Article 5 - PREVENTION OF INTERIOR FIRE SPREAD

Section 27-339

Section 27-339

  §  27-339  Fire  segregation  of  occupancies. (a) Segregation by fire
divisions. When different occupancies  are  to  be  segregated  by  fire
divisions  under the provisions of section 27-240 of subchapter three of
this chapter, the  occupancies  shall  be  separated  from  each  other,
vertically  and  horizontally,  by  fire  divisions  having at least the
fire-resistance ratings listed in table 5-2  for  the  occupancy  groups
involved. Every building section shall be constructed of elements having
at least the fire-resistance rating of a construction class required for
the  area and height of the building section as listed in tables 4-1 and
4-2.
  (b) Segregation by fire separations. When different spaces are  to  be
segregated by fire separations under the provisions of section 27-240 of
subchapter  three  of  this  chapter, the occupancies shall be separated
from each other, vertically and horizontally, by fire separations having
at least the fire-resistance ratings listed in table 5-1.  In  buildings
of  construction  group  I,  fire  separations  shall  be constructed of
noncombustible materials.

      (For Tables 5-1 and 5-2 see chapter 839 of the laws of 1986)
  Key: Fire-resistance ratings are given in hours. For Table  5-1,  read
above  heavy  line.  For  Table  5-2, read below heavy line. NR means No
requirement.

                      NOTES FOR TABLES 5-1 AND 5-2
  a. An office, or group of  offices,  whose  use  is  accessory  to  an
occupancy, and totals four hundred square feet or less in area shall not
be required to have a fire separation. Such office, or group of offices,
totalling  more  than  four  hundred  square  feet  in area shall not be
required to have a  fire  separation  if  such  offices  exit  directly,
without having to pass through the area of the related occupancy.
  b. Counters  and  backbars for the sale of publications, tobacco prod-
ucts, liquors, or candies, or for making of reservations for travel, car
rental,  or  theatre,  or  otherwise  involving  similar  business   and
mercantile activities that are accessory to an occupancy and are limited
in  area  to  one hundred square feet, within the area of the occupancy,
need not comply with the requirements of this table.
  c. The  provisions  of  this  table  shall  not   apply   to   closets
seventy-five square feet or less in area.
  d. Nonresidential  kitchens  need not be separated by fire separations
from adjoining dining spaces, provided:
  (1) The cooking equipment is vented directly to the outdoors, and
  (2) 2 draft curtain of noncombustible material, at  least  twenty-four
inches  down  from  the  ceiling,  is  provided  to separate the cooking
facilities from dining spaces, and
  (3) Sprinkler heads constructed in accordance with the  provisions  of
subchapter  seventeen  of  this  chapter,  are  provided  on the cooking
facilities side of the curtain, or any opening between the  kitchen  and
dining  space,  located  within  twenty-four  inches  of  the curtain or
opening, and spaced not more than forty-eight inches on centers  if  the
opening  is  more  than  sixty  inches  wide.  When fire separations are
provided double-action doors may be permitted.
  e. Kitchens having a floor area of  fifty-nine  square  feet  or  less
located within dwelling units shall be separated from adjacent spaces by
partitions  having  a fire-resistance rating of at least one hour except
for the entrances thereto which need comply with section 27-342 of  this
article. If doors are provided they may be of wood.

  f. In buildings or spaces classified in occupancy group J-1 or J-2 all
partitions  in  dwelling  units  located in cellars shall have a minimum
fire-resistance rating of one hour.

  (c)  Compartmentation. Notwithstanding the provisions of table 4-1, in
existing office buildings one hundred feet  or  more  in  height  having
air-conditioning  and/or  mechanical ventilation systems that serve more
than the floor on which the equipment is  located,  unsprinklered  floor
areas,  more  than  forty  feet above curb level, shall be subdivided by
fire separations into spaces or compartments of  the  size  required  by
paragraphs  one  through  five  of this subdivision. Floor area shall be
defined as the area  within  exterior  walls  and  excluding  any  areas
enclosing stairs, corridors, elevators and shafts:
  (1)  Unless  otherwise  provided  below, all unsprinklered floor areas
shall  be  segregated  by  one-hour  fire  separations  into  spaces  or
compartments not to exceed seventy-five hundred square feet.
  (2)  Where  the  floor area exceeds ten thousand square feet, at least
one  of  the  subdividing  fire  separations  shall   be   of   two-hour
fire-resistive  construction,  creating  areas of refuge, complying with
section 27-372 of article five of subchapter six  of  this  code  except
that the requirement for an elevator in each area shall not apply.
  (3) The floor area or any subdivided area may be increased to not more
than  fifteen  thousand  square  feet  if  complete  area  protection by
approved devices for the detection of products of combustion other  than
heat is provided within such increased area and provided further than at
least  one  of  the  subdividing  fire  separations shall be of two-hour
fire-resistive  construction  where  the  floor  area  exceeds   fifteen
thousand  square  feet,  creating areas of refuge in the same manner and
under the same conditions as provided in two of  this  subdivision.  The
activation  of any such detectors shall have the same effect as provided
in subdivision (f) of section  27-972  of  article  five  of  subchapter
seventeen of this code.
  (4)  In  existing  buildings,  existing  fire  separations of one-hour
fire-resistive  construction  may  be  accepted  in  lieu  of  the  fire
separation  of  two hour fire-resistive construction providing all other
requirements of  paragraphs  two  and  three  of  this  subdivision  are
complied with.
  (5)  Regardless  of  the  floor area, no subdivision of the floor area
shall  be  required  under  this  subdivision  when  complete  sprinkler
protection is provided in accordance with the construction provisions of
subchapter seventeen of this chapter.
  (6) Existing office buildings one hundred feet or more in height shall
comply with the requirements of this subdivision as follows:
  a.  Whenever  an  alteration is performed involving partition changes,
compliance with this subdivision shall be required in  that  portion  of
the building being altered.
  b.  At  least one-third of the total floor area of the building not in
compliance  with  the  requirements  of  this  subdivision  on  February
seventh,   nineteen   hundred  seventy-three,  shall  comply  with  such
requirements  on  or  before  December  thirteenth,   nineteen   hundred
eighty-one.  Complete plans showing such compliance for the phase of the
work to be done shall be filed with, and  a  permit  secured  from,  the
commissioner on or before September thirteenth, nineteen hundred eighty.
  c.  At least two-thirds of the total floor area of the building not in
compliance  with  the  requirements  of  this  subdivision  on  February
seventh,   nineteen   hundred  seventy-three,  shall  comply  with  such
requirements on or before August seventh, nineteen hundred eighty-four.

  d. Full compliance shall be provided on or  before  February  seventh,
nineteen hundred eighty-eight.
  (7)  In  existing  office buildings one hundred feet or more in height
where compliance would cause practical difficulty or undue hardship, the
commissioner may waive or modify  the  requirements  of  paragraphs  one
through  five of this subdivision and accept alternatives fulfilling the
intent  of  these  requirements.  Where   compliance   with   the   time
requirements  of  paragraph  six  of  this subdivision would cause undue
hardship, the commissioner, with the approval of the fire  commissioner,
may  extend  the  time  for  compliance,  in  accordance  with rules and
regulations to be  promulgated.  Before  such  application  for  a  time
extension  shall  be considered all required applications and plans must
be filed and approved, permits obtained and a good faith effort  towards
completion of the work shall have been made.

