Article 5 - GAS VENT SYSTEMS

Section 27-879

Section 27-879

  §  27-879 General. (a) Vent systems of gas-fired equipment shall be so
designed and constructed  as  to  completely  exhaust  the  products  of
combustion to the outdoor air.
  (b)  When  required  by the commissioner, gas vents shall be tested to
determine fire safety and the adequate exhausting  of  the  products  of
combustion.
  (c)  Vents  shall  be  installed  if  required, in accordance with the
applicable standards for gas-fired equipment. See reference standard  RS
15-2 for a tabulation of these standards.

Section 27-880

Section 27-880

  §  27-880  Equipment not required to be vented. (a) Ranges for which a
vent is not required by reference standard RS 15-2.
  (b) Built-in domestic cooking units for which a vent is  not  required
by reference standard RS 15-2.
  (c) Hot plates and laundry stoves.
  (d) Type 1 clothes dryers.
  (*e)  Water  heaters  with  inputs not over five thousand Btu/hr. (See
note below.)
  (*f) Automatically controlled instantaneous water heaters that  supply
water  to  a  single  faucet which is attached to and made a part of the
equipment.
  (*g) A single booster type (automatic instantaneous) water heater when
designed and used solely for the  sanitizing  rinse  requirements  of  a
national  sanitation  foundation  class  one,  two  or three dishwashing
machine, provided that the input is limited to  fifty  thousand  Btu/hr.
the  storage  capacity is limited to twelve and one-half gallons and the
heater is installed in a commercial kitchen having a mechanical  exhaust
system.
  (*h) Refrigerators.
  (*i) Counter equipment.
  (*j)  Room  heaters  for  which  a  vent  is not required by reference
standard RS 15.0.
  (*k) Other equipment for which a vent is not required  and  which  are
not provided with flue collars.
  (*l) Specialized equipment of limited input such as laboratory burners
or gas lights.
  Note:  When  any, or all, of the equipment marked with an asterisk (*)
is installed so that the aggregate input rating exceeds  thirty  Btu/hr.
per  cubic  foot  of room or space in which it is installed, one or more
pieces of the equipment shall be provided with a venting system or other
equivalent means for removing the vent gases to the outdoor air so  that
the  aggregate input rating of the remaining unvented equipment does not
exceed the thirty Btu/hr. per cubic foot figure. When the room or  space
in  which  such  equipment is installed is directly connected to another
room or space by a doorway, archway,  or  other  opening  of  comparable
size,  which cannot be closed, the volume of such adjacent room or space
may be included in the calculations.

Section 27-881

Section 27-881

  §  27-881 Draft hoods. (a) All vented equipment, except dual oven type
combination ranges, equipment with sealed combustion chambers, and units
designed for power burners or forced venting, shall be installed with  a
draft hood or with a barometric damper.
  (b)  The  draft  hood  supplied  with,  or  forming  a part of, vented
equipment shall be installed in accordance with the requirements of  the
applicable  standard in reference standard 15-2. The draft hood shall be
located in the same room as the combustion air opening of the equipment.

Section 27-882

Section 27-882

  §  27-882  Chimneys  for  venting gas-fired equipment. When venting of
gas-fired equipment is  provided  for  by  the  use  of  chimneys,  such
chimneys  shall  be  constructed  in accordance with the requirements of
this subchapter.

Section 27-883

Section 27-883

  § 27-883 Gas equipment connected to chimneys. Automatically controlled
gas-fired  equipment  connected  to a chimney that also serves equipment
for the combustion of solid or liquid fuel shall  be  equipped  with  an
automatic  pilot.  A  gas-fired  equipment  vent connector and a chimney
connector from equipment burning  another  fuel,  located  on  the  same
floor, may be connected into the same chimney through separate openings,
or  may  be  connected  through a single opening if joined by a suitable
fitting located as close as practicable to the chimney. If two  or  more
openings  are  provided  into  one  chimney,  they shall be at different
levels.

