the
lowest  floor  in  buildings  shall also comply with the requirements of
Section 1305.9.
  1305.5 System pressure. The system shall be designed for  the  maximum
pressure  required by the fuel-oil-burning appliance. Air or other gases
shall not be used to pressurize tanks. Pressure in a  storage  tank  for
the purpose of discharging oil shall be prohibited.
  1305.6  Fill piping. Fill piping shall comply with the requirements of
Section 1305.6.1 through 1305.6.6.
  1305.6.1 Size. Fill piping shall be a minimum of 2 inches (51  mm)  in
diameter or 3 inches (76 mm) for No. 6 fuel oil.
  1305.6.2  Termination location. A fill pipe shall terminate outside of
a building at or above grade at a point least 2 feet (610 mm)  from  any
building  opening  and  5 feet (1524 mm) away from-any subway grating at
the same or lower level.  A  fill  pipe  shall  terminate  in  a  manner
designed  to  minimize  spilling  when the filling hose is disconnected.
Where No. 6 fuel oil is  used, the fill pipe terminal shall be within  3
feet (914 mm) of the curb unless otherwise required by the Department of
Transportation  or the Transit Authority. If facilities exist for an oil
delivery truck to drive onto the premises, the fuel-oil terminal may  be
located elsewhere other than the curb.
  1305.6.3  Separate  fill  piping.  Each storage tank shall be provided
with a separate  fill  pipe,  except  that  where  a  battery  of  tanks
containing  the same grade of oil is installed, a common fill and header
pipe may be installed.
  1305.6.4 Check valve. Where the top of the storage tank is  above  the
fill  pipe  terminal, the fill pipe shall be connected to the top of the
tank and provided with a shut-off valve and swing check valve,  both  of
which shall be located at the fill pipe terminal. The shut-off valve and
swing  check valve may be installed in an accessible location inside the
building at or below the level of the fill pipe terminal.
  1305.6.5 Terminal opening. The fill opening shall be equipped  with  a
tight  metal  cover  designed  to  discourage  tampering.  All fill pipe
terminals shall be of an approved type and shall be provided  with  lugs
for  embedding  in  concrete. In lieu of lugs, a set screw or threads to
fasten the terminal to the fill pipe may be used. The  outer  flange  of
the fill pipe terminal or the seal cap shall be permanently marked: FUEL
OIL.  The  fill  pipe  terminal shall be threaded or provided with other
equivalent means to receive the seal cap. The seal cap shall be suitably
slotted for receiving an opening wrench, and an oilproof casket inserted
in a groove in the fill pipe terminal shall be provided so  as  to  make
the  seal  cap  leakproof. A strainer shall not be required but if used,
shall be of at least 1/4-inch (3.2 mm) mesh. Where a storage system  for
volatile  flammable oil and a storage system for fuel oil are to be used
in the same premises,  the  terminal  of  the  fuel-oil  pipe  shall  be
provided with a left-handed thread and the fill pipe fitting shall be of
a  different  size  than  that  required for the fill pipes to the tanks
containing the volatile flammable oil.
  1305.6.6 Spill containment. For fill pipes serving tanks greater  than
660  gallons  (2500  L),  an  approved overflow/spill containment device
shall be provided.
  1305.7 Normal vent piping,. Normal vent piping shall comply  with  the
requirements of Section 1305.7.1 through 1305.7.9.

  1305.7.1 Size. Normal vent sizes shall comply with the sizes listed in
Tables  1305.7(1) and 1305.7(2); provided, however, for tanks other than
those  complying  with  the  alternate  tank  design  and   construction
standards  contained  in  Section  1305.14, the normal vent shall not be
smaller in size than the supply pipe.
                            TABLE 1305.71(1)
                    VENT PIPING FOR UNDERGROUND TANKS
------------------------------------------------------------------------

      TANK SIZE                         |   MINIMUM VENT DIAMETER
  660 gallons (2500 L) or less          | 1 1/4 inch (32 mm)
------------------------------------------------------------------------
  661 gallons (2505 L) to 3,000 gallons |
  (11,355 L)                            | 1 1/2 inch (38 mm)
------------------------------------------------------------------------
  3,001 gallons (11,360 L) to 10,000    |
  gallons 37,850 L)                     | 2 inch (51 mm)
------------------------------------------------------------------------
  10,001 gallons 37,855 L) to 20,000    |
  gallons (75,700 L)                    | 2 1/2 inch (64 mm)
------------------------------------------------------------------------
  Larger than 20,000 gallons (75,700 L) | 3 inch (76 mm)
------------------------------------------------------------------------

                             TABLE 1305.7(2)
            VENT PIPING FOR TANKS INSTALLED INSIDE BUILDINGS
------------------------------------------------------------------------
         TANK SIZE                |    MINIMUM VENT DIAMETER
------------------------------------------------------------------------
  660 gallons (2500 L) or less    | 1 1/4 inch-(32 mm){a}
------------------------------------------------------------------------
                                  | Sized to prevent abnormal pressure
  Larger than 660 gallons (2500 L)| in the tank during filling but not
                                  | smaller than the pipe size speci-
                                  | fied in Table 1305.7(1)
------------------------------------------------------------------------
  a.  For  tanks  constructed  to  UL 80 specifications the minimum vent
diameter shall be 2 inch (51 mm) or as required by Section 1305.8,  Item
.3, whichever is greater.
  1305.7.2  Termination  location.  The location of the normal vent pipe
terminations shall comply with the following:
  1. Liquid fuel normal vent pipes shall terminate outside of  buildings
in  a  nonhazardous  location  at  a point not less than 2 feet (610 mm)
measured vertically or horizontally from any building  opening  and  not
less than 2 feet (610 mm) nor more than 12 feet (3658 mm) above the fill
pipe terminal.
  2.  If the normal vent pipe terminal is not visible from the fill pipe
terminal location, a finch (25 mm) tell-tale line shall be connected  to
the tank and shall parallel the fill pipe and terminate at the fill pipe
terminal  with an unthreaded end. Such tell-tale lines shall be provided
with a check valve set to prevent flow of surface water to  the  storage
tank.
  3.  Normal vent pipes shall terminate sufficiently above the ground to
avoid being obstructed with snow or ice.
  4. Normal vent pipes from tanks containing heaters shall  be  extended
to  a location where oil vapors discharging from the normal vent will be
readily diffused.

  1305.7.3 Termination caps. Outer  ends  of  normal  vent  pipes  shall
terminate  in  a  weatherproof vent cap or fitting or be provided with a
weatherproof hood. All normal vent caps shall have a minimum  free  open
area equal to the cross-sectional area of the normal vent pipe and shall
not employ screens finer than No. 4 mesh.
  1305.7.4  Tank  pressure.  The  tank shall be designed for the maximum
static head that will be imposed with the normal vent piping filled with
oil.
  1305.7.5 Multiple Tanks. A normal vent pipe shall be provided for each
storage tank. Normal vent piping from multiple tanks of the  same  grade
oil  with  not  more than 660 gallons (2500 L) aggregate capacity may be
combined. Where a battery of storage tanks complying with the  alternate
tank  design  and  construction  standards  contained in Section 1305.14
designed to hold the same grade of oil with not more  than  660  gallons
(2500  L)  aggregate capacity is installed, normal vent pipes may be run
into a main header.
  1305.7.6 Pitch. Normal vent pipes shall drain  toward  the  tank.  The
normal vent pipes shall have no sags or traps where liquid can collect.
  1305.7.7  Protection.  Normal vent pipes shall be located so that they
are not subjected to physical damage.
  1305.7.8 Cross-connection. Liquid fuel normal vent pipes shall not  be
cross-connected  with  fill  pipes, lines from burners or overflow lines
from auxiliary tanks.
  1305.7.9 Tanks above the lowest floor. For tanks installed  above  the
lowest  floor,  the  normal  vent shall be piped, in an approved manner,
into the vent or too of tank of  the  lowest  floor  storage  tank  that
supplies the fuel to such tank.
  1305.8   Emergency   relief   vent  piping.  Each  primary  tank,  the
interstitial space of a secondary containment tank and each  compartment
of  a  compartment  tank  complying  with  UL 142 shall be provided with
emergency relief venting. A tank's  emergency  relief  vent  piping  and
normal vent piping shall be combined. The design and installation of the
combined  normal  and  emergency relief vent shall be in accordance with
Section 1305.7 and Sections 1305.8.1 through 1305:8.4.
  1305.8.1 Piping. The combination normal and emergency  relief  venting
shall  be  provided  through  an  open  vent pipe connected directly, as
applicable, to the primary tank, interstitial space or compartment.  The
use  of  a  self-closing manway cover, a manway cover provided with long
bolts that permit the cover to lift under internal  pressure,  or  other
type emergency relief vent device, shall be prohibited.
  1305.8.2  Termination.  Combination  normal  and emergency relief vent
piping shall terminate outdoors.
  1305.8.3 Tanks above the lowest floor. For tanks installed  inside  of
buildings  above  the lowest floor, the combination normal and emergency
vent piping shall be piped, in an approved manner, into the vent or  top
of  tank of the lowest floor storage tank that supplies the fuel to such
tank.
  1305.8.4  Capacity.  The  total  relief  venting   capacity   of   the
combination  normal  and emergency relief venting shall be in accordance
with Section 4.2.5.2 of NFPA 30. Construction  documents  shall  include
calculations   demonstrating  that  the  extension  of  the  normal  and
emergency vent piping  is  adequately  sized  to  provide  the  required
emergency  vent  flow  while limiting the back pressure to less than the
maximum pressure permitted by the  design  of  the  tank.  Additionally,
consistent  with Section 4.2.5.2.5 of NFPA 30, where the design provides
for a reduction in the required emergency relief venting capacity  based
upon  the  properties  of  the  fuel  oil  to be stored in the tank, the
construction documents shall include supporting calculations.

