Article 4 - AUTOMATIC SPRINKLER REQUIREMENTS

Section 27-954

Section 27-954

  §  27-954  Required sprinklers. A system of automatic sprinklers shall
be provided in the areas listed in  this  section  and  as  required  in
subchapters  four  through eight of this chapter. A summary of sprinkler
requirements is given in table 17-2.
  (For Table 17-2 see chapter 839 of the laws of 1986 and amendments)

  (a) Buildings classified in high hazard occupancy group A.
  (b) Spaces classified in high hazard occupancy group A.
  (c) Buildings classified in storage occupancy group B-1 exceeding  one
thousand  square  feet  in  floor  area, or seventy-five feet or more in
height, except as modified under subdivisions a,  b  and  c  of  section
27-455 of article ten of subchapter seven of this code.
  (d)  Spaces  classified  in storage occupancy group B-1 exceeding five
hundred square feet in floor area, except as modified under subdivisions
a, b and c of section 27-455 of article ten of subchapter seven of  this
code.
  (1)  Such  storage  spaces  less than five hundred square feet in area
shall install a system of automatic sprinklers,  when  required  by  the
commissioner or the fire commissioner.
  (e)  Buildings  and  spaces  classified in storage occupancy group B-2
exceeding five thousand square feet in floor area, or seventy-five  feet
or  more  in height, except as modified under subdivisions a, b and c of
section 27-455 of article ten of subchapter seven of this code.
  (f) Spaces in high rise buildings classified in  mercantile  occupancy
group  C,  spaces  classified  in mercantile occupancy group C exceeding
seventy-five hundred square feet in floor area  or  with  an  unenclosed
stair or escalator between any two or more floors.
  (g) Buildings classified in industrial occupancy group D when required
by section two hundred eighty of the labor law or when seventy-five feet
or more in height.
  (h)  Spaces  classified  in  industrial  occupancy group D-1 exceeding
seventy-five hundred square feet, in floor area excluding heliports.
  (i) Buildings classified in occupancy group E,  one  hundred  feet  or
more  in  height  having  air-conditioning and/or mechanical ventilation
systems that serve more  than  the  floor  in  which  the  equipment  is
located,   and   on  or  before  January  eighteenth,  nineteen  hundred
seventy-six, in existing office buildings one hundred feet  or  more  in
height  having  such  systems,  showroom  spaces  exceeding seventy-five
hundred square feet in area located more  than  forty  feet  above  curb
level.  The  sprinkler  system  may  be  connected to the domestic water
supply and/or the standpipe risers.   Where  connected  to  a  standpipe
riser,  provision  shall  be  made  to prevent excessive pressure on the
sprinkler heads. If such  work  is  not  completed  on  or  before  July
eighteenth,  nineteen  hundred  seventy-four,  the  owner shall submit a
statement to the commissioner, with a copy  to  the  fire  commissioner,
setting  forth  a plan and time schedule for the performance of the work
and completion within the prescribed time. Such plan and schedule  shall
be  subject  to the approval of the commissioner. Failure to comply with
the provisions of this subdivision, or to perform the work in accordance
with  the  time  schedule,  as  approved  by  the  commissioner,   shall
constitute a violation.
  (j)  Dressing  rooms  and  property rooms used in conjunction with all
places of assembly, except for F-1B places  of  assembly  not  providing
live entertainment.
  (k)   Corridors  and  exit  passageways  of  buildings  classified  in
institutional occupancy group H where the building or  building  section
is  not  otherwise  required  to  be  fully  sprinklered  as provided in
subchapter four. Patient rooms in H-2  occupancies  shall  be  protected

