Article 13 - FLOOR FURNACES

Section 27-817

Section 27-817

  §  27-817  Location.  Floor  furnaces  shall  be  located  so as to be
accessible and shall not be installed in the floor of  any  corridor  or
passageway, nor in any exit in a place of assembly.

Section 27-818

Section 27-818

  § 27-818 Enclosures. Enclosures of floor furnaces shall be constructed
entirely of noncombustible materials with a fire resistance rating of at
least one hour and the enclosure shall be provided with adequate outdoor
air  in  accordance  with  the  requirements  of  article  nine  of this
subchapter to ensure proper combustion. The enclosure shall be  provided
with adequate means of access for servicing the furnace.

Section 27-819

Section 27-819

  §  27-819  Furnace supports. Floor furnaces shall be installed only in
floors of noncombustible construction having at least a  two  hour  fire
resistance  rating, except as provided for one- and two-family dwellings
in section 27-823  of  this  article.  Floor  furnaces  shall  have  the
following clearances:
  (a)  Pit  clearances. Floor furnaces, when other than gas-fired, shall
be mounted independently of the floor grille with a six  inch  clearance
at  the  bottom and a twelve inch clearance at the sides except that the
clearance on the control side shall be at least eighteen inches.
  (b) Pit waterproofing. When there is likelihood of water rising  above
the  bottom  clearance  of the unit, the pit shall be constructed with a
watertight enclosure with the sides extending at least four inches above
the ground level.

Section 27-820

Section 27-820

  §  27-820  Pit  access openings. The access foundation wall opening or
floor trap door shall be at least eighteen inches by twenty-four  inches
and the under floor passage to the furnace shall be at least twenty-four
inches by twenty-four inches in cross-section.

Section 27-821

Section 27-821

  §  27-821  Duct  temperature.  The outlet duct temperature of warm air
heating furnaces shall not be greater than  two  hundred  fifty  degrees
Fahrenheit.

Section 27-822

Section 27-822

  §  27-822  Pressure  regulator.  In gas-fired furnaces, a gas pressure
regulator shall be provided so that the gas input does  not  exceed  the
manufacturer's   rating.  Pressure  regulators  shall  comply  with  the
requirements of article five of this subchapter.

Section 27-823

Section 27-823

  § 27-823 One- and two-family dwellings. Floor furnace enclosures shall
be constructed of noncombustible materials with a fire resistance rating
of at least one hour. Means shall be provided for supporting the furnace
when  the  floor  grille  is removed. Clearances shall be as provided in
reference standards RS 14-15 and 14-16.