Article 4 - PREVENTION OF EXTERIOR FIRE SPREAD

Section 27-331

Section 27-331

  §  27-331  Exterior  walls.  Exterior  walls  shall  comply  with  the
fire-resistance rating requirements of table 3-4.  Where  provisions  of
this  code  require a space or facility to be enclosed, the construction
requirements for the enclosure shall not apply to any exterior wall that
forms part of the enclosure.
  (a) Openings in exterior walls. In addition  to  the  requirements  of
table  3-4  and  subchapters  six  and  eight  of this chapter, exterior
openings above the third floor level of a building or above a height  of
forty  feet,  except  buildings  in  occupancy  group  J-3, open parking
structures, and buildings of construction classes II-D and  II-E,  shall
have  opening  protectives when (1) any part of the opening is less than
thirty feet distant in a direct unobstructed line not in the same plane,
from an opening in another building or from a wood frame building or (2)
any part of the opening is above and less than thirty feet in  a  direct
unobstructed line from, any roof construction that has a fire-resistance
rating  of  less  than one hour or that has unprotected openings therein
within this distance, whether the  roof  construction  is  on  the  same
building or on an adjacent building.
  (b)  Opening  protective  required  ratings.  In  a  building or space
classified in occupancy  group  A,  all  opening  protectives  shall  be
three-quarter   hour   (class   E)   opening   protectives  meeting  the
requirements of reference standard RS 5-8.  Such  protectives  shall  be
fixed  self-closing  or  automatic. Alternatively, these openings may be
protected with three-quarter hour (class F)  protectives  together  with
outside   sprinklers   installed   in   accordance   with   construction
requirements of subchapter seventeen of this  chapter.  In  such  cases,
there  shall  be an automatic dry pipe sprinkler head centered over each
opening with the orifice  directed  against  the  opening.  All  opening
protectives  required  by  table  3-4  or  by  subdivision  (a) above in
buildings  classified  in  other  than  occupancy  group  A   shall   be
three-quarter hour (class F) openings.
  (c)  First  story  openings. Opening protectives required by table 3-4
may be omitted in show windows or other openings on the lowest story  of
a building facing on a street or public space.
  (d) Nonautomatic protectives. Required opening protectives in exterior
openings,  if not self-closing or automatic, shall be kept closed by the
occupants at all times when not required for light or ventilation  under
the provisions of subchapter twelve of this chapter.
  (e)  Construction of unprotected openings. Exterior windows and doors,
including their frames and glazing, that are not required by  this  code
to have a fire-protection rating, may be of combustible materials. Below
a  height of seventy-five feet, slow-burning plastic glazing may be used
in windows. Glazing in balcony doors shall comply with the  requirements
of  paragraph  four of subdivision (g) of section 27-369 of article five
of subchapter six of this chapter.
  (f) Vertical  separation  of  openings.  In  buildings  classified  in
occupancy groups A, B, C, D and E, exceeding three stories or forty feet
in  height,  openings  located  vertically above one another in exterior
walls except in stairway enclosures, shall be separated  by  a  spandrel
wall  at  least  three  feet high between the top of one opening and the
bottom of the opening immediately above; or each such opening above  the
lower one shall be protected against fire by an opening protective; or a
fire canopy of noncombustible materials, extending out at least two feet
horizontally  from  the  wall  and  at least as long as the width of the
lower opening, shall be constructed between the two openings.  Spandrels
and  fire  canopies  shall  be  constructed  to  provide  at  least  the
fire-resistance rating required for the exterior wall, but in  no  event
less than one hour.

Section 27-332

Section 27-332

  §  27-332  Party  walls. The construction, design, and fire-resistance
rating of party walls shall be the same as required  by  this  code  for
vertical fire divisions. Concealed spaces in cornices and eaves shall be
fire-stopped as a continuation of the party wall.

