Article 9 - NOISE CONTROL IN MULTIPLE DWELLINGS

Section 27-768

Section 27-768

  §  27-768  Requirements.  Interior  walls,  partitions,  floor-ceiling
constructions, and  mechanical  equipment  in  spaces  or  buildings  of
occupancy group J-2 shall be designed and constructed in accordance with
the  requirements  of this subchapter, to provide minimum protection for
each dwelling unit from extraneous noises emanating from other  dwelling
units  and  from  mechanical equipment. In addition, airborne sound from
exterior mechanical equipment of buildings in any occupancy group  shall
conform to the requirements of this subchapter.
  (a)  Field  testing.  Where  conditions  indicate  that  the installed
construction or equipment does not meet the noise control prescribed  in
this subchapter, measurements shall be taken to determine conformance or
non-conformance.  For  conformance  with this subchapter, the results of
such measurements shall not fail  by  more  than  two  db  to  meet  the
requirements  in any octave band, or by more than two points to meet any
STC or INR requirements.
  (b) Materials or  assemblies  of  materials  utilized  to  meet  noise
control  requirements shall comply with load bearing, fire protection or
other applicable requirements of this code  for  walls,  partitions  and
floor-ceiling constructions.

Section 27-769

Section 27-769

  §  27-769  Acoustical isolation of dwelling units. (a) Airborne noise.
(1)  Walls,  partitions,  and  floor-ceiling  constructions   separating
dwelling  units  from  each  other  or  from public halls, corridors, or
stairs shall have a minimum sound transmission  class  (STC)  rating  of
forty-five  for  airborne  noise.  This  requirement  shall not apply to
dwelling unit entrance doors. However, such doors shall fit closely  and
not  be  undercut.  For  permits  issued  after  January first, nineteen
hundred seventy-two, the STC required shall be fifty for airborne noise.
For   permits   issued   after   April   thirtieth,   nineteen   hundred
seventy-three,  dwelling unit entrance doors shall have a minimum STC of
thirty-five.
  (2) STC ratings shall be obtained by  tests  conducted  in  accordance
with  the procedures of reference standard RS 12-2 except as provided in
paragraph three of this subdivision.
  (3) The STC ratings of construction assemblies as listed in  reference
standard  RS  12-2  may  be  used  to  determine  conformance  with  the
requirements of paragraph one of this subdivision  and  with  any  other
section that requires a specific STC rating.
  (4)  Penetrations or openings in walls, partitions, or floors for pipe
sleeves, medicine cabinets, hampers, electric devices, or similar  items
shall be packed, sealed, lined, back-plastered, or otherwise isolated by
sufficient mass to maintain the required STC ratings.
  (5)  Where  grilles,  registers, or diffusers in one dwelling unit are
connected by duct-work with grilles, registers, or diffusers in  another
dwelling  unit,  and  where such connecting duct is less than seven feet
long, it shall be lined with duct lining; otherwise, an  approved  sound
attenuating device shall be installed therein. Duct lining shall conform
to the requirements of subchapter thirteen of this chapter.
  (b)  Structure-borne noise. (1) Floor-ceiling constructions separating
dwelling units from each other or from public halls or  corridors  shall
have a minimum impact noise rating (INR) of zero.
  (2)  Such  INR shall be obtained by tests conducted in accordance with
the procedure of reference  standard  RS  12-3  except  as  provided  in
paragraph three of this subdivision.
  (3)  The  INR  of  floor-ceiling  constructions  listed  in  reference
standard RS 12-3  shall  be  used  to  determine  conformance  with  the
requirements  of  paragraph  one  of this subdivision and with any other
paragraph that requires a specific INR. Constructions shall be  designed
and  installed  to avoid short circuiting the isolation devices that are
incorporated into the constructions.
  (4) This subdivision shall apply  only  to  construction  pursuant  to
permits  issued after the thirty-first day of December, nineteen hundred
seventy-six.