with smoke detectors complying with provisions of section 27-955 of this
article  when  not  required  to  be  sprinklered  by  the provisions of
subchapters four through seven.
  (l)  Regardless  of  occupancy  group  classification, any story above
grade that cannot be ventilated by at least twenty square feet  of  free
openable  area  and  the  first  story  below  grade  when  it cannot be
ventilated by at least thirty-five square feet of openable area per  ten
thousand  cubic  feet  of  volume. Such ventilation shall be provided by
operable windows or other natural  ventilation  sources  complying  with
section  27-749 of article six of subchapter twelve of this chapter. All
other stories below  grade  shall  be  sprinklered.  Sprinklers  may  be
omitted  in toilets, shower rooms, stairs, and mechanical and electrical
equipment rooms.
  For purposes of this subdivision fixed windows may  be  considered  as
"openable"  (may be broken inward) if they are not more than one hundred
feet above grade, or fifteen feet below grade; or if  they  are  located
within six feet of an accessible roof or setback; or if they are located
within  six  feet  of  an  operable window having at least three foot by
three foot openings.
  (1) Buildings classified in occupancy group J-2  with  not  more  than
three  dwelling  units  and  buildings classified in occupancy group J-3
shall be exempt from this provision provided all  spaces  classified  in
storage occupancy group B-2 exceeding one thousand square feet have been
sprinklered in accordance with the requirements of this subchapter.
  (m)  Rubbish  chutes,  laundry  chutes,  and  chutes for similar uses.
Sprinklers, protected from damage, shall be provided in accordance  with
reference standard RS 17-2, RS 17-2A, or RS 17-2B, as applicable.
  (n) Soiled linen collection and sorting areas.
  (o)  Workshops  exceeding  one  hundred square feet except in one- and
two-family dwellings.
  (p) Refuse collection and disposal areas.
  (q) Drying area of laundries or similar spaces in which  two  or  more
clothes  drying machines are installed. Sprinklers to be spaced to cover
area five feet in front, rear, and sides of machines.
  (r) Sprinklers for cooling towers, where required by  subchapter  five
of this chapter, shall be either a dry pipe or deluge system designed in
accordance with the provisions of reference standard RS 17-4.
  (s) (1) F-4 places of assembly used as cabarets.
  (2)  Stages  within  F-1a, F-1b, F-3 or F-4 occupancies providing live
entertainment at anytime as  set  forth  in  subchapter  eight  of  this
chapter.
  (t)  Buildings classified in occupancy group J-1, buildings classified
in occupancy  group  J-2  with  four  or  more  dwelling  units,  spaces
classified  in  occupancy  group J-1, and spaces classified in occupancy
group J-2 with four or more dwelling units.
  (u) Places  of  assembly  located  within  a  building  classified  in
occupancy group J-1.
  (v) Catering establishments and banquet halls with an occupant load of
three hundred or more persons.
  (w)  In  all  existing  buildings  classified  in  occupancy group J-1
(except for "residential  hotels,"  as  such  term  is  defined  by  the
commissioner  pursuant to rules,) all spaces listed in subdivisions (c),
(d), (l), (m), (n), (o), (p) and (q) of this  section,  except  that  an
approved  smoke  detection  alarm  system  may  be  installed  in  those
locations described under subdivisions (o) and (q) in lieu of sprinklers
other than in those locations where sprinklers are required pursuant  to
section  27-123.2  of this chapter. Such smoke detection system shall be
of the supervisory type connected to an approved central station.

  (x) High rise buildings classified in occupancy group F-1,  F-3,  F-4,
or G, or any spaces classified in such occupancy groups located within a
high rise building or building section more than seventy-five feet above
curb level.
  (y)  Spaces  in  existing  high rise buildings classified in occupancy
group C and any space in an existing building  classified  in  occupancy
group  C  with  an unenclosed stair or escalator between any two or more
floors.
  (z) Notwithstanding the provisions of subdivision i of  this  section,
high  rise  buildings  classified  in  occupancy  group  E  and low rise
buildings classified in occupancy group E with a total gross floor  area
of one hundred thousand square feet or more.
  (aa)  Regardless  of occupancy group classification, in each basement,
cellar or other location below grade, regardless of the  floor  area  of
such   space,   in  any  mercantile  establishment  in  which  the  fire
commissioner permits the storage of flammable  or  combustible  mixtures
pursuant  to  sections  27-4066, 27-4070 or 27-4094 of this code, except
that, where such flammable or combustible mixtures are  stored  in  such
basement,  cellar or other location below grade, in a room or other area
that is segregated, vertically and horizontally, from surrounding spaces
by a fire separation of not less than a two-hour fire-resistance rating,
such system of automatic sprinklers shall be required only  within  such
room or other area. Such system of automatic sprinklers shall conform to
the  requirements  for  automatic  sprinklers  for  spaces classified in
storage occupancy group B-1 pursuant to subdivision d of this section.

