Article 3 - STANDPIPE REQUIREMENTS

Section 27-932

Section 27-932

  § 27-932 When required. (a) Wet standpipe systems shall be installed:
  (1)  In  all  buildings  or  portions thereof exceeding six stories or
seventy-five feet in height, except that open parking  structures  shall
not  require  installation  of a wet standpipe system unless they exceed
ten parking levels or seventy-five feet in height.
  (2) In all portions of buildings two or more stories  in  height  that
have a floor area of ten thousand square feet or more on any floor.
  (b)  Where  standpipes are required by the height and area limitations
of subdivision (a) of this section, a  non-automatic  or  automatic  dry
standpipe  system  may  be installed in lieu of the wet standpipe in all
buildings classified in occupancy  group  G  not  over  six  stories  or
seventy-five  feet  in height. A dry standpipe system shall be installed
in all open parking structures which exceed  three  parking  levels  and
contain not more than ten parking levels.
  (c)  A  standpipe system shall be installed in all buildings exceeding
three stories in height that have an area exceeding seven thousand  five
hundred  square  feet  on  any floor and where a standpipe system is not
otherwise required by the provisions of this subchapter. A  nonautomatic
or automatic dry system may be used in lieu of the wet standpipe.
  (d)  The  following  buildings  shall be exempt from the provisions of
subdivisions (a), (b) and (c) of this section:
  (1) Buildings classified in occupancy groups F, G, H, and  J  that  do
not  exceed  two  stories or thirty feet in height and an area of twenty
thousand square feet on any floor and are provided with hand or portable
fire extinguishers as required by the fire department.
  (2) Buildings classified in occupancy groups E, F, G, H,  and  J  that
require  a wet standpipe as provided in paragraph two of subdivision (a)
and subdivision (c) of this section but not  exceeding  six  stories  or
seventy-five  feet  in  height  and that are equipped throughout with an
automatic wet or dry sprinkler system connected to a central supervisory
station, and such system complies with the provision of this subchapter.

Section 27-933

Section 27-933

  §   27-933  Yard  hydrant  systems  required.  Outdoor  amusement  and
exhibition places, oil storage  plants,  lumber  yards,  trailer  camps,
industrial  parks,  and  similar  occupancies  shall  have yard hydrants
installed so that the entire area may be reached by  two  hundred  fifty
feet  of  hose  from  a yard hydrant or a street hydrant. Single hydrant
connection shall be at least in six inch I.P.S. Such hydrants  shall  be
directly  connected  with  city  water  main  or  private water main, or
supplied from gravity tanks or  pressure  tanks,  as  provided  in  this
subchapter.
  (a)  Where  the  area  of  such  enclosure is more than forty thousand
square feet and where the available city water service is less than that
specified in paragraph one of subdivision (b) of section 27-945 of  this
article, the yard hydrant system shall be supplied as follows:
  (1) A gravity tank of at least fifty thousand gallon capacity shall be
provided  and  elevated  so  that  the  bottom  of  the tank is at least
seventy-five feet  above  the  highest  grade  elevation  and  at  least
twenty-five feet above the highest building in the area supplied by this
tank.
  (2)  In  lieu  of  paragraph  one  of this subdivision, there shall be
provided a manual fire pump with a capacity of  at  least  one  thousand
gpm,  and a suction tank of at least fifty thousand gallon capacity. The
suction tank shall be supplied through a six inch connection to the city
water main controlled by an automatic ball float valve  in  the  suction
tank.  A  bypass  shall be provided so that the pump may be fed directly
from the city water main.
  (3) The pump shall be located in a pump house at the street main  side
of the area or enclosure.
  (4)  Suction from a river or well may be permitted by the commissioner
if the required quantity of reasonably clean fresh water may be obtained
thereby, subject to the approvals of such other authorities as may  have
jurisdiction over the primary source of supply.
  (b)  The  maximum distance between hydrants shall be two hundred fifty
feet. At each yard hydrant, two hundred fifty feet of rubber lined hose,
with a smooth bore one and one-eighth inch approved play-pipe, shall  be
placed  in  a  hose  house painted red, and the words "Fire Hose" in six
inch white letters shall be painted on the door.
  (c) The approval of the fire department shall be obtained for location
of any monitor  nozzles  that  may  be  required  in  addition  to  yard
hydrants.  Not  more than one monitor nozzle with remote control will be
required for each forty thousand square feet of area or fraction thereof
unless, in the fire department's opinion, an unusual hazard exists.
  (d) Standpipes and sprinkler  systems  may  be  connected  to  a  yard
hydrant system in accordance with the requirements of this subchapter.
  (e)  Yard  hydrant  systems  connected  to  city  water mains shall be
provided with post indicator valves located in an  accessible  position.
Post indicator valves shall be locked open and be painted red.
  (f)  Fire  extinguishing  equipment, in addition to that prescribed by
this section, shall be  provided  in  accordance  with  requirements  of
chapter  four  of this title for oil storage plants, oil refineries, and
other plants deemed by the fire commissioner  to  present  unusual  fire
hazards,  and  also in rooms or spaces housing electrical equipment when
such fire extinguishing equipment is deemed necessary.