  1305.9 Supplemental requirements for piping  from  transfer  pumps  to
equipment  or  storage tanks above lowest floor. Fuel-oil piping systems
utilizing pumps to transfer fuel-oil to equipment at  levels  above  the
lowest  floor  or  storage  tanks  at  levels  above the lowest floor in
buildings shall comely with the requirements of Section 1305.9.1 through
1305.9.12.
  1305.9.1 Shaft enclosure. The piping from a transfer pump to equipment
at  levels  above  the lowest floor or storage tanks at levels above the
lowest floor in buildings, the return piping, and vent piping  shall  be
enclosed  in  a shaft constructed of 4-inch (102 mm) concrete or masonry
having a 4-inch (102 mm) clearance  from  all  pipe  or  pipe  covering,
except  that  no  such  enclosures  shall  be  required  within the room
containing the pump, tank,  or  equipment  where  such  room  is  itself
enclosed  with  construction and materials having at least a 2-hour fire
resistance rating.
  1305.9.2 Ducts or other  piping  in  shafts.  Pipe  shafts  containing
fuel-oil  piping  shall  not be penetrated by or contain other piping or
ducts.
  1305.9.3 Horizontal offsets. Where it is necessary to make  horizontal
offsets  in  the  supply  piping  and  pipe shafts, such piping shall be
enclosed in a sleeve of other piping of at least No.  10  standard  Gage
steel,  two  sizes  larger  than the supply piping and arranged to drain
into the shaft. Horizontal piping offsets shall be further  enclosed  in
construction  having a 2-hour fire-resistance rating except that no such
enclosure or pipe sleeve shall be required within  the  room  containing
the  pump,  tank,  or  equipment where such room is itself enclosed with
construction and materials having  at  least  a  2-hour  fire-resistance
rating.
  1305.9.4  Drain  at base of shafts; leak detection. A drain pipe shall
be installed at the base of shafts enclosing  the  supply  and  overflow
piping.    The  pipe  shall lead to a dedicated sum or minimum 55 gallon
(208 L) container with a leak detection alarm, arranged so as  to  sound
an  alarm  and stop the-transfer pump. The alarm shall be connected to a
local audible alarm and to a  remote  alarm  located  at  a  supervising
station.    The  wiring  shall  comply with the New York City Electrical
Code.
  1305.9.5 Piping materials. Oil lines for equipment or tanks  shall  be
steel  pipe  ASTM  A 53 or ASTM A 106, grade B seamless Schedule 40 with
welded connections up to the oil tank or equipment, except that fittings
at the tank or equipment, shut-off valves and other  fuel-oil  flow  and
control devices may be screwed or flanged.
  1305.9.6  Expansion.  Provision  shall be made for expansion in piping
without the use of expansion joints.
  1305.9.7 Movement and vibration.  The  piping  shall  be  located  and
secured from movement so as to prevent undue stress on the piping and to
isolate the piping from vibrations from any equipment.
  1305.9.8  Connections  to  header. Pipe connections to the main header
(supply or return) shall be made from the top of the header, except  for
systems  with  equipment  above the lowest floor where such equipment is
designed to operate utilizing fuel pumped  as  needed  from  the  lowest
floor and without utilizing fuel oil stored above the lowest floor.
  1305.9.9 Air vent and breakers. Required air vents and vacuum breakers
shall be designed for their required use.
  1305.9.10  Curb  or  pan.  All  air vents and vacuum breakers shall be
hard-piped to a curb or pan.
  1305.9.11 Pipe size; fuel storage above the lowest floor.  In  systems
with  equipment  above the lowest floor where such equipment is designed
to  operate  utilizing  fuel  stored  above  the  lowest  floor.  piping

diameters  shall  not  exceed  4  inches  (102  mm).  However,  where an
applicant  demonstrates  by  the  inclusion  of  calculations   in   the
construction  documents  that  a greater diameter is necessary to ensure
the proper flow for the functioning of the system. such greater diameter
may be permitted. Piping shall not be used for fuel storage purposes.
  1305.9.12  Pipe  size; without fuel storage above the lowest floor. In
systems with equipment above the lowest floor, where such  equipment  is
designed  to  operate  utilizing  fuel  pumped as needed from the lowest
floor and without utilizing fuel oil  stored  above  the  lowest  floor,
piping  diameters  throughout  such  systems shall not exceed the design
flow (three times the maximum firing rate as calculated by the  engineer
or  architect).  However,  piping diameters within rooms containing such
equipment may exceed the calculated design flow  pipe  size  to  provide
limited  reservoir  storage  to prime equipment, provided such reservoir
storage is counted toward the maximum permitted oil storage  per  story.
as provided for in Section 1305.11.1.3.
  1305.10   Devices  to  control  flow  to  oil-burning  equipment.  The
following requirements shall apply:
  1. The pressure in oil lines to oil-burning  equipment  located  above
the  lowest  floor  of  a building shall not be more than is required to
circulate oil to and from the burners, and all parts of the  oil  system
shall  be  capable  of withstanding the maximum working pressure in that
part of the system.
  2. A remote control shall be provided to stop the flow of oil  to  any
burner  wherever  located.  and  to any oil-burning equipment located on
levels above the lowest  floor  in  buildings.  Such  control  shall  be
located  outside the entrance to the room in which the burner is located
and as close to such  entrance  as  practicable,  except  that  when  an
outside   location   is  impracticable,  such  control  may  be  located
immediately inside the room in which the  burner  is  located,  provided
such  location  is  accessible  at all times. All such controls shall be
permanently labeled:  "REMOTE CONTROL FOR OIL BURNER",  "REMOTE  CONTROL
FOR  GENERATOR",  or  as  appropriate  to  the oil-burning equipment. On
storage tanks of 60 gallons (227 L) or less capacity used with  manually
operated  equipment,  such remote control may be installed in the supply
lines between tank and burner.
  3. In systems where either steam or air is used for atomizing the oil,
the oil and the atomizing supply shall be interlocked so that where  the
supply  of  either  is  interrupted.  the  supply  of  the other will be
immediately cut off.
  1305.11 Limitations on quantities of fuel-oil storage.  Quantities  of
fuel-oil  storage  shall be limited in accordance with the provisions of
this section. For the purposes of this section, fuel oil stored on roofs
shall be deemed inside of buildings and located on the  floor  to  which
they are adjacent.
  1305.11.1  Inside  of  buildings.  A  total  of  not more than 100.000
gallons (378 000 L) shall be stored inside of any building.  Oil-storage
inside  of  buildings  shall also comply with applicable requirements of
Sections 1305.11.1.1 through 1305.11.1.3.
  1305.11.1.1 Inside of buildings: below ground.  The  maximum  size  of
each  below-ground oil-storage tank inside of a building shall be 35.000
gallons (132 475 L).
  1305.11.1.2 Inside of buildings: above ground  on  the  lowest  floor.
Fuel-oil  storage  tanks installed above around on the lowest floor of a
building shall be mounted on and  anchored  by  adequate  noncombustible
supports.  The maximum size of each individual tank shall be 660 gallons
(2500 L). and a total of not more than 1375 gallons (5200  L)  shall  be
stored within the same 2-hour fire area.

  Exceptions,  Fuel-oil  storage  tanks  shall  be to exceed 660 gallons
(2500 L), and the total quantity within a fire area shall  be  permitted
to  exceed  1375  gallons  (5200  L)  in  accordance with any one of the
following options:   1.  Buildings  of  Type  I,  II,  IIIA,  IV  or  VA
construction  with  a total limit of 15,000 gallons. The maximum size of
each individual tank shall be 15,000 gallons (56 775  L)  provided  that
all  such  tanks  are  located  in  a room or enclosure dedicated to oil
storage  that  is  separated  from  the  rest   of   the   building   by
fire-resistance-rated  construction of at least 3 hours. Notwithstanding
Section 1305.11.1, in such cases, the  maximum  total  quantity  in  the
building shall be limited to 15.000 gallons (56 775 L).
  2.  Buildings  of  Type  IIIB or VB construction with a total limit of
10,000 gallons. The maximum size of each individual tank shall be 10,000
gallons (37 850 L) provided that all such tanks are located in a room or
enclosure dedicated to oil storage that is separated from  the  rest  of
the  building by fire-resistance-rated construction of at least 3 hours.
Notwithstanding Section 1305.11.1  in  such  cases,  the  maximum  total
quantity in the building shall be limited to 10.000 gallons (56 775 U.
  3.  Buildings  of  any type construction with a total limit of 100,000
gallons. The maximum size  of  each  individual  tank  shall  be  25,000
gallons  (94 625 L) provided that all such tanks are enclosed in a vault
(i) with walls, floor, and top having a fire resistance  rating  of  not
less  than  3 hours, (ii) with such walls bonded to the floor, and (iii)
with such top and  walls  of  the  vault  independent  of  the  building
structure.  An exterior building wall having a fire resistance rating of
not less than 3 hours shall be permitted to  serve  as  a  wall  of  the
vault.  The  vault  shall  be located in a dedicated room or area of the
building that is cut off vertically and horizontally  from  other  areas
and floors of the building by assemblies having a fire resistance rating
of  not  less  than 2 hours. Where the aggregate fuel-oil storage on the
lowest level of the building exceeds 50.000 gallons (189  250  L),  such
storage shall be protected with an alternate extinguishing system comply
with Section 904 of the New York City Building Code.
  1305.11.1.3  Inside  of  buildings:  above  the lowest floor. Fuel-oil
above the lowest floor inside of a building; shall  be  limited  to  330
gallons (1249 L) per story. The maximum quantity shall include oversized
piping as described in 1305.9.12. Piping installations shall comply with
the requirements of Section 1305.9.
  1305.11.2 Outside of buildings. Oil-storage outside of buildings shall
comply   with   applicable  requirements  of  Sections  1305.11.2.1  and
1305.11.2.2.
  1305.11.2.1 Outside of buildings: below ground. The  maximum  size  of
each below-ground oil-storage tank outside of a building shall be 35.000
gallons (132 475 L).
  1305.11.2.2  Outside  of  buildings: above ground. The maximum size of
each aboveground oil-storage tank outside of a building shall be 100,000
gallons (37 800 L).
  1305.12 Standards  for  Tank  Design.  Tanks  shall  be  designed  and
constructed in compliance with Sections 1305.12.1 and 1305.12.2.
  1305.12.1  Below ground. Tanks located below around, inside or outside
of buildings,  shall  comply  with  any  one  of  the  following  design
standards, as appropriate for the specific installation as determined by
the engineer:
  1. UL 58; such tanks shall be listed and labeled;
  2. UL 1316; such tanks shall be listed and labeled; or
  3.  Alternate  tank  design  and  construction  standards contained in
Section 1305.14