Section 27-884

Section 27-884

  §  27-884  Types  of gas vents. (a) Type B gas vents. Type B gas vents
conforming to the requirements of section 27-855 of article one of  this
subchapter may be used to vent gas-fired equipment. Type B gas vents may
be  used for single-story or multi-story installations when they conform
to the requirements of section 27-855 of article one of this  subchapter
and  the  gas  equipment  used  in  multi-story  installations  shall be
accepted for such use. Type B gas vents  shall  be  used  to  vent  only
listed  gas  appliances with draft hoods and other gas appliances listed
for use with Type B gas vents. However, Type B gas vents  shall  not  be
used for venting:
  (1) vented wall furnaces listed for use with Type BW gas vents only;
  (2) incinerators;
  (3)  appliances  which may be converted readily to the use of solid or
liquid fuels;
  (4) combination gas-oil burning appliances;
  (5) appliances listed for use with chimneys only.
  (b) Type  B-W  gas  vents.  Type  B-W  gas  vents  conforming  to  the
requirements  of  section 27-855 of article one of this subchapter shall
be used to vent gas-fired vented recessed heaters. Type  B-W  gas  vents
may  be  used  with  single-story or multi-story installations when they
conform to the requirements of section 27-855 of  article  one  of  this
subchapter and the gas equipment used in multi-story installations shall
be accepted for such use. Type BW vents shall be used with listed vented
gas  wall furnaces having a capacity not greater than that of the listed
Type BW gas vent.
  (c) Single-wall metal vents. Single-wall metal vents may  be  used  to
vent  gas-fired  equipment  and shall be constructed of not less than 16
oz.  sheet copper, or No. 20 galvanized sheet gauge steel, or  of  other
equivalent   noncombustible  corrosion-resistive  material.  Single-wall
metal gas vents may pass through  the  roof  or  exterior  wall  to  the
outdoor  air,  but  shall  not pass through any attic or other concealed
space nor through any intermediate floor construction.
  (d) Connection to a common vent. Connection of gas-fired equipment  on
more  than  one  floor level to a common vent, except as provided for in
subdivisions (a) and (b) of this section, shall be prohibited.
  (e) Ventilating hoods. Ventilating hoods and exhaust  systems  may  be
used to vent kitchen, laboratory, and commerical equipment.

Section 27-885

Section 27-885

  §  27-885  Labeling  gas  vents.  Gas  vents  for  use  with gas-fired
equipment, and which are not designed  for  use  with  solid  or  liquid
fuel-fired  equipment,  shall be plainly and permanently identified by a
metal label etched or embossed to read: "This gas vent is for  equipment
which  burns  gas only. Do not connect to incinerator or solid or liquid
fuel-burning equipment." This label shall be attached to the vent  at  a
point  near  where  the  gas  vent  system  enters the wall, ceiling, or
chimney.

Section 27-886

Section 27-886

  §  27-886  Special  venting  arrangements.  (a)  Equipment with sealed
combustion chambers. The vent requirements contained in this  subchapter
do  not  apply  to equipment having sealed combustion chambers and which
are so constructed and installed that all air for combustion is  derived
from outside the space being heated and all flue gases are discharged by
integral  vent to the outdoors. Such equipment, having integral venting,
shall be installed in accordance with the conditions of  the  applicable
standard governing their use.
  (b)  Gas-vent  exhausters  and chimney exhausters. Gas-vent exhausters
and chimney exhausters may be  used  with  gas  appliances  in  lieu  of
natural  draft  vents.  Where  an  exhauster  is  used  with gas-burning
equipment requiring venting, provisions shall be  made  to  prevent  the
flow  of  gas  to the main burner in the event of failure of the exhaust
system. A vent connector serving gas equipment vented by  natural  draft
shall not be connected into the discharge side of a power exhauster.
  (c)  Ventilating  hoods  and  exhaust  systems.  Ventilating hoods and
exhaust  systems  may  be  used  to  vent  gas  equipment  installed  in
commercial  applications. When automatically operated equipment, such as
water heaters,  are  vented  through  natural-draft  ventilating  hoods,
dampers  shall  not  be  installed  in  the ventilating system. When the
ventilating hood or exhaust  system  is  equipped  with  a  power-driven
exhaust  fan, the equipment control system shall be so interlocked as to
permit equipment operation only when the power exhaust is in  operation.
When  used, ventilating hoods shall be built and installed in accordance
with the provisions of subchapter thirteen of this chapter.

Section 27-887

Section 27-887

  §  27-887  Installation  requirements.  (a)  The gas vent connected to
equipment with a single vent shall not be less  than  the  size  of  the
draft hood outlet, and in no case less than two inches in diameter.
  (b)  When more than one piece of equipment is connected to a gas vent,
the area shall be not less than the area of the largest  vent  connector
plus  fifty  percent  of  the  areas of additional vent connectors or in
accordance with the provisions of reference standard RS 15-1.
  (c) Where two or more vent connectors enter a common vertical gas vent
or chimney, the smaller connector  shall  enter  at  the  highest  level
consistent with available headroom or clearance to combustible material.
Two  or  more items of gas equipment may be vented through a common vent
connector or manifold located  at  the  highest  level  consistent  with
available  headroom  or clearance to combustible material. The manifold,
all junction fittings, and the common vent connector shall be of a  size
adequate for the combined volume of the vent gases.
  (d)  Gas  vents  shall  be  enclosed as provided in subdivision (c) of
section 27-861 of article two of this subchapter.

