Article 19 - SOLID FUEL FIREPLACES, FIREPLACE STOVES AND ROOM HEATERS

Section 27-848.01

Section 27-848.01

  §  27-848.01  General.  The construction, installation, alteration and
operation of all fireplaces, fireplace stoves and room heaters used  for
space  heating  shall be subject to the provisions of this article. This
article shall not be construed to apply to a central heater with hot air
distribution, a central boiler with  either  hot  water  or  steam  heat
distribution or a water tank, water heaters, furnaces or cooking stoves.

Section 27-848.02

Section 27-848.02

  §  27-848.02  Reference  standards. The applicable reference standards
shall be as follows:
  (a) Fireplaces and wood  burning  appliances.  Reference  standard  RS
14-18.
  (b) Factory-built fireplaces. Reference standard RS 14-19.
  (c) Fireplace stoves. Reference standard RS 14-20.
  (d) Room heaters. Reference standard RS 14-21.

Section 27-848.03

Section 27-848.03

  §  27-848.03 Definitions. As used in this article, the following terms
shall have the following meaning:
  Accessories, factory-built. Such devices as fireplace heater  inserts,
heat  exchangers  circulating  air  or  water or other devices which may
alter the combustion or heating characteristics of the fireplace.
  Appliance. A device which utilizes fuel or other forms  of  energy  to
produce  light,  heat,  power,  refrigeration  or air conditioning. This
definition  shall  also  include  wood  burning  appliances  and  vented
decorative appliances.
  Fireplace,   factory-built.  A  fireplace  composed  of  factory-built
components assembled in accordance with the terms  of  the  listing  and
acceptance  to  form the completed fireplace and provided with a chimney
complying with subchapter fifteen of this chapter (see figure 14-1).
  Fireplace, masonry. A hearth and fire chamber made  of  solid  masonry
units such as bricks, stones, or reinforced concrete and provided with a
chimney complying with subchapter fifteen of this chapter.
  Fireplace   heat  exchangers.  Metal  heat  circulators  designed  for
installation wholly within a masonry fireplace built in accordance  with
this  code.  Fireplace  heat exchangers extract heat from the firebox of
masonry fireplaces and return it to the area to be  heated  (see  figure
14-2).
  Fireplace  inserts.  Solid-fuel  burning  appliances located partially
within a complying masonry fireplace. Stove and room heaters may be used
as inserts for installation in masonry fireplaces (see figure 14-3).
  Fireplace stoves. Freestanding assemblies having firechambers intended
to be operated open to the room or if equipped with doors to be operated
with doors either open or closed and provided with a  chimney  complying
with subchapter fifteen of this chapter (see figure 14-4).
  Room  heater.  A  solid fuel burning freestanding firechamber assembly
designed to be operated with the firechamber closed except  for  fueling
and  provided  with  a chimney complying with subchapter fifteen of this
chapter (see figure 14-5).
  Hearth extension. The noncombustible surfacing applied  to  the  floor
area  beneath,  and  extending  beyond  the  front,  back and sides of a
heating appliance.
  Listed and listings. Terms referring to equipment which is shown in  a
list  published  by an accepted nationally recognized testing laboratory
qualified and equipped  for  experimental  testing  and  maintaining  an
adequate  periodic  inspection  of  current production and whose listing
shows that the equipment  complies  with  nationally  recognized  safety
standards.
  Manufacturer's   installation   instructions.   Printed   instructions
included with equipment as part of the conditions of the listing.
  Solid fuel. A material such as natural wood which will ignite and burn
when subjected to fire.

  FACTORY-BUILT FIREPLACE -- (See figure 14-1)

  FIREPLACE HEAT EXCHANGER -- (See figure 14-2)

  AIRTIGHT FIREPLACE INSERT -- (See figure 14-3)

  FREESTANDING FIREPLACE STOVE -- (See figure 14-4)

  AIRTIGHT ROOM HEATER -- (See figure 14-5)

Section 27-848.04.

Section 27-848.04.