Section 27-340

Section 27-340

  §  27-340  Fire  divisions.  Fire  divisions  shall  be constructed of
non-combustible materials or assembly  of  noncombustible  materials  to
provide the fire-resistance ratings required by table 5-2. Vertical fire
divisions  shall  be  continuous between foundation, roof, or horizontal
fire divisions, and  through  any  concealed  space  in  floor  or  roof
construction.  Horizontal  fire  divisions  shall  be continuous between
exterior walls and/or vertical fire divisions.
  (a) When roof construction is combustible on both sides of a  vertical
fire  division, the vertical fire division shall extend through the roof
construction to a height of at least four inches above the high point at
the roof framing. Decking shall tightly butt the  fire  division.  Above
the  decking  of  roofs  that  are  flatter  than  twenty degrees to the
horizontal, blocking shall be constructed to form cants on both sides of
the fire division with slopes not steeper than 1:4. Combustible  decking
shall not extend over the top of the fire division.
  (b)  Except  as required in subdivision (c) of this section, when roof
construction is noncombustible on one or both sides of a  vertical  fire
division,  the  vertical fire division may terminate at the underside of
the noncombustible roof construction provided the junction of  the  wall
and roof construction is made smoke tight.
  (c)  When  a vertical fire division is required by table 5-2 to have a
fire-resistance rating of three or four hours, and the roof construction
has a fire-resistance rating of less than two hours, the  fire  division
shall  extend  above  the  roof  construction to form a parapet at least
three feet high.
  (d) Fire divisions  shall  be  so  constructed  that  the  removal  or
collapse  of  construction  on one side will not endanger the support of
construction on the other side.
  (e) Fire divisions shall be made smoketight  at  their  junction  with
exterior  walls.  In  buildings  of  construction  class  II-D and II-E,
exterior walls shall be constructed of noncombustible  materials  for  a
distance  of at least eighteen inches on each side of the fire division,
or the fire division shall project at least twelve  inches  through  the
exterior wall.
  (f)  Fire  divisions  may  be  offset  if the construction between the
offset  divisions,  including  their   supports,   has   at   the   same
fire-resistance  rating  as  the  fire  division, with all hollow spaces
within the construction firestopped with noncombustible material.
  (g) Where combustible members such as joists, beams, or  girders  bear
on,  or  frame  into,  vertical  fire  divisions, such members shall not
extend through the wall and shall have at least  four  inches  of  solid
noncombustible  material  below,  at  the sides, and at the ends of each
such member.
  (h) Chases or recesses shall not be cut into fire divisions so  as  to
reduce  their  thickness  below  that  required  for the fire-resistance
rating.
  (i) Vertical fire divisions that are hollow shall be firestopped  with
at least four inches of noncombustible material so as to prevent passage
of  flame,  smoke,  or  hot gases through the hollow spaces to the story
above or below, or to hollow spaces  within  connecting  floor  or  roof
construction.

Section 27-341

Section 27-341

  §  27-341  Fire  separations. Fire separations shall be constructed of
materials or assembly of materials having at least  the  fire-resistance
ratings required by table 5-1.
  (a)  Different tenancies. Different tenant apartments, suites, stores,
offices, or other spaces that are not separated from each other by  fire
divisions, shall be separated from each other by fire separations having
at  least  the fire-resistance rating prescribed in table 5-1, but in no
case less than one hour, and shall continue through any concealed spaces
of the floor or roof construction above.

Section 27-342

Section 27-342

  §  27-342 Openings in fire divisions and separations. Openings in fire
divisions  and  fire  separations  that   are   required   to   have   a
fire-resistance rating, shall be protected by opening protectives having
the  fire-resistance  ratings  prescribed in table 5-3, shall not exceed
the limits in size and area herein prescribed, and shall comply with the
provisions of section 27-329 of article three of this subchapter.   Door
and  other  openings  in enclosures of vertical exits, exit passageways,
corridors,  and  places  of  assembly  shall  be  protected  by  opening
protectives  as  required by the provisions of subchapters six and eight
of this chapter.  When such enclosures also serve as fire  divisions  or
fire separations, openings therein shall be protected as required by the
provisions of this subchapter.
  (a)  Size of opening. In buildings that are not sprinklered no opening
through a fire division or fire  separation  shall  exceed  one  hundred
twenty  square feet in area, with no dimension greater than twelve feet,
and the aggregate width of all openings at any level  shall  not  exceed
twenty-five  percent of the length of the wall.  Where the areas on both
sides  of  a  fire  division  or  fire  separation  are  sprinklered  in
accordance  with  the construction provisions of subchapter seventeen of
this chapter, the size of the opening may be one  hundred  fifty  square
feet in area, with no dimension greater than fifteen feet.  In buildings
fully  sprinklered  in  compliance  with  the  provisions  of subchapter
seventeen of ths chapter, the  size  and  aggregate  width  of  openings
through  fire  divisions or fire separations shall be unlimited.  When a
fire division or fire separation serves as a horizontal  exit  also,  it
shall  have  no opening other than door openings not exceeding fifty-six
square feet in area, the aggregate width of all openings  at  any  level
shall  not  exceed  twenty-five  percent  of the length of the wall, and
shall comply with the provisions of section 27-373 of  article  five  of
subchapter six of this chapter.
  (b)  Conveyor  openings.  Where fire doors or shutters are impractical
for the protection of  conveyor  openings  in  fire  divisions  or  fire
separations, a system of water spray nozzles may be used.  At least four
nozzles  shall  be  provided  on  each side of the opening so as to give
complete coverage of the opening.   Nozzles shall be  controlled  by  an
automatic  valve  actuated by a heat detector.  Nozzles shall be located
at an angle not more than  thirty  degrees  between  the  centerline  of
nozzle  discharge  and a line perpendicular to the plane of the opening.
The water discharge rate shall be at least three gallons per square foot
per minute.  When conveyor openings through floors are protected by this
method, the openings shall also  be  provided  with    a  noncombustible
enclosure  constructed  around  the  conveyor  from  the  floor up to or
slightly beyond the spray nozzles, and draft curtains shall be  provided
extending twenty-four inches below and around the floor opening.