Section 27-955

Section 27-955

  §  27-955  Smoke detector alternate. An approved smoke detection alarm
system may be used in lieu of sprinklers in those locations described in
subdivisions (o) and (q) of section 27-954 of this  article,  except  in
buildings or spaces classified in occupancy group J-1 or J-2. Such smoke
detection  system  shall  be  of  the  supervisory  type connected to an
approved central station.

Section 27-956

Section 27-956

  § 27-956 Standard for installation of sprinklers. (a) Except as herein
provided   in   subdivision  (b)  of  this  section,  the  installation,
components, sizing, spacing, location, clearances, position, and type of
systems shall be in accordance with reference standard RS  17-2,  except
that  sprinkler  systems  in  one  and  two  family dwellings may in the
alternative be in accordance  with  reference  standard  RS  17-2B,  and
sprinkler  systems  in  other  residential  buildings  not exceeding six
stories or seventy-five feet in height and in other  residential  spaces
in  buildings  not  exceeding six stories or seventy-five feet in height
may in the alternative be  in  accordance  with  reference  standard  RS
17-2A.
  (b)  Notwithstanding  any  provision  to  the  contrary  contained  in
reference standards RS 17-2, RS 17-2A or  RS  17-2B  sprinklers  may  be
omitted  from  clothes  closets, linen closets, pantries, water closets,
water closet compartments, bathrooms, general toilet  rooms  and  shower
rooms in buildings and spaces classified in occupancy group J-2 and J-3.

Section 27-957

Section 27-957

  § 27-957 Sprinkler alarm system. (a) A sprinkler alarm system shall be
provided  in  accordance  with  the  applicable  provisions of reference
standards RS 17-2, RS 17-2A, RS 17-2B and RS 17-3. Where the building is
provided with a class E or modified class E fire  alarm  signal  system,
compliance with the applicable provisions of reference standard RS 17-3A
or  RS  17-3B  shall  be  acceptable  in  lieu  of  compliance  with the
provisions of reference standard RS 17-3.
  (b) A  sprinkler  alarm  system  shall  be  required  when  more  than
thirty-six  heads  are  installed in any fire area or section. See table
17-2 for general requirements.

Section 27-958

Section 27-958

  §  27-958  Approved devices. No device, valve, pipe, or fitting may be
used in a sprinkler system unless such device, valve, pipe,  or  fitting
is of a type approved for such use.