Section 27-888

Section 27-888

  §  27-888  Gas  vent  height  and locations. Gas vents shall extend at
least two feet above the highest construction, such  as  a  roof  ridge,
parapet  wall,  or penthouse, within ten feet of the vent outlet whether
the construction is on the same building as the chimney  or  on  another
building.  However,  such constructions do not include chimneys or other
vents, or open structural framing. The vent shall be  as  high  as  such
construction  which  is  located beyond ten feet from the vent and up to
and including the distance determined by the following formula:

                             D = 2(sq.rt.)A

where: D = Distance in ft., measured from the center of the vent  outlet
             to the nearest edge of the construction.
       A = Free area, in sq. in., of vent flue space.

  Vents shall be subject to the following additional requirements:
  (a) No gas vent shall terminate less than five feet in vertical height
above the highest connected equipment draft hood outlet or flue collar.
  (b)  No  type  B-W  gas  vent  serving  a vented recessed heater shall
terminate less than twelve feet in vertical height above the  bottom  of
the heater.
  (c)  All  gas vents shall terminate in an approved vent or cowl, which
shall prevent down drafts and prevent rain and debris from entering  the
vent.

Section 27-889

Section 27-889

  §  27-889  Adjoining  gas vents. (a) Responsibility of owner of taller
building. Whenever a building is  erected,  enlarged,  or  increased  in
height  so  that any portion of such building, except chimneys or vents,
extends above the top of a previously constructed gas vent within  fifty
feet,  the  owner  of  the  new  or  altered  building  shall  have  the
responsibility of altering such gas vents that have their outlets within
fifty feet measured horizontally, of  any  part  of  the  newly  erected
building.  Such  alterations shall be at the expense of the owner of the
new or altered  building  and  shall  be  accomplished  by  one  of  the
following means or a combination thereof:
  (1)   Carry  up  such  previously  constructed  vents  from  gas-fired
equipment to the height required in section 27-888 of this article.
  (2) Offset such gas vents to a distance of more than fifty  feet  from
the  new  or  altered  building,  provided  that the new location of the
outlet of the offset gas vent shall comply with the requirements of this
subchapter.
  (b) Protection of draft.  After  the  alteration  of  a  gas  vent  as
described   in  subdivision  (a)  of  this  section,  it  shall  be  the
responsibility of the owner of the new or altered  building  to  provide
any  mechanical  devices  or  equipment necessary to maintain the proper
draft in the equipment.
  (c) Written notification. The owner of the  new  or  altered  building
shall  notify  the  owner  of  the building affected in writing at least
forty-five days before starting the work and request written consent  to
do  such work. Such notice shall be accompanied by a written description
or a plan showing how the proposed alterations are to be made.
  (d) Approval. The  method  of  correction  shall  be  subject  to  the
approval of the commissioner.
  (e)  Refusal of consent. If consent is not granted by the owner of the
previously constructed or altered building to  do  the  alteration  work
required by paragraph one of subdivision (a) of this section, such owner
shall  signify  his or her refusal in writing to the owner of the new or
altered building and to the commissioner, and the owner of  the  new  or
altered building has submitted plans that conform to the requirements of
this   section,   he  or  she  shall  thereupon  be  released  from  any
responsibility for the operation of his or her  equipment  and  for  any
health  hazard  or  nuisance  that  may  occur  as a result of the newly
erected or  modified  building.  Such  responsibilities  shall  then  be
assumed  by  the owner of the previously constructed building. Likewise,
should such owner neglect to grant consent within forty-five  days  from
the date of written request or fail to signify his or her refusal, he or
she shall then assume all responsibilities as prescribed above.
  (f)  Procedures. It shall be the obligation of the owner of the new or
altered building to:
  (1) Schedule this work so as to create a minimum of disturbance to the
occupants of the affected building.
  (2) Provide such essential services as are normally  supplied  by  the
equipment while it is out of service.
  (3)  Where  necessary, support such extended gas vents from his or her
building or carry up such vents within his or her building.
  (4) Provide for the maintenance, repair, and/or  replacement  of  such
alterations.
  (5)  Make  such  alterations  of the same material as the original gas
vent except where the owner of the vent affected shall give his  or  her
consent  to  do  otherwise. All work shall be done in such fashion as to
maintain the architectural esthetics of the existing building.
  (g) Existing violations. Any existing  violations  on  the  previously
constructed  equipment  shall be corrected by the owner of the equipment

before any equipment is added or alterations made at the expense of  the
owner of the new or altered building.
  (h)  The  commissioner  may  grant  a  variance in accordance with the
provisions of section 27-107 of article one of subchapter  one  of  this
chapter.

Section 27-890

Section 27-890

  §  27-890  Support  of  gas  vents. All portions of gas vents shall be
adequately supported for the weight of the material  used  and  for  the
applied loads on the vent.

Section 27-891

Section 27-891

  §  27-891  Prohibited termination. Gas vents extending through outside
walls shall not terminate below eaves or parapets.