                                Table 5-3
       Opening Protectives for Fire Divisions and Fire Separations

     Fire-Resistance Rating of Fire     Fire Protection Rating
     Division or Fire Separation        of Opening Protective
     in which Opening Occurs (hr.)

        3 or 4                            3 hr. (Class A)*
        2 or 1-1/2                        1-1/2 hr. (Class B)
        1                                 3/4 hr. (Class C)

  * Note--Shall  consist  of two one and one-half hour (class B) opening
protectives, with one protective  installed  on  each  face  of  a  fire
division or fire separation.

Section 27-343

Section 27-343

  §  27-343  Ducts,  pipes  and conduits through rated construction. (a)
Installation of ducts which pass through construction required to have a
fire-resistance rating shall comply with the requirements of  subchapter
thirteen,  provided  that,  notwithstanding the provisions of subchapter
thirteen or reference standard RS 13-1, noncombustible ducts which  pass
through  construction  required  to have a fire-resistance rating of one
hour must be provided with fire dampers unless:
  (1) The building is classified in occupancy group C, E, or H-2; and
  (2) Complete  sprinkler  protection  is  provided  for  the  floor  in
accordance with subchapter seventeen; or
  (3)  The openings for the ventilation ducts do not exceed three square
feet in area; or
  (4) The duct is protected  on  both  sides  of  the  partition  for  a
distance  equal  to the maximum duct dimension by a sleeve affording one
hour fire separation for such horizontal distance.
  (b)  Noncombustible  pipes  and  conduits.  Noncombustible  pipes  and
conduits   may   pass   through   construction   required   to   have  a
fire-resistance rating provided that  the  space  between  the  pipe  or
conduit  and  its sleeve or opening does not exceed one-half inch and is
completely  packed  with  mineral  wool  or  equivalent   noncombustible
material  and  is  closed off by close-fitting metal escutcheons on both
sides of the construction; and provided further that the  aggregate  net
area  of  such openings does not exceed twenty-five square inches in any
one hundred square feet of wall or floor area (excluding  the  areas  of
openings  for  sleeves  which  are  firestopped in conformance with this
section and section 27-345).
  (c) Openings for passage of pipe and ducts whose  aggregate  net  area
exceeds twenty-five square inches in any one hundred square feet of wall
or  floor  area  (excluding opening for sleeves which are firestopped in
conformance  with  this  section  and   section   27-345)   may   pierce
constructions  required  to  have a fire-resistance rating only when the
type of construction to be used has  been  tested  with  such  types  of
facilities  installed in place and the proportionate area of openings of
such facilities to be installed in the construction does not exceed  the
proportionate  area  of openings in the assembly tested, and provided no
opening is larger than that in the assembly tested. Protection  of  such
openings shall be the same as provided in the test. All openings through
hollow  fire  rated construction shall be sleeved with sheet metal least
No. 14 U.S. std. gage thick.
  (d) The installation and proper functioning of required  fire  dampers
shall  be  subject  to the controlled inspection requirements of section
27-132 of this code, except that it  shall  not  be  required  that  the
architect or engineer be in the employ of the owner.

Section 27-344

Section 27-344

  §  27-344  Shafts. The requirements of this section shall apply to all
shafts, except that floor openings accommodating a slide pole in a  fire
house  and openings other than for ventilation, chimneys or gas vents in
buildings three stories or less in height classified in occupancy  group
J-3  shall  be  exempt  from  these  requirements,  and  except  as more
restrictive requirements may be specified for chimneys and gas vents  in
subchapter  fifteen  of  this chapter, stairway enclosures in subchapter
six, duct enclosures in subchapter thirteen,  elevator,  escalator,  and
dumbwaiter enclosures in subchapter eighteen of this chapter, and except
as permitted in reference standard RS 5-18.
  (a)  Construction.  Shafts  shall be enclosed with materials having at
least fire-resistance rating required by table 3-4. A shaft that  serves
the  topmost  story of a building shall extend through the roof at least
thirty-six inches above any combustible  roof  construction.  Where  the
roof construction is of noncombustible materials, the shaft shall extend
through  any  concealed  space  within  the  roof  construction  and may
terminate at the underside of the roof deck. Pipes and ducts penetrating
shaft construction shall comply with the requirements of section  27-343
of this article.
  (b)  Combustible  Contents. Shafts shall be kept free of bookstacks or
other combustible contents except for stair  construction  as  permitted
under  subchapter  six  of  this  chapter,  duct  and  pipe coverings as
permitted under subchapters  thirteen  and  sixteen,  and  elevator  car
enclosures as permitted under subchapter eighteen of this chapter.
  (c)  Openings  in  shafts.  All  shaft openings below the top terminus
shall be provided with opening  protectives  that  comply  with  section
27-329 of this subchapter and table 5-3. In shafts that contain only one
opening below the roof terminus, no opening protective need be provided.
Openings  in  elevator  and dumbwaiter shafts shall comply only with the
requirements of subchapter eighteen of this chapter. Where a  window  is
located  in  a shaft wall that is an exterior wall and is ten stories or
less above grade or three stories or less above  a  roof,  it  shall  be
protected against entrance by a permanently secured grille consisting of
5/8  in.  dia.  bars,  10 in. o. c. vertically, or by a stationary metal
sash window having 1/8 in. thick solid section steel muntins, 8  in.  o.
c.  one way. This protection shall not be required in stair shafts where
there is a stair landing or platform not more than three  feet  directly
below the window sill.
  (d)  Smoke  venting of closed shafts. All closed shafts having an area
exceeding four square feet, other than elevator  or  dumbwaiter  shafts,
shall be provided with a smoke vent having an area of at least three and
one-half percent of the maximum shaft area at any floor, but in no event
less  than  one-half  square  foot.  Elevator and dumbwaiter shaft vents
shall comply with  the  requirements  of  subchapter  eighteen  of  this
chapter.  Smoke vents may be windows, louvers, skylights, vent ducts, or
similar devices. Vent ducts shall be enclosed by construction having the
same fire resistance rating as required for the  shaft  enclosure.  Such
vent  ducts  shall  extend  vertically,  diagonally,  or horizontally as
provided below.
  (1) Through any roof of the building provided the vent opening  is  at
least  ten feet from any window, door, outside stairway, or interior lot
line. This dimension may be reduced to five feet if  the  vent  duct  is
extended up to at at least the level of the top of the window or door. A
vent that is required to extend above a roof shall extend at least eight
inches  above  a  roof assembly constructed of noncombustible materials,
and at least thirty-six inches above  a  roof  assembly  constructed  of
combustible materials that are within a horizontal distance of ten feet.