  1305.12.2 Above ground. Tanks located above ground. inside or  outside
of  buildings,  shall  comply  with  any  one  of  the  following design
standards, as appropriate for the specific installation as determined by
the engineer:
  1. UL 80; such tanks shall be listed and labeled;
  2. UL 142; such tanks shall be listed and labeled;
  3.  ASME  Boiler and Pressure Vessel Code, Section VIII. Division 1 or
2:  such tanks shall be listed and labeled; or
  4. Alternate tank  design  and  construction  standards  contained  in
Section 1305.14
  1305.13  Installation of tanks. Tanks shall be installed in accordance
with the provisions of section  1305.13.1  through  1305.13.4.  For  the
purposes  of  this  section,  fuel  oil  stored on roofs shall be deemed
inside of buildings.
  1305.13.1 Below ground. Tanks located below around, inside or  outside
of buildings, shall comply with the following requirements:
  1.  Containment.  Fuel-oil  tanks  having  a capacity of more than 660
gallons (2500 L) shall be provided with secondary  containment  intended
to  prevent  any  leakage  of  fuel  oil from the tank from entering the
environment. The capacity of the containment shall equal or  exceed  the
capacity of the tank served.
  2. Burial. Regardless of capacity. fuel-oil tanks shall be buried with
the  top  of the tank at least 2 feet (610 mm) below ground. Tanks shall
be placed in firm  soil  and  shall  be  surrounded  by  clean  sand  or
well-tamped  earth,  free  from  ashes or other corrosive substance, and
free from stones that will not pass a 1-inch (25 mm) mesh.
  3. Anchorage. When necessary  to  prevent  floating,  fuel-oil  tanks,
regardless of capacity, shall be securely anchored.
  4.  Distance  to foundations. Regardless of capacity, no fuel-oil tank
shall be buried within 3  feet  (914  mm)  of  any  foundation  wall  or
footing.
  5.  Special  limitations  near  subways.  Regardless  of  capacity, no
fuel-oil tank shall be placed within 20 feet (6096 mm)  of  the  outside
line  of  a subway wall. For the purpose of the foregoing requirement, a
subway shall be deemed to  include  any  subsurface  railroad  or  rapid
transit roadbed.
  1305.13.2  Above  ground; on the lowest floor inside a building. Tanks
located above ground, on the lowest floor  inside  of  buildings,  shall
comply with the following requirements:
  1.  Containment.  Fuel-oil  tanks  having  a capacity of more than 660
gallons (2500 1) storage shall be provided  with  secondary  containment
intended  to capture any leakage of fuel oil from the tank. The capacity
of the containment shall equal  or  exceed  the  capacity  of  the  tank
served.    Special  limitations  near  subways.  Regardless of capacity,
fuel-oil tanks located within the outer lines of the subway,  or  within
20  feet  (6096 mm) of the outside line of a subway wall shall be placed
within a welded steel oil tight pan of not less than No. 18  Gage  metal
suitably reinforced and of capacity to contain the contents of the tank.
For  the  purpose of the foregoing requirement, a subway shall be deemed
to include any subsurface railroad or rapid transit roadbed.
  1305.13.3 Above ground: above the  lowest  floor  inside  a  building.
Regardless  of  capacity,  fuel-oil tanks and fuel-oil-burning equipment
located above around, above the lowest floor inside of buildings,  shall
comply with the following requirements:
  1.  Enclosure  of  room. Fuel-oil tanks and fuel-oil-burning equipment
shall be located in  a  dedicated  room  or  enclosure,  having  a  fire
resistance  rating  of  at  least  2  hours.  Rooftop  tanks need not be
enclosed provided that all exterior walls and roof  surfaces  within  10

feet (3048 mm) horizontally and 20 feet (6096 mm) vertically have a fire
resistance rating of at least 2 hours.
  2.  Fire  extinguishing  system.  Rooms  containing fuel-oil tanks and
fuel-oil-burning equipment shall be equipped with an automatic sprinkler
system in accordance with section 903.3.1 of the New York City  Building
Code.  To  prevent  overfilling  of  the containment barriers, sprinkler
shut-offs shall be located on the outside of tank  and  generator  rooms
and prominently placarded for immediate control by the Fire Department.
  3.    Smoke   detection.   Rooms   containing   fuel-oil   tanks   and
fuel-oil-burning  equipment  shall  be  equipped  with  automatic  smoke
detection  in  accordance with Section 907 of the New York City Building
Code, except that heat detectors may be utilized  where,  during  normal
operation,  products of combustion are present in sufficient quantity to
actuate a smoke detector.
  4. Ventilation. Rooms containing fuel-oil tanks shall be ventilated to
limit the concentration of vapors within the room at or below 25% of the
Lower Flammable Limit (LFL) of the fuel oil being used.
  5.  Containment.  Fuel-oil  tanks,  fuel-oil-burning  equipment,   and
related  equipment  shall  be  provided  with secondary containment area
intended to capture any leakage of  fuel  oil.  Floor  drains  shall  be
prohibited  in  containment  areas.  For  tanks,  the  capacity  of  the
containment area shall equal or exceed 2 times the capacity of the  tank
served.  For  fuel-oil-burning equipment the capacity of the containment
area shall equal or  exceed  1.5  times  the  storage  capacity  of  the
equipment.
  6.  Transfer  pumps.  Fuel-oil  tanks  shall  be  filled by means of a
transfer pump supplied from a primary storage tank located on the lowest
floor. A separate transfer pump and piping circuit shall be provided for
each storage tank installed above  the  lowest  floor.  No  intermediate
pumping  stations  shall  be  provided  between the storage tank and the
transfer pump. Appropriate devices shall be provided for  the  automatic
and  manual starting and stopping of the transfer pumps so as to prevent
the overflow of oil from these storage tanks.
  7. Indicators and alarms. Indicators and alarms shall be provided  for
fuel   oil   tanks  and  rooms  containing  fuel-oil-burning  equipment,
including a level sensor for height and capacity of fuel oil,  high  and
low  levels,  and  leak  detection.  The  float switch shall be provided
within the containment areas and shall be arranged so  as  to  sound  an
alarm  and  stop the transfer pump in case of failure of the tank or the
control in the tank. These indicators shall  be  connected  to  a  local
audible  alarm  in  the  tank  room  and  to a remote alarm located at a
supervising station.  The wiring shall comply with  the  New  York  City
Electrical Code.
  8.  Weekly  testing. The operation of the float switch shall be tested
at least once each week by the holder of the certificate of  fitness  as
provided for in Sections 1301.9 and .1308.3.
  1305.13.4  Above  ground;  outside  a  building.  Tanks  located above
ground,  outside  of  buildings,  shall  comply   with   the   following
requirements:
  1.  Containment.  Regardless  of  capacity, each fuel-oil storage tank
shall be protected by an embankment or dike. Such protection shall  have
a  capacity  at least 1 1/2 times the capacity of the tank so surrounded
and shall be at least 4 feet (1219 mm) high, but in no  case  shall  the
protection  be higher than 1/4 the height of the tank when the height of
the tank exceeds 16 feet (4877 mm). Embankments or dikes shall  be  made
of earthwork with clay core, of masonry, of of reinforced concrete or of
steel.  Earth  work  embankments  shall be firmly and compactly built of
good  earth  free  from  stones,  vegetable  matter,  or  other  similar