Section 27-934

Section 27-934

  §  27-934 Standpipe systems in structures being erected or demolished.
(a) During construction or demolition  of  any  structure  for  which  a
standpipe  system  is  required,  provision shall be made for the use of
such standpipe by the fire department in accordance with the  provisions
of  section  27-1014  of  article  one  of  subchapter nineteen and this
subchapter.
  (b) Temporary risers shall be at least four  inches  in  diameter  for
structures  less  than  four  hundred  fifty  feet high and at least six
inches in diameter for structures four hundred fifty feet high or  more.
There  shall  be  as  many  risers as will be, or were, required for the
permanent system.  Each  such  riser  shall  be  connected  to  a  cross
connection  that  is  supplied  through  siamese hose connections at the
street level, and shall be  equipped  on  each  floor  with  a  two  and
one-half inch hose outlet valve. The installations shall be made so that
each  riser,  cross-connection, and branch line can be plugged or capped
when work is not being done on the system. The location of  the  siamese
hose  connection  shall  be  placarded,  kept free from obstruction, and
identified by a red light.

Section 27-935

Section 27-935

  §  27-935 Number of standpipe risers required. The number of standpipe
risers shall be such that every point of every floor can be reached by a
twenty foot stream from a nozzle attached to not more than  one  hundred
twenty-five feet of hose connected to a riser outlet valve.

Section 27-936

Section 27-936

  §  27-936  Location  of standpipe risers. (a) Standpipe risers and two
and one-half inch angle hose valves shall  be  located  within  stairway
enclosures.  For  additional  requirements see section 27-343 of article
five of subchapter five and subdivision (j) of section 27-375 of article
five of subchapter six of this chapter. When stairway enclosures are not
available within the distance limitations  of  section  27-935  of  this
article,  the  standpipe  risers  and  two  and one-half inch angle hose
valves shall be located as near to the enclosure as practicable, subject
to the approval  of  the  commissioner.  A  metal  sign  with  one  inch
lettering indicating the location of the outlet shall be provided in the
stair  enclosure  on  each  floor  where the riser is not located in the
enclosure.
  (b) No standpipe riser shall be placed in any shaft containing  a  gas
or fuel pipeline.

Section 27-937

Section 27-937

  §  27-937  Omission of standpipe service. (a) Standpipe outlets may be
omitted in portions of first floors or  basements  that  are  completely
separated  from  the  entrance hall or enclosed stairways leading to the
upper  floors,  provided  portable  fire  extinguishers  are  installed,
subject to the approval of the commissioner.
  (b)  Standpipe  protection  shall  be omitted from transformer vaults,
high-tension switchboard rooms, and other locations  where  the  use  of
hose streams would be hazardous. Any space or room that houses equipment
of  such  nature  that the use of water would be ineffective in fighting
the fire, or would be hazardous, shall have a conspicuous metal sign  on
each  door  opening  on such space or room stating the nature of the use
and the warning: "Use No Water".

Section 27-938

Section 27-938

  §  27-938 Size of standpipe risers. The size of standpipe risers shall
be in accordance with Table 17-1.

                   Table 17-1 Size of Standpipe Risers
========================================================================
                                                          Minimum Riser
                                                          Size Required
                Height(1)                                   (I.P.S.)
------------------------------------------------------------------------
          150 ft. or less........................            4 in.
          Greater than 150 ft....................            6 in.
========================================================================
  Note:
  (1) The height shall be that of the individual riser  to  the  highest
hose  outlet  (not  including  manifold  outlets)  from the level of the
entrance floor at street level at which the riser begins.

Section 27-939

Section 27-939

  §  27-939  Devices  used in system. No device, valve, pipe, or fitting
may be used in a standpipe system unless such  device,  valve,  pipe  or
fitting  has been accepted or approved in accordance with the provisions
of section 27-135 of article eight of subchapter one of this chapter.