Section 27-770

Section 27-770

  §  27-770  Noise control of mechanical equipment. (a) Minimum airborne
noise insulation requirements.
  (1) BOILER ROOMS.  Boiler  rooms  adjoining  dwelling  spaces,  either
vertically   or   horizontally,   shall   be   separated   therefrom  by
floor-ceiling or partition constructions having a minimum STC rating  of
fifty.
  (2)  MECHANICAL  EQUIPMENT  SPACES.  Spaces  or  shafts containing air
conditioning,  refrigeration,   or   ventilating   equipment,   elevator
machinery,  or  other  mechanical  equipment  shall  be  separated  both
vertically and horizontally from dwelling units  by  constructions  that
will  provide a minimum STC rating of fifty. Spaces or shafts containing
equipment totaling more  than  seventy-five  rated  h.p.  shall  not  be
located vertically or horizontally adjacent to dwelling units unless the
total  sound  power  level  output  of all the equipment in the space or
shaft is certified not to exceed the maximum sound power levels of table
12-3 in any octave  band.  Such  sound  power  level  ratings  shall  be
obtained  by  tests  conducted  in  accordance  with  the  procedures of
reference standard RS 12-5.
  a. Ventilating openings into mechanical equipment spaces.  Ventilating
openings  into  boiler rooms and other mechanical equipment spaces shall
not be located in yards or courts where there are windows  opening  from
living  quarters,  unless  such  ventilating  openings are provided with
sound attenuating devices if needed to limit noise transmission to NC-40
(noise criterion) levels in the  exposed  dwelling  units.  For  permits
issued   after   January   first,   nineteen  hundred  seventy-two,  the
permissible noise levels shall not exceed NC-35.
  b. Noise criteria requirements. Noise criteria requirements prescribed
in this subchapter shall be in accordance  with  reference  standard  RS
12-4.

 Table 12-3 Maximum Sound Power Levels Permitted in Mechanical Spaces or
                    Shafts Adjoining Dwelling Spaces
========================================================================
                                             Max. Sound Power
                                                Level db(a)
                                   -------------------------------------
Octave Bands, c.p.s.                  db re                  db re
   Mid-Frequency                  10(-13) Watts          10(-12) Watts
------------------------------------------------------------------------
        63                              101                     91
       125                              101                     91
       250                              103                     93
       500                              105                     95
      1000                              102                     92
      2000                              101                     91
      4000                               98                     88
      8000                               96                     86
========================================================================

Notes:
  a.  The  maximum  sound  power  levels shall be reduced five db in any
octave band where the equipment data indicate pure tone generation.  The
presence  of  pure  tones may be determined by means of one-third octave
band analysis. The criterion for a significant pure-tone component shall
be an audible pure-tone sound together with an  increase  of  the  sound
pressure level in the corresponding one-third octave band above the mean
of the two adjacent one-third of at least:

Center frequency of
  one-third octave
  band..........  40/125    160/250   215/500   630/1,000   1,000/10,000
Increase in sound
  pressure level
  (db)............   6         4         3          2           1 1/2
------------------------------------------------------------------------
  b.   For   permits   issued  after  January  first,  nineteen  hundred
seventy-two, the maximum sound power levels shall be changed as follows:

========================================================================
Octave Bands, c.p.s.                  db re                  db re
   Mid-Frequency                    10(-13) Watts          10(-12) Watts
------------------------------------------------------------------------
        63                                 98                    88
       125                                 97                    87
       250                                100                    90
      1000                                 97                    87
      2000                                 96                    86
      4000                                 93                    83
      8000                                 91                    81
========================================================================