Section 27-333

Section 27-333

  § 27-333 Parapets on exterior walls. Parapets shall be provided on all
exterior  walls  of  buildings of construction class II-A, II-B, or II-C
that have roof construction of combustible materials.
  (a) Exceptions. A parapet need not be provided on the exterior wall of
any building:
  (1) That is less than twenty-two feet high; or
  (2) Whose roof has  a  pitch  of  more  than  twenty  degrees  to  the
horizontal   and  whose  overhang,  fascia,  cornice  or  gutter  is  of
noncombustible  construction,  or  if  of  combustible  construction  is
separated  from the roof and ceiling construction by construction having
the fire-resistance  rating  required  for  the  exterior  wall  of  the
building.   Combustible   members,  excluding  roof  sheathing  and  its
supporting members, if covered by a class A roof covering and  complying
with  the  restrictions  as  required by section 27-335 of this article,
shall not extend through this construction, but shall have at least four
inches of solid noncombustible material below, at the sides, and at  the
ends of such members; or
  (3)  That is provided with a fire canopy at, or not more than two feet
below the roof level, continuous around that portion of the wall that is
without a parapet, constructed as required by subdivision (f) of section
27-331 of this article.
  (b) Construction. Parapets required under this  section  shall  be  of
materials and assembly having at least the fire-resistance rating of the
wall below, and shall be at least two feet high.

Section 27-334

Section 27-334

  §  27-334  Protective  guards. Buildings that are more than twenty-two
feet in height and have roofs that are flatter than  twenty  degrees  to
the horizontal shall be provided with a parapet not less than three feet
six  inches high, or be provided with a three foot six inch high railing
or fence, or a combination of a  parapet  and  railing  or  fence  which
together  are  not  less  than  three  feet six inches high. Railings or
fences may be located inward from  the  face  of  the  exterior  wall  a
distance  not  exceeding  six  feet,  and  shall  be of a type that will
prevent children from crawling through or over  them.  Where  roofs  are
used  for  recreational  purposes,  wire  fencing at least ten feet high
shall be constructed. Where ball games are  played  on  roofs  the  wire
fencing  shall  be  extended  to  provide an overhead closure. Except on
buildings of class II-D or II-E construction, railings or  fences  shall
be of noncombustible material. Railings shall be constructed as required
in section 27-558 of article three of subchapter nine of this chapter.

Section 27-335

Section 27-335

  §  27-335  Exterior  trim.  For the purposes of this section, exterior
trim shall be defined as any material, other than door and window frames
and sash, that is applied to exterior walls and  which,  if  removed  or
destroyed,  will  not  reduce  the  structural stability of the building
enclosure, and which is installed so  as  not  to  reduce  the  required
fire-resistance  rating  of  the  enclosure. Exterior trim shall include
cornices,  overhanging  eaves,   fascias,   belt   courses,   pilasters,
surrounds, gutters, leaders, half-timber work, shutters, trellises, etc.
  (a) Combustible exterior trim:
  (1)  May not be used on buildings required to be of construction group
I except that slow-burning plastics or approved equivalent materials may
be used up to a height of twenty-five  feet,  provided  that  such  trim
covers  not  more  than five percent of the surface area of the building
enclosure (openings not included), or not more than one thousand  square
feet.
  (2) May be used to a height of forty feet on buildings of construction
classes  II-A,  II-B,  and  II-C provided that such trim covers not more
than ten percent of the surface area of the building enclosure (openings
not included), projects not more than eight inches  beyond  the  outside
face  of  the  building  enclosure, and has an exterior separation of at
least fifteen feet measured from the outermost surface of the trim.
  EXCEPTION. Cornices, gutters, or overhanging  roofs,  when  permitted,
may  project  up  to  three feet beyond the outside face of the building
enclosure if they are at least eight inches above the  topmost  opening,
are  firestopped  as  required by section 27-345 of article five of this
suchapter and either:
  a. have their combustible structural members protected by soffits  and
fascias   of  a  material  or  assembly  having  at  least  a  one  hour
fire-resistance rating, or
  b. have all their combustible members  separated  from  the  roof  and
ceiling  construction  by construction having the fire-resistance rating
required for the exterior wall, with  at  least  four  inches  of  solid
noncombustible  material  below,  at  the sides, and at the ends of such
members;
  (3) May be used to an unlimited extent in  buildings  of  construction
classes  II-D and II-E on exterior walls that are not required to have a
fire-resistance rating.