Section 27-959

Section 27-959

  § 27-959 Siamese connections required. (a) Where required.
  (1)  Siamese  connections shall be provided in accordance with section
27-940  of  article  three  of  this  subchapter,  except  as   modified
hereinafter.
  (2)  In below grade sprinkler systems for garage occupancies involving
the storage or repair of motor vehicles, a siamese connection  shall  be
provided  within  fifty  feet  of  every  exit or entrance used by motor
vehicles.
  (3) Where partial sprinkler protection is required for storage spaces,
one siamese connection shall be provided when more than thirty-six heads
are  installed  in  one  fire  section.  Areas  subdivided,   when   the
subdivisions  are totally enclosed by noncombustible construction having
at least a two hour fire-resistance rating, shall be considered separate
fire sections and the number of  heads  in  the  largest  section  shall
determine the necessity for siamese connections.
  When  partial  sprinkler systems are installed to protect entire floor
areas, siamese connections shall be provided in accordance with  section
27-940 of article three of this subchapter.
  In  all  cases  where  partial  sprinkler  protection  is provided and
siamese connections installed, metal signs shall  be  securely  fastened
to,  or  above,  the  siamese  connection indicating the area protected.
Where the building has two or more  frontages,  additional  metal  signs
shall be installed indicating the location of the siamese connection.
  (4)  When  a  sprinkler  system supplies a group of buildings, siamese
connections  shall  be  provided  for  each  building  as  required   by
paragraphs one, two and three of this subdivision.
  (5) A single three-inch (seventy-six millimeter) inlet fire department
connection  acceptable  to the fire commissioner may be provided for the
sprinkler  system  in  lieu  of  each  required  siamese  connection  in
buildings classified in occupancy group J-2 not exceeding six stories or
seventy-five  feet in height and in spaces classified in occupancy group
J-2 in buildings not exceeding  six  stories  or  seventy-five  feet  in
height.
  (b)  Installation  and construction. The installation and construction
of siamese connections shall be the same as required for fire  standpipe
systems,  except  that  the  caps  of  each  automatic sprinkler siamese
connection shall be painted green and the entire siamese connection of a
nonautomatic sprinkler system shall be painted with aluminum paint,  and
except  that  caps  of  each  siamese  connection  used  for combination
standpipe and sprinkler  systems  shall  be  painted  yellow  and  signs
provided  as  required  in  subdivision  (b) of section two of reference
standard RS17-1.
  (c) A siamese connection need not be provided for a  sprinkler  system
in one and two family dwellings.

Section 27-960

Section 27-960

  §  27-960  Piping  from  siamese  connection.  Piping from the siamese
connection shall be the same size as the riser or trunk main to which it
is connected, except that it need  not  be  more  than  five  inches  in
diameter  when  supplying larger riser or feed mains. When more than one
siamese connection is required, the piping from each siamese  connection
need not exceed four inches in diameter.

Section 27-961

Section 27-961

  §  27-961  Classification  of water supplies. (a) Automatic sources of
water supply for sprinkler systems. Automatic sources  of  water  supply
for  sprinkler  systems  shall  include  a  gravity tank, pressure tank,
automatic fire pump, or direct connection to the public  water  systems.
Automatic  fire  pumps where used for sprinkler supply shall comply with
the applicable provisions of sections 27-946 and 27-947 except  that  no
enclosures  shall be required, and provided that when an emergency power
system is provided, the electric power to the motor shall  be  connected
to the emergency power source.
  (b) Auxiliary sources of water supply for sprinkler systems. Auxiliary
sources  of  water supply for sprinkler systems shall include a manually
actuated fire pump or siamese connection.
  (c) Combination sprinkler and standpipe tank sources of water  supply.
Tanks  used  to provide the required primary water supply to a standpipe
system may also be used as a supply for an automatic sprinkler system.
  (d) Nonautomatic  sources  of  water  supply  for  sprinkler  systems.
Nonautomatic  sources  of  supply  for  sprinkler  systems shall include
siamese connections.