  (2)  Through  an  exterior wall of the building, provided there are no
openings in the wall within a distance of thirty feet  vertically  above
the  vent opening, and within five feet either side of the vent opening.
When a side of a shaft is an exterior wall or a wall of a roof bulkhead,
the  required  vent  may  be  a  louver  or window. Any window or louver
located in  a  shaft  wall  above  a  roof  constructed  of  combustible
materials shall have its sill at least thirty-six inches above the roof.
  (e)  Terminus  of  shaft  vents.  Of  the total required vent area for
shafts, at least one-third shall  be  clear  opening  to  the  outdoors,
either  in  the  form  of  fixed  louvers,  ridge  vents,  or  hooded or
goosenecked openings.  In lieu thereof, skylights or trap doors  may  be
used  if  constructed and arranged to open automatically by fusible link
or other mechanical device  when  subjected  to  a  temperature  of  one
hundred  sixty degrees Fahrenheit or to a rapid rise in temperature at a
rate of fifteen to twenty degrees Fahrenheit per minute.  The  remaining
portion  of  the  required  vent area may be a window or skylight glazed
with plain glass not more than one-eighth inch  thick  or  slow  burning
plastic.
  (f)   Machine   rooms.   Any  compartment  containing  machinery  that
communicates with a shaft enclosure shall comply with  all  requirements
for  shafts.  The required louver or glazing shall not be located in any
door leading into such compartment.

Section 27-345

Section 27-345

  §  27-345  Firestopping.  Concealed  spaces  within partitions, walls,
floors, roofs, stairs, furring, pipe  spaces,  column  enclosures,  etc.
that  would permit passage of flame, smoke, fumes, or hot gases from one
floor to another floor or roof space, or  from  one  concealed  area  to
another,  shall  be  firestopped  to form an effective draft barrier, or
shall be filled with noncombustible  material  in  accordance  with  the
requirements of this section. Firestopping shall not be required where a
concealed  space  is  sprinklered  in  accordance  with the construction
provisions of subchapter seventeen of this chapter, or is constructed as
a shaft.
  (a) Firestopping materials. In  buildings  of  construction  group  I,
firestopping  or  fill  shall  be of noncombustible material that can be
shaped, fitted, and permanently secured in  position.  In  buildings  of
construction  group  II,  firestopping  may  be  of combustible material
consisting of wood not less than two inches nominal thickness with tight
joints, two layers of one inch nominal thickness assembled so that there
are no through joints or of one-half inch  exterior  type  plywood  with
joints  backed, except that noncombustible firestopping shall be used in
concealed spaces of fire divisions and where in contact with fireplaces,
flues, and chimneys. Noncombustible firestopping may be masonry  set  in
mortar,   concrete,  three-quarter  inch  thick  mortar  or  plaster  on
noncombustible lath, plasterboard at  least  three-eighths  of  an  inch
thick,  fire-rated  wallboard  at  least  five-eighths of an inch thick,
sheet metal at least No. 14  U.S.  std.  gage  thick,  solid  web  metal
structural  members,  asbestos-cement  board  at least one-quarter of an
inch thick, or equivalent rigid noncombustible material. Mineral,  slag,
or  rockwool may be used for firestopping when compacted to a density of
at least three and one-half pounds per cubic foot into a confined  space
of least dimension not more than one-third its second dimension.
  (1)  The  performance  of  through-penetration  fire  stops  shall  be
measured and specified according to reference standard RS 5-19.
  (2) The commissioner may accept reference standard RS 5-19  test  data
results  from  an  independent laboratory acceptable to the commissioner
pursuant to subdivision  (c)  of  section  27-131,  when  such  data  is
submitted by a registered architect or licensed professional engineer to
justify the usage of fire stops or the details of their installation not
specified herein.
  (b)  Hollow  partitions  and  furred spaces. All hollow partitions and
furred out spaces shall be firestopped at each  floor  level.  Firestops
shall be the full thickness of the hollow space or furred out space.
  (c)  Stairs.  Concealed  spaces  within  stair  construction  shall be
firestopped between stringers at the top and bottom of  each  flight  of
stairs so as not to communicate with concealed spaces in the floor, roof
or intermediate landing construction.
  (d)  Ceiling  spaces.  Floor  or  roof  assemblies  required to have a
fire-resistance  rating  shall  have  any   concealed   spaces   therein
firestopped in accordance with section 27-327 of this subchapter.
  (e)  Exterior  cornices.  Exterior  cornices and eaves, constructed of
combustible materials or with combustible framing, shall be  firestopped
at  the ends of fire divisions and party walls, and at maximum intervals
of twenty feet. If not continuous, they shall have closed  ends  and  at
least four inches separation between adjoining sections.
  (f)  Trim  and  finish. Where combustible trim and finish is permitted
all hollow spaces shall be firestopped at ten foot intervals or shall be
solidly filled with noncombustible materials.
  (g) Duct and pipe spaces. Ducts and  pipes  enclosed  in  construction
that  does not meet the requirements of this code for shaft construction
shall be firestopped at every floor level.

  (h) Inspection of  firestopping.  The  installation  of  all  required
firestopping  shall be subject to the controlled inspection requirements
of section 27-132 of article seven of subchapter one  of  this  chapter,
except that the architect or engineer need not be retained by the owner.
Firestopping shall not be concealed from view until inspected.

Section 27-346

Section 27-346

  § 27-346 Partitions and furring. In buildings of construction group I,
partitions and furring shall be constructed of noncombustible materials,
except  that  nonbearing  partitions  that  are  not  required to have a
fire-resistance rating, and furring may be constructed of fire retardant
treated wood as provided in subdivision (d) of section 27-328 of article
three of this subchapter, and except that such partitions  and  furring,
may  be  constructed  of  combustible  materials in spaces classified in
occupancy group E, J-2, or J-3, provided the  following  conditions  are
met:
  (a)  the  space  containing the combustible partitions does not exceed
five thousand square feet in  area  within  a  noncombustible  enclosure
having a fire-resistance rating of at least one hour.
  (b) the space is in a single tenancy.
  (c) glass or slow burning plastic is used for glazing.