  § 27-848.04. Installations. (a) Application.
  (1)  An  application  for  the  installation  of  a fireplace or stove
equipment  shall  be  filed  by  a  registered  architect  or   licensed
professional  engineer  at  the  borough  office  of the department. The
application  shall  describe  the  equipment   in   question   and   its
installation.
  (2)  The applicant, prior to the filing of the application, shall make
an inspection to determine the adequacy of the air supply for combustion
and ventilation and the ability of the  equipment  to  be  installed  to
comply with code requirements.
  (b) Qualifications of installer.
  (1)  Installation  shall  be  made  only  by persons authorized by the
manufacturer to install the specific equipment in question.
  (2) The  installer  shall  certify  to  the  registered  architect  or
licensed  professional  engineer  who has filed the application that the
installation is in full  compliance  with  the  terms  of  the  listing,
acceptance and the manufacturer's instructions.
  (3)  For retrofit installations in occupied residential dwellings, the
installer shall have a home improvement contractor's  license  from  the
department of consumer affairs.
  (c) Controlled inspection. Installation shall be subject to controlled
inspection to ensure that the installation is in accordance with:
  (1) the structural elements shown on the approved plans,
  (2) the fire protection requirements, and
  (3)  the  listing,  acceptance  and  the  manufacturer's  installation
recommendations.
  (d) Environmental requirements.  All  solid  fuel  burning  appliances
shall  comply  with  the  requirements of the air pollution control law,
chapter one of title twenty-four of this code.
  (e) State energy conservation code. The requirements of the  New  York
State  energy  conservation  construction code concerning the combustion
air supply shall be complied with.

Section 27-848.05

Section 27-848.05

  §  27-848.05 Structural adequacy. The registered architect or licensed
professional engineer filing the application for the installation  shall
certify on the application as to the adequacy of the structural supports
and chimney bracing to sustain the loadings when in operation.

Section 27-848.06

Section 27-848.06

  §  27-848.06  Chimneys.  Fireplace,  fireplace  stove  and room heater
chimneys shall meet the  requirements  of  subchapter  fifteen  of  this
chapter. Separate flues shall be provided for every fireplace, fireplace
stove and room heater.

Section 27-848.07

Section 27-848.07

  § 27-848.07 Masonry fireplaces. (a) Construction.
  (1)  Masonry fireplaces shall be constructed of solid masonry units of
reinforced portland or refractory cement  concrete.  Masonry  fireplaces
shall  be  supported on foundations of masonry or reinforced portland or
refractory cement concrete,  or  on  other  noncombustible  construction
having  a  fire  resistance  rating  of  not less than three hours. Such
supports shall be designed to support the loadings.
  (2) Where a lining of low-duty fire clay refractory brick at least two
inches thick laid in medium-duty  fireclay  refractory  mortar,  or  the
equivalent two inches thick soapstone, three-sixteenths inch thick steel
or   cast  iron,  or  equivalent  material  capable  of  withstanding  a
temperature of 2000 degrees Fahrenheit without cracking or  spalling  or
other  accepted  lining  is  provided,  the  total thickness of back and
sides, including the lining, shall be not less than eight inches.
  (3) Where such lining is not provided, the thickness of the  back  and
sides shall be not less than twelve inches.
  (4)  Where  the  masonry supporting a fireplace is designed to support
vertical loads from the building and corbels are used to  support  beams
or  girders,  corbeling  shall  be as described in reference standard RS
14-18 as recommended for  masonry  chimneys.  The  lintel  spanning  the
fireplace  shall  be  designed and constructed to support the additional
load transferred by the member.
  (5) Masonry fireplaces shall be provided with  chimneys  designed  and
constructed in accordance with the requirements of subchapter fifteen of
this chapter for construction of masonry chimneys or, where permitted by
the  individual  listing,  shall be provided with accepted factory-built
chimneys having accepted adapters in accordance  with  the  requirements
for factory-built chimneys of subchapter fifteen of this chapter.
  (b) Steel fireplace units.
  (1)  Steel  fireplace  units incorporating a firebox liner of not less
than one quarter inch thick steel and an air chamber shall be  installed
with  masonry  to provide a total thickness at the back and sides of not
less than eight inches, of which not less  than  four  inches  shall  be
solid  masonry.  Listed  firebox liners shall be installed in accordance
with the terms of the listing.
  (2) Warm  air  ducts  employed  with  steel  fireplace  units  of  the
circulating  air  type  shall be constructed of metal in accordance with
reference standard RS 14-22, or of masonry.
  (c) Clearance.
  (1) All wood beams, joists, studs and other combustible material shall
have a clearance of not less than two inches from the  front  faces  and
sides of masonry fireplaces, and not less than four inches from the back
faces  of masonry fireplaces. Headers of combustible material supporting
masonry trimmer arches or concrete hearth extensions  shall  be  located
not less than twenty inches from the face of the chimney breast.
  (2)  Spaces  between  headers  or trimmers of combustible material and
masonry fireplaces shall be fire-stopped with  noncombustible  material.
The material used for firestopping shall be galvanized sheet metal of at
least  no.  14 U.S. standard gauge thickness, mineral board at least one
quarter inch thick or equivalent rigid noncombustible sheet material not
less than one half inch thick or other accepted noncombustible material.
  (3) Woodwork, such as wood trim  and  mantels,  or  other  combustible
material  shall  not be placed within six inches of a fireplace opening.
Combustible material above and projecting more  than  one  and  one-half
inches  from  a  fireplace  opening shall not be placed less than twelve
inches from the top of the fireplace opening.
  (4) Clearances specified in reference standard RS 14-18 shall apply if
greater than those specified in this subdivision.