Section 27-962

Section 27-962

  §  27-962  Sources  of  water  supply for sprinkler systems. Sprinkler
systems shall be provided with water from the following sources.
  (a) Two automatic sources  of  water  supply  shall  be  provided  for
sprinklers in:
  (1) Buildings classified in occupancy group A.
  (2)  Buildings  classified  in  occupancy group C when the area on one
floor exceeds twenty thousand square feet.
  (3) Buildings classified in occupancy group F-1a when open  heads  are
required for stages of unlimited size.
  (b)  At  least  one automatic source of water supply shall be provided
for sprinklers installed in all occupancy groups, except those listed in
subdivision (a) and except  as  provided  in  subdivision  (c)  of  this
section.
  (c)  The  domestic  water  supply may be used to supply any sprinklers
required  under  section  27-954  of  this  article  when  installed  in
buildings classified in occupancy groups E, G, H and J, or to supply any
sprinklers  required  under subdivision (aa) of said section, regardless
of occupancy group classification, provided that  all  the  requirements
stated in subdivision e of section 27-962 of this article are met.
  (d)  The  domestic  water  supply  may  be  used  to  supply  water to
sprinklers in cooling towers if provision is made to automatically  stop
the use of water through the domestic supply lines and provided that all
of the requirements stated in subdivision (e) of this section are met.
  (e)  When the domestic water is used to supply sprinklers as permitted
in subdivisions (c) and (d)  of  this  section,  all  of  the  following
conditions shall be met:
  (1)  The  domestic water supply line from the tank or street supply is
at least the size of the sprinkler line and that the capacity  available
is at least equal to the capacity required for the sprinklers.
  (2)  The  domestic  water  supply line from the tank or street has the
required pressure as provided in section 27-963 of this article.
  (3) The domestic water supply line is of  nonferrous  material  except
when the domestic water supply is four inches or over.
  (4)  An  o.s.  and  y.  valve  or  an  approved  valve  having  visual
indication, sealed open, is installed in the sprinkler supply branch, or
such other valve  arrangement  as  may  be  provided  for  in  reference
standard RS 17-2A or RS 17-2B, as applicable.
  (5)  The  pipe  connecting the domestic water supply and the sprinkler
control valve is of nonferrous material and not less than twelve  inches
long.
  (6)  The  number of heads in each fire section does not exceed twenty,
except that the number of heads in each fire section may  exceed  twenty
in  buildings classified in occupancy group J-2 or J-3 not exceeding six
stories or seventy-five feet in  height  and  in  spaces  classified  in
occupancy  group  J-2  or  J-3 in buildings not exceeding six stories or
seventy-five feet in height, and no more than  ten  heads  are  supplied
from any one domestic water riser.
  (7) The connection is made at the supply or riser side of any domestic
branch control valves.
  (8)  In  connection  with  the  above  conditions,  the number of fire
sections  having  twenty  or  less  heads  may  be  unlimited;  and  the
installation  of  alarms in branches supplying fire sections shall be at
the option of the owner, except that such alarms shall be provided where
required by reference standard RS 17-2A or RS 17-2B.
  (9) A check valve is installed on the sprinkler supply branch.
  (f) Nonautomatic sprinkler systems shall be provided with:
  (1) Siamese connections in accordance with section 27-940  of  article
three of this subchapter.

  (2) Malleable iron fittings approved for sprinkler installations.
  (3)  An  approved  automatic  fire  alarm  with direct connection to a
central station of an approved operating fire  alarm  company  shall  be
installed in the area protected by the sprinkler system.
  (g)  There  shall  be  no more than ten sprinkler heads connected to a
plumbing riser supplying anything other than  sprinkler  heads,  and  no
more  than  twenty  sprinkler  heads connected to a riser supplying only
sprinkler heads in any fire section separated  by  two  hour  enclosures
from adjoining fire sections. The number of sprinkler heads connected to
a  riser  supplying  only sprinkler heads may exceed twenty in buildings
classified in occupancy group J-2 or J-3 that do not exceed six  stories
or  seventy-five  feet in height and in residential spaces classified in
occupancy group J-2 or J-3 in buildings not  exceeding  six  stories  or
seventy-five feet in height.
  (h) Standpipe risers may be used to supply water to sprinklers in high
rise  buildings  classified  in  occupancy  groups  E, G, H and J and in
existing office buildings, one  hundred  feet  or  more  in  height,  in
accordance  with  applicable provisions of this subchapter and reference
standards RS 17-1 and RS 17-2.
  (i) The domestic water supply in  buildings  classified  in  occupancy
group  J-1  or  J-2  may  be used for sprinklers in corridors, in refuse
chutes and in other similar areas, as approved by the commissioner.  The
domestic  water  may  be  supplied  by direct public water connection or
equipment and  pumps  approved  for  water  supply  in  accordance  with
reference standard RS-16.

