Article 7 - WOOD

Section 27-617

Section 27-617

  §  27-617 General requirements. Materials (other than non-stress grade
lumber), design, and construction methods shall meet the requirements of
the following reference standards:
  (a) Lumber and timber. Reference standard RS 10-8.
  (b) Plywood. Reference standard RS 10-9.
  (c) Structural glued--laminated lumber. Reference standard RS 10-18.

Section 27-618

Section 27-618

  §  27-618  Identification.  Except as provided for in subdivisions (a)
and (c) of this section, all wood used for structural elements shall  be
identified as to grade and shall bear an identifying mark of an approved
bureau  or agency performing the grading, or the official grade mark and
trade mark of the bureau or association under whose rules the  wood  was
graded, in accordance with the following:
  (a)  Lumber  and  timber.  All lumber and timber, including non-stress
grade lumber, shall be identified by the grade mark of a lumber  grading
or inspection bureau or agency approved by the commissioner, except that
pre-cut  material  and rough-sawn lumber may be covered by a certificate
of inspection issued by a lumber grading or inspection  agency  approved
by the commissioner in lieu of grade marking.
  (b) Plywood. Plywood used structurally shall bear identification as to
grade,   type,   and   species  group,  or  identification  index.  Such
identification shall be affixed by and identified by the trademarks of a
testing and grading agency approved by the commissioner.
  (c) Glued-laminated. Glued-laminated  structural  members  shall  bear
identification   and/or   shall   be  accompanied  by  certification  in
accordance with the provisions of reference standard RS 10-18.
  (d) Resawn lumber. Resawn  (or  reused)  lumber  shall  be  marked  in
accordance with its regraded status.

Section 27-619

Section 27-619

  §  27-619  Use  of  non-stress grade wood. The use of non-stress grade
wood  in  structural  elements  shall  be  limited  to   the   following
conditions:
  (a)  Studs,  joists,  and  rafters  proportioned  on  the basis of the
empirical provisions of section 27-622 of this article.
  (b) The architect or engineer responsible for the design may assign an
allowable stress value for the proposed material based on the provisions
of reference standard RS 10-8 relating to  "other  species  and  grade".
Under  such  condition, the required species and grade of wood, together
with the assigned stress value, shall be conspicuously indicated on  the
plans.

Section 27-620

Section 27-620

  §   27-620   Quality   control.   Inspection  of  the  fabrication  of
glued-laminated assemblies, as stipulated in table 10-2, shall include a
check of sizes of members, of fit, and of gluing operations.

Section 27-621

Section 27-621

  §  27-621  General  construction  requirements. The provisions of this
section shall be considered as supplemental to  the  provisions  of  the
applicable reference standards.
  (a)  Firecutting.  The ends of wood beams, joists, and rafters resting
on masonry or concrete walls shall be firecut to a bevel of three inches
in their depth.
  (b) Protection of members.
  (1) Positive drainage shall  be  provided  for  all  areas  under  the
building not occupied by basements or cellars.
  (2) All loose wood and debris and all wood forms shall be removed from
spaces  under  the  building. All stumps and roots shall be grubbed to a
minimum depth of twelve inches.
  (3) Wood members embedded in the ground and used for  the  support  of
buildings shall be treated.
  (4) Wood joists or wood structural floors closer than eighteen inches,
wood  girders  closer  than  twelve  inches,  or sills closer than eight
inches to an exposed ground surface within or without the building shall
be treated or shall be of an equivalent resistant species.
  (5) Sleepers, sills, columns,  and  posts  supported  on  concrete  or
masonry  piers  shall  be treated or shall be of an equivalent resistant
species unless isolated from the ground as specified in  paragraph  four
of  this subdivision or by a concrete slab. Where the isolation consists
of a concrete slab-on-grade, the  sleepers,  sills,  columns,  or  posts
shall be raised at least three inches above the top of such slab.
  (6)  Ends  of wood girders entering masonry or concrete walls shall be
provided with a minimum one-half inch air space on top,  sides,  and  at
the  end,  unless the girder is treated or is of an equivalent resistant
species.
  (7) Wood or plywood used as siding or  a  combination  of  siding  and
sheathing shall be isolated from exposed ground by at least six inches.
  (8)  Crawl spaces shall be ventilated as required in subchapter twelve
of this chapter.
  (9) Where treated timber is required, the preservative treatment shall
comply with reference standards RS 10-20 and RS 10-22. Treatment of wood
poles shall comply with reference standard RS 10-28.  All  treated  wood
shall be handled in accordance with the provisions of reference standard
RS 10-29.

