Article 10 - PIPING CONTAINING STEAM, HOT WATER OR OTHER FLUIDS

Section 27-809

Section 27-809

  § 27-809 Insulation and clearances. All accessible piping in habitable
and   occupiable  rooms  carrying  steam,  water,  or  other  fluids  at
temperatures exceeding one hundred sixty-five degrees  Fahrenheit  shall
be  insulated  to  prevent  the  temperature at the outer surface of the
insulation from exceeding sixty degrees  Fahrenheit  above  the  ambient
temperature.  The  openings  for  insulated  piping  through combustible
floors, walls, partitions, ceilings and other  combustible  construction
shall   include   clearance  and  insulation  adequate  to  satisfy  the
requirements of section 27-792 of article one of this subchapter.  Where
accessible  piping  carries  a  fluid  not  exceeding  two hundred fifty
degrees Fahrenheit and insulation would interfere with  the  functioning
of  the  system,  such  piping  may  be  uninsulated provided sufficient
clearance is maintained from the combustible construction  so  that  the
temperature  limitation  of  section  27-792  of  article  one  of  this
subchapter is not exceeded, and all uninsulated piping shall be provided
with at least one-half inch clearance from combustible materials.

Section 27-810

Section 27-810

  §  27-810 Firestopping. For requirements governing firestopping around
piping  passing  through  floors,  roofs,  or  fire   separations,   see
subchapter five of this chapter.

Section 27-811

Section 27-811

  §   27-811   Insulation   materials.   All  insulations  shall  be  of
noncombustible materials. All coverings, vapor  barriers  and  adhesives
shall  have a flame spread rating no higher than twenty-five and a smoke
developed rating no higher than fifty.  Adhesives  and  mastic  finishes
shall be tested in sufficient bulk to produce maximum burning, and shall
be tested in accordance with reference standard RS 14-11.