Section 27-335.1

Section 27-335.1

  §  27-335.1  Acoustical  and thermal insulation; use in noncombustible
construction.
  (a) Notwithstanding any  provision  of  this  code  to  the  contrary,
acoustical or thermal insulation which is not noncombustible may be used
where noncombustible construction is required if:
  (1)  it satisfactorily passes a test for determining noncombustibility
of elementary materials,  based  on  the  test  procedures  of  A.S.T.M.
El36-65,  and,  upon  exposure  to  fire  will  not  produce products of
decomposition  or  combustion  that  are  more   toxic   in   point   of
concentration  that those given off by wood or paper when decomposing or
burning under comparable conditions; or
  (2) it has a flame-spread rating not greater than twenty-five, a smoke
developed  rating  not  greater  than  fifty,  is  without  evidence  of
continued progressive combustion when tested in accordance with the test
procedure  of  reference standard RS 5-5, and upon exposure to fire will
not produce products of decomposition or combustion that are more  toxic
in  point  of  concentration  than those given off by wood or paper when
decomposing or burning under comparable conditions.
  (b) Notwithstanding any provision of subdivision a of this section  or
any  other provision of this code to the contrary, acoustical or thermal
insulation, which is not noncombustible and  which  does  not  meet  the
requirements  of  subdivision  a  of  this  section,  may  be used where
noncombustible construction is required subject to the approval  of  the
commissioner,  and  provided  it  is  installed in a composite method of
construction, with a minimum of three inches  of  unpierced  masonry  or
concrete on all sides.
  (c)  Notwithstanding  any  provision  of  subdivision  a  or b of this
section or any other provision of this code  to  the  contrary,  thermal
insulation,  which  is  not  noncombustible  and which does not meet the
requirements of subdivisions a and b of this section, may  be  installed
in  an  exterior  wall  system in any noncombustible construction group,
provided that:
  (1) such insulation is of a thickness no  greater  than  four  inches;
provided,  additional  thickness  used  exclusively  for  decorative  or
leveling  purposes  shall  be  permissible,  where  the  area  of   such
additional thickness does not exceed fifteen percent of the wall area on
any single story;
  (2) such insulation has a heat value not in excess of six thousand BTU
per square foot;
  (3) such insulation is installed in a composite method of construction
and  is  separated  from  interior spaces by a thermal barrier having at
least a one-hour fire resistance rating;
  (4) such insulation  has  a  flame  spread  rating  not  greater  than
twenty-five  and  a smoke developed rating not greater than four hundred
fifty, and is covered with, and sealed or joined by, material  having  a
flame  spread  rating not greater than twenty-five and a smoke developed
rating not greater than  fifty,  when  tested  in  accordance  with  the
procedures of reference standard RS 5-5;
  (5)  such  insulation  is  installed  in  a  manner  which  meets  the
requirements for firestopping set forth in section 27-345;
  (6) upon exposure to fire, the exterior wall system and  each  of  its
components will not produce products of decomposition or combustion that
are more toxic in point of concentration than those given off by wood or
paper when decomposing or burning under comparable conditions;
  (7) the structure on which the exterior wall system is installed meets
the  requirements of section 27-331 pertaining to minimum horizontal and
vertical separation distances; provided, however, that  such  insulation
shall  not be used on the exterior surface of a wall of a court or shaft

if the horizontal or vertical separation distance between such wall  and
another wall of such court or shaft is less than twenty feet;
  (8)  the  use  of such insulation on soffits or other horizontal areas
shall not extend more than three feet beyond the  outside  face  of  the
building enclosure;
  (9)  the  use of such insulation on buildings having party walls meets
the requirements of section 27-332;
  (10) such insulation meets  the  acceptance  requirements  of  section
27-131;
  (11)  the  results  of  a fire test of a representative portion of the
exterior wall system meet the requirements of reference standard RS5-21;
  (12) the edge or face of the assembly containing  such  insulation  is
labeled with the following information:
  a.  the  name of a nationally recognized testing laboratory acceptable
to the commissioner which has inspected such insulation;
  b. the model of the exterior wall assembly for which  such  insulation
is  listed  by  a nationally recognized testing laboratory acceptable to
the commissioner;
  c. the identity of the manufacturer of such insulation;
  d. the flame spread and smoke developed ratings; and
  (13)  the  installation  of  such  insulation  shall  be  subject   to
controlled   inspection   to  ensure  that  the  installation  is  fully
consistent with the terms of the  listing  by  a  nationally  recognized
testing   laboratory   acceptable   to   the   commissioner,  acceptance
requirements of  section  27-131  and  the  manufacturer's  installation
recommendations.
  (d)  The  commissioner may, with regard to thermal insulation, the use
of which is authorized by  this  subdivision,  establish  by  regulation
training  criteria  for persons installing such insulation, and prohibit
the installation of such insulation by persons not  adequately  trained.
Any  person installing such insulation shall certify to the commissioner
that the installation is fully consistent with the terms of the  listing
by   a  nationally  recognized  testing  laboratory  acceptable  to  the
commissioner,  acceptance  requirements  of  section  27-131   and   the
manufacturer's installation recommendations.
  (e) Definitions. As used in this section:
  (1)  "Composite  method  of  construction"  shall  mean  a  method  of
construction  in  which  diverse  materials  are  combined  to  form  an
assembly,  whether  the  assembly  is prefabricated or fabricated at the
site of installation.
  (2) "Exterior wall system" shall  include  the  exterior  walls  of  a
building and the appurtenances thereof.