Section 27-940

Section 27-940

  §  27-940  Siamese  connections required. Siamese connections shall be
provided as follows:
  (a) One siamese connection shall be provided for  each  three  hundred
feet  of  exterior  building  wall  or fraction thereof facing upon each
street or public space.
  (b) Where buildings face upon two parallel streets  or  public  spaces
without  an  intersecting  street  or public space, one siamese shall be
provided for each three  hundred  feet  of  exterior  building  wall  or
fraction thereof facing upon each such parallel street or public space.
  (c)  Where  a  building  faces upon two intersecting streets or public
spaces and the total length of the exterior building walls  facing  upon
such  streets  or  public spaces does not exceed three hundred feet only
one siamese connection need be installed provided the siamese connection
is located within fifteen feet of the corner and on the longer street.
  (d) Where a building faces on three  streets  or  public  spaces,  one
siamese  connection  shall  be  provided  for each three hundred feet of
building wall or fraction thereof facing upon  such  streets  or  public
spaces,  provided  that  at least one siamese connection is installed on
each of the parallel streets or public spaces, and further provided that
the siamese connections shall be located so that  the  distance  between
them does not exceed three hundred feet.
  (e)  Where  a  building  faces  upon four streets or public spaces, at
least one siamese connection shall be provided on each street  front  or
public  space;  however, only one siamese connection need be provided at
the corner of two intersecting streets or public spaces if  the  siamese
connection  is  located  within  fifteen  feet  of the corner and on the
longer street or public space, and  if  the  distances  between  siamese
connections, in all cases, does not exceed three hundred feet.
  (f) In any case where the exterior building walls of a building facing
a  street or public space is obstructed in part by another building, one
siamese connection shall be provided for each clear three  hundred  feet
of exterior building wall or fraction thereof facing upon such street or
public space.

Section 27-941

Section 27-941

  §  27-941  Cross  connections. (a) Standpipe systems that include more
than one riser shall have all risers cross-connected at, or  below,  the
street  entrance  floor  level,  except  as  otherwise  provided in this
section.
  (b) Standpipe systems in  buildings  required  by  the  provisions  of
section  27-943  of  this  article to have one or more zones shall be so
designed and installed that the risers supplied from each zone  will  be
cross-connected  below, or in, the story of the lowest hose outlets from
the water source in each  zone.  Horizontal  intermediate  check  valves
shall  be  installed  in  the run of each riser continuing into a higher
zone in such manner as to permit all upper zones of the system to be fed
through one riser from the zone below and to prevent any lower  zone  of
the system from being supplied from a zone above.
  (c)  Risers  supplied  by  an  upper  level  cross connection shall be
provided with  manual  control  valves  or  remote  control  valves,  so
arranged  that  risers supplied by the upper level cross connections may
independently be shut off from the tank supplies.
  (d) Cross connections shall be at least as large as the largest  riser
supplied  by  the cross connection. However, when supplying two, but not
more than four four-inch risers, the cross connection shall not be  less
than five inches. The cross connection shall not be less than six inches
for all other riser combinations.
  (e)  Where  there is no cellar, cross connections may be hung from the
ceiling of the lowest story.
  (f) Each siamese connection shall be connected to  a  riser  or  to  a
cross  connection  connecting  other siamese hose connections or risers.
The pipe from the siamese connection to the riser  or  cross  connection
shall  be  five  inch  i.p.s.,  except  that  a  four inch pipe shall be
sufficient when such pipe supplies a single four inch riser system.  The
pipe from the siamese connection shall be run as directly as practicable
to the riser or cross connection.