Section 27-347

Section 27-347

  §  27-347  Folding partitions. Folding partitions shall not be used as
partitions that are required by this  code  to  have  a  fire-resistance
rating.
  (a)  Construction  group  I.  In  buildings  of  construction group I,
folding partitions may be used if they are constructed of noncombustible
materials, or of fire retardant treated  wood,  or  are  constructed  of
non-combustible  frame  covered  with fabric that has a class A interior
finish rating. Where partitions of combustible materials  are  permitted
by  section  27-346  of  this  article,  folding  partitions may also be
constructed  of  combustible  materials.  Where  doors  constructed   of
materials  having  a  class  C  interior  finish rating are permitted by
section 27-348 of this article, folding  doors  may  be  constructed  of
combustible materials.
  (b)  Construction  group  II.  In  buildings of construction group II,
folding partitions may be constructed of combustible materials, surfaced
with interior finish  materials  meeting  the  requirements  of  section
27-348 of this article.

Section 27-348

Section 27-348

  §  27-348  Interior  finish.  (a) Definition. For the purposes of this
section, interior finish  shall  mean  those  materials  that  form  the
exposed  interior surfaces of a building and that are part of or affixed
to walls, fixed or folding partitions, ceilings, and other  construction
elements.
  (b)  Classification.  Interior finish materials shall be classified in
accordance with the surface flame-spread rating obtained  as  prescribed
in the provisions of reference standard RS 5-5. Where an interior finish
material is comprised of two or more materials laminated, glued, nailed,
or otherwise secured together, the test rating for flame spread shall be
based  upon  the composite of the materials in the form in which it will
be used in construction. Interior finish materials shall be  grouped  in
the  following  classes,  in  accordance with their surface flame spread
characteristics:

          Interior Finish Class         Flame-Spread Rating
                    A                         0 to  25
                    B                        26 to  75
                    C                        76 to 225
                    D                        Over  225

  (c)  Requirements.  Interior  finishes  and  exposed   structural   or
construction materials shall have a flame-spread rating not greater than
that designated by the class prescribed for the various occupancy groups
in  which  they  are  used,  as listed in table 5-4. Exceptions to these
requirements are:
  (1) Finish flooring and floor coverings,  which  are  subject  to  the
requrements of section 27-351.
  (2)  Wall  coverings  and  coatings  that are less than 0.036 in total
thickness, when applied directly to a noncombustible, or  fire-retardant
treated wood, substrate.
  (3) Exposed structural members and planking in buildings of class II-A
construction,  which may be left exposed in any room or space, except in
exits.
  (4) Twenty per cent (20%) of the aggregate wall and  ceiling  area  of
any  room, space, or corridor required to have a class A or B rating may
be finished with materials having a class C rating. This allowance shall
include  the  area  of  doors,  folding  partitions,  windows,  glazing,
skylights,   luminous   ceilings,  trim,  bases,  chair  rails,  panels,
moldings, etc. This exception shall not operate as  a  waiver  of  other
requirements of this code relating to opening protectives.
  (5)  When  a sprinkler system is provided in any room or space, and is
installed in compliance with the construction provisions  of  subchapter
seventeen  of  this  chapter, interior finish materials may be one class
higher in flame-spread rating than required by tables 5-4.
  (d) Smoke density. No material shall be used for  interior  finish  in
the  following  locations  if  the  material  develops  smoke in greater
density than the rating shown, based upon a test conducted in accordance
with the provisions of reference standard RS  5-5.  Materials  used  for
interior finish that cover not more than twenty percent of the aggregate
wall  and  ceiling  area of any room, space, or corridor shall be exempt
from the above requirements.

     Location or Occupancy                   Smoke Developed Rating

     Exits, corridors ...............................   25
     Occupancy groups H-1 and H-2 ...................   50
     Rooms in which the net floor area

      per occupant is ten square feet,
      or less .......................................  100

  (e) Toxicity. No material shall be used in any interior location that,
upon  exposure  to  fire  will  produce  products  of  decomposition  or
combustion that are more toxic in  point  of  concentration  than  those
given  off by wood or paper when decomposing or burning under comparable
conditions.
  (f) Attachment of interior finish.
  (1) To be credited with the same  rating,  interior  finish  materials
that  were  applied  to  a substrate when tested shall be applied at the
building to an equivalent substrate.
  (2) Interior finish materials shall be cemented or  otherwise  secured
in  place in the same manner and with materials equivalent to those used
in flame-spread tests conducted in accordance with  subdivision  (b)  of
this section for the applicable classification.
  (3)  Where walls, ceilings, partitions, or other construction elements
are required to have a fire-resistance rating  or  are  required  to  be
constructed  of  noncombustible  materials,  and  the interior finish is
secured to studs or furring, the surface of the interior  finish  facing
the concealed space shall either have a class A rating, shall be applied
to  a  substrate  that has a class A rating, or shall have the concealed
space completely filled with noncombustible material.

                 Table 5-4  Interior Finish Requirements
                                  Class
========================================================================
Occupancy                                       Rooms More  Rooms Less
  Group        Occupancy    Exits                Than 1500   Than 1500
Classification  Group       and                 Sq. Ft. in  Sq. Ft. in
of the Space   Designation  Shafts Corridors{b}  Area{a}     Area{a,g}
________________________________________________________________________
High Hazard      A             A        A             B            B
Storage          B-1           A        A             B            C
Storage          B-2           A        B             B{c}         C
Mercantile       C             A        B             B{c}         C
Industrial       D-1           A        A             B            C
Industrial       D-2           A        B             B{c}         C
Business         E             A        B             C            C
Assembly         F-1a          A        B             B            B{d}
Assembly         F-1b          A        B             B{c}         B{c,d}
Assembly         F-2           A        B             B{c}         B{c,d}
Assembly         F-3           A        B             B{c}         B{c,d}
Assembly         F-4           A        B             B{c}         C
Educational      G             A        A             B            C
Institutional    H-1,H-2       A        A             B            B{d}
Residential      J-1,J-2       A        A             B            B{f}
Residential      J-3           B        D{e}          D{e}         D{e}
========================================================================

