Article 7 - STANDARDS OF MECHANICAL VENTILATION

Section 27-752

Section 27-752

  §   27-752   Areas   requiring   mechanical   ventilation.  Mechanical
ventilation shall be provided in all occupiable rooms  or  spaces  where
the  requirements  for  natural ventilation are not met; in all rooms or
spaces, which because of the nature of their use or  occupancy,  involve
the  presence  of  dust,  fumes,  gases,  vapors,  or  other  noxious or
injurious impurities, or substances which create a fire hazard; or where
required by the provisions  of  article  eight  of  this  subchapter  or
subchapters six through eight of this chapter.

Section 27-753

Section 27-753

  § 27-753 Index for ventilation. The index for ventilation for any room
or space shall be computed by adding the following:
  (a) The contents per occupant, in cubic feet.
  (b) The floor area per occupant, times ten, in square feet.
  (c)  The  clear, unobstructed openable area of windows, skylights, and
other sources of natural ventilation per occupant times two hundred,  in
square feet. In all cases, the number of occupants used in computing the
index  for  ventilation  shall be the maximum number who will occupy the
room or space simultaneously during any two-hour period.

Section 27-754

Section 27-754

  §  27-754  Minimum quantity of outside air for mechanical ventilation.
The minimum quantity of outside air required for mechanical  ventilation
in  any  occupiable  room,  where  not  otherwise  prescribed,  shall be
determined according to table 12-2.

       Table 12-2 Required Minimum Outdoor Air Supply and Exhaust
                            (cfm per sq. ft.)
========================================================================
               Ventilated Rooms    Ventilated Rooms
                 with Natural        without Natural
Index for         Ventilation         Ventilation     Air Conditioned
Ventilation        Openings            Openings            Rooms
------------------------------------------------------------------------
               Supply    Exhaust   Supply  Exhaust    Supply   Exhaust
------------------------------------------------------------------------
   0- 300...     2.5      2.0        2.5     2.0        1.5     1.5
 301- 520...     2.0      1.5        2.0     1.5        1.2     1.2
 521- 850...     1.5      1.25       1.5     1.25       0.9     0.9
 851-1250...      ..      1.0        1.0     1.0        0.6     0.6
1251-1650...      ..      0.67       0.67    0.67       0.5     0.5
over 1650...      ..       ..        0.33    0.33       0.4     0.4
========================================================================

  (a) Window requirements. To be credited as ventilating openings  under
the  provisions of this subchapter, windows or other openings shall meet
the requirements of section 27-749 of article six  of  this  subchapter,
and  where  mechanical  supply ventilation is not provided, shall have a
free openable area of at least one square foot per  one  hundred  square
feet of floor area.
  (b) Air conditioning.
  (1) In air conditioned rooms, the windows and other openings shall not
be  credited  as  such  in  computing  the  index  for  ventilation. Air
conditioned rooms shall be considered as interior rooms.
  (2) Air that has been exhausted from an air conditioned space  may  be
reconditioned   by   air  conditioning  apparatus  and  recirculated  as
equivalent outdoor air, provided that the total of  supply  air  is  not
less  than required for air conditioned rooms by table 12-2 and that the
amount of actual outdoor air is at least thirty-three and one-third  per
cent  of  the  required  total. The actual outdoor air supply shall not,
under any circumstances, be reduced to less than five cfm per  occupant,
except  that these minimum requirements may be reduced by fifty per cent
as provided in section 27-755 of this article.
  (c) Required exhaust. Required exhaust may be accomplished by  raising
the  pressure within the space with consequent leakage through doors and
windows, or by drawing the vitiated air from air conditioned spaces into
the return air duct of air conditioning apparatus  or  into  an  exhaust
duct discharging directly to the outdoor air.
  (d)  Make-up  air.  A  sufficient  quantity of air to make the exhaust
system effective shall be provided to the space being exhausted  by  one
or by any combination of the following methods:
  (1) By supplying air to the space by means of a blower system.
  (2)  By  infiltration  through  louvres, registers, or other permanent
openings in walls, doors, or partitions, adjoining spaces where  air  is
supplied by one of these methods.
  (3) By infiltration through cracks around window sash and doors.
  (4) By other methods acceptable to the commissioner.
  (e)  Prohibited  use  of  recirculated  air. Air drawn from any of the
following spaces may not be recirculated; mortuary rooms;  bathrooms  or