  (d) Hearth extensions.
  (1)   Masonry  fireplaces  shall  have  hearth  extensions  of  brick,
concrete, stone, tile or other accepted noncombustible  materials.  Such
hearths  shall  be  supported on trimmer arches of brick, stone, tile or
concrete at least four inches thick, or of  other  equivalent  materials
and  with  noncombustible material against the underside thereof. Wooden
forms or centers used during the construction of the hearth  and  hearth
extension shall be removed when the construction is completed.
  (2)  Where  the  fireplace  opening  is less than six square feet, the
hearth extension shall extend at least sixteen inches in  front  of  the
facing  material  and  at  least  eight  inches  beyond each side of the
fireplace opening.
  (3) Where the fireplace opening is six  square  feet  or  larger,  the
hearth  extension  shall  extend  at least twenty inches in front of the
facing material, and at least twelve inches  beyond  each  side  of  the
fireplace opening.
  (4)  Where  a  fireplace  is  elevated above or overhangs a floor, the
hearth extension shall also extend over the area under the fireplace.
  (e) Fireplace dampers. Every fireplace shall be equipped with a damper
able to  withstand  distortion,  binding,  cracking  or  corrosion  when
exposed to the fireplace operating temperature.
  (f)   Accessories.  Factory-built  accessories  shall  be  listed  and
accepted and shall be installed in accordance with the  terms  of  their
listing and acceptance.