Section 27-942

Section 27-942

  § 27-942 Hose stations. (a) Hose outlet valves.
  (1) At the riser on each floor served by the riser and on the entrance
floor above the riser control valve, a two and one-half inch hose outlet
valve  shall be provided for fire department use. Such hose outlet valve
shall be readily accessible from a stairway landing or from a floor, and
shall be located between five feet and six feet  above  the  landing  or
floor.
  (2) At the top of the highest riser, there shall be provided above the
main  roof  level,  a  three-way  manifold  equipped  with three two and
one-half inch hose valves with hose valve caps. Where  the  manifold  is
located  other  than  within  a  heated stair enclosure or bulkhead, the
control valve shall be located in a horizontal run of piping  below  the
roof.
  (b)  Location.  Hose stations shall be located at the standpipe risers
located either within a stair enclosure or adjacent to the  entrance  to
such  enclosure  as provided in section 27-936 of this article. When the
hose station is located outside the stair enclosure  and  the  riser  is
within  the  stair  enclosure,  it  shall be known as and referred to as
"Auxiliary Hose Station".
  (1) Hose stations shall be located so that every point  in  the  floor
area  served by the hose station is within twenty feet of the end of the
hose nozzle with the hose in its extended position. The  maximum  length
of  hose  that  shall  be  permitted  at any hose station is one hundred
twenty-five feet.
  (c) Size, type and quality of hose. Hose shall  be  provided  on  hose
racks at each hose station as follows:
  (1) Hose shall be one and one-half inch "flax-line" unlined linen hose
or  equivalent,  factory coupled, in occupancy groups C, E, F, G, H, and
J.
  (2) Hose shall be two and one-half inch cotton, rubber-line, or rubber
hose or equivalent, factory coupled, in occupancy group A.
  (3) Hose shall be two and one-half inch "flax-line" unlined linen hose
or equivalent, factory coupled, for occupancy groups other than those in
paragraphs one and two of this subdivision.
  (4) Hose for auxiliary hose stations shall be one  and  one-half  inch
"flax-line" unlined hose or equivalent.
  (5)  Hose  lines  shall  be made up of fifty foot factory coupled hose
except that required hose lengths of less than fifty feet  shall  be  in
one section of the required length. Only one length less than fifty feet
will  be  permitted  where  hose  length  is  not  of  equal  fifty foot
increments, and no length shall be less than twenty-five feet.
  (6) Hose may be omitted from hose racks in occupancy  groups  J-1  and
J-2 whenever at least three open nozzles, two one and one-half inch, and
two  two and one-half inch spanner wrenches, two two and one-half by one
and one-half  inch  non-swivel  reducing  couplings  and  three  hundred
seventy-five  feet  of  one  and  one-half  inch  hose  are  stored  and
maintained in a locked cabinet located on the main entrance floor  in  a
location  near  the standpipe riser enclosure subject to the approval of
the commissioner, and hose valves are  capped  with  a  hose  valve  cap
fastened  to  the  valve  with  a  chain. The person responsible for the
maintenance of the standpipe system shall maintain on the premises a key
for unlocking the storage cabinet. The key shall be kept in  a  location
where  it  is readily available to authorized persons, but not available
to the general public. A sign shall be placed  on  the  storage  cabinet
indicating  the location of the key. An additional labelled key shall be
kept in a locked receptacle near the storage cabinet openable by a  fire
department  standard  key.  Such  receptacle  shall  be marked "For Fire
Department Use Only." A  metal  sign  shall  be  placed  in  each  stair

enclosure  on  the main entrance floor stating clearly where the storage
cabinet is located.
  (7) Hose may be omitted from hose racks for nonautomatic dry standpipe
systems  provided that the hose outlet valves are capped with hose valve
caps which are chained to the valves.
  (d) Auxiliary hose stations.
  (1) Auxiliary hose stations may  be  installed  in  those  occupancies
where   one  and  one-half  inch  hose  is  permitted  as  specified  in
subdivision (c) of this section.
  (2) When auxiliary hose stations are installed, the required  two  and
one-half  inch  hose valve at the riser shall be installed and the valve
shall be equipped with a cap fastened to the valve with a chain.

Section 27-943

Section 27-943

  § 27-943 Maximum pressures. The standpipe system shall be zoned by the
use  of  gravity tanks, automatic fire pumps, pressure tanks, and street
pressure so that the maximum pressure at the inlet of any hose valve  in
the zone does not exceed one hundred sixty psig.

Section 27-944

Section 27-944

  §  27-944  Pressure  reducing  valves. (a) When the normal hydrostatic
pressure at a two and one-half inch hose outlet valve exceeds fifty-five
psig, each valve shall be equipped  with  an  adjustable  type  pressure
reducer  so  that  the  pressure  on the downstream side will not exceed
fifty psig when the discharge is at the rate of two hundred gpm  from  a
one inch orifice nozzle attached to one hundred feet of two and one-half
inch unlined hose.
  (b)  At  one  and  one-half  inch hose stations, an adjustable type of
pressure reducer shall be provided on each hose outlet valve  where  the
hydrostatic  pressure  exceeds eighty-five psig and shall be so adjusted
that the pressure on the downstream side will  not  exceed  eighty  psig
when  seventy  gpm  is  discharged  from  a one-half inch orifice nozzle
attached to the length of hose to be provided at the hose station.
  (c) The pressure reducing valve shall be permanently marked  with  the
address  of  the  premises  in  which it is installed and with the floor
location and the setting for the location at which it is to be used.