Section 27-336

Section 27-336

  §   27-336  Porticos,  porches,  etc.  Porticos,  entranceways,  storm
enclosures, bay windows, oriel windows, porches, or  similar  appendages
may  be  constructed of combustible materials or assemblies on buildings
of construction class II-E to an unlimited extent, and on  buildings  of
construction  classes  II-A,  II-B,  II-C,  and  II-D  under  all of the
following conditions:
  (a) The building is classified in occupancy group J-2 or J-3.
  (b) The building is not more than three stories or forty feet high.
  (c) The appendage has an exterior separation on all exposed  sides  of
at  least  fifteen  feet,  measured  from  the  outermost surface of the
appendage.
  (d) The appendage is so constructed that its  removal  or  destruction
will  not reduce the structural stability or fire resistive integrity of
the building.
  (e) The vertical surface area  of  the  combustible  portions  of  the
appendage,  including any exterior trim, is not more than ten percent of
the total wall area (windows excluded) of the building.
  (f) The appendage has  a  superficial  roof  area  not  exceeding  one
hundred  fifty  square  feet  and is included in the area limitations of
table 4-1 and 4-2 for the entire building.
  (g) The appendage is not higher than the sills  of  the  second  story
windows.
  (h) The roof of the appendage has a class A roof covering.
  (i) The soffit or ceiling covering the combustible roof framing of the
appendage has a one hour fire-resistance rating.
  (j) The requirements of subdivisions (h) and (i) of this section shall
not  apply  in  the  case  of  roofs  or awnings over patios or entrance
platforms where the area of vertical exposure of the patios or platforms
to the outdoors is equal to at least that of the patio or platform area.
Plastic  shall  be  slow  burning;  canvas  or  other  fabric  shall  be
noncombustible  or  flameproofed  in  accordance  with the provisions of
title fifteen of the administrative code.

Section 27-337

Section 27-337

  §  27-337  Roof coverings. Roof coverings shall be classified as A, B,
or C on the basis of their  resistance  to  exterior  fire  exposure  as
listed  in  reference standard RS 5-9, or as determined by tests made in
conformance with reference standard RS 5-10 for those not listed.
  (a) Limitations of use. Every roof  placed  on  a  building  shall  be
covered  with  class A or B roof covering, except class C roof coverings
may be placed on buildings classified in occupancy group J when not more
than three stories or forty feet in height, and on  buildings  permitted
by  this  code  to  be  of  class  II-D or II-E construction. The use of
roofing having no rating is prohibited, except for  replacement  to  the
extent  of  twenty-five  percent  of  the  roof area in any twelve month
period.
  (b)  Combustible   roof   decking.   Unless   attached   directly   to
noncombustible  framework,  all  roof  coverings  shall  be applied to a
closely fitted deck; except that wood shingles, to the extent  permitted
in subdivision (a) of this section, may be applied to wood slats.
  (c) Roof insulation. Combustible roof insulation may be applied on top
of  roof  decking  or  slab  provided that it is protected with the roof
covering applied directly thereto.