                           NOTES FOR TABLE 5-4
  a. In determining the applicable requirements for  rooms  or  enclosed
spaces, the occupancy group classification of the room or enclosed space
shall  be  the  governing  factor,  regardless  of  the  occupancy group
classification of the building. For the purposes of this table, the area
of  a  room  shall  be  that  floor  area  contained  within   enclosing
construction   in  which  interior  doors  or  other  interior  openings
represent not more than  ten  percent  of  the  area  of  the  enclosing

construction.   Interior  doors  or  windows  that  are  constructed  of
noncombustible materials and that are self-closing or automatic  may  be
ignored  in  computing  door  or opening area. Rooms or spaces that have
unprotected  openings  constituting more than ten percent of the area of
enclosing construction shall not  be  considered  as  a  room.  Interior
finish  requirements  for  rooms  are based upon rooms being enclosed in
ceiling high partitions. Partitions,  to  be  considered  ceiling  high,
shall  extend up to the floor or roof construction above or to a ceiling
having at least a three-quarter hour fire-resistance rating.  Partitions
that  do  not  comply  with  this requirement shall not be considered as
enclosing the spaces, and the rooms or  spaces  on  both  sides  thereof
shall be considered as one.
  b.  Rooms  or spaces through which it is necessary for occupants of an
adjacent room to pass in order to reach the only  exit  shall,  for  the
purposes  of  this  table,  be  considered  as  corridors. Where used in
corridors, class B finish material shall not extend more than fifty feet
between separations of class A finish material that  are  at  least  two
feet wide.
  c.  On  the  street floor of one-story buildings in construction group
II, ceilings, beams, trusses, etc. that  are  twenty  feet  or  more  in
height from the floor to their lowest part, may have a class C finish.
  d.  Class  C  interior  finish  may  be  used in offices, or groups of
offices, whose use is accessory to an occupancy, provided  such  offices
are  separated from the occupancy, by construction having at least a two
hour fire-resistance rating.
  e. Class C interior finish may be used in  the  residential  rooms  of
one-  and two-story motels when there is a direct exit from each room to
the exterior.
  f. Interior finish when used in the following spaces shall be at least
class B:
  (1) Kitchens, cooking spaces, and pantries in buildings classified  in
occupancy groups other than J-2 and J-3.
  (2) Repair and maintenance rooms.
  (3) Boiler rooms and incinerator combustion rooms.

Section 27-349

Section 27-349

  §  27-349  Coatings.  Coatings  applied in the field by brush or spray
shall not be used as flame-spread retardants except on existing surfaces
of buildings existing on December sixth, nineteen  hundred  sixty-eight,
and  then  only with the express permission of, and in a manner directed
by, the commissioner.

Section 27-350

Section 27-350

  § 27-350 Ceiling construction. Ceilings that are to be suspended below
floor or roof construction by means of a framing system shall consist of
supporting  hangers,  carrying  channels and a supporting grid complying
with reference standard RS 5-16 or shall  have  supporting  hangers  and
carrying  channels and a supporting grid that can be demonstrated to the
satisfaction of the commissioner to be of strength adequate  to  support
the  ceiling  material.  The  hangers  and  supporting  grid shall be of
noncombustible materials. In buildings of construction group  II,  every
other  hanger supported from wood members shall be attached by a through
bolt or clinched through nail.  Where,  in  table  3-4,  floor  or  roof
construction  is  required  to  have a fire-resistance rating, a ceiling
having  no  fire-resistance  rating   may   be   suspended   below   the
fire-resistance construction.
  (a)  Luminous  ceilings.  For  the purpose of this section, a luminous
ceiling shall  be  defined  as  a  ceiling  consisting  of  translucent,
louvered,   egg-crated,   mesh,   or  similar  light-diffusing  material
suspended from the ceiling or structural framework. A suspended  ceiling
containing  less  than  twenty  square  feet  of  translucent, louvered,
egg-crated, mesh, or similar material in any one hundred square feet  of
ceiling  area  shall  not be considered a luminous ceiling, and shall be
constructed and installed in accordance  with  department  of  buildings
requirements for lighting fixtures. Luminous ceilings shall, in addition
to  the requirements of this section, conform to all of the requirements
of section 27-348 of this article for interior finish.
  (1) LUMINOUS CEILINGS OF NONCOMBUSTIBLE  MATERIAL.  Luminous  ceilings
constructed  of glass and/or metal or other noncombustible materials may
be used in any location.
  a. Glass used in  luminous  ceilings,  unless  it  is  wire  glass  or
heat-resistant  glass  as specified below, shall not weigh more than two
psf, nor shall any pane be larger than eight square  feet  in  area.  If
glass  used  in luminous ceilings is wire glass, or is heat resistant by
reason of having a maximum coefficient of expansion of 36 x 10-7 in. per
in. per degree C, the glass may be of any weight and any  size,  limited
only by considerations of structural safety.
  b.   Luminous  ceilings  installed  below  sprinkler  heads  shall  be
constructed of a type of noncombustible  louver,  mesh,  or  other  open
material that will not impede the flow of water from the sprinkler heads
over  the  intended  area  of  coverage.  The  luminous ceiling shall be
constructed so as to provide access to all heads and valves.
  (2) LUMINOUS  CEILINGS  OF  COMBUSTIBLE  MATERIAL.  Luminous  ceilings
constructed of combustible materials shall not be installed in:
  a. Any exit or corridor.
  b.  Any  room  classified  in  occupancy  group H, or any room leading
therefrom as defined in note b of table 5-4.
  c. Any room in which the net floor area per occupant is twenty  square
feet  or  less,  or  any  room leading therefrom as defined in note b of
table 5-4.
  d. Luminous ceilings constructed elsewhere than in the  spaces  listed
in  subparagraphs  a, b, and c above shall be exempt from the provisions
of section 27-348 of this article, provided that:
  1. The panels of such ceilings are of slow-burning plastic;
  2. The panels  are  installed  above  or  below  sprinklers  that  are
constructed in accordance with the provisions of subchapter seventeen of
this chapter;
  3.  No individual plastic panel exceeds ten feet in maximum dimension.
Where installed below sprinkler heads, the plastic shall be  a  material
that  will  fall  from  its  mounting  at a temperature at least fifteen
degrees lower than the temperature at  which  the  sprinkler  heads  are

designed  to  operate or are constructed of open material which will not
impede the flow of water from the  sprinkler  heads.  Luminous  ceilings
shall  be  installed  so  as  to  provide  ready access to all heads and
valves.
  (b)  Suspension  of new ceilings below existing suspended ceilings. In
construction group I a new ceiling may be suspended below not more  than
one  existing suspended ceiling and shall be supported directly from the
ceiling carrying channels adjacent to the hangers. In construction group
II, an existing suspended ceiling shall be completely removed  before  a
new ceiling may be suspended.