Section 27-945

Section 27-945

  §  27-945 Water supply for standpipe systems. (a) Primary water supply
for standpipe systems. Every standpipe system  except  nonautomatic  dry
standpipe  systems  shall  have  a primary water supply available at all
times at every hose outlet, or made  available  automatically  when  the
hose  valve  at  any  outlet is opened. Such primary water supply may be
from one or more gravity tanks from a pressure tank  or  tanks,  from  a
direct  connection  to a city water main, from a connection to a private
water main, or from an automatic fire pump.
  (b)  Method  of  providing  water  supply   for   standpipe   systems.
Combinations  of  two or more of the following methods shall be used; in
using such combinations, the siamese connections shall be considered  as
a source of supply.
  (1) Direct connections of standpipes to the city water system provided
one of the following conditions is met:
  a.  A  statement  furnished  by  the  bureau  of  water  supply of the
department of environmental  protection  indicates  a  pressure  in  the
street main that is capable of maintaining a static pressure of at least
fifteen  psig.  at the highest hose outlet between the hours of eight a.
m. and five p. m.  on a normal working day  when  a  street  level  fire
hydrant  within  two hundred fifty feet of the building is supplied from
the same street main and  is  discharging  at  least  five  hundred  gpm
through a two and one-half inch hydrant butt.
  b. For buildings forty feet or less in height with an area of not more
than  twenty thousand square feet per floor, there is a four inch direct
connection to the street main that is fed two ways or there  is  a  four
inch  direct connection to each of two street mains on two street fronts
so installed that shutting off one service will not interfere  with  the
supply of the other, and there is sufficient pressure in the street main
to  maintain  a  minimum  static  pressure  of  twenty-five psig. at the
highest  required  hose  outlet  and  the  department  of  environmental
protection states that the required street pressure is available.
  (2)  A private yard main when meeting the conditions of a direct water
connection to the city water system.
  (3) Gravity tanks provided:
  a. The minimum quantity of water reserved  for  standpipe  service  is
thirty-five hundred gallons in each standpipe zone.
  b. The bottom of the tank shall be at least twenty-five feet above the
highest  hose outlet that such tank supplies, (except the roof manifold)
and those hose outlets in a penthouse  enclosing  mechanical  equipment,
except as otherwise provided in subparagraph e of this paragraph.
  c. Each zone of the standpipe system having three risers or more shall
have a total fire reserve capacity of five thousand gallons or more from
one or more gravity tanks for each zone.
  d.  Where a group of two or more buildings, connected or separated, is
operated under a single control, a single gravity  tank  having  a  fire
reserve  capacity  of  at least five thousand gallons may be accepted as
the primary water supply for  the  several  standpipe  systems  of  such
group,  provided  a dead riser is carried from the bottom of the tank to
an underground header or  cross  connection  system  and  provided  each
building unit has a post indicator type control valve outside or an o.s.
and  y.  control  valve  inside  the  building  at  a readily accessible
location. The underground cross connection  may  not  cross  any  public
street without the approval of the city departments having jurisdiction.
  e.  Useable  storage  or  office  space  on  penthouse floors shall be
provided with a riser  outlet  valve  within  the  distances  stated  in
section  27-935  of this article. In lieu of elevating the bottom of the
gravity tank twenty-five feet above these  outlets,  an  automatic  fire
pump  with  local supervisory alarms may be installed. The pump shall be

capable  of  delivering  two  hundred  fifty  gpm.  at  a  pressure   of
twenty-five  psig.    above  the  normal  static pressure at the highest
outlet supplied by the pump.  The  pump  shall  take  suction  from  the
gravity  tank and be so arranged as to permit the siamese connection and
any required manual fire pump to supply  these  outlets.  No  more  than
three  stories  of  any  penthouse  or of penthouse and building stories
combined, may be supplied by this method.
  (4) Pressure tanks shall be acceptable as the primary  supply  to  the
system provided all of the following conditions are met:
  a.  A  pressure  tank,  or  tanks,  so proportioned and located that a
pressure of at least fifteen psig will be available at the nozzle of the
highest required hose station, exclusive of roof outlets, when  all  the
water has been discharged from the pressure tank.
  b. The storage quantities stated for gravity tanks in subparagraphs a,
c and d of paragraph three of this subdivision are met and an additional
volume  equivalent  to  one-half  of the required water storage space is
provided for the required air.
  c. An air compressor is provided with suitable automatic  control  and
of sufficient capacity to build up air pressure of at least seventy-five
psig.  in  the tank within three hours and to maintain thereafter an air
pressure between seventy and eighty psig. The  automatic  control  shall
also maintain the proper air-to-water ratio in the pressure tank.
  d.  Pressure  tanks shall be supplied with water through a fixed pipe,
independent of the standpipe riser, and at least two inches in size. The
water supply and connection shall be capable of supplying the tank at  a
rate  of  at  least  sixty-five gpm without reducing the pressure in the
tank. The tank shall have a fixed water level plate on the end  opposite
the gauge glass, or other equivalent indicating device.
  (5)  An  automatic fire pump shall be acceptable as the primary supply
to the system provided:
  a. The building is three hundred feet high or less, or if the building
is higher than three hundred feet, the automatic fire pump is used  only
for  the  lower  three  hundred feet. The zones above three hundred feet
shall be supplied by either a gravity tank conforming to paragraph three
of subdivision (b) of this section or  a  pressure  tank  conforming  to
paragraph  four of subdivision (b) of this section and in addition shall
be supplied by the manual fire pump required by section 27-946  of  this
article.
  b.  The  automatic  fire  pump  supplying  the system or section has a
capacity of at least five hundred gpm with a discharge  pressure  of  at
least  twenty-five  but  not  exceeding  seventy psig (above the normal)
static pressure at the highest hose outlet within the zone  supplied  by
the pump plus the frictional resistance from the pump to the outlet at a
flow of five hundred gpm.
  c. The electrical power to the pump is connected to the street side of
the building service switch.
  (c)  High  and  low risers and cross connections in standpipe systems.
When tanks are used for the primary water supply, the standpipe  systems
may use separate riser systems serving, respectively, low and high parts
of  the  building.  Separate  gravity tanks or pressure tanks may supply
each zone, but in every case the standpipe system shall be  so  designed
that  every hose outlet of the entire system can be supplied through the
required cross connections from every siamese connection and from  every
manually operated fire pump located at or below the street level.
  (d)  Use  of  standpipe  riser  for  sprinkler  system  water  supply.
Standpipe risers may be used to supply water to sprinklers in  buildings
classified in occupancy group E, one hundred feet or more in height, and
in  existing  office  buildings,  one hundred feet or more in height, in