Section 27-338

Section 27-338

  §  27-338  Roof  structures. (a) Construction of penthouses. Enclosure
walls of penthouses shall comply  with  the  requirements  for  exterior
walls  of  table 3-4 for the construction class of the building on which
they are erected. Roofs of penthouses shall comply with the requirements
for roof construction of table 3-4 and section 27-337 of article five of
subchapter six of this chapter.
  (b) Construction of  bulkheads.  Bulkheads  shall  be  constructed  of
noncombustible  materials  having  a  one  hour  fire-resistance rating,
except that in  buildings  of  construction  class  II-E,  they  may  be
constructed  of  combustible materials having a one hour fire-resistance
rating.
  (c)  Scuttles.  Scuttles  shall  be  constructed   of   noncombustible
materials,  or  of  combustible materials covered on the top, sides, and
edges with noncombustible materials.
  (d) Skylights. For the purposes of this section, the  term  "skylight"
shall  be  construed  to  include  the sash, frames, and glazing of roof
monitors and sawtooth roofs.
  (1) SASH AND FRAMES. Skylights that are inclined at  less  than  sixty
degrees  to  the  horizontal on all buildings of other than construction
classes II-D and  II-E,  shall  have  sash  and  frames  constructed  of
noncombustible  materials,  and  their glazing shall be as prescribed in
paragraph two of  this  subdivision.  Skylights  that  are  inclined  at
greater  than sixty degrees to the horizontal shall have sash and frames
constructed as required for windows,  and  their  glazing  shall  be  as
required  for windows. Glass, glass blocks, or plastic used in skylights
shall be designed and constructed to withstand the same  live  loads  as
required for roofs plus any concentrated live loads required herein.
  (2)  GLAZING. a. Skylights over stairways and shafts. Skylights placed
over stairways and shafts shall be glazed with plain glass not more than
one-eighth  inch  thick  or   unreinforced   plastic   not   more   than
three-sixteenths of an inch thick.
  b.  Skylights over other spaces. Skylights in all locations other than
over stairways and shafts shall be glazed with  one-quarter  inch  wired
glass, plain glass, glass block, or plastic of material and installation
complying with subparagraph c of this paragraph.
  c.  Plastic.  Plastic  used  for  the  glazing of skylights other than
skylights over stairways and shafts shall be slow burning  plastic.  The
aggregate  area  of  skylight  openings,  other  than over stairways and
shafts, shall not exceed thirty-nine per cent of the floor area  of  any
room or space sheltered by the roof in which they are located. The edges
of   plastic,   if  exposed,  shall  be  protected  by  metal  or  other
noncombustible material. Skylights in which plastic is used, if on roofs
having a pitch of twenty degrees to the horizontal  or  less,  shall  be
constructed in accordance with the following:
  1.  The  area  within the curbs of each skylight shall not exceed five
square feet, except that this area may be of any size, limited  only  by
other  provisions  of  this  section,if  the opening is protected on all
sides by a noncombustible railing thirty-six inches in height  complying
with  the  provisions  of  section 27-558 of article three of subchapter
nine of this chapter for railings; or the skylight  is  subdivided  into
areas  of  five  square  feet  or less by noncombustible muntins or bars
capable of supporting a live load of three hundred pounds at any  point;
or a noncombustible screen or grid capable of supporting a load of three
hundred  pounds  over  any  one foot by two foot area as provided above,
integral with, or not more than three feet below the skylight, with  the
wire or bars spaced into areas of five square feet or less (if above the
roof, the wires shall be of corrosion resistive metal).