Section 27-622

Section 27-622

  §  27-622  Empirical  provisions  in lieu of design. The provisions of
this section may be used in lieu of structural analysis only  for  those
buildings   in  occupancy  group  J-3  where  the  specific  occupancies
correspond to a live load requirement of forty  psf,  or  less,  and  to
constructions  wherein  the  supporting  framing  consists  of multiple,
closely spaced members, such  as  joists,  studs,  platform  or  balloon
frames.  All  wood  structural  members in other classes of construction
shall be proportioned on the basis of  the  analysis  of  stresses.  All
requirements established in this section may be reduced when an analysis
of  stresses,  executed  in  accordance with reference standard RS 10-8,
indicates such reduction is feasible. Sizes of wood  members  stated  in
this section are nominal sizes.
  (a) Stud walls and partitions.
  (1)  Studs  shall  be  of  equivalent or better grade than the minimum
grades for the various species as established in reference  standard  RS
10-13.
  (2)  Corner  posts  shall  be  3-stud members or members of equivalent
strength.
  (3) Load bearing studs shall be set  with  the  larger  cross  section
dimension  perpendicular  to  the  wall  or partition. Studs in exterior
walls of one story buildings of construction class II-D and  II-E  shall
be  at  least  two  inches  by three inches spaced not more than sixteen
inches on center, or where studs are two inches by four  inches,  spaced
not  more  than twenty-four inches on center. Studs for other classes of
construction shall be at least two inches by four inches spaced not more
than sixteen inches on center.
  (4) Stud walls resting on concrete or  masonry  shall  have  sills  at
least  two  inches  in  nominal  thickness.  Where  such  sills  bear on
concrete, they shall  be  fastened  with  minimum  one-half  inch  bolts
embedded  at  least  six inches. Each sill piece shall have at least two
anchor bolts, with one bolt located at least one inch from each  end  of
the plate, and with intermediate spacing not more than eight feet. Where
such  sills  bear  on masonry, they shall be anchored in accordance with
the applicable provisions of reference standard RS 10-1.
  (5) Stud partitions that rest directly over each  other  and  are  not
parallel to floor joists or beams may extend down between the joists and
rest  on the top plate of the partition, partition girder, or foundation
below, or may be constructed on sill plates running on top of the  beams
or joists.
  (6)  All  load  bearing  stud  partitions shall be supported on walls,
other partitions, double joists or beams, solid bridging, or on beams at
least as wide as the studs. Joists supporting a  partition  parallel  to
the  joists wherein the joists are spaced apart to permit the passage of
piping or duct work shall be provided with solid blocking  at  intervals
of not more than sixteen inches.
  (7)  Load  bearing  partitions  perpendicular  to  joists shall not be
offset from supporting girders, walls or partitions  by  more  than  the
depth  of  the joists unless the joists are proportioned on the basis of
analysis of stress.
  (8) In interior walls and in bearing partitions, double studs shall be
provided at the sides of openings that are greater than three  feet  six
inches  up  to  six feet in width, and triple-studs shall be provided at
the sides of openings of greater width.
  (9) Headers shall be provided over each opening in exterior walls  and
bearing  partitions.  Where the opening does not exceed three feet, each
end of the header shall be supported on a stud or framing anchor.  Where
the  opening exceeds three feet in width each end of the header shall be