material,  and  shall have a flat section of at least 3 feet (914 mm) at
the top and a slope of at least 1 1/2 (457 mm) rise to 2 feet  (610  mm)
of  run on all sides. Concrete, masonry or steel dikes shall be designed
so  as  to  contain  safely  all  of  the oil in the tank so surrounded.
Embankments or dikes shall be continuous and unpierced, and the  outside
toe  shall  be  located at least 5 feet (1524 mm) inside of the property
line, and no less than 5 feet (1524 mm) from a driveway or parking area.
  2. Distances to buildings, lot lines, and other tanks.  Storage  tanks
of a capacity greater than 330 gallons (1250 L) shall be not less than 1
1/4  tank  diameters and in no case less than 10 feet (3048 mm) from the
tax lot line, the nearest building or adjacent tank. However, in no case
shall the clearance between individual tanks and the  tax  lot  line  be
less than the distance fixed by the following formula:
  M.C. = 10 + 4 [(G-275)/5000]
  Where:
  M.C. = minimum clearance from nearest surface of tank to tax lot line,
in feet.
  G = capacity of tank, in gallons.
  3.  Means  of  egress. Tanks shall be located so as not to obstruct or
interfere with any means of egress.
  1305.14 Alternate tank design and construction standards.  Oil-storage
tanks,  other  than  those conforming to ASME Boiler and Pressure Vessel
Code, Section VIII, Division 1 or 2, UL 58, UL 80, UL 142,  or  UL  1316
shall  be  designed,  constructed  and  installed in accordance with the
requirements of Section 1305.14.1.1 through 1305.14.9.
  1305.14.1 General construction standards. All tanks shall comply  with
the requirements of Section 1305.14.1.1 through 1305.14.1.9.
  1305.14.1.1  Materials  and  workmanship.  All  fuel-oil storage tanks
shall be built of steel plates or sheets, made by  the  open  hearth  or
basic   oxygen   process.   Such  steel  shall  be  free  from  physical
imperfections, and shall be new, in good condition, and free from rust.
  1305.14.1.2 Assembly. Tanks, flanges or other pipe  connections  shall
be welded. Filler of any kind between plates shall be prohibited.
  1305.14.1.3  Corrosion resistance. Tanks to be buried shall be cleaned
and then coated on the outside with two coast  of  corrosion  protective
material.  They  shall  be  further  protected  by a coating of hot tar,
asphalt, or equivalent rust resistive  material,  applied  at  the  work
site. Tanks installed inside buildings above ground shall be coated with
one coat of corrosion protective material.
  1305.14.1.4  External  loads  on underground tanks. All buried storage
tanks shall be constructed of at least 1/4-inch (6.4 mm) thick metal and
shall be designed to withstand any external loads to which the tank  may
be subjected.
  1305.14.1.5  Identification.  At  the time of installation all storage
tanks shall bear a permanently-fixed plate, spot welded  or  equivalent,
bearing the name of the tank manufacturer, the gage of the material, and
capacity  of  the tank. Shop-fabricated storage tanks shall be installed
without structural alteration.
  1305.14.1.6 Openings. All openings shall be through  the  top  of  the
storage  tank, except that storage tanks of 275 gallon (1041 L) capacity
or less, located above  ground  but  below  the  lowest  story,  may  be
provided  with  a 3/4-inch (19.1 mm) opening for gravity discharge and a
1-inch (25 mm) opening in the bottom for cleaning and protection against
corrosion.
  1305.14.1.7 Manholes.  Tanks  for  No.  1,  No.  2,  No.  3  and  No.4
commercial  grade  oils need not have manholes. However, if manholes are
used for tanks containing such oils, the manhole covers shall be  bolted
and  made  gas  tight.  Tanks  for No. 5 and No. 6 commercial grade oils

shall have manhole covers bolted or otherwise secured to the  tanks  and
kept  hydostatically  tight  at  all  times.  Tanks  275  gallon (104 L)
capacity or less,  and  all  other  tanks  without  manholes,  shall  be
provided  with  a  2 screwed connection on the top of the tank to permit
measuring the level of the oil within.
  1305.14.1.8 Electrical grounding. Tanks outside of buildings shall  be
electrically  grounded in accordance with the requirements for equipment
grounding of the New York City Electrical Code.
  1305.14.1.9 Protection from heat and flame. Tanks shall be located  at
least  7  feet  (2134  mm), measured in the most direct manner, from any
source  of  exposed  flame  unless  protected  as  provided  in  Section
1305.11.1.2,  exception 3, and at least 2 feet (610 mm) from any surface
where the temperature exceeds 165°F (74°C).
  1305.14.2 Additional  construction  standards  for  cylindrical  tanks
exceeding  275  gallons  (1041  L).  Cylindrical  tanks, including oval,
elongated oval, or round tanks, exceeding 275  gallons  (1041  L)  shall
comply with the requirements of Section 1305.14.2.1 through 1305.14.2.3.
  Exception:  Such  above-ground  vertical  tanks  that  are  outside of
buildings shall comply with Section 1305.14.1 and 1305.14.5.
  1. Tanks 36 inches (914 mm) in diameter or less shall have at least  a
1/4-inch (6.4 mm) shell and 1/4-inch (6.4 mm) heads.
  2.  Tanks  37 inches (940 mm) to 72 inches (1829 mm) in diameter shall
have at least a 1/4-inch (6.4 mm) shell and 5/16-inch (7.9 mm) heads.
  3. Tanks 73 (1854 mm) to 120 (3048 mm) in diameter shall have at least
5/16-inch (7.9 mm) shell and 3/8-inch (9.5 mm) heads.
  4. Tanks over 120 inches (3948 mm) in diameter shall be  of  at  least
3/9-inch  (9.5  mm)  steel  and  shall  be  stiffened  by angle rings or
equivalent members so as to retain their cylindrical form.
  1305.14.2.2 Dished heads. Dished heads for such  tanks  shall  have  a
curvature  the  radius  of which is not greater than the diameter of the
tank.  Dished  heads  shall  be  formed  with  an  adequate  cylindrical
extension rim to provide a welding surface.
  1305.14.2.3  Flat  heads. If flat heads are used, they shall be braced
in the same manner as  described  for  the  bracing  of  flat  sides  of
rectangular tanks as provided for in Section 1304.14.3.
  1305.14.3  Additional  construction  standards  for  rectangular tanks
exceeding 275 gallons (1041 L). Rectangular tanks exceeding 275  gallons
(1241  L)  capacity  shall  comply  with  the  requirements  of  Section
1305.14.3.1 through 1305.14.3.7.
  1305.14.3.1 Thickness. Plates for rectangular tanks of more  than  275
gallon (1040 L0 capacity shall be at least 5/16 inches (7.9 mm) thick.
  1305.14.3.2  Corners.  Corners may be made up by bending the plates or
by using angles.
  1305.14.3.3 Seams. All tanks shall have full penetration 5/16 welds at
all seams.
  1305.14.3.4 Bracing. All flat surfaces of rectangular tanks  shall  be
braced by structural members or rods.
  1305.14.3.5  Structural work. All structural members shall be designed
in accordance with the requirements of the New York City Building Code.
  1305.14.3.6 Connections. Connections between bracing members  and  the
sides of the tank shall be designed so that the connection will not fail
before the member will fail.
  1305.14.4 Additional construction standards for tanks 275 gallon (1041
L)  or  less. Storage tanks with a capacity of less than or equal to 275
gallons (1041 L) shall have a minimum thickness of shell and head plates
of No. 10 manufacturer's standard Gage steel plate. Storage tanks of  60
gallon  (227 L) capacity or less shall be similarly constructed but need
not be thicker than No. 14 manufacturer's standard Gage.

  Exception:
  1.  Such  vertical above-ground cylindrical tanks outside of buildings
shall comply with Sections 1305.14.1 and 1305.14.5.
  2. Such underground tanks need comply only with Sections 1304.14.1.
  3. Storage containers of 6 gallons (23 L) or less used with burners or
oil burning  heaters  need  only  be  designed  so  as  to  withstand  a
hydrostatic  pressure  test of at least 5 psi (34 kPa) without permanent
deformation, rupture, or leakage, and shall be approved. Such containers
shall be installed with  rigid  metal  fasteners  for  wall,  floor,  or
stand-type  installations,  and  shall  be  protected against mechanical
damage. Portable storage containers of 6 gallons (23 L) or less  may  be
filled  by  a  pump mounted on a storage tank, provided that the pump is
approved.
  1305.14.5 Additional construction standards for vertical  above-ground
cylindrical  tanks  outside  of  buildings  exceeding  6  gallon (23 L).
Vertical above-ground cylindrical storage tanks exceeding 6 gallons  (23
L)  that  are  located  outside  of  buildings  shall  comply  with  the
requirements of Section 1305.14.5.1 through 1305.14.5.3.
  1305.14.5.1 Plates. Such tanks shall be built of steel plates  of  the
quality  required  for  cylindrical  tanks  in  accordance  with Section
1305.14.2.
  1305.14.5.2 Thickness. The minimum thickness of shell or bottom plates
shall be 1/4 inches (6.4 mm), and the minimum thickness of  roof  plates
1/8  inch (3.2 mm). The thickness of shell plates shall be determined in
accordance with the following formula:
     P x R x F
  t = ----------
     T x E
  where:
  t = thickness of shell plate in inches.
  P = head pressure at bottom of ring under consideration in psi.
  R = radius of shell, in inches.
  F = factor of safety (taken as 5).
  T = tensile strength of  plate,  in  psi  as  verified  by  mill  test
certificate.
  E  = efficiency of vertical joint in ring under consideration. E shall
in no case be taken greater than 1.00.
  1305.14.5.3 Seams. Roof plates shall have  welded  water-tight  seams,
and  the  roof  shall  be  built to shed water. Bottom plates shall have
welded seams. Shell plate seams shall be designed to  develop  the  full
strength of the plate.
                             SECTION MC 1306
                               OIL GAUGING
  1306.1  Level  indication. All tanks located inside buildings shall be
equipped with a method of determining the oil level.
  1306.2 Test wells. Test wells shall not be installed inside buildings.
Unused tank openings shall be permanently sealed. For  outside  service,
test  wells  shall  be  equipped  with  a  tight metal cover designed to
discourage tampering.
  1306.3 Inside tanks. The gauging of inside tanks by means of measuring
sticks shall not be permitted. An inside tank  provided  with  fill  and
vent  pipes  shall be provided with a device to indicate either visually
or audibly at the fill point when the oil in  the  tank  has  reached  a
predetermined safe level.
  1306.4   Gauging   devices.  Gauging  devices  such  as  liquid  level
indicators or signals shall be designed and installed so that oil  vapor
will  not  be  discharged  into  a  building from the liquid fuel supply
system.

