Section 27-735
§ 27-735 Artificial light requirements. Adequate means for producing
artificial light by electricity shall be provided in every room or floor
space in every building hereafter erected and in the portions of
existing buildings where alterations are performed except as follows:
(a) Artificial light need not be provided in rooms or spaces occupied
exclusively during the daylight hours between one hour after sunrise and
one hour before sunset, and which are provided with natural light
meeting the requirements of sections 27-733 and 27-734 of article three
of this subchapter.
(b) Artificial light need not be provided in rooms or spaces with less
than forty square feet of floor area if they are used exclusively for
storage purposes or for mechanical facilities containing no rotating or
moving parts, no combustion equipment, or no other hazardous equipment.
Section 27-736
§ 27-736 Means of egress. All means of egress shall be provided with
the levels of artificial illumination as required in article six of
subchapter six of this chapter.
Section 27-737
§ 27-737 Places of assembly. All places of assembly shall be provided
with the levels of artificial illumination as required in subchapter
eight of this chapter.
Section 27-738
§ 27-738 Bathrooms and toilet rooms. In all bathrooms and toilet
rooms, the required means for producing artificial illumination shall be
capable of producing an average intensity of not less than ten foot
candles, when measured at thirty inches above the floor.
Section 27-739
§ 27-739 Yards and courts. Where a building is classified in occupancy
group J-1 or J-2, or where a building contains a space or spaces
classified in occupancy group J-1 or J-2, all yards and courts shall be
provided with adequate means of providing artificial light by
electricity having a minimum intensity of not less than one foot candle
measured at the lower level or levels of all yards or courts.