Section 27-848.08

Section 27-848.08

  §  27-848.08  Wood  burning  appliances: Installation. (a) Scope. Wood
burning appliances include factory-built fireplaces,  fireplace  stoves,
room heaters, and fireplace inserts.
  (b)  Listing. Wood burning appliances shall be listed and accepted and
shall be installed in accordance with the terms  of  their  listing  and
acceptance.
  (c) Location of appliances.
  (1)  Every  appliance  shall  be  located  with  respect  to  building
construction  and  other  equipment  so  as  to  permit  access  to  the
appliance.  Sufficient  clearance shall be maintained to permit cleaning
of surfaces, the replacement of air filters, blowers,  motors,  controls
and  chimney  connectors,  and  the  lubrication and servicing of moving
parts.
  (2) Wood burning appliances shall not be installed in confined  spaces
or alcoves. The minimum size of the space or room in which the appliance
is  located  shall  be three hundred cubic feet. There shall be at least
one openable window serving such space or room.
  (3) Wood burning appliances shall not be  installed  in  any  location
where  gasoline  or  any  other  flammable  liquids, vapors or gases are
present or likely to be present.
  (4) Wood burning appliances shall not be installed in any garage.
  (d) Air for combustion and ventilation. Wood burning appliances  shall
be  installed  in  a  location  in  which the facilities for ventilation
permit proper chimney draft and maintenance of  safe  temperature  under
conditions  of use and provide sufficient air to prevent carbon monoxide
from entering the dwelling space. Appliances shall be located so as  not
to  interfere  with  proper  circulation of air within the heated space.
Where buildings are so tightly sealed that normal infiltration does  not
provide the necessary air, outside air shall be introduced.
  (e) Mounting for residential type appliances.
  (1)  Residential  type  wood  burning  appliances  that are tested and
listed by an accepted national testing laboratory  for  installation  on
floors  constructed  of  combustible  materials  shall be placed on such
floors in accordance with  the  requirements  of  the  listing  and  the
conditions  of  acceptance.  Such  appliances  which  are not listed for
installation on combustible  floors  by  an  accepted  national  testing
laboratory  shall  be  provided with floor protection in accordance with
the provisions of subdivision (g) of this section. Residential type wood
burning appliances are permitted to be placed without  floor  protection
in any of the following manners:
  a.  on  concrete bases adequately supported on compacted soil, crushed
rock or gravel;
  b. on concrete slabs or masonry arches that do  not  have  combustible
materials attached to the underside; or
  c.  on  accepted  assemblies  constructed  entirely of non-combustible
materials, and having a fire resistance rating  of  not  less  than  two
hours, with floors constructed of noncombustible materials.
  (2)  Any  floor  assembly,  slab  or  arch  shall extend not less than
eighteen inches beyond the appliance on all sides.
  (3) In lieu of the requirements for floor protection specified herein,
a  floor  protector  listed  by  a  recognized  testing  laboratory  and
installed in accordance with the installation instructions may be used.
  (4)  Appliances  shall be supported by concrete bases, concrete slabs,
masonry arches and floor ceiling assemblies and their supports which are
designed and constructed to support the appliance.
  (f) Mounting for fireplace stoves and room heaters.
  (1) Fireplace stoves and  room  heaters  which  are  set  on  legs  or
pedestals that provide not less than six inches of ventilated open space

beneath  the  fire  chamber  or  base  of the appliance may be placed on
floors  of  combustible  construction,  provided  the  floor  under  the
appliance  is protected with closely spaced solid masonry units not less
than  two  inches  in thickness. The top surface of the masonry shall be
covered with sheet metal not less than  24  gauge  (0.024  inches).  The
floor  protection  shall extend not less than eighteen inches beyond the
appliance on all sides.
  (2) Fireplace stoves  and  room  heater  which  are  set  on  legs  or
pedestals  providing  two to six inches of ventilated open space beneath
the fire chamber or base of the appliance may be  placed  on  floors  of
combustible  construction,  provided  the  floor  under the appliance is
protected with one course of hollow masonry units  not  less  than  four
inches  in thickness. The masonry units shall be laid with ends unsealed
and joints matched in such a way as to provide a free circulation of air
through the core spaces of the masonry. The top surface of  the  masonry
shall be covered with sheet metal not less than 24 gauge (0.024 inches).
The  floor  protection shall extend not less than eighteen inches beyond
the appliance on all sides.
  (3) Fireplace stoves and room heaters  with  legs  or  pedestals  that
provide  less  than two inches of ventilated open space beneath the fire
chamber or base of the appliance  shall  not  be  placed  on  floors  of
combustible construction.
  (g)  Clearances.  Woodburning  appliances  shall be installed with the
following minimum clearances to combustible construction: Above the  top
of  appliance--thirty-six  inches;  from  front--thirty-six inches; from
back--thirty-six inches;  from  sides--thirty-six  inches.  The  minimum
clearance  to noncombustible construction shall be six inches when table
14-1 herein is used except that forty-eight inches shall  be  maintained
where  the  fuel  is  inserted. Accepted stoves shall be exempt from the
above-mentioned clearances and shall be installed in accordance with the
appropriate  reference  standard  and  clearances  determined  therefrom
through tests specified in the reference standard.
  (h) Reduction of clearances from wood burning appliances.
  (1)  Clearances  from  listed  and unlisted wood burning appliances to
combustible material may be  reduced  if  the  combustible  material  is
protected as described in table 14-1 herein and as shown in figures 14-6
to 14-10 herein.
  (2)  Clearances  from  wood burning appliances to combustible material
may be reduced by the use  of  materials  or  products  listed  for  the
purpose  of  reducing such clearances. Materials and products listed for
such purpose shall be installed in accordance with the conditions of the
listing and the manufacturer's instructions.
  (3) For clearance reduction systems  using  an  air  space  between  a
combustible  wall  and wall protector, adequate air circulation shall be
provided by one of the  following  methods  as  shown  in  figure  14-10
herein:
  a.  Adequate  air  circulation may be provided by leaving all edges of
the wall open with an air gap of at least two inches.
  b. If the wall protector is mounted on a single flat  wall  away  from
corners,  adequate  air  circulation may be provided by leaving only the
bottom and top edges or only the side and top edges open with an air gap
of at least two inches.
  c. Wall protectors that cover two walls in a corner shall be  open  at
the bottom and top edges with an air gap of at least two inches.

