Article 6 - GAS VENT CONNECTORS

Section 27-892

Section 27-892

  §  27-892 Construction. Vent connectors for conversion burners without
draft hoods, or other gas-fired equipment without draft hoods, shall  be
constructed  of materials having resistance to corrosion and temperature
not less than that of no. 24 galvanized sheet gauge steel.
  (a) Vent connectors used for gas-fired equipment  having  draft  hoods
and  for  conversion burners having draft hoods, shall be constructed of
type B gas vent material or materials having resistance to corrosion and
temperature not less than that of no. 26 galvanized sheet gauge steel.
  (b) The vent connector between the equipment and the vertical gas vent
or chimney shall have the greatest possible initial rise consistent with
the headroom available in the  equipment  area  and  with  the  required
clearance  to  combustible  material.  The  horizontal  run  of the vent
connector shall be as short as  possible  and  the  equipment  shall  be
located  as  near  the  gas  vent or chimney as practicable. The maximum
length of an uninsulated horizontal run  of  vent  connector  shall  not
exceed seventy-five percent of the height of the gas vent or chimney.
  (c)   No   vent   connector   shall  pass  through  floor  or  ceiling
construction.

Section 27-893

Section 27-893

  § 27-893 Clearances. (a) Minimum clearance. Minimum clearances at vent
connectors  to combustible materials shall not be less than those listed
in table 15-10.
  (b) Reduced clearances. These  clearances  may  be  reduced  when  the
combustible construction is protected as provided in table 15-11.

      Table 15-10 Vent Connector Clearance for Gas-Fired Equipment
========================================================================
                                  Minimum Distances from Combustible
                                           Materials (in.)
                                ----------------------------------------
                                 Type B Gas Vent        Other Than Type
   Equipment                         Material             B Materials
------------------------------------------------------------------------
Boiler                          As required by Std.              6
Warm air furnace                As required by Std.              6
Water heater                    As required by Std.              6
Room heater                     As required by Std.              6
Floor furnace                   As required by Std.              6
Conversion burner (with
  draft hood)                           6                        9
Equipment with draft hoods              6                        9
Equipment without draft
  hoods                            Not Permitted                18
========================================================================

         Table 15-11 Reduced Clearances for Vent Connectors with
                    Specified Forms of Protection (a)
========================================================================
                                   Reduced Clearances Where the Required
Specified Form of Protection (b)     Clearance with No Protection is:
                                  --------------------------------------
                                             18 in.    9 in.    6 in.
------------------------------------------------------------------------
(a) 1/4 in. asbestos millboard
    spaced out 1 in. (c)                       12       6         3
(b) 28 gauge sheet metal on 1/4 in.
    asbestos millboard                         12       4         2
(c) 28 gauge sheet metal spaced out
    1 in. (c)                                   9       4         2
(d) 28 gauge sheet metal on 1/8 in.
    asbestos millboard spaced out 1
    in. (c)                                     9       4         2
(e) 1 1/2 in. asbestos cement
    covering on heating appliance              18       9         6
(f) 1/4 in. asbestos millboard
    on 1 in. mineral fiber bats
    reinforced with wire mesh or
    equivalent                                  6       4         2
(g) 22 gauge sheet metal on 1 in.
    mineral fiber bats reinforced with
    wire or equivalent                          3       2         2
(h) 1/4 in. asbestos cement board
    or 1/4 in. asbestos millboard              18       9         4
(i) 1/4 in. cellular asbestos                  18       9         3
    ====================================================================

Notes:
  a. Except for the protection described in (e) above, all clearances
should  be  measured  from  the  outer  surface  of the appliance to the
combustible material disregarding any intervening protection applied  to
the combustible material.
  b. Applied to the combustible material unless otherwise specified and
covering  all  surfaces  within  the  distance specified as the required
clearance with no protection. Thicknesses are minimum.
  c. Spacers shall be on noncombustible material.

Section 27-894

Section 27-894

  § 27-894 Thimbles. (a) When passing through combustible constructions,
bent  connectors  constructed  of  type  B  gas  vent  material shall be
installed  so  that  the  clearances  required  by  the   standard   are
maintained.
  (b)  Vent  connections  made  of single-wall metal pipe shall not pass
through any combustible walls or partitions unless they are  guarded  at
the  point  of passage by ventilated metal thimbles not smaller than the
following:
  (1) For equipment conforming to standards --  four  inches  larger  in
diameter than the vent connector.
  (2)  For equipment having draft hoods -- six inches larger in diameter
than the vent connector.
  (3) For equipment without draft  hoods  --  twelve  inches  larger  in
diameter than the vent connector.

Section 27-895

Section 27-895

  §  27-895  Size of connectors. The vent connector shall not be smaller
than the size of the flue  collar  or  the  draft  hood  outlet  of  the
gas-fired  equipment. Where a single item of equipment has more than one
draft hood outlet, the vent connector shall equal the combined  area  of
the  draft  hood  outlets for which it acts as a common connector to the
gas vent or chimney.