toilet  rooms; or any space where an objectionable quantity of flammable
vapors, dust, odors, or noxious gases is present. Air drawn  from  rooms
that  must  be  isolated to prevent the spread of infection shall not be
recirculated, except that air drawn from hospital operating rooms may be
recirculated, if in compliance with the following requirements:
  (1)  There  shall  be  a  minimum of twenty-five total air changes per
hour, of which five air changes per hour shall be outdoor air.
  (2) All fans serving exhaust systems shall be located at the discharge
end of the system.
  (3) Outdoor air intakes shall be located  at  least  twenty-five  feet
from   exhaust   outlets   of  ventilation  systems  and  other  exhaust
discharges,  combustion  equipment  stacks,  medical   surgical   vacuum
systems,  and  plumbing  vent  stacks,  from  areas  which  may  collect
vehicular exhaust such as off-street loading bays, and from areas  which
may  collect  other  noxious  fumes.  The  bottom of outdoor air intakes
serving central systems if installed above a roof, shall be  located  at
least three feet above roof level.
  (4) Positive air pressure shall be maintained at all times in relation
to adjacent areas.
  (5)  All  ventilation  or  air conditioning systems serving such rooms
shall be equipped with a filter bed of twenty-five per  cent  efficiency
upstream  of  the  air conditioning equipment and a filter bed of ninety
per cent efficiency downstream of  the  supply  fan,  any  recirculating
spray  water  systems  and  water reservoir type humidifiers. All filter
efficiencies shall be average atmospheric dust spot efficiencies  tested
in accordance with ASHRAE standard 52-68.
  (6) A manometer shall be installed across each filter bed.
  (7) Duct linings shall not be used in ventilation and air conditioning
systems  serving  such  rooms unless terminal filters of at least ninety
per cent efficiency are installed downstream of linings.
  (8) Air supplied shall be delivered at or near the  ceilings  and  all
exhaust air shall be removed near floor level, with at least two exhaust
outlets not less than three inches above the floor.
  (f)  Outdoor  air  intakes.  For  high-rise  office  buildings erected
pursuant to new building applications filed on or  after  the  effective
date  of  this  section,  outdoor  air  intakes serving spaces above the
second story and serving spaces greater than ten thousand square feet of
floor area shall be located at least twenty feet above ground level,  at
least  twenty feet from exhaust outlets of ventilation systems and other
exhaust discharges, and at least twenty feet from areas that may collect
vehicular exhaust such as off-street loading bays.

Section 27-755

Section 27-755

  §  27-755  Use  of  adsorption  devices. In all cases where the use of
recirculated air is permitted, the required outdoor air  supply  may  be
reduced  up  to  fifty  per  cent, provided that the recirculated air is
passed through adsorption  devices.  The  adsorption  devices  shall  be
approved  and  rated.  Means  shall  be  provided  for  maintaining  the
effectiveness of the adsorption devices.
  (a) Improper maintenance. Should the adsorption devices be  improperly
maintained so that their effectiveness is impaired, the commissioner may
order  their  removal.  If  the  adsorption devices are removed, the air
conditioning  or  ventilating  system  shall  not  be  operated  without
supplying  one  hundred  per  cent  of  the outdoor air required by this
article or article eight of this subchapter.
  (b) Test records. The building owner shall, at all times,  maintain  a
maintenance  record  showing  the  manufacturer's  recommendation of the
frequency of tests, the method of making tests, and the results  of  all
tests  of the adsorption devices. Such tests shall be made and certified
by the manufacturer or by a laboratory acceptable to the commissioner at
least twice every six  months.  The  records  of  such  tests  shall  be
maintained  for  a  period of at least two years, and shall be available
for inspection by the commissioner.
  (c) Ventilation of water closet compartments. The use  of  any  device
that  returns  exhaust air from water closet compartments or from toilet
rooms after passing through adsorption devices is  not  permitted  as  a
means  of providing ventilation for a water closet compartment for which
a mechanical system of ventilation is required.

Section 27-756

Section 27-756

  §   27-756   Installation   and   operation  of  ventilating  and  air
conditioning systems. Where mechanical ventilation  is  accepted  as  an
alternate  for,  or a supplement to, natural means of ventilation, or is
required under the conditions herein prescribed, or where ventilation is
provided by means of air conditioning system, the system, equipment, and
distributing ducts shall be installed in accordance with the  applicable
provisions of subchapters thirteen through fifteen of this chapter. Such
required  ventilating  and/or  air conditioning systems shall be kept in
operation at all times when the building or space is  being  used  in  a
normal manner in accordance with the purpose for which it was intended.