Article 8 - VENTILATION OF SPECIAL SPACES

Section 27-757

Section 27-757

  § 27-757 Rooms in institutional H-1 occupancy. In occupancy group H-1,
rooms  or  spaces  in  which persons are detained under restraint may be
naturally ventilated by means meeting the intent of this subchapter.

Section 27-758

Section 27-758

  §  27-758  Kitchens.  Kitchens  shall  be  ventilated  as follows: (a)
Kitchens located within dwelling  units  and  having  a  floor  area  of
greater  than  fifty-nine  square feet shall have natural ventilation as
prescribed in article six of this subchapter. When  the  floor  area  is
fifty-nine  square  feet  or  less,  the  kitchen shall be ventilated by
either of the following:
  (1) Natural means complying with article six of  this  subchapter  and
further  that the windows shall have a minimum width of twelve inches, a
minimum area of thee square feet or ten per cent of the  floor  area  of
the space whichever is greater and so constructed that at least one-half
of  their  required area may be opened. When the space is located at the
top story the window or windows may be replaced with  a  skylight  whose
minimum  width  shall be twelve inches, whose minimum area shall be four
square feet or one-eighth the floor  area  of  the  space  whichever  is
greater  and shall have ventilating openings of at least one-half of the
required area of the skylight.
  (2) Mechanical means exhausting at least two cfm  of  air  per  square
foot of floor area. Where doors are used to separate the space the lower
portion  of  each  door  shall  have  a metal grille containing at least
forty-eight square inches of clean openings or in lieu  of  such  grille
two  clear  open  spaces  may  be provided, each of at least twenty-four
square inches, one between the bottom of each door and the floor and the
other between the top of each door and the head jamb.
  (b) Kitchens, except those located within  dwelling  units,  and  side
spaces, where cooking of any kind is done, shall be ventilated by either
of  the  following;  provided  that  in  no  instance  may  there be any
violation of the nuisance provisions of the health code.
  (1) Natural means complying with article six of  this  subchapter  and
supplemented  with  auxiliary  mechanical supply and exhaust ventilation
adequate to remove the fumes and smoke from the cooking  equipment  when
operating.
  (2)  Mechanical  means exhausting at least three cfm of air per square
foot of floor area, but in no case less than one hundred fifty cfm. Such
air shall be exhausted through duct or chimney constructed in accordance
with the provisions of subchapters  thirteen  through  fifteen  of  this
chapter.
  (c) Kitchens, snack bars, or pantries, where the operation consists of
heating  or  warming previously prepared food that was cooked elsewhere,
or preparation of food in vending machines may be ventilated  by  either
of the following:
  (1) Natural ventilation complying with article six of this subchapter.
  (2)  Mechanical  ventilation  complying  with  article  seven  of this
subchapter.

Section 27-759

Section 27-759

  §  27-759 Bathrooms and toilet rooms. Bathrooms and toilet rooms shall
be ventilated as follows:
  (a) When ventilated by natural means, the natural ventilation  sources
shall  comply  with section 27-749 of article six of this subchapter and
shall have an unobstructed free area of at least five per  cent  of  the
floor  area.  In  no  case  shall  the  net free area of the ventilation
sources be less than  one  and  one-half  square  feet  except  that  in
occupancy   groups   H-1  and  H-2,  provided  the  ventilation  opening
conforming with section 27-749 of article six of this subchapter may  be
in  a  vent  shaft provided that the net free area of the opening is not
less than three square feet. The vent shaft cross-sectional  area  shall
be increased by one-fifth of a square foot for every foot of height, but
shall  not  be  less than nine square feet in area and open to the outer
air at the top; or, the vent shaft may be open at the  sides  above  the
roof,  with  louvres  providing  an equivalent net free area at the top,
equal to the area of the shaft.
  (b) By individual vent shafts or ducts constructed  of  noncombustible
materials  with  a  minimum  cross-sectional area of one square foot and
one-third additional square foot for each  additional  water  closet  or
urinal above two in number. The upper termination of such ducts shall be
equipped with a wind-blown ventilator cap.
  (c)  When  a  bathroom  or  toilet  room  is not ventilated by natural
ventilation as required  by  this  section,  it  shall  be  mechanically
ventilated as follows:
  (1)  Rooms  containing  only  one  water  closet  or  urinal  shall be
mechanically ventilated by an exhaust system capable  of  exhausting  at
least  fifty  cubic  feet of air per minute. Means shall be provided for
air ingress by louvres in the door, by  undercutting  the  door,  or  by
transfer ducts, grilles, or other openings.
  (2)  Rooms  containing  more  than one water closet or urinal, and any
auxiliary spaces such as those used in  hand  basins,  slop  sinks,  and
locker rooms, shall be mechanically ventilated by an independent exhaust
system capable of exhausting at least forty cubic feet of air per minute
per  water closet or urinal. The outdoor air supply shall conform to the
requirements of article seven of this subchapter.
  (3) Toilet exhaust systems shall be arranged to expel air directly  to
the outdoors.

Section 27-760

Section 27-760

  §  27-760  Inside locker rooms. Inside locker rooms and dressing rooms
for more than one person shall  be  provided  with  exhaust  ventilation
giving at least four changes of air per hour.