  (3)  DUCTWORK.  Ducts  serving dwelling units shall be lined with duct
lining for at least twenty  feet  from  the  fan  discharge  or  intake;
otherwise,  an  approved  sound  attenuating  device  shall be installed
therein. All toilet exhaust ducts shall be lined with duct lining for at
least twenty feet upstream of the  exhaust  fan  intake,  otherwise,  an
approved  sound  attenuating  device  shall  be  installed therein. Duct
lining shall conform to the requirements of subchapter thirteen of  this
chapter.
  (4)  EXTERIOR MECHANICAL EQUIPMENT. Mechanical equipment in a building
in any occupancy group, when located outside of the building in  a  yard
or  court  or on a roof, or where the equipment opens to the exterior of
the building, shall be subject to the noise output limitations given  in
table  12-4 where one or more windows of a dwelling unit in any building
in occupancy groups J-1, J-2, or J-3 is located within a sphere  of  one
hundred  foot  radius  whose  center is any part of the equipment or its
housing, unless it can be shown  that  the  sound  pressure  levels,  in
octave  bands,  of  the exterior mechanical equipment as measured within
the dwelling unit do not exceed the levels given in table 12-5.

          (For Table 12-4 see chapter 839 of the laws of 1986)

Notes:
  a.  The  minimum  distance  shall  be  measured  in  a  straight  line
regardless   of  obstructions.  Interpolated  levels  may  be  used  for
distances between those given in this table. See note a. at end of table
12-3.
  1. In the event sound power level data  for  the  exterior  mechanical
equipment  is  not available, the sound pressure levels in octave bands,
of the exterior mechanical equipment shall be measured.
  2. The measurements shall be  obtained  with  the  microphone  of  the
measuring  equipment  located  at  the  interior  of  the  dwelling unit
affected in a line with  the  window  nearest  the  exterior  mechanical
equipment.  The  window  shall be fully open and the microphone shall be
located three ft. away from the open portion of the window.

  3. Measurements shall be obtained during times when the ambient  sound
pressure  levels,  in  octave  bands,  are  at least six db lower at all
octave bands than the sound pressure levels measured with  the  exterior
equipment  operating.  By  ambient  sound  pressure  levels is meant the
measured  sound  pressure  levels,  at  the  above  described  measuring
location, with the exterior equipment not in operation.
  b.  For  permits  issued  after  January   first,   nineteen   hundred
seventy-two,  the  permitted  maximum  sound  power  levels for exterior
mechanical equipment adjoining buildings shall be changed as follows:

          (For Table 12-5 see chapter 839 of the laws of 1986)

Notes:
  a. Measurements shall be obtained with a sound level meter and  octave
band  analyzer,  calibrated  both electronically and acoustically before
and after the measurements are made. The equipment used shall  meet  the
requirements of reference standards RS 12-6.
  b.   For   permits   issued  after  January  first,  nineteen  hundred
seventy-two, the maximum sound  pressure  levels  shall  be  changed  as
follows:

  ======================================================================
             Octave Bands                            Decibels
       Center Frequencies (cps)                 re .0002 microbar
------------------------------------------------------------------------
                   63                                   61
                  125                                   53
                  250                                   46
                  500                                   40
                 1000                                   36
                 2000                                   34
                 4000                                   33
                 8000                                   32
========================================================================

  (b)    Minimum   structure-borne   noise   and   vibration   isolation
requirements.   All isolators used  in  accordance  with  the  following
requirements shall be approved.
  (1) BOILER ROOMS.
  a.  Boilers.  All  boilers  supported  on  floors above a story having
dwelling units shall  be  supported  on  resilient  isolators  having  a
minimum  static deflection of one inch. The isolators shall be installed
directly under the structural frame of the boiler.
  b. Boiler  breeching  and  piping.  When  boilers  are  equipped  with
mechanical draft fans, the boiler breeching and piping that is supported
from  or  on slabs, floors, or walls that are contiguous to the dwelling
unit shall be supported for a distance of fifty  pipe  diameters  on  or
from  resilient  isolators.  Each  isolator  shall have a minimum static
deflection of one inch.
  (2) INCINERATOR CHARGING CHUTES.
  a. Metal chutes. Metal chutes,  metal  chute  supports,  and/or  metal
chute  bracing, shall be free of direct contact with the shaft enclosure
and the openings provided in the floor construction. Metal chutes  shall
be  resiliently supported at each structural support location. Isolators
shall provide a minimum static deflection of 0.30 in. All  chutes  shall
be plumb.