Section 27-351

Section 27-351

  §  27-351  Finish  flooring  and  floor coverings. Finish flooring and
floor coverings shall comply with the following:  (a)  In  buildings  or
spaces  classified in occupancy group A and in all exits except those in
buildings of construction  group  II-E,  finish  flooring  shall  be  of
noncombustible  material  and except as otherwise provided for stairs in
subdivision (h) of section 27-375 of article five of subchapter  six  of
this chapter.
  (b) Flooring in buildings or spaces of construction group I. Except as
provided  in subdivision (a) of this section combustible finish flooring
may be used in buildings or spaces of construction group I when cemented
directly to the top surface of  noncombustible  floor  construction,  or
attached  to  combustible  or  noncombustible sleepers. When attached to
sleepers, the space between the noncombustible  floor  construction  and
the  bottom  of  flooring  shall  be  solidly filled with noncombustible
material to within one-quarter  inch  of  the  flooring,  or  the  space
between  the sleepers under the flooring shall be firestopped into areas
of not more than twenty square feet, and provided further that  no  open
spaces  shall  extend  under  or  through fire divisions or through fire
separations. Combustible insulating or sound absorbing boards  not  more
than  one-half  inch  thick and having a flame-spread rating not greater
than class C may be used when attached directly to noncombustible  floor
construction and covered with finish flooring.
  (c)  Flooring  in buildings or spaces of construction group II. Except
as provided in subdivision (a)  of  this  section,  finish  flooring  in
buildings  or  spaces  of  construction  group  II may be of combustible
material.
  (d) Floor coverings.
  (1) Exits. Where exits are required under any provision of this  code,
carpets  and  carpet  assemblies  shall  not be installed in such exits,
except that wool  carpeting  may  be  installed  in  lobby  areas,  exit
passageways and convenience stairs.
  (2)  Flammability  requirements.  The requirements of this subdivision
shall apply to carpets and carpet assemblies only when used as  a  floor
covering  (for  requirements pertaining to carpets and carpet assemblies
used as interior finishes, see section  27-348  of  this  article).  For
purposes  of  this  subdivision,  carpeting assemblies shall include the
carpet, its underlay, and adhesives which when  tested  as  a  composite
shall be representative of the proposed installation.
  a.  Pill  test.  All  carpets and underlayments shall pass a methanine
pill test in accordance with the requirements of reference  standard  RS
5-20.
  b.  Critical radiant flux test. Carpets and carpet assemblies shall be
tested by the method for critical radiant flux in  accordance  with  the
requirements of reference standard RS 5-20. The time frame for such test
shall be at least a fifteen minute exposure.
  1.   Carpets  and  carpet  assemblies  representative  of  the  actual
installation on floors of  corridors,  shall  have  a  minimum  critical
radiant flux of 0.5 watts per square centimeter (W/cm{2}).
  2.   Carpets  and  carpet  assemblies  representative  of  the  actual
installation on floors of general areas shall have  a  minimum  critical
radiant flux of 0.4 W/cm{2}.
  c.   Smoke   developed   ratings.   Carpets   and   carpet  assemblies
representative of the actual installation  on  floors  of  corridors  or
general  areas shall be tested for smoke developed ratings in accordance
with the requirements of reference standard RS 5-20. The smoke developed
ratings in either the flaming or no-flaming mode shall not exceed  three
hundred within the first four minutes of the test.

  d.  The manufacturer of the carpets and carpet assemblies shall submit
a  certificate  from  an  independent  laboratory  acceptable   to   the
commissioner  pursuant to section 27-131, showing the complete test data
results, prior to final acceptance. The certification shall  state  that
the  material  is  treated  for  fire  resistance and shall indicate the
service life of the treatment or that the material  is  inherently  fire
resistant  by  virtue  of  its  construction, chemical properties and/or
composition. Materials which are not inherently fire  resistant  may  be
used only when the certified fire resistant service life exceeds that of
the  planned  service  life  of  the  carpets and carpet assemblies with
consideration being given to cleaning, traffic, and other conditions  of
use which may affect the treatment.
  (3) Volatile organic compounds emissions in carpet and carpet cushion.
On  and  after  July  1,  2013  carpet  and carpet cushion as defined in
section 17-1401 of the administrative code shall comply with the  limits
on  volatile organic compound emissions set forth in chapter 14 of title
17 of such code.

Section 27-353

Section 27-353

  §  27-353  Smoke  and  heat  venting.  (a)  Where  the floor area of a
one-story building classified in occupancy  group  A,  B-1,  or  D-1  is
greater  in  depth  than  one  hundred  feet from a frontage space, that
portion beyond one hundred feet shall be provided with  roof  vents  and
smoke  curtains complying with the requirements of reference standard RS
5-11. Where the effective area of vents are glazed with plain  glass  or
plastic not thicker than one-eighth inch, they need not be provided with
automatic opening devices.
  (b)  Buildings  classified  in  occupancy group E, one hundred feet or
more in height, having air-conditioning  and/or  mechanical  ventilation
systems  that  serve  more  than  the  floor  on  which the equipment is
located, shall be provided with at least one smoke  shaft  by  means  of
which  smoke  and  heat  shall be mechanically vented to the outdoors as
provided in reference standard RS 5-17. Buildings that  are  sprinklered
throughout shall be exempt from the smoke shaft requirements.
  (c)  Existing  office  buildings,  one hundred feet or more in height,
having air-conditioning and/or mechanical ventilation systems that serve
more than the floor on which the equipment is located, shall be provided
with at least one smoke shaft by means of which smoke and heat shall  be
mechanically vented to the outdoors as provided in reference standard RS
5-17,  or  in  lieu of such smoke shaft or shafts, all interior enclosed
stairs other than a fire tower or access stairs may be provided  with  a
system of pressurization for fire emergency use.
  Such  pressurization shall be provided by means of a system or systems
as provided in reference standard RS 5-18. Such buildings  shall  comply
with  the  smoke  and  heat  venting  requirements  herein  on or before
September  thirteenth,  nineteeen  hundred  eighty-two.  Complete  plans
showing  such compliance shall be filed with, and a permit secured from,
the commissioner on or before  September  thirteenth,  nineteen  hundred
eighty.
  Existing  buildings  that  are  sprinklered throughout shall be exempt
from the smoke shaft and stair pressurization requirements.
  An existing building which is to be sprinklered  throughout  shall  be
exempt  from the smoke shaft and stair pressurization requirements under
the following conditions:
  (1)  the  installation  proceeds  in  conformance  with   a   schedule
acceptable   to   the  commissioner,  setting  forth  the  sequence  and
corresponding time for installation in  the  various  locations.  On  or
before September thirteenth, nineteen hundred eighty such a schedule, as
well  as  complete plans of the installation, shall be filed with, and a
permit secured from, the commissioner for the phase of the  work  to  be
done as required by paragraph two of this subdivision.
  (2)  at  least  one-third  of  the  total  floor area of the building,
including but not limited to the entrance lobby, corridors and  elevator
landing areas, is sprinklered on or before December thirteenth, nineteen
hundred eighty-one.
  (3)  at  least  two-thirds  of the total floor area of the building is
sprinklered  on  or  before  December   thirteenth,   nineteen   hundred
eighty-two.
  (4)  the  building  is  sprinklered  throughout  on or before December
thirteenth, nineteen hundred eighty-three.
  Where compliance with the time requirements of this subdivision  would
cause  undue  hardship,  the commissioner, with the approval of the fire
commissioner, may extend the time for  compliance,  in  accordance  with
rules  and  regulations to be promulgated. Before such application for a
time extension shall be considered all required applications  and  plans
must  be  filed  and  approved, permits obtained and a good faith effort
towards completion of the work shall have been made.

