Article 2 - INSPECTIONS AND TESTS FOR EQUIPMENT USE PERMITS

Section 27-778

Section 27-778

  §  27-778  General  requirements.  No  required ventilating system, no
voluntary air duct system containing smoke detection or fire  protection
devices  that  are  required  by  this  subchapter, and no refrigeration
system shall be placed in  operation,  until  it  has  been  tested  and
inspected  in  accordance  with  the requirements of this subchapter and
until an equipment use permit  has  been  issued  by  the  commissioner,
except as hereinafter provided.

Section 27-779

Section 27-779

  §  27-779  Required  ventilating  systems.  The  following  tests  and
inspection requirements shall be complied with in  order  to  obtain  an
equipment use permit for a required ventilating system.
  (a)  Procedure.  A required ventilating system shall be subject to the
requirements for controlled inspection as provided in article  eight  of
subchapter one of this chapter except that it shall not be required that
the  architect  or  engineer  be  in  the  employ  of  the  owner.  Such
requirements shall include (1) a controlled inspection  to  verify  that
the  installation  and operation of the completed system comply with the
requirements of this subchapter, comprising tests to ascertain that  the
amount  of  air being supplied to and exhausted from each space conforms
with the requirements of this code, and tests that  all  required  smoke
detection  and fire protection devices are functioning properly; and (2)
a controlled inspection comprising tests to verify  that  required  fire
dampers  are  installed  and  functioning  properly  as  provided for in
subdivision (d)  of  section  27-343  of  this  code.  When  a  required
ventilating  system  handles  five  thousand  cfm  or  less, it shall be
subject to controlled inspection  except  that  the  person  making  the
inspection  may be an architect, engineer or a person with at least five
years of experience installing ventilating systems. However, if  such  a
system exhausts any of the following:
  (1) fumes, dusts, vapors or other noxious or injurious substances,
  (2) substances that create a fire hazard,
  then  the  person  making  the  inspection  shall  be  an architect or
engineer.  It shall not be required that the architect or engineer be in
the employ of the owner. The test reports required under the  provisions
of article eight of subchapter one of this chapter shall be filed in the
form prescribed by the commissioner. The form shall include the quantity
of air supplied or exhausted by each outlet.
  (b) Fire extinguishing systems. No equipment use permit for a required
ventilating system containing a required fire extinguishing system shall
be   issued   until   a  signed  statement  has  been  obtained  from  a
representative of the fire commissioner who has witnessed  the  test  of
the  extinguishing  system  and its control devices, certifying the fire
commissioner's acceptance of such a system.
  (c)  Owner's  statement.  A  statement  shall  be   filed   with   the
commissioner  by  the  owner or lessee of the building that the required
ventilating system will be kept in continuous  operation  at  all  times
during the occupancy of the building and, if any smoke or fire detection
devices  or  fire  extinguishing systems have been installed, that he or
she will have such devices and the fan shut-offs actuated by them tested
and inspected by a competent person or agency at one year  intervals  or
less.  The owner or lessee shall also state that he or she will promptly
make any necessary adjustments  and  repairs  to  keep  the  ventilating
system and its safety devices in proper operating condition. A record of
each  inspection  and  test  shall  be maintained on the premises by the
owner or lessee, and records for at least the last two  years  shall  be
made   available  for  inspection  by  the  commissioner  and  the  fire
commissioner.

Section 27-780

Section 27-780

  §  27-780  Voluntary  ventilating  systems or other voluntary air duct
systems.  The  following  test  and  inspection  requirements  shall  be
complied with in order to obtain an equipment use permit for a voluntary
ventilating system or other air duct system when smoke detectors or fire
protection devices are required.
  (a)  Procedure.  A voluntary ventilating system or other voluntary air
duct system shall be subject to test and inspection  to  ascertain  that
all   smoke  detection  and  fire  protection  devices  are  functioning
properly, and that the installation conforms with  the  requirements  of
this subchapter.
  (b)  Fire  extinguishing  systems.  No  equipment  use  permit  for  a
voluntary ventilating system containing a  required  fire  extinguishing
system shall be issued until a signed statement has been obtained from a
representative  of  the  fire commissioner who has witnessed the test of
the extinguishing system and its control devices,  certifying  the  fire
commissioner's acceptance of such system.
  (c)   Owner's   statement.   A  statement  shall  be  filed  with  the
commissioner by the owner or lessee of the building that he or she  will
have  such  devices  and  the  fan shut-offs actuated by them tested and
inspected by a competent person or agency at one year intervals or less.
The owner or lessee shall also state that he or she will  promptly  make
any   necessary  adjustments  and  repairs  to  keep  these  devices  in
operation. A record of each inspection and test shall be  maintained  on
the  premises  by  the owner or lessee, and the records for at least the
last two years of operation shall be made available  for  inspection  by
the commissioner and the fire commissioner.

Section 27-781

Section 27-781

  §  27-781  Refrigerating  systems.  The  following test and inspection
requirements shall be complied with in order to obtain an equipment  use
permit for a refrigerating system, except as hereinafter provided.
  (a) Procedure. A refrigeration system shall be designated for test and
inspection  under the requirements for controlled inspection as provided
in article eight of subchapter one of this chapter, except that it shall
not be required that the architect or engineer be in the employ  of  the
owner.  Test information and all other information required by reference
standard RS 13-6 shall be posted, and the inspection shall  be  made  of
the  completed  system to verify that the installation complies with the
requirements of this subchapter.
  (b) Temporary permits. A  temporary  equipment  use  permit  shall  be
required  for a nonoperating system in which a charge is maintained. See
subchapter one  of  this  chapter  for  provisions  governing  temporary
permits.
  (c)  Exception.  No  equipment  use  permit or temporary equipment use
permit shall be required for any refrigerating system exempted under the
provisions of section 27-189 of article eighteen of  subchapter  one  of
this  chapter; for any system using a group A2, B1 or B2 refrigerant and
having a prime mover of one horsepower or less; or for any system  using
water or air as a refrigerant.