  b.  Masonry chutes. The interior chute wall shall be plumb and without
obstructions for the full height of the shaft and shall  have  a  smooth
interior finish.
  (3) PIPING.
  a.   Metal  piping  connected  to  power  driven  equipment  shall  be
resiliently supported from or on the building structure for  a  distance
of  fifty  pipe diameters from the power driven equipment. The resilient
isolators shall have a minimum static deflection of  one  inch  for  all
piping  with  a four inch or larger actual outside diameter and one-half
inch for piping with less than four inches in actual  outside  diameter.
Piping connected to fluid pressure-reducing valves, shall be resiliently
isolated  for  a distance of fifty pipe diameters from pressure reducing
valves and isolators  shall  provide  a  minimum  static  deflection  of
one-half inch.
  b.   Equipment  such  as  heat  exchangers,  absorption  refrigeration
machines, etc., that is located on any floor or roof other than a  floor
on  grade, and that is not power driven but is connected by metal piping
to power driven equipment, shall be resiliently supported from or on the
building structure, for a distance of  fifty  pipe  diameters  from  the
power  driven  equipment.  The  resilient  supports  shall  be vibration
isolators having a minimum static  deflection  of  one  inch  and  shall
incorporate  approved  resilient  pads  having  a  minimum  thickness of
one-quarter inch.
  (4) Fans. Except for fans installed in compliance with section  27-353
of  article  five  of  subchapter five of this chapter all fan equipment
located on any roof or floor other  than  a  floor  on  grade  shall  be
mounted  on or from vibration isolators. Fan equipment with motor drives
separated from the fan equipment  shall  be  supported  on  an  isolated
integral  rigid  structural  base supporting both the fan and motor. Fan
equipment with motor drives supported from the fan  equipment  shall  be
mounted  directly  on  vibration  isolators.  Each  isolator  shall have
provision for  leveling.  Isolators  shall  incorporate  resilient  pads
having  a minimum thickness of one-quarter inch. The vibration isolators
shall provide a minimum isolator efficiency of  ninety  percent  at  fan
rotor  rpm with a maximum deflection of two inches. Fans and compressors
of three h.p. or less assembled in  unitary  containers  may  meet  this
requirement  with  isolators  internal  to  the  container providing the
isolators meet the above minimum isolator efficiencies.
  (5) PUMPS. All pumps of three h. p. or more located on any floor other
than a floor on grade shall be supported on vibration isolators having a
minimum isolation efficiency of  eighty-five  per  cent  at  the  lowest
disturbing  frequency. Each isolator shall incorporate a leveling device
and a resilient pad having a minimum thickness of one-quarter inch.
  (6) COMPRESSORS. Compressors and drives located on a floor other  than
a  floor  on  grade  shall  be  mounted  on vibration isolators having a
minimum isolation efficiency of  eighty-five  per  cent  at  the  lowest
disturbing  frequency. Each isolator shall incorporate a leveling device
and a resilient pad having a minimum thickness of one-quarter inch.
  (7) COOLING TOWERS. All moving parts of cooling towers  located  on  a
roof  or  floor  other  than  a  floor  on  grade  shall be installed on
vibration  isolators  providing  a  minimum  isolation   efficiency   of
eighty-five  per  cent at fan rotor rpm with a maximum static deflection
of four inches.  Each isolator shall incorporate a leveling device and a
resilient pad having a minimum thickness of one-quarter inch.
  (8) EVAPORATIVE CONDENSERS.  Evaporative  and  air  cooled  condensers
located  on a roof or floor other than a floor on grade shall be mounted
on vibration isolators  providing  a  minimum  isolation  efficiency  of
eighty-five  per  cent at fan rotor rpm with a maximum static deflection