accordance with applicable provisions of this subchapter  and  reference
standards RS17-1 and RS17-2.

Section 27-946

Section 27-946

  §  27-946  Fire  pumps.  (a) Additional water supply. Additional water
supply shall be provided for standpipes in buildings over three  hundred
feet  high.  The  primary  water supply to the standpipe system shall be
supplemented by one or more manually operated fire pumps as follows:
  (1) Standpipe systems in buildings more than three hundred  feet  high
shall have at least one seven hundred fifty gpm pump or two five hundred
gpm  pumps. Pumps shall be capable of delivering their rated capacity at
a pressure of fifty psig above the  normal  static  pressure  determined
from  the highest hose outlet (except the roof manifold) in the building
plus the frictional resistance through the pipe from  the  pump  to  the
outlet.
  (2)  Where  a  group  of  two  or more buildings, whether connected or
separated, are operated  under  a  single  ownership  and  one  or  more
buildings  exceed  three  hundred feet in height, one fire pump shall be
accepted as the supplemental supply for the group.  The  pump  shall  be
installed  in  the building where the maintenance personnel are located,
and a metal sign with one inch lettering  shall  be  installed  in  each
building at all of the hose outlets on the entrance floor indicating the
location of the fire pump.
  (b) Standpipe pump rooms and location.
  (1)  Fire  pumps  shall  be  installed  at the entrance floor level or
below, in rooms enclosed by noncombustible  construction  having  a  two
hour  fire-resistance rating and that are adequately heated, ventilated,
lighted, and drained. The pump room shall  have  access  to  the  street
level  by a direct opening to a street or a court, or by a passageway or
stairway having a fire-resistance rating of at least two hours.
  (2) No person shall install other machinery or mechanical equipment in
a fire pump room, unless the building is of construction class  IA,  IB,
or IC.
  (3)  No  person  shall  place  or  install  any equipment containing a
refrigerant classified in groups A1, A2, A3, B1, B2 or B3 in  subchapter
thirteen  of  this  chapter,  or  place  or  install  gas  piping or gas
consuming devices or any other equipment within any space housing a fire
pump that would create a hazardous condition.
  (c) Power supply for standpipe fire pumps. The type of fire  pump  and
prime  mover  used  in  a  standpipe  system  shall  be suitable for the
required service in a standpipe system provided for fire department use.
If the prime mover employs any form of  power  other  than  an  electric
current  supplied  by a public utility, the use thereof shall be subject
to the approval of the commissioner. Electrical power to the motor shall
be taken from the street side of the house service switch.
  (d) Combined use of fire pumps for standpipe and  automatic  sprinkler
systems.  A fire pump that furnishes the required auxiliary water supply
either to a standpipe system or to an automatic sprinkler  system  shall
be  accepted  as  furnishing the corresponding water supply to the other
system if such pump is in the same premises, provided that in every such
case of combined use,  suitable  relief  and  shutoff  valves  shall  be
installed so as to prevent the water pressure on the automatic sprinkler
system  resulting  from  any  required  operation  of  the  pump for the
standpipe system from becoming greater  than  one  hundred  seventy-five
psig.