  1306.5 Gauge glass. A tank used in  connection  with  any  oil  burner
shall  not  be  equipped  with  a  glass  gauge or any gauge which, when
broken, will permit the escape of oil from the tank.
  1306.6  Storage  above lowest floors. Fuel-oil stored above the lowest
floor shall also comply  with  the  indicator  requirements  of  Section
1305.13.3, Item 7.
                              SECTION MC 1307
                             FUEL-OIL VALVES
  1307.1  Building  shutoff.  A  shutoff valve shall be installed on the
fuel-oil supply  line  at  the  entrance  to  the  building.  Inside  or
above-ground  tanks  are permitted to have valves installed at the tank.
The valve shall be capable of stopping the  flow  of  fuel  oil  to  the
building  or  tot  he appliance served where the valve is installed at a
tank inside the building.
  1307.2 Appliance shutoff. A shutoff valve shall be  installed  at  the
connection  to  each  appliance  where  more  than  one fuel-oil-burning
appliance is installed.
  1307.3 Pump relied valve. A relief valve shall  be  installed  on  the
pump discharge line where a valve is located downstream of the pump.
  1307.4 Fuel-oil heater relief valve. A relief valve shall be installed
on the discharge line of fuel-oil-heating appliances.
  1307.5 Relief valve operation. Relief valves shall be set to discharge
at not more than 1 1/2 times the maximum working pressure of the system.
The  discharge  from relief valves shall be returned to the storage tank
or to the supply line. Shut-off valves are not permitted in the line  of
relief.
                              SECTION MC 1308
                                 TESTING
  1308.1  Testing  required.  Fuel-oil  storage  tanks, other than tanks
complying with the alternate  tank  design  and  construction  standards
contained  in  Section  1305.14, shall be tested in accordance with NFPA
31.
  1308.2  Hydrostatic  test.  All  liquid-fuel  piping,  and  all  tanks
complying  with  the  alternate  tank  design and construction standards
contained in  Section  1305.14,  shall  be  hydrostatically  tested  for
tightness by the contractor who made the installation before the work is
closed  in and before the system is operated. The piping shall be tested
at 1 1/2 times the maximum working pressure applicable to that  part  of
the piping system but at a pressure less than the test pressure required
for  the storage tank. The minimum pressure for testing tanks shall be 1
1/2 times the maximum working pressure applicable to the tank but in  no
case  less  than 25 psig (172 kPag), except as provided for containers 6
gallons (23 L) or less in capacity as provided for in Section  1305.14.4
Exception  3.    The  hydrostatic pressure shall be maintained until all
joints and connections have been visually inspected for leaks, but in no
case for less than 1/2 hour. the  tank  shall  not  show  any  permanent
deformation  as  a  result  of  the  test. A record shall be kept of the
pressure tests showing the name of the contractor and the  pressures  at
which the piping and the tank were tested.
  1308.3.  Weekly  testing.  For  fuel-oil  tanks  and  fuel-oil-burning
equipment located  above  around,  above  the  lowest  floor  inside  of
buildings,  the  operation  of the float switch shall be tested at least
once each week by the holder of the certificate of fitness  as  provided
for in Section 1301.9 and Section 1305.13.3, item 8.
                                CHAPTER 14
                              SOLAR SYSTEMS
                             SECTION MC 1401
                                 GENERAL

  1401.1  Scope.  This  chapter  shall  govern the design, construction,
installation, alteration and repair of systems, equipment and appliances
intended to utilize solar energy for space heating or cooling,  domestic
hot water heating, swimming pool heating, or process heating.
  1401.2  Potable  water supply. Potable water supplies to solar systems
shall be protected against contamination in accordance with the New York
City Plumbing Code.
  Exception: Where all solar system piping is  a  part  of  the  potable
water  distribution  system,  in accordance with the requirements of the
New York City Plumbing Code, and all components of the piping system are
listed for potable water use, cross connection protection measures shall
not be required.
  1401.3 Heat exchangers. Heat exchangers used in domestic water-heating
systems shall be approved for the intended use. The  system  shall  have
adequate  protection  to  ensure that the potability of the water supply
and distribution system is properly safeguarded.
  1401.4 Solar energy equipment and appliances. Solar  energy  equipment
and  appliances  shall  conform  to the requirements of this chapter and
shall be installed in accordance with  the  manufacturer's  installation
instructions.
  1401.5  Ducts.  Ducts  utilized  in  solar heating and cooling systems
shall be constructed and installed in accordance with Chapter 6 of  this
code.
                              SECTION MC 1402
                              INSTALLATION
  1402.1  Access. Access shall be provided to solar energy equipment and
appliances for maintenance. Solar systems and  appurtenances  shall  not
obstruct  or  interfere with firefighting operations or the operation of
any doors, windows, fire escapes, or other  means  of  egress  or  other
building components requiring operation or access.
  1402.2  Protection  of equipment. Solar equipment exposed to vehicular
traffic shall be installed not less than 6  feet  (1829  mm)  above  the
finished floor.
  Exception:  This  section  shall  not  apply  where  the  equipment is
protected from motor vehicle impact.
  1402.3 Controlling condensation. Where attics or structural spaces are
part of a passive solar system, ventilation of such spaces, as  required
by   Section  406,  is  not  required  where  other  approved  means  of
controlling condensation are provided.
  1402.4 Roof-mounted collectors.  Roof-mounted  solar  collectors  that
also serve as a roof covering shall conform to the requirements for roof
coverings in accordance with the New York City Building Code.
  Exception:  The use of plastic solar collector covers shall be limited
to those approved plastics meeting the  requirements  for  plastic  roof
panels in the New York City Building Code.
  1402.4.1  Collectors  mounted above the roof. When mounted on or above
the roof covering, the collector array and supporting construction shall
be constructed of  noncombustible  materials  or  fire-retardant-treated
wood  conforming  to  the  New  York  City  Building  Code to the extent
required for the type of roof construction of the building to which  the
collectors are accessory.
  Exception:  The use of plastic solar collector covers shall be limited
to those approved plastics meeting the  requirements  for  plastic  roof
panels in the New York City Building Code.
  1402.5  Equipment.  The  solar  energy  system  shall  be  equipped in
accordance with the requirements of Sections 1402.5.1 through 1402.5.4.
  1402.5.1 Pressure and  temperature.  Solar  energy  system  components
containing  pressurized  fluids shall be protected against pressures and

temperatures  exceeding  design  limitations  with     a  pressure   and
temperature  relief valve. Each section of the system in which excessive
pressures are capable of developing shall have a relief  device  located
so  that  a  section  cannot  be valved off or otherwise isolated from a
relief device. Relief valves  shall  comply  with  the  requirements  of
Section 1006.4 and discharge in accordance with Section 1006.6.
  1402.5.2 Vacuum. The solar energy system components that are subjected
to  a  vacuum while in operation or during shutdown shall be designed to
withstand such vacuum or shall be protected with vacuum relief valves.
  1402.5.3  Protection  from  freezing.  System  components   shall   be
protected from damage by freezing of heat transfer liquids at the lowest
ambient  temperatures  that  will be encountered during the operation of
the system.
  1402.5.4 Expansion tanks. Liquid  single-phase  solar  energy  systems
shall  be equipped with expansion tanks sized in accordance with Section
1009.
  1402.6 Penetrations. Roof and wall penetrations shall be  flashed  and
sealed to prevent entry of water, rodents and insects.
  1402.7  Filtering.  Air transported to occupied spaces through rock or
dust-producing materials by means other than natural convection shall be
filtered at the outlet from the heat storage system.
                              SECTION MC 1403
                          HEAT TRANSFER FLUIDS
  1403.1 Flash point. The flash point of the actual heat transfer  fluid
utilized  in a solar system shall be not less than 50°F (28°C) above the
design maximum nonoperating (no-flow) temperature of the fluid  attained
in the collector.
  1403.2  Flammable  gases  and liquids. A flammable liquid or gas shall
not be utilized as a heat transfer fluid.
                              SECTION MC 1404
                                MATERIALS
  1404.1  Collectors.  Factory-built  collectors  shall  be  listed  and
labeled,  and  bear a label showing the manufacturer's name and address,
model  number,  collector  dry  weight,  collector   maximum   allowable
operating and nonoperating temperatures and pressures, minimum allowable
temperatures  and  the types of heat transfer fluids-that are compatible
with the collector. The label shall clarify  that  these  specifications
apply only to the collector.
  1404.2  Thermal storage units. Pressurized thermal storage units shall
be listed and labeled, and bear a label showing the manufacturer's  name
and  address,  model  number,  serial  number,  storage unit maximum and
minimum allowable  operating  temperatures,  storage  unit  maximum  and
minimum  allowable  operating  pressures  and the types of heat transfer
fluids compatible with the storage unit. The label  shall  clarify  that
these specifications apply only to the thermal storage unit.
                                CHAPTER 15
                          REFERENCED STANDARDS
                             SECTION MC 1501
                                 GENERAL
  1501.1  General.  This chapter lists the standards that are referenced
in various sections of this document. The standards are listed herein by
the promulgating agency of the standard,  the  standard  identification,
the  effective  date  and  title  and  the  section  or sections of this
document that reference the standard.
  1501.2 Subsequent additions, modifications, or deletions. Refer to the
rules of the department for any subsequent additions,  modifications  or
deletions  that may have been made to these standards in accordance with
Section 28-103.19 of the Administrative Code.