Section 27-353.1

Section 27-353.1

  §   27-353.1  Smoke  protection  for  elevators  and  escalators.  (a)
Elevators.  In existing buildings classified in occupancy group J-1,  at
every  floor  above  the  main  entrance floor, all passenger elevantors
shall open only into elevator vestibules, except for:
  (1)  Such  existing  buildings  which  contain  spaces  classified  in
occupancy group C or F and have an automatic sprinkler system protecting
all  spaces  (except  boiler  rooms)  not in occupancy group J-1 and all
exits and corridors serving such spaces located on or below  the  lowest
floor containing sleeping rooms as well as all storage closets no matter
where located, except that storage closets less than seventy-five square
feet  may,  in  the  alternative, be provided with smoke detectors which
shall be of the  central  supervisory  type  connected  to  an  approved
central station; or
  (2) Such existing buildings which contain no spaces in occupancy group
C or F, and have either:
  a.  An  automatic  sprinkler  system  protecting  all public areas and
storage closets; or
  b. An automatic sprinkler system protecting  all  sleeping  rooms  and
storage closets.
  c.  Notwithstanding  subparagraphs  a and b of this paragraph, storage
closets less than seventy-five square feet may be  provided  with  smoke
detectors  of  the  central  supervisory  type  connected to an approved
central station.
  d. Notwithstanding any other provision of this  code,  the  sprinklers
serving  the  storage  closets  may be connected with the domestic water
supply.
  (b) Escalators. In buildings  and  existing  buildings  classified  in
occupancy group J-1, fire protection for escalators shall be provided by
any one of the following methods:
  (1)  Enclosure  in  accordance  with  sections  27-375  and  27-378 if
escalator is used as an exit; or
  (2) Automatic rolling shutters in accordance with  reference  standard
RS 18-1; or
  (3) Kiosks in accordance with reference standard RS 18-1; or
  (4)  Where  the  building  section  is fully protected by a supervised
automatic sprinkler system and the escalator sprinklers  are  spaced  to
protect  exposed  sides  of the escalator opening, a noncombustible heat
apron constructed to bank heat around the sprinkler  heads  adjacent  to
the  opening where the bottom edge of the draft curtain is not less than
twelve inches below the bottoms of sprinkler heads  when  heads  are  in
operation,  and  in  no  event  less  than  twenty-four inches below the
ceiling; or
  (5) Spray nozzles in accordance with reference standard RS 18-1.
  (c) The requirements of this subdivision shall be complied with on  or
before April first, nineteen hundred eighty-seven.

Section 27-353.2

Section 27-353.2

  §  27-353.2  Smoke  protection  for elevators in E occupancies. For an
elevator in a high rise building where such elevator serves four or more
stories that contain space  classified  in  occupancy  Group  E  (office
space),  inclusive of any lobby or entry level, such elevator shall meet
the following requirements at every level served by  such  elevator  (i)
for  such  buildings erected pursuant to new building applications filed
on or after the effective date of this section, or  (ii)  where  two  or
more new elevator shafts are installed in such buildings in existence on
the effective date of this section:
  (a)  Elevator  vestibule  required.  At  every  floor  above  the main
entrance floor where the fire command station is located, all  elevators
shall  open  into an enclosed elevator vestibule. The elevator vestibule
shall be  separated  from  the  building  occupancy  by  smoke  barriers
extending from floor slab to floor slab.
  (b)   Permitted   penetrations.  Penetrations  in  addition  to  those
permitted in section 27-353.3 (smoke barrier)  shall  be  provided  with
smoke  dampers  as  defined in reference standard RS 13-1, except that a
package pass through or communication opening not exceeding  one  square
foot in area need not be provided with smoke dampers.
  (c)  Access  to  exits.  Access  to  an  exit on any floor through the
enclosed elevator vestibule shall be permitted if the occupied areas  on
that floor have access to at least one other required exit that does not
require passing through the elevator vestibule.
  (d)  On  floors  with  a  floor  area of less than twenty-five hundred
square feet, the  commissioner  may  accept  an  alternative  design  or
construction  method that accomplishes the purposes of this section, or,
if the commissioner determines that  compliance  with  this  section  is
impracticable  in  whole  or  in part, the commissioner may authorize an
exemption from the requirements of this section.

Section 27-353.3

Section 27-353.3

  §  27-353.3  Smoke barrier. A smoke barrier may or may not have a fire
resistance rating. Smoke barriers may have openings that  are  protected
by  automatic  closing  devices,  adequate  to inhibit movement of smoke
through  the  opening.  The  smoke  barrier  may   be   constructed   of
heat-strengthened or tempered glazing or the equivalent and protected by
sprinkler  heads  constructed in accordance with subchapter seventeen of
this chapter and installed a maximum of six feet (6'-0")  on  center  on
each  side of the barrier. If the smoke barrier is constructed of glass,
the portions of the smoke barrier located within two feet  of  the  door
opening  and  within  five  feet  of  the  floor shall be constructed of
tempered glass. Glass panels having an area in  excess  of  nine  square
feet  with  the  bottom  edge  less than eighteen inches above the floor
shall likewise be constructed of tempered glass. Portions of glass smoke
barriers shall be marked where required in accordance with the rules  of
the board of standards and appeals.