Section 27-963

Section 27-963

  §  27-963  Direct connection of sprinklers to the public water system.
Direct connection of sprinklers to a city water main shall be acceptable
as  an  automatic  water  supply,  provided  the  main  is  capable   of
maintaining  a  pressure  of  at  least  fifteen  psig at the top of the
highest sprinkler riser, with five hundred gpm of water flowing  from  a
two  and one-half inch hydrant outlet located at the street level within
two hundred fifty feet of the building. The hydrant test shall  be  made
between  the  hours of eight a.m. and five p.m. on a working day. If the
pressure found in this test is insufficient to  comply  with  the  above
requirement,  a  minimum  of  twelve  psig  at  the  top  of the highest
sprinkler riser shall be acceptable, provided that  all  piping  in  the
affected area and supply piping thereto that is four inches and under is
increased one pipe size above those sizes required by reference standard
RS 17-2, RS 17-2A or RS 17-2B, as applicable. In addition to the fifteen
psig  or  twelve  psig requirements, the following requirements shall be
met.
  (a) The size of each connection shall be as large as that of the  main
riser  and,  except in sprinkler systems in multiple dwellings, shall be
at least three inches and shall be controlled by an  accessible  shutoff
valve.
  (b) The service pipe shall be flushed out thoroughly before connecting
to  the  sprinkler system. A flow sufficient to produce a water velocity
of at least five fps shall be used.
  (c) Each service shall be equipped, under the sidewalk, with a control
valve in a flush sidewalk box located within two feet of the front  wall
of  the  building  or  street  line  as  required  by  the department of
environmental protection. The location of the  control  valve  shall  be
indicated  by  a  sign  placed  on  the  structure directly opposite the
sidewalk flush box, and such sign shall have a white background with one
inch red letters  reading:  "Automatic  Sprinkler  Shutoff  Valve...Feet
Opposite  This  Sign." Alternatively, brass, bronze, or other metal sign
with one inch letters, raised or counter-sunk one-eighth of an inch  may
be used.
  (d)  The  plans  submitted  in  connection with the permit application
shall be accompanied by a statement from the bureau of water  supply  of
the  department  of environmental protection, stating the size of street
main or mains, distance to and size of mains from which it or  they  are
fed,  the location of control valves, the static pressure on the hydrant
nearest the premises, and the residual pressure in the street main taken
on a hydrant near the premises when the flow from the nearest hydrant is
equal to the flow required to meet the requirements of this  section.  A
letter   from   the   bureau  of  water  supply  of  the  department  of
environmental protection estimating available flow and residual pressure
shall be acceptable to the borough superintendent when  a  hydrant  test
cannot be conducted.

Section 27-964

Section 27-964

  §  27-964  Sprinkler  booster  pumps. Where the pressure from the city
water main is insufficient to comply with the  requirements  of  section
27-963  of  this article but is sufficient to give at least five psig at
the highest line of sprinklers as  determined  by  test,  an  automatic,
electrically  driven  pump  installed  for  the  purpose  of boosting or
increasing the city water  pressure  in  the  sprinkler  system  may  be
accepted subject to the following requirements:
  (a) Pumps shall be of approved centrifugal type, capable of delivering
at  least two hundred gpm, and shall be capable of supplying twenty-five
per cent of the heads, in the largest area supplied, at twenty gpm, at a
pressure of at  least  twenty-five  psig  at  the  top  of  the  highest
sprinkler riser.
  (b)  Pumps  shall  be maintained under approved automatic control with
closed circuit supervisory attachment. The supervisory attachments shall
be directly connected to an office where maintenance  personnel  are  in
attendance twenty-four hours a day; or, in lieu thereof, the supervisory
attachment  may  be  directly  connected  to  the  central station of an
approved operating fire alarm company. The  supervisory  alarm  services
shall  be  arranged  so as to provide positive indication at an approved
central office or sprinkler alarm panel board that the pump has operated
or that the source of electrical supply has failed.
  (c) Such pumps shall also comply with  the  applicable  provisions  of
sections  27-946  and 27-947 of article three of this subchapter, except
that only one supply  shall  be  required  and  no  enclosure  shall  be
required.