                               TABLE 14-1
        Reduction of Appliance Clearance with Specified Forms of
                    Protection{1,2,3,4,5,6,7,8,9,10}

Clearance reduction      Maximum allowable    When the required clear-
system applied to and    reduction in clear-  ance with no protection
covering all combust-    ance (percent)       is 36 in., the clearances
ible surfaces within the                      below are the minimum
distance specified as                         allowable clearance. For
required clearance with                       other required clearances
no protection                                 with no protection,
                                              calculate minimum
                                              allowable clearance from
                                              maximum allowable
                                              reduction.{9,10}

                                                     As Wall  As Ceiling
                              As Wall   As Ceiling  Protector  Protector
                             Protector   Protector     (in.)     (in.)
                             _________  __________  _________ _________
  (a) 3 1/2 in. thick           33%         __          24        __
masonry wall without
ventilated air space.
  (b) 1/2 in. thick             50%         33%         18        24
noncombustible insul-
ation board over 1 in.
glass fiber or mineral
wool batts without vent-
ilated air space.
  (c) 0.024 in. (24 gauge)      66%         50%         12        18
sheet metal over 1 in.
glass fiber or mineral
wool batts reinforced
with wire, or equivalent,
on rear face with vent-
ilated air space
  (d) 3 1/2 in. thick           66%         __          12        __
masonry wall with vent-
ilated air space
  (e) 0.024 in. (24 gauge)      66%         50%         12        18
sheet metal with vent-
ilated air space.
  (f) 1/2 in. noncombustible    66%         50%         12        18
insulation board with vent-
ilated air space.
  (g) 0.024 in. (24 gauge)      66%         50%         12        18
sheet metal with vent-
ilated air space over
0.024 in. (24 gauge)
sheet metal with vent-
ilated air space.
  (h) 1 in. glass fiber         66%         50%         12        18
or mineral wool batts
sandwiched between two
sheets 0.024 in. (24 gauge)
sheet metal with vent-
ilated air space.

Notes:
  {1} Spacers  and  ties shall be of noncombustible material. No spacers
or ties shall be used directly behind appliance or conductor.

  {2} With all clearance reduction systems using a ventilated air space,
adequate air circulation shall be provided. There shall be  at  least  2
in.  between  the  clearance  reduction system and combustible walls and
ceilings for clearance reduction systems using a ventilated air space.
  {3} Mineral wool batts (blanket or board) shall have a minimum density
of 8 lb. per ft{3} and have a minimum melting point of 1500°F.
  {4} Insulation  material  used  as  part of clearance reduction system
shall have a thermal conductivity of 1.0(BTU-In.)/(Sq ft-Hr-°F) or less.
Insulation board shall be formed of noncombustible material.
  {5} If a single wall connector passes through a masonry wall used as a
wall shield, there shall be at least 1/2 in.  of  open,  ventilated  air
space between the connector and the masonry.
  {6} There  shall  be  at  least  2  in.  between the appliance and the
protector. In no case shall the clearance between the appliance and  the
wall surface be reduced below that allowed in the table.
  {7} Clearances in front of the loading door and/or ash removal door of
the appliance shall not be reduced from those in Section 8-6.