  2.  There  shall  be  a  minimum  clear distance of three feet between
skylights.
  (3)  Separation  of skylights from structures. There shall be at least
ten feet between a plain glass or plastic skylight and  any  door  in  a
stair  bulkhead located above the roof in which the skylight is located,
and at least ten feet between such a skylight and  any  opening  in  any
roof structure or other wall above the roof not equipped with an opening
protective. On buildings up to one hundred feet in height there shall be
at  least  ten  feet  from  such  a  skylight  to the outside face of an
exterior wall facing on a frontage space.
  (4) SCREENS.  Plain  glass  skylights  shall  be  protected  on  their
underside  by  noncombustible  screens  having  a  mesh not smaller than
three-quarters of an inch by three-quarters of an inch nor  larger  than
one  inch by one inch of at least No. 12 B. & S. gauge wires. The screen
shall be installed tight against the roof opening or  shall  project  on
all  sides  for  a  distance of not less than the distance of the screen
below the glass, and shall be of such material and construction so as to
support a load of three hundred pounds over any one  foot  by  two  foot
area. The provisions for wire glass or screen protection shall not apply
to glass block skylights.
  (e)  Greenhouses.  Greenhouses  on  the  roofs of buildings other than
buildings of construction class II-D or II-E  shall  be  constructed  of
noncombustible  framework  and shall be glazed with plain or wire glass,
or slow burning plastic. The floors of greenhouses shall be  constructed
at  least  as  required  for  roof  construction  in  table  3-4 for the
construction class of the building on which it is located.
  (f) Construction of sloping roofs. Roofs having a slope of  more  than
sixty  degrees to the horizontal shall be constructed of material having
the same fire-resistance rating as required for an exterior  non-bearing
wall  of  the  building  of  which it is a part. When the slope is sixty
degrees or less to the horizontal, the sloping roof shall be constructed
as required for the roof of the building. Where  the  back  of  a  false
mansard  is  exposed  to  the  outdoors,  the back shall be covered with
noncombustible material or with roof coverings as required for the  roof
of the building.
  (g)   Dormers.  Roofs  of  dormers  shall  be  of  the  same  type  of
construction and have roof covering of the same class  as  required  for
the roof of the building on which they are located. The walls of dormers
shall be constructed of materials having the same fire resistance rating
as required for non-bearing exterior walls of the building on which they
are  located;  except  that  in  buildings of construction classes II-A,
II-B, II-C, and II-D,  the  walls  may  be  constructed  of  combustible
framing  provided that the outside face of the framing is protected with
noncombustible sheathing and the  aggregate  area  of  all  such  dormer
walls, including openings therein, does not exceed twenty percent of the
roof area.
  (h) Water tanks.
  (1)  SUPPORTS. All water tanks placed in or on a building and having a
capacity of more  than  five  hundred  gallons  shall  be  supported  on
noncombustible  walls  or  framing. When such tank is located within the
building, above the lowest story, its framing shall be fire protected as
required for columns supporting one floor or the tank shall  be  located
within  a  room  or  space  that  is enclosed with construction having a
fire-resistance rating equivalent to that  otherwise  required  for  the
protection of the framing.
  (i)   Cooling   towers.   Cooling   towers  shall  be  constructed  of
noncombustible materials, except as follows:

  (1) Outside the fire districts,  when  located  on  a  building  three
stories or forty feet in height or less of construction group I, cooling
towers may be constructed of combustible materials provided they are not
more than fifteen feet high and do not exceed seven hundred fifty square
feet in area.
  (2)  Outside  the  fire  districts, when located on the ground and not
exceeding three stories or forty feet in height  or  one  thousand  five
hundred  square  feet  in  area,  cooling  towers  may be constructed of
combustible material provided they are  protected  by  a  noncombustible
screen,  fence, or wall at least twenty feet from the tower and at least
seven feet high.
  (3) Filling and drift eliminators may be of combustible  materials  if
the  towers  are  provided with automatic sprinkler protection complying
with the construction provisions of subchapter seventeen.
  (4) Filling and drift eliminators  may  be  of  combustible  materials
where  the  towers are not provided with automatic sprinkler protection,
provided all of the following conditions are met:
  a. The cooling tower is constructed of noncombustible material;
  b. The cooling tower is located on a building  in  construction  group
I-A or I-B;
  c.  The cooling tower and filling and drift eliminators are located at
least thirty feet away from any windows or fresh air intakes  which  are
at  an  elevation  above the roof on which the cooling tower is located,
whether in the same building or in an adjoining building;
  d. The cooling tower is located not less than fifteen  feet  from  the
nearest lot line; and
  e.  The  cooling  tower  is  located  not  less than ten feet from any
chimney, except that the distance shall be not  less  than  twenty  feet
from a chimney venting products of combustion other than from gas or oil
fired appliances, whether on the same building or an adjoining building.
  (5)  In no event shall cooling towers or filling and drift eliminators
be constructed of materials that contain asbestos.
  (j) Miscellaneous roof structures. The following roof  structures  may
be  constructed  of  combustible  material if less than twelve feet high
above the roof: antenna  supports;  flagpoles;  clothes  drying  frames;
duckboarding or platforms that do not cover more than twenty per cent of
the roof area at that level.