Section 27-965

Section 27-965

  § 27-965 Gravity and pressure tanks. When the requirements of sections
27-963  and  27-964  of  this article are not met, a pressure or gravity
tank or other device  shall  be  used,  complying  with  the  applicable
provisions  of subchapter sixteen of this chapter and reference standard
RS 17-2, RS 17-2A or RS 17-2B.

Section 27-966

Section 27-966

  § 27-966 Protection of sprinkler system. (a) All parts of an automatic
system exposed to freezing temperatures shall be protected from freezing
in  accordance with the provisions of section 27-949 of article three of
this subchapter, or in lieu thereof, an automatic drypipe  system  or  a
system filled with a nonfreezing, noncombustible solution shall be used,
and  when  a  system  filled  with  nonfreezing solution is used and the
system is connected to a potable water supply, it shall  be  subject  to
the requirements of the health department and the bureau of water supply
of the department of environmental protection.
  (b) Sprinkler heads subject to damage shall be protected in accordance
with  the applicable provisions of reference standard RS 17-2, RS 17-2A,
or RS 17-2B.

Section 27-967

Section 27-967

  §  27-967 Inspection and tests. All inspections and tests of sprinkler
systems  shall  be  conducted  in  accordance  with  the  provisions  of
subdivisions  a  through  f  of  section 27-951 of article three of this
subchapter and the requirements of this article.
  (a) Automatic wet and dry systems. Automatic  wet  and  dry  sprinkler
systems  shall  be subjected to a hydrostatic pressure test for a period
of one hour at a pressure of at least one hundred psig  at  the  topmost
sprinkler  head  and  at  least  two  hundred  psig  at the lowest cross
connection to the siamese connections.
  (b) Automatic dry pipe systems. In addition to the hydrostatic test in
subdivision (a) of this section, the automatic dry  pipe  systems  shall
also  be tested to forty psig air pressure for a twenty-four hour period
with the pressure loss not to exceed one and one-half psig.
  (c) Nonautomatic sprinkler  systems.  Nonautomatic  sprinkler  systems
shall  be  subjected to a hydrostatic pressure test of fifty psig at the
topmost sprinkler head, with the test pressure maintained for  a  period
of at least one hour.
  (d)  Pressure tanks. Pressure tanks shall be hydrostatically tested to
a pressure of at least one and one-half times the working pressure for a
period of one hour.
  (e)  Sprinkler  branches  and  heads  supplied  from  domestic  water.
Sprinkler branches and heads shall be tested at the pressure required by
this section or at the pressure of the domestic water supply as required
by subchapter sixteen of this chapter, whichever is greater.
  (f)  System performance. A performance or operation test shall be made
on  each  completed  system  to  determine  that  all  alarms,   valves,
indicators,   pumps,   deluge   valves,   dry  pipe  valves,  and  other
appurtenances are in good working order.
  (g) Supervisory service. All components connected to a central station
of an approved operating fire alarm company shall be tested to determine
that  they  are  in  good  working  order.  The  test  report  shall  be
accompanied  by  a statement from the central supervisory agency stating
that the agency has been retained to provide the  required  supervision;
and when the services of the agency have been terminated it shall notify
the commissioner in writing.
  (h)  Altered systems. When additions, alterations, or repairs are made
to a sprinkler system, the entire system shall be tested  as  stated  in
subdivisions  (a),  (b),  (c), (e), and (g) of this section, except that
the pressure at the top of the system need not exceed one hundred  psig.
In  addition,  a  flow  test of at least twenty gpm shall be made from a
test connection at the end  of  the  sprinkler  header  or  the  section
altered or repaired.
  (i)  Pump  tests.  Pumps  shall  be  tested  in  accordance  with  the
applicable provisions of subdivisions (h) and (i) of section  27-951  of
article three of this subchapter.