Section 27-947

Section 27-947

  §  27-947 Direct connections of standpipes to the public water system.
(a) Control valve. Each service directly supplying a standpipe system or
a fire pump shall be equipped with a control  valve  located  under  the
sidewalk  in  a flush sidewalk box located within two feet of the street
line, or in such other locations as may be approved by the department of
environmental protection. The purpose of each such control  valve  shall
be  clearly  indicated  by the words "Standpipe Supply Control," cast in
the cover of such flush sidewalk box or, in lieu thereof, a  metal  sign
with  one  inch lettering shall be located on the exterior building wall
indicating the use and location of the valve.
  (b) Water supply to standpipe fire pumps.
  (1) Any required manual or automatic fire pump  shall  draw  from  two
independent  street  water  mains in different streets, except that: (i)
any manual or automatic fire  pump  serving  a  building  classified  in
occupancy  group  J-2  that  is fully protected by a system of automatic
sprinklers may draw from a single water main; and (ii) an automatic fire
pump may draw from a single water main if augmented by a suction tank or
tanks, and if the valves at the meter and pump are provided with  tamper
switches  that  are wired to an approved central station of an operating
fire alarm company. Where two services are installed, one  service  from
the  street  water main shall be run directly to the pump, and the other
service may be used for domestic water supply. The connection from water
mains to the pumps shall be at least six inch pipe  size  and  shall  be
flushed before connection is made to the system. Connections shall be in
accordance with subchapter sixteen of this chapter.
  (2)  In  the  event that two separate and distinct water mains are not
available as a supply or the street mains cannot  produce  the  required
supply,  there  shall  be  provided  a  suction tank, or tanks, suitably
located and of sufficient capacity to furnish  the  fire  pump  with  at
least a one-half hour supply at the rated capacity of such pump. Suction
tanks  shall  be  filled  by  a  six  inch connection to the water main,
controlled by an automatic ball float valve in the suction tank.  A  six
inch bypass shall be provided so that pumps may be fed directly from the
street water main.
  (3)  When  a  water service supplies both the domestic service and the
manual fire pump, a remote control valve shall be placed on the domestic
service connection at the point where such connection is taken from  the
city  supply  or  service  main.  Such  remote  control  valve  shall be
controlled from a point near the pump control panel. In lieu of a remote
control valve, a manually operated valve may be installed  to  shut  off
the entire domestic water supply to the building, provided such valve is
located in the fire pump room and is properly tagged for identification.

Section 27-948

Section 27-948

  § 27-948 Installation of private fire hydrants. (a) When buildings are
not  required  to  be  provided  with  a  standpipe system, at least one
entrance to the building shall be located within two hundred fifty  feet
of  a street hydrant; or, a private hydrant of the same type as the city
hydrant connected to the street water main shall be provided within  two
hundred fifty feet of entrance. The private hydrant shall be supplied by
at  least  an  eight  inch  pipe,  and  the domestic water supply may be
connected to this private supply provided a shutoff valve  is  installed
in  a  curb  box  in  the domestic supply within six feet of the hydrant
shutoff valve.

Section 27-949

Section 27-949

  §  27-949  Protection  of  standpipe  system.  (a)  All  parts  of the
standpipe systems that may be exposed to frost shall be  protected  from
freezing by any one of the following methods:
  (1)  The piping shall be frostproofed with insulation having a thermal
conductance of 0.1 Btu/hr. per square foot of surface per degree F at  a
mean  temperature of seventy to seventy-five degrees F. Insulation shall
be protected to prevent water infiltration,  and  when  exposed  to  the
weather  the insulation shall be covered with a forty-five pound roofing
felt jacket or equivalent.
  (2) Steam or electric tracers may be  used  in  conjunction  with  the
insulation.
  (b) Tanks subject to freezing temperatures shall be protected.

Section 27-950

Section 27-950

  §   27-950  Standards  for  installation.  Details  for  installation,
components, sizing, valves, fittings, protection against freezing, etc.,
for standpipe systems and related equipment shall be in accordance  with
reference standard RS 17-1.