  1501.3 Applicability. The  application  of  the  referenced  standards
shall be as specified in Section 102.8.
                             SECTION MC 1502
                                STANDARDS
ACCA         Air Conditioning Contractors of America
             1712 New Hampshire Ave, NW
             Washington, DC 20009
Standard                                             Referenced
Reference                                            in code
Number       Title                                   section number
Manual D-95  Residential Duct Systems                603.2
ANSI         American National Standards Institute
             25 West 43rd Street, Fourth Floor
             New York, NY 10036
Standard                                             Referenced
Reference                                            in code
Number       Title                                   section number
Z21.8-1994   Installation of Domestic Gas Conversion 919.1
             Burners
Z21.50-2003  Vented Gas Fire-places                  901.6, 901.6.3
Z21.60-2003  Decorative Gas Appliances for           901.6.2
             Installation in Solid-Fuel Burning
             Fireplaces
Z21.83-1998  Fuel Cell Power Plants                  924.1
ARI          Air-Conditioning & Refrigeration
             Institute
             4100 North Fairfax Drive, Suite 200
             Arlington, VA 22203
Standard                                             Referenced
Reference                                            in code
Number       Title                                   section number
700-95       Specifications for Fluorocarbon and     1102.2.2.3
             Other Refrigerants
ASHRAE       American Society of Heating,
             Refrigerating and Air-Conditioning
             Engineers, Inc.
             1791 Tullie Circle, NE
             Atlanta, GA 30329-2305
Standard     Referenced
Reference    in code
Number       Title                                   section number
ASHRAE-2001  ASHRAE Fundamentals Handbook-2001       312.1, 603.2
15-2001      Safety Standard for Refrigeration       1101.6, 1101.11,
             Systems                                 1104.2, 1105.3,
             1105.7, 1105.8,
             1105.10, 1108.1
34-2001      Designation and Safety Classification   202, 1102.2.1,
             of Refrigerants                         1103.1
ASHRAE-2000  HVAC Systems and Equipment              312.1
             Handbook-2000
ASME         American Society of Mechanical
             Engineers
             Three Park Avenue
             New York, NY 10016-5990
Standard                                             Referenced
Reference                                            in code
Number       Title                                   section number
B1.20.1-1983 Pipe Threads, General Purpose (Inch)    1203.3.5, 1303.3.3

(R1999)
B16.3-l999   Malleable Iron Threaded Fittings,       Table 1202.5
             Classes 150 & 300
B16.5-1996   Pipe Flanges and Flanged Fittings NPS   Table 1202.5
             1/2 through NPS 24-With B16.5a-1998
             Addenda
B16.9-1993   Factory-Made Wrought Steel Buttwelding  Table 1202.5
             Fittings
B16.11-1996  Forged Fittings, Socket-Welding and     Table 1202.5
             Threaded
B16.15-1985  Cast Bronze Threaded Fittings           Table 1202.5
(R1994)
B16.18-1984  Cast Copper Alloy Solder Joint          513.13.1, Table
(R1994)      Pressure Fittings                       1202.5
B16.22-1995  Wrought Copper and Copper Alloy Solder  513.31.1, Table
             Joint Pressure Fittings-with B16.221-   1202.5
             1998 Addenda
B16.23-1992  Cast Copper Alloy Solder Joint          Table 1202.5
             Drainage Fittings DWV
B16.24-1991  Cast Copper Alloy Pipe Flanges and      Table 1202.5
(R1998)      Flanged Fittings: Class 150, 300,
             400, 600, 900, 1500 and 2500
B16.26-1988  Cast Copper Alloy Fittings for Flared   Table 1202.5
             Copper Tubes
B16.28-1994  Wrought Steel Buttwelding Short Radius  Table 1202.5
             Elbows and Returns
B16.29-1994  Wrought Copper and Wrought Copper       Table 1202.5
             Solder Joint Drainage Fittings-DWV
B31.1-2004   Power Piping Code                       12102.2, 1210.2.3
BPVC-2004    Boiler & Pressure Vessel Code           1003.3, 1004.1,
             (Sections I, II, IV, V, VI, VIII & IX)  1011.1, 1210.2.2,
                                                     1305.12.1
CSD-1-1998   Controls and Safety Devices for         1004.1, 1007.2
             Automatically Fired Boilers
ASNT         American Society for Nondestructive
             Testing
             3200 Riverside Drive
             Columbus, OH 43221
Standard                                             Referenced
Reference                                            in code
Number       Title                                   section number
SNT-TC-1A-   Recommended Practice                    1210.2.2
ASTM         ASTM International
             100 Barr Harbor Drive
             West Conshohocken, PA 19428-2959
Standard                                             Referenced
Reference                                            in code
Number       Title                                   section number
A 53/A       Specification for Pipe, Steel, Black    Table 1202.4,
53M-01       and Hot-Dipped, Zinc-Coated Welded      Table 1302.3,
             and Seamless                            1305.9
A 106-99el   Specification for Seamless Carbon       Table 1202.4,
             Steel Pipe for High-Temperature         Table 1302.3,
             Service                                 1305.9
A 126-01     Specification for Gray Iron Castings    Table 1202.5
             for Valves, Flanges, and Pipe
             Fittings
A 254-97     Specification for Copper Brazed Steel   Table 1202.4

             Tubing
A 420/A      Specification for Piping Fittings of    Table 1202.5
420M-01      Wrought Carbon Steel and Alloy Steel
             for Low-Temperature Service
B 32-00      Specification for Solder Metal          1203.3.3
B 42-98      Specification for Seamless Copper Pipe  513.13.1, 1107.4.2,
             Standard Sizes                          Table 1202.4,
                                                     Table 1302.3
B 43-98      Specification for Seamless Red Brass    513.13.1, 1107.4.2,
             Pipe, Standard Sizes                    Table 1202.4,
                                                     Table 1302.3
B 68-99      Specification for Seamless Copper       513.13.1
             Tube, Bright Annealed
B 75-99      Specification for Seamless Copper Tube  Table 1202.4,
                                                     Table 1302.3
B 88-99el    Specification for Seamless Copper       513.13.1, 1107.4.3,
             Water Tube                              Table 1202.4,
                                                     Table 1302.3
B 135-00     Specification for Seamless Brass Tube   Table 1202.4
B 251-97     Specification for General Requirements  513.13.1,
             for Wrought Seamless Copper and         Table 1202.4
             Copper-Alloy Tube
B 280-99el   Specification for Seamless Copper Tube  513.13.1, 1107.4.3,
             for Air Conditioning and Refrigeration  Table 1302.3
             Field Service
B 302-00     Specification for Threadless Copper     Table 1202.4,
             Pipe, Standard Sizes                    Table 1302.3
B 813-00e01  Specification for Liquid and Paste      1203.3.3
             Fluxes for Soldering of Copper and
             Copper Alloy Tube
C 315-00     Specification for Clay Flue Linings     801.16.1, Table
             803.10.4
C 411-97     Test Method for Hot-Surface             604.3
             Performance of High-Temperature
             Thermal Insulation
D 56-01      Test Method for Flash Point by Tag      202
             Closed Tester
D 93-00      Test Method for Flash Point of Pensky-  202
             Martens Closed Cup Tester
D 1527-99    Specification for Acrylonitrile-        Table 1202.4
             Butadiene-Styrene (ABS) Plastic
             Pipe, Schedules 40 and 80
D 1693-01    Test Method for Environmental Stress-   Table 1202.4
             Cracking of Ethylene Plastics
D 1785-99    Specification for Poly (Vinyl           Table 1202.4
             Chloride)(PVC) Plastic Pipe,
             Schedules 40, 80 and 120
D 2235-01    Specifications for Solvent Cement for   1203.3.4
             Acrylonitrile-Butadiene-Styrene
             (ABS) Plastic Pipe and Fittings
D 2241-01    Specification for Poly (Vinyl           Table 1202.4
             Chloride)(PVC) Pressure-Rated Pipe
             (SDR-Series)
D 2282-99    Specification for Acrylonitrile-        Table 1202.4
             Butadiene-Styrene(ABS) Plastic Pipe
             (SDR-PR)
D 2412-96a   Test Method for Determination of        603.8.3
             External Loading Characteristics of