Section 27-761

Section 27-761

  §  27-761  Corridors.  Unless  natural  sources complying with section
27-749 of article six of this subchapter provides  ventilating  openings
equivalent  to  at  least  two  and  one-half percent of the floor area,
corridors in buildings of occupancy groups H-1, J-1 and  J-2  more  than
three  stories  in  height, shall be mechanically ventilated by a system
supplying at least one-half cubic foot of outdoor  air  per  minute  per
square  foot of floor area. When air conditioned, a part of the required
supply may be recirculated as  equivalent  outdoor  air,  but  at  least
thirty-three  and  one-third percent of the required air supply shall be
actual outdoor air.

Section 27-762

Section 27-762

  § 27-762 Crawl spaces. (a) Buildings and structures without basements.
In  buildings and structures constructed without basements, and in which
the first floor construction does not bear directly  on  the  ground,  a
space at least eighteen inches high shall be provided directly under the
floor  beams, girders or sill of the first floor construction. Where the
floor above such a space is constructed of  wood  or  metal,  the  space
shall be ventilated by one of the following means:
  (1) At least four widely-distributed ventilating openings, providing a
total  net  free area of at least one eight-hundredth of the area of the
crawl space, shall be provided in the foundation walls, and  the  ground
within  the  crawl  space  shall  be  covered  with  a  vapor barrier in
durability equivalent to at least fifty-five pounds, roofing  felt  with
unsealed laps and with a transmission rate of one perm or less. At least
two  ventilating  openings,  providing a total net free area of at least
one fifteen-hundredth the area of the crawl space shall be  provided  in
foundation walls, provided that a vapor barrier with a transmission rate
of  one perm or less is installed over the entire underside of the first
floor construction and overlaps the walls.
  (2) Other means acceptable to the commissioner.
  (b) Buildings and structures with basements. No foundation wall  vents
shall  be  required  where  one side of a crawl space is completely open
except for structural members, to a basement that has an area  at  least
equivalent  to  that  of  the crawl space, provided that the basement is
naturally ventilated  by  openings  complying  with  section  27-749  of
article  six  of  this  subchapter and having a free openable area of at
least five per cent of the floor area of the basement.

Section 27-763

Section 27-763

  §   27-763  Ventilation  of  refrigeration  plants.  Rooms  containing
refrigeration  plants  shall  be  ventilated  in  accordance  with   the
provisions of subchapter thirteen of this chapter.

Section 27-764

Section 27-764

  § 27-764 Ventilation of boiler rooms. Boiler rooms shall be ventilated
in  a manner that will provide air for combustion in accordance with the
provisions of subchapter fourteen of this chapter and also  prevent  the
accumulation of hot air over or near the equipment within the room.

Section 27-765

Section 27-765

  § 27-765 Ventilation for schools. School buildings shall be ventilated
in accordance with the following requirements:
  (a)  Rooms  of instruction and administration. Classrooms, other rooms
of  instruction,  and  administrative  rooms,  where   the   index   for
ventilation  is  less  than one thousand six hundred fifty, shall have a
supply of  outdoor  air  of  at  least  fifteen  cfm  per  occupant  and
mechanical exhaust.  Where windows are used as the source of supply air,
mechanical  air  exhaust shall be fifteen cfm per occupant. When outdoor
air is supplied by mechanical means,  the  exhaust  shall  be  at  least
eighty per cent of the supply. In air-conditioned rooms, the conditioned
air supply may be reduced to a minimum of ten cfm per occupant, of which
at least five cfm shall be outdoor air.
  (b) Lockers and wardrobes. Lockers, wardrobes, or wardrobe rooms shall
be  ventilated  in  accordance  with the provisions of section 27-760 of
this article, and where these spaces are located within or  adjacent  to
classroom,  the  exhaust  air  from  the  classroom may be used for such
ventilation.
  (c) Auditoria and assembly rooms. Rooms  where  there  are  more  than
seventy-five  occupants  shall  have a supply of outdoor air of at least
fifteen cfm per occupant and mechanical exhaust. Where windows are  used
as  the  source  of supply air, mechanical air exhaust shall be at least
fifteen cfm per occupant. When outdoor air  is  supplied  by  mechanical
means,  the  mechanical exhaust shall be at least eighty per cent of the
supply. In air-conditioning spaces, the conditioned air  supply  may  be
reduced to a minimum of ten cfm per occupant, of which at least five cfm
shall be outdoor air.

Section 27-766

Section 27-766

  §  27-766  Ventilation of rooms or spaces with excessive temperatures,
strong odors, toxic substances, or airborne irritants. In these rooms or
spaces,  prevention  of  all  of  the  following  conditions  shall   be
considered in the design and installation of a ventilating system:
  (a) Excessive temperatures that may be detrimental to the occupants.
  (b) The danger of large concentrations of toxic substances in the air.
  (c)  The  danger  of  large  concentrations  of  airborne irritants an
impurities, such as steam, gases, vapor, and dust, that may be injurious
to health.
  Where the  exhausted  air  may  contain  toxic  substances  or  strong
objectional  odors,  the  exhaust system shall be independent of exhaust
systems serving other parts of the building.

Section 27-767

Section 27-767

  §  27-767  Ventilation  for special uses and occupancies. Special uses
and  occupancies,  not  provided  for  in  this  subchapter,  shall   be
ventilated  in  accordance  with the requirements of subchapter seven of
this chapter.  Ventilation of stage areas shall be  in  accordance  with
the requirements of subchapter eight of this chapter.