of four inches. Each isolator shall incorporate a leveling device and  a
resilient pad having a minimum thickness of one-quarter inch.
  (9)  DUCT  CONNECTIONS TO FAN EQUIPMENT. Flexible connections shall be
installed between fan equipment and connecting ductwork.
  (10) ELEVATOR MACHINERY. Gear-driven  machinery,  gearless  machinery,
motor  generators, and controllers located in an elevator machinery room
or shaft on a roof, or on a floor other than a floor on grade, shall  be
supported  on  vibration  isolator  pads  having  a minimum thickness of
one-half inch.
  (c) Maximum permissible air velocities in ducts.
  (1) DUCTS LOCATED  OVER  CEILINGS  OF  DWELLING  SPACES.  The  maximum
permissible  air  velocity  in  ductwork  located  over  the ceilings of
dwelling spaces or in masonry shafts adjoining dwelling spaces shall not
exceed the velocities prescribed in table 12-6.

         Table 12-6 Maximum Permissible Air Velocities in Ducts
========================================================================
Type of System     Branch Ducts     Sub-Main Ducts     Main Ducts
------------------------------------------------------------------------
Low Velocity          750 fpm          1000 fpm         1500 fpm
High Velocity        1000              2000             3000
========================================================================

  In the application of table 12-6 the following shall apply:
  a. Any duct that connects directly to  any  terminal  device  (grille,
diffuser,  etc.)  shall be classified as a branch duct for a distance of
at least four feet from the terminal device.
  b. Any duct that connects a branch duct to a main duct or to  the  fan
shall  be  classified as a sub-main duct. No duct may be classified as a
sub-main duct if it  connects  to  a  terminal  device  by  means  of  a
connection less than four feet in length.
  c.  When  a  duct  is connected to the fan and to two or more sub-main
ducts it shall be classified as a main duct.
  d. The maximum  velocities  shown  in  table  12-6  for  low  velocity
ductwork  shall  apply  in  all  cases  except  where  a system of round
ductwork is used and an acoustic air control device with  self-contained
attenuation  components  is  located  in the duct work prior to each air
terminal device. Branch ducts,  if  any,  connecting  the  acoustic  air
control devices to the terminals shall not have air velocities exceeding
seven  hundred  fifty  fpm. Maximum power level ratings for the acoustic
air control devices shall be three db less  than  the  values  shown  in
table 12-7.
  (d) Maximum permissible sound power levels of fan coil units, grilles,
registers,  diffusers  and  induction  units. Sound power level data, in
octave bands, shall be certified in accordance with  the  provisions  of
section  27-131  of article seven of subchapter one of this chapter, for
grilles, registers, diffusers and induction units  at  design  operating
conditions and for coil units when operating at specified cfm. The sound
power  levels  shall  not  exceed  the  levels listed in table 12-7 when
measured in accordance with the  provisions  of  reference  standard  RS
12-5.

 Table 12-7 Maximum Permissible Sound Power Levels for Terminal Units(1)
========================================================================
                                        Sound Power Levels, db
    Octave Bands, c.p.s.          ----------------------------------
       Mid-Frequency             db re 10(-13)   db re 10(-12) Watts
________________________________________________________________________
             63                      79                    69
            125                      73                    63
            250                      67                    57
            500                      62                    52
           1000                      59                    49
           2000                      57                    47
           4000                      54                    44
           8000                      53                    43
========================================================================

Note:
  (1)   For   permits  issued  after  January  first,  nineteen  hundred
seventy-two, the Maximum Permissible  Sound  Power  Level  for  terminal
units shall be changed as follows:

========================================================================
    Octave Bands c.p.s.                  Sound Power Levels
      Mid Frequencies        dB re 10(-13) Watts    db re 10(-12) Watts
------------------------------------------------------------------------
             63                       76                     66
            125                       69                     59
            250                       62                     52
            500                       57                     47
           1000                       54                     44
           2000                       52                     42
           4000                       49                     39
           8000                       48                     38
========================================================================