             Plastic Pipe by Parallel-Plate Loading
D 2447-99    Specification for Polyethylene          Table 1202.4
             (PE) Plastic Pipe, Schedules 40
             and 80, Based on Outside Diameter
D 2466-01    Specification for Poly (Vinyl           Table 1202.5
             Chloride)(PVC) Plastic Pipe
             Fittings, Schedule 40
D 2467-01    Specification for Poly (Vinyl           Table 1202.5
             Chloride)(PVC) Plastic Pipe
             Fittings, Schedule 80
D 2468-96a   Specification for Acrylonitrile-        Table 1202.5
             Butadiene-Styrene (ABS) Plastic
             Pipe Fittings, Schedule 40
D 2513-00    Specification for Thermoplastic Gas     Table 1202.4,
             Pressure Pipe, Tubing, and Fittings     1203.15.3
D 2564-96a   Specification for Solvent Cements       1203.3.4
             for Poly (Vinyl Chloride)(PVC)
             Plastic Piping Systems
D 2683-98    Specification for Socket-Type           Table 1202.4,
             Polyethylene Fittings for Outside       1203.15.1
             Diameter-Controlled Polyethylene
             Pipe and Tubing
D 2837-98a   Test Method for Obtaining Hydrostatic   Table 1202.4
             Design Basis for Thermoplastic Pipe
             Materials
D 2846/D     Specification for Chlorinated Poly      Table 1202.4,
2846M-99     (Vinyl Chloride)(CPVC) Plastic Hot and  1203.3.4
             Cold Water Distribution Systems
D 2996-00    Specification for Filament-Wound        Table 1302.3
             Fiberglass (Glass Fiber Reinforced
             Thermosetting Resin) Pipe
D 3035-01    Specification for Polyethylene (PE)     Table 1202.4
             Plastic Pipe (DR-PR) Based on
             Controlled Outside Diameter
D 3278-96el  Test Methods for Flash Point of         202
             Liquids by Small Scale Closed-Cup
             Apparatus
D 3350-01    Specification for Polyethylene          Table 1202.4
             Plastics Pipe and Fittings Materials
E 84-01      Test Method for Surface Burning         202, 510.8,
             Characteristics of Building Materials   602.2.1, 602.2.1.5,
                                                     604.3, 1204.1
E 119-00e    Test Method for Fire Tests of Building  607.5.2, 607.5.5.1,
             Construction and Materials              607.6.1, 607.6.2
E 136-99e01  Test Method for Behavior of Materials   202
             in a Vertical Tube Furnace at 750°C
E 814-00     Test Method for Fire Tests of Through-  506.3.10
             Penetration Fire Stops
F 438-01     Specification for Socket Type           Table 1202.5
             Chlorinated Poly (Vinyl Chloride)
             (CPVC) Plastic Pipe Fittings,
             Schedule 40
F 439-01     Specification for Socket Type           Table 1202.5
             Chlorinated Poly (Vinyl Chloride)
             (CPVC) Plastic Pipe Fittings,
             Schedule 80
F 441/F      Specification for Chlorinated Poly      Table 1202.4
441M-99      (Vinyl Chloride)(CPVC) Plastic Pipe,

             Schedules 40 and 80
F 442/F      Specification for Chlorinated Poly      Table 1202.4
F 442M-99    (Vinyl Chloride)(CPVC) Plastic Pipe
             (SDR-PR)
F 493-97    S1203.3.4tion for Solvent Cements for
             Chlorinated Poly (Vinyl Chloride)
             (CPVC) Plastic Pipe and Fittings
F 876-01     Specification for Crosslinked           Table 1202.4
             Polyethylene (PEX) Tubing
F 877-01     Specification for Crosslinked           Table 1202.4,
             Polyethylene (PEX) Plastic Hot and      Table 1202.5
             Cold-Water Distribution Systems
F 1055-98    Specification for Eiectrofusion Type    Table 1202.4,
             Polyethylene Fittings for Outside       1203.15.2
             Diameter Controlled Polyethylene Pipe
             and Tubing
F 1281-01    Specification for Crosslinked           Table 1202.4
             Polyethylene/Aluminum/Crosslinked
             Polyethylene (PEX-AL-PEX) Pressure
            Pipe
F 1974-00e   Standard Specification for Metal        Table 1202.5
             Insert Fittings for
             Polyethylene/Aluminum/Polyethylene
             and Crosslinked
             Polyethylene/Aluminum/Crosslinked
             Polyethylene Composite Pressure Pipe
AWS          American Welding Society
             550 N.W. LeJeune Road
             Miami, FL 33126
Standard                                             Referenced
Reference                                            in code
Number       Title                                   section number
A5.8-92      Specifications for Filler Metals for    1203.3.1, 1303.3.1
             Brazing and Braze Welding:
CSA          Canadian Standards Association
             178 Rexdale Blvd.
             Rexdale (Toronto), Ontario,
             Canada M9W 1R3
Standard                                             Referenced
Reference                                            in code
Number       Title                                   section number
CAN/CSA
B137.10M-99  Crosslinked Polyethylene/Aluminum/      Table 1202.4
             Polyethylene Composite Pressure Pipe
             Systems
DOL          Department of Labor
             Occupational Safety and Health
             Administration
             c/o Superintendent of Documents
             US Government Printing Office
             Washington, DC 20402-9325
Standard                                             Referenced
Reference                                            in code
Number       Title                                   section number
29 CFR Part
1910 1000    Air Contaminants                        502.6
(1974)
IIAR         International Institute of Ammonia

             Refrigeration
             Suite 700
             1101 Connecticut Ave., NW
             Washington, DC 20036
Standard                                             Referenced
Reference                                            in code
Number       Title                                   section number
2-99         Equipment, Design, and Installation of  1101.6
             Ammonia Mechanical Refrigerating
             Systems
MSS          Manufacturers Standardization Society
             of the Valve & Fittings Industry, Inc.
             127 Park Street, N.E.
             Vienna, VA 22180
Standard                                             Referenced
Reference                                            in code
Number       Title                                   section number
SP-69-1996   Pipe Hangers and Supports-Selection     305.4
             and Application
NAIMA        North American Insulation
             Manufacturers Association
             Suite 310
             44 Canal Center Plaza
             Alexandria, VA 22314
Standard                                             Referenced
Reference                                            in code
Number       Title                                   section number
AH116-02     Fibrous Glass Duct Construction         603.5, 603.9
             Standards
NFPA         National Fire Protection Association
             Batterymarch Park
             Quincy, MA 02269
Standard                                             Referenced
Reference                                            in code
Number       Title                                   section number
30-96        Flammable Combustible Code              605.4, 1305.8
31-01        Installation of Oil-Burning Equipment   801.2.1, 801.18.1,
                                                     801.18.2, 901.2,
                                                     9181.1, 920.2,
                                                     922.1. 1301.2,
                                                     1305.11, 1308.1
37-98        Stationary Combustion Engines and       811.1, 811.2,
             Gas Turbines                            915.1, 915.2
45-04        Fire Protection for Laboratories Using  Table 403.3,
             Chemicals                               407.1, 502.20
54-06        National Fuel Gas Code                  901.2, 910.7, 918.2
58-01        Liquefied Petroleum Gas Code            502.9.10
69-97        Explosion Prevention Systems            510.8.3
70-02        National Electric Code                  1104.2.2
82-99        Incinerators and Waste and Linen        601.1, 907.1
             Handling Systems and Equipment
88B-97       Repair Garages                          304.5
91-99        Exhaust Systems for Air Conveying of    502.9.5.1,
             Vapors, Gases, Mists, and               502.17
             Noncombustible Particulate Solids
96-84        Installation of Equipment for the       506.3.7.1
             Removal of Smoke and Grease-laden
             Vapors from Commercial Cooking

             Equipment
211-00       Chimneys, Fireplaces, Vents, and Solid  802.1, Table
             Fuel-Burning Appliances                 803.10.6,
                                                     806.1, 811.1,
                                                     901.2
262-99       Standard Method of Test for Flame       602.2.1.1
             Travel and Smoke of Wires and Cables
             for Use in Air-Handling Spaces
704-96       Identification of the Hazards of        502.8.4, 510.1,
             Materials for Emergency Response        Table 1103.1,
                                                     1105.10
853-00       Installation of Stationary Fuel         924.1
             Power Plants
8501-97      Single Burner Boiler Operation          1004.1
8502-99      Prevention of Furnace Explosions/       1004.1
             Implosions in Multiple Burner
             Boiler-Furnaces
8504-96      Atmospheric Fluidized-Bed Boiler        1004.1
             Operation
NYC/NYS      New York City Codes/New York State
             Codes/NYC Agencies
Standard                                             Referenced
Reference                                            in code
Number       Title                                   section number
             Energy Conservation Construction Code   202, 301.2,
             of New York State                       303.3, 312.1,
                                                     514.1, 603.9,
                                                     604.1, 905.4,
                                                     1204.1, 1204.2
             New York City Air Pollution Code        801.5, 811.2.2,
                                                     904.1, 905.3,
                                                     907.2
             New York City Building code based       106.4, 106.5,
             2003 IBC                                107.1, 201.3,
             301.12, 301.12,
             301.14, 301.15,
             302.1, 302.2,
                                                     304.7, 304.10,
                                                     308.8, 308.10,
                                                     401.4, 401.6,
                                                     402.1, 405.2.1,
                                                     406.1, 502.10,
                                                     502.10.1, 502.16.2,
                                                     504.2, 506.3.3,
                                                     506.3.10, 506.3.12.2,
                                                     506.4.1, 509.1,
                                                     510.6, 510.6.1,
                                                     510.6.2, 510.7,
                                                     511.1.5, 512.2,
                                                     513.1, 513.2,
                                                     513.3, 513.4.3,
                                                     513.5, 513.5.2,
                                                     513.5.2.1, 513.6.2,
                                                     513.10.5, 513.12,
                                                     513.12.2, 513.12.3,6
                                                     513.20, 513.20.2,
                                                     601.2, 602.2.1.5.1,
                                                     602.2.1.5.2, 602.3,