Section 27-951

Section 27-951

  §  27-951 Inspections and tests. (a) Inspections. Every new system and
every part of an existing system that is altered,  extended,  renovated,
or  repaired,  except  for  ordinary  repairs,  shall  comply  with  the
applicable requirements of this subchapter.
  (b)  Notification.  Advance  notification  of  tests  and  inspections
required by this section shall be given to the commissioner.
  (c)  Representation  at  test. Tests required by this section shall be
conducted in the presence of the commissioner or his or  her  authorized
representative, or in lieu thereof, the commissioner may accept a signed
statement  of an architect or engineer, whose name is submitted with the
notification in subdivision (b) of this section, declaring  that  he  or
she  has  witnessed  the  tests  and that the standpipe system meets the
requirements of this code. If a representative of the commissioner  does
not  appear  within  two  days  after  receipt  of  such  report  by the
commissioner,  the  report  shall  be  deemed  to  be  accepted  by  the
commissioner.
  (d)  Testing  equipment  required.  All equipment, material, and labor
required for testing a system or part thereof shall be furnished by, and
at the expense of, the person responsible for installing the work.
  (e) Testing of system. Systems may be tested in sections, or parts, in
accordance with the requirements of this subchapter.
  (f) Acceptance. Before the acceptance  of  such  system,  each  system
shall be subjected to the tests required by this section.
  (g) Standpipe system tests.
  (1) PRESSURE TESTS.
  a.  The  test  shall  demonstrate  that  the  system  will  sustain  a
hydrostatic pressure of at least one hundred psig, and  at  least  three
hundred  psig  at  the  siamese connection, for a period of at least one
hour at the topmost hose outlet and  at  the  lowest  fire  pump  supply
connection  to  the  system. In buildings not exceeding three stories or
forty feet in height, the test pressures need not  be  more  than  fifty
psig.  in excess of the normal hydrostatic pressures at the topmost hose
outlet, and this pressure must be maintained for a period  of  at  least
one hour.
  b.  Pressure  tanks  shall  be  tested  to  demonstrate that they will
sustain a hydrostatic pressure of at least one hundred fifty per cent of
the normal maximum required operating pressure for a period of at  least
one hour.
  (2) FLOW TEST. The system shall be flow tested to determine that water
is  available at the top outlet of each riser, the lowest outlet in each
riser, and through each siamese connection. The system shall be  flushed
to  remove  all foreign matter from the system. Flow shall be through at
least a two and one-half inch hose without nozzle at  each  one  of  the
above mentioned locations at separate times.
  (3) ALTERATION TESTS. When alterations, additions, or repairs are made
to  a  standpipe  system,  the  entire  system  shall  be subjected to a
hydrostatic test pressure of at least fifty psig  at  the  highest  hose
outlet,  and  in  addition,  a  flow  test  shall  be  made as stated in
paragraph two of this subdivision through the new or altered portion  of
the system.
  (h) Pump tests.
  (1)  Fire  pumps  shall be tested at the factory, and a certified test
curve shall be furnished with each pump.
  (2) Pumps shall be tested after installation  to  ascertain  that  the
pump is supplying its rated capacity at the highest required hose outlet
or through the roof manifold. The test shall be performed as follows:
  a.  At least fifty feet of approved two and one-half inch rubber lined
hose equipped with a one and one-eighth inch nozzle shall  be  connected

to  the  highest  two  and one-half inch hose outlet valve. One of these
assemblies shall be connected in parallel for each two hundred fifty gpm
of rated pump capacity.
  b.  The  nozzle or nozzles of the hose assembly shall discharge at, or
above, the highest required hose outlet or through a manifold.
  c. Pitot tube  gauge  readings  shall  be  taken  at  each  nozzle  to
determine that the required pump capacity is being discharged.
  d.  For  manually  operated  fire  pumps,  the  suction  and discharge
pressures shall be recorded for each step or pump speed.  The  pump  rpm
electrical  current,  and  voltage  readings  shall be recorded with the
specific discharge pressure for each supply condition.
  e. Automatic fire pumps shall be tested to ascertain that all  of  the
automatic controls are in good working order.
  f.  All of the above readings shall be noted on the required standpipe
diagram or a framed chart, which shall be mounted in a visible  location
near the pump control panel.
  g. When pumps are supplied by two independent services, the test shall
be  conducted  from  each  service  independent  of  the  other  and, in
addition, with both services supplying the pump.
  (i) Test equipment for fire pumps.
  (1) For every fire pump installation, there shall be provided for test
purposes at least three fifty foot lengths of approved two and  one-half
inch  rubber  lined  fire  hose.  Hose shall be hung in the pump room or
other convenient location.
  (2) Three two and one-half inch by one and  one-eighth  inch  nozzles,
three  spanner  wrenches,  and  twelve  washers shall be stored with the
required hose.

Section 27-952

Section 27-952

  §  27-952  Standpipe signal systems. Standpipe signal systems shall be
provided in accordance with section  27-974  of  article  five  of  this
subchapter.

Section 27-953

Section 27-953

  §  27-953  Elevators  for  fire  department  use.  Elevators  for fire
department use shall be  provided  as  required  by  section  27-989  of
article one of subchapter eighteen.