supported on one stud and where the opening exceeds six  feet  each  end
shall be supported on two studs.
  (10)  All  studs  in exterior walls and in bearing partitions shall be
capped with double  top  plates  installed  to  provide  overlapping  at
corners  and  at  intersections with other walls and bearing partitions.
End joists in double top plates shall be  offset  at  least  twenty-four
inches.  In  lieu  of  double top plates, a continuous header of similar
dimensions may be used. For platform  frame  construction,  studs  shall
rest on a single bottom plate.
  (b)  Bracing of exterior walls. Exterior stud walls shall be braced by
one inch by four inch continuous diagonal strips let into  the  face  of
the  studs  and  into  the  top  and bottom plates at each corner of the
building. Bracing may also be provided by one of the following means:
  (1) Wood board  sheathing  of  one  inch  nominal  thickness,  applied
diagonally.
  (2)  For  one and two-story dwellings, plywood sheathing at least four
feet by eight feet (except where cut to  fit  around  openings  and  for
similar purposes) and at least five-sixteenths of an inch thick on studs
spaced  sixteen  inches or less on centers and at least three-eighths of
an inch thick on studs spaced more than sixteen inches but not exceeding
twenty-four inches on centers.
  (3) For one story dwellings and for  the  upper  story  of  two  story
dwellings,  fiberboard  sheathing  applied vertically in panels at least
four feet by eight feet (except where cut to fit around openings and for
similar purposes). Fiberboard sheathing shall be at least one-half  inch
thick  and  shall  conform  to  the  provisions of reference standard RS
10-27.
  (4) For one story dwellings and for  the  upper  story  of  two  story
dwellings,  gypsum  board  sheathing  applied  horizontally in panels at
least two feet by eight feet (except where cut to  fit  around  openings
and for similar purposes). Gypsum boards shall be at least one-half inch
thick  and  shall  conform  to  the  provisions of reference standard RS
10-19.
  (c) Floor and roof framing.
  (1) SPAN TABLES. Joists and rafters may be  used  in  accordance  with
reference standard RS 10-13.
  (2)  BRIDGING.  In all floor and roof and roof framing, there shall be
at least one line of bridging for each eight feet of span. The  bridging
shall  consist  of  at least one inch by three inch lumber or equivalent
metal bracing. A line of  bridging  or  solid  blocking  shall  also  be
required  at supports unless lateral support is provided by nailing to a
beam, header, or to the studs. Midspan  bridging  is  not  required  for
floor or roof framing in one- and two-family dwellings where joist depth
does  not exceed twelve inches. Bridging shall bear securely against and
be anchored to the members to be braced.
  (3) NOTCHES. Notches in the ends  of  joists  and  rafters  shall  not
exceed one-fourth the depth unless adequate reinforcement is provided or
analysis of stresses indicates that larger openings are feasible without
the  necessity  for reinforcement. Notches in joists or rafters, located
in the span shall not exceed  one-sixth  the  depth  and  shall  not  be
located in the middle third of the span. Bored holes shall not be within
two inches of the top or bottom of the joists or rafter and the diameter
of  any  such  hole  shall  not  exceed  one-third  the depth. For stair
stringers, the minimum effective depth of the wood at any notch shall be
three and one-half inches unless the stringer is continuously  supported
on a wall or partition.
  (4) SUPPORT.
  a. Floor or roof framing may be supported on stud partitions.

  b.  Tail  beams over twelve feet long and all header and trimmer beams
over six feet long shall be hung in metal stirrups having anchors, or by
other methods providing adequate support. Trimmers and headers shall  be
doubled where the header is four feet or more in length.
  c.  Except where supported on a one inch by four inch ribbon strip and
nailed to the adjoining stud, the ends of floor  joists  shall  have  at
least one and one-half inches of bearing on wood or metal, nor less than
four inches on masonry.
  d.  Joists  framing  from  opposite  sides of and supported on a beam,
girder, or partition shall be lapped at least four inches and  fastened,
butted  end-to-end  and  tied by metal straps or dogs, or otherwise tied
together in a manner providing adequate support.
  e. Joists framing into the side of a wood girder shall be supported by
framing anchors, on ledger strips at least two inches by two inches,  or
by equivalent methods.
  f.  Wood joists and rafters bearing on masonry walls shall be anchored
to such walls in accordance with the applicable provisions of  reference
standard RS 10-1.
  (5) RAFTERS AND CEILING JOISTS.
  a.  Where  rafters meet to form a ridge, they shall be placed directly
opposite each other and nailed to a ridge board at least one inch thick,
and not less than the cut end of the rafters in depth.
  b. Provisions shall be made to resist the thrust from inclined rafters
by connection of collar beams at  least  one  inch  by  six  inches,  by
connection to joists, or by equivalent means.
  c.  Where  ceiling  joists are not parallel to rafters, subflooring or
metal straps attached to the ends of the rafters shall be installed in a
manner to provide a continuous tie across the building.
  d. Ceiling joists  shall  be  continuous,  or  where  they  meet  over
interior  partitions,  shall  be securely joined to provide a continuous
tie across the building.
  e. Valley rafters shall be double members. Hip rafters may  be  single
members.  Valley  and  hip  rafters shall be two inches deeper than jack
rafters.
  f. Trussed rafters shall be designed in accordance with the provisions
of reference standard RS 10-8.
  (6) Built-up members shall be securely spiked or bolted  together  and
provision   shall  be  made  to  resist  the  horizontal  shear  between
laminations.
  (d) Nailing schedule. The size and number  of  nails  for  connections
shall be in accordance with table 10-4.