                                                     603.1, 603.6.1.1,
                                                     603.10, 603.15,
                                                     607.1.1, 607.3.2.1,
                                                     607.5.1, 607.5.2,
                                                     607.5.3, 607.5.4,
                                                     607.5.4.1, 607.5.5,
                                                     607.5.5.1, 607.5,
                                                     701.4.1, 701.4.2,
                                                     801.3, 801.16.1,
                                                     801.18.4, 901.5,
                                                     902.1, 908.3,
                                                     908.3.2, 908.4,
                                                     910.3, 925.1,
                                                     1004.6, 1104.2.2,
                                                     1105.1, 1206.4,
                                                     1206.10, 1402.4,
                                                     1402.4.1
             New York City Electrical Code based     201.3, 301.7,
             on 2002 NEC                             306.3.1, 306.4.1,
                                                     513.11, 513.12.1,
                                                     602.2.1.1, 606.3,
                                                     1305.11.1.1
             New York City Fire Code                 201.3, 310.1,
                                                     311.1, 502.5,
                                                     502.7.2, 502.8.1,
                                                     502.9.5, 502.9.5.3,
                                                     502.9.8.2,
                                                     502.9.8.3,
                                                     502.9.8.5,
                                                     502.9.8.6, 502.7,
                                                     502.8, 502.9,
                                                     502.9.10, 502.10,
                                                     502.10.3, 509.1,
                                                     510.2.1, 510.2.2,
                                                     510.4, 513.15,
                                                     513.16, 513.17
                                                     513.18, 513.19,
                                                     513.20.3, 515.1,
                                                     606.2.1, 908.7,
                                                     1101.9, 1105.7.2,
                                                     1109.2, 1301.1
             New York City Fuel Gas Code based on    101.2, 201.3,
             2003 IFGC                               301.3, 701.1,
                                                     801.1, 801.2.2,
                                                     807.1, 901.1,
                                                     906.1, 917.6,
                                                     1101.5
             New York City Fuel Oil tank             1301.2, 1305.11
             Construction Standards
             New York City Plumbing Code based on    201.3, 301.8,
             2003 IPC                                512.2, 908.5,
                                                     1002.1, 1002.2,
                                                     1002.3, 1005.2,
                                                     1006.6, 1008.2,
                                                     1009.3, 1101.4,
                                                     1201.1, 1206.2,
                                                     1206.3, 1401.2
             New York State Department of            1301.2

             Environmental Conservation Petroleum
             Bulk Storage Code (6 NYCRR-612, 613,
             614)
             New York State Department of Labor      1003.3, 1004.1
             Industrial Code Rule Part 4
             New York State Department of Labor      1003.3
             Industrial Code Rule Part 4-6.2
             New York State Department of Labor      1003.3, 1004.1
             Industrial Code Rule Part 14
             United States Environmental Protective  1301.6
             Agency Technical Requirements and
             Corrective Action Requirements for
             Owners and Operators of Underground
             Storage Tanks 40 CFR Part 280
SMACNA       Sheet Metal & Air Conditioning
             Contractors National Assoc., Inc.
             4021 Fafayette Center Road
             Chantilly, VA 22021
Standard                                             Referenced
Reference                                            in code
Number       Title                                   section number
SMACNA-95    HVAC Duct Construction Standards-       603.4, 603.9
             Metal and Flexible
SMACNA-92    Fibrous Glass Duct Construction         603.5, 603.9
             Standards
UL            Underwriters Laboratories. Inc.
             333 Pfingsten Road
             Northbrook, IL 60062-2096
Standard                                             Referenced
Reference                                            in code
Number       Title                                   section number
17-94        Vent or Chimney Connector Dampers for   803.6
             Oil-Fired Appliances--with Revisions
             through September 1998
58-96        Steel Underground Tanks for Flammable   1305.12.1
             and Combustible Liquids
80-04        Steel Tanks for Oil-Burner Fuel         1305.12.1, Table
                                                     1305.7(2)
103-98       Factory-Built Chimneys, Residential     805.2
             Type and Building Heating Appliance--
             with Revisions through March 1999
127-96       Factory-Built Fireplaces--with          805.3, 903.1
             Revisions through November 1999
142-02       Steel Aboveground Tanks for Flammable   1305.8, 1305.12.1
             and Combustable Liquids
174-98       Household Electric Storage Tank Water   1002.1
             Heaters-with revisions through October
             1999
181-96       Factory-made Air Ducts and Air          512.2, 603.5,
             Connectors-with Revisions through       603.6.1.1,
             December 1998                           603.6.2, 603.11.1,
                                                     604.1.3
197-93       Commercial Electric Cooking             507.1
             Appliances-With Revisions Through
             January 2000
207-93       Refrigerant-Containing Components and   1101.2
             Accessories, Nonelectrical-with

             Revisions Through October 1997
343-97       Pumps for Oil-Burning Appliances-       1302.7
             with revisions through December
             22, 1999
391-95       Solid-Fuel and Combination-Fuel         918.1
             Central and Supplementary
             Furnaces-with Revisions Through
             May 1999
412-93       Refrigeration Unit Coolers-with         1101.2
             Revisions through November 1998
471-95       Commercial Refrigerators and            1101.2
             Freezers-with Revisions through
             April 1998
536-97       Flexible metallic Hose - with           1302.8
             revisions through October 2000
555-99       Fire Dampers - with Revisions through   607.3
             October, 2000
555C-96      Ceiling Dampers                         607.3 607.6.2
555S-99      Smoke Dampers--with Revisions through   607.2.1, 607.3,
             December 1999                           607.3.1.1
586-96       High-Efficiency, Particulate, Air       605.2
             Filter Units - with revisions through
             April 21, 2000
641-95       Type L Low-Temperature Venting          802.1
             Systems--with Revisions through
             April 1999
710-95       Exhaust Hoods for Commercial Cooking    507.1
             Equipment--with Revisions through
             April 1999
726-98       Oil-Fired Boiler Assemblies--with       916.1, 1004.1
             Revisions through January 1999
727-94       Oil-Fired Central Furnaces--with        918.1
             Revisions through January 1999
729-98       Oil-Fired Floor Furnaces--with          910.1
             Revisions through January 1999
730-98       Oil-Fired Wall Furnaces--with           909.1
             Revisions through January 1999
731-95       Oil-Fired Unit Heaters--with            920.1
             Revisions through January 1999
732-95       Oil-Fired Storage Tank Water            1002.1
             Heaters--With revisions through
             January 1999
737-96       Fireplace Stoves--with Revisions        805.2, 905.1
             through January 2000
762-99       Outline of Investigation for Power      506.5.1
             Ventilators for Restaurant Exhaust
             Appliances
791-93       Residential Incinerators--with          901.1
             Revisions through May 1998
834-98       Heating, Water Supply and Power         1004.1
             Boilers Electric--with Revisions
             Through November 1998
867-03       Control Units and Accessories for       513.12
             Fire Alarm Systems
867-00       Electrostatic Air Cleaners              605.2
900-94       Air Filter Units - with revisions       605.2, 607.2.3
             through October 1999
959-01       Medium Heat Appliance Factory-Built     805.5

             Chimneys
1046-00      Grease Filters for Exhaust Ducts        507.11
1240-94      Electric Commercial Clothes Drying      913.1
             Equipment--with Revisions through
             October 1999
1261-96      Electric Water Heaters for Pools and    916.1
             Tubs--with revisions through November
             25, 1998
1316-94      Glass-Fiber Reinforced Plastic          1305.12.1
             Underground Storage Tanks for
             Petroleum Products, Alcohols, and
             Alcohol-Gasoline Mixtures
1453-95      Electronic Booster and Commercial       1002.1
             Storage Tank Water Heaters--with-
             Revisions Through September 1998
1482-98      Solid-Fuel Type Room Heaters-with       905.1
             Revisions through January 2000
1777-98      Chimney Liners--with Revisions through  801.18.4,
             July 1998                               806.16.1
1820-97      Fire Test of Pneumatic Tubing for       602.2.1.3
             Flame and Smoke Characteristics--with
             Revisions through March 1999
1887-96      Fire Tests of Plastic Sprinkler Pine    602.2.1.2
             for Visible Flame and Smoke
             Characteristics--with Revisions
             through June 1999
1995-98      Heating and Cooling Equipment--with     911.1, 918.1,
             Revisions through August 1999           918.3, 1101.2
2043-96      Fire Test for Heat and Visible Smoke    602.2.1.4
             Release for Discrete Products and
             their Accessories Installed in
             Air-Handling Spaces--With
             Revisions through February 1998
2158-97      Outline of Investigation Electric       913.1
             Clothes Dryer--with Revisions
             through February 1999
2162-94      Outline of Investigation for            917.1
             Commercial Wood-Fired Baking Ovens--
             Refractory Type
  ASHRAE            American Society of Heating, Refrigerating and
                    Air-Conditioning Engineers, Inc.
                    1791 Tullie Circle, NE
                    Atlanta, GA 30329-2305
________________________________________________________________________
  Standard
  Reference
  Number            Title
________________________________________________________________________
  52.2 - 2007       Method of Testing General Ventilation
                    Air-Cleaning Devices for Removal Efficiency by
                    Particle Size
  62.1 - 2010       Ventilation for Acceptable Indoor Air Quality
  62.2 - 2010       Ventilation and Acceptable Indoor Air Quality in
                    Low-Rise Residential Buildings

   ______________________________________________________________
   1                                                            |
   2                                                            |

   1          COPY OF APPENDIX A                                |
   2          COMBUSTION AIR OPENINGS AND CHIMNEY CONNECTOR     |
   3          PASS-THROUGHS                                     |
   4          MAY BE OBTAINED FROM:                             |
   5          NYS LEGISLATIVE BILL DRAFTING COMMISSION          |
   6          CONTACT: LEGISLATIVE RETRIEVAL SYSTEM'S HELPLINE  |
   7                                                            |
   8                                                            |
   9____________________________________________________________|

                                APPENDIX B
                                RESERVED