Section 27-623

Section 27-623

  §  27-623  Heavy  timber  construction  (construction class II-A). (a)
Minimum sizes of members. To  conform  to  the  fire  resistance  rating
requirements  for  heavy  timber construction (construction class II-A),
members shall be solid sawn or solid glue-laminated and of the following
minimum dimensions: (Sizes of wood members indicated in this section are
nominal sizes).
  (1) COLUMNS, FRAMES AND ARCHES.
  a. Columns shall be at least  eight  inches  in  all  dimensions  when
supporting  floor  loads,  and at least six inches wide and eight inches
deep when supporting roof and ceiling loads only.
  b. Beams and girders shall be at least six inches wide and ten  inches
deep.
  c.  Frames  or  arches  that  spring  from grade or the floor line and
support floor loads shall be at least eight inches in all dimensions.
  d. Timber trusses supporting floor loads shall have members  at  least
eight inches in all dimensions.
  e.  Frames  or  arches for roof construction that spring from grade or
the floor line and do not support floor  loads  shall  have  members  at
least  six  inches  wide and eight inches deep for the lower half of the
height, and at least six inches deep for the upper half.
  f. Frames or arches for roof construction that spring from the top  of
walls  or wall abutments, framed timber trusses, and other roof framing,
which do not support floor loads,  shall  have  members  at  least  four
inches  wide  and six inches deep. Spaced members may be composed of two
or more pieces at least three inches thick when blocked solidly  through
their  intervening  spaces  or  when such spaces are tightly closed by a
continuous wood cover plate at least two inches  thick  secured  to  the
underside  of  the members. Splice plates shall be at least three inches
thick. When protected by approved automatic sprinklers  under  the  roof
deck, framing members shall be at least three inches wide.
  (2) FLOORS.
  a.  Planks  shall be splined or tongue-and-groove, not less than three
inches thick, covered with one  inch  tongue-and-groove  flooring,  laid
crosswise or diagonally to the plank, or other surface having equivalent
fire resistance; or shall be,
  b.  At  least  four  inches  wide, set on edge close together and well
spiked, and covered the same as for three inch thick plank.  The  planks
shall  be  laid so that there is no continuous line of end joints except
at points of support. Floors shall not extend closer than one-half  inch
to  walls  to provide an expansion joint, but the joint shall be covered
at top or bottom to avoid flue action.
  (3) ROOF DECKS. Roof  decks  shall  be  splined  or  tongue-and-groove
planks  at  least  two inches thick; or tongue-and-groove plywood panels
(bonded with exterior glue) at least one and one-eighth inch thick, with
face grain perpendicular to supports that shall be spaced not more  than
forty-eight  inches  on  center; or of planks at least three inches wide
set on edge close together and laid as required for floors.
  (b) Construction details. Self releasing  type  wall  plate  boxes  or
approved  hangers  shall  be  provided  where  beams  and  girders enter
masonry.

         (For Table 10-4 see chapter 839  of the  laws of 1986)

   ______________________________________________________________
   1                                                            |
   2                                                            |
   3          COPY OF Chapter 839 of the laws of 1986           |

   1          MAY BE OBTAINED FROM:                             |
   2          NYS LEGISLATIVE BILL DRAFTING COMMISSION          |
   3          CONTACT: LEGISLATIVE RETRIEVAL SYSTEM'S HELPLINE  |
   4                                                            |
   5                                                            |
   6____________________________________________________________|

Section 27-624

Section 27-624

  §  27-624  Construction  methods. (a) Fabrication. All timber shall be
accurately cut and framed to a close fit  in  such  a  manner  that  the
joints  will have even bearing over the contact surfaces. Mortises shall
be true to size for their full depth and tenons  shall  fit  snugly.  No
shimming in joints, or open joints, shall be permitted.
  (b) Erection.
  (1)  ASSEMBLY.  Joints  shall  have  a  tight  fit. Fasteners shall be
installed in a manner that will not damage  the  wood.  End  compression
joints  shall be brought to full bearing. All framework shall be carried
up true and plumb.
  (2) TEMPORARY CONNECTIONS. As erection progresses, the work  shall  be
bolted,  or  nailed  as  necessary,  to  resist all dead load, wind, and
erection stresses.
  (3) ALIGNMENT. The structure shall be properly  aligned  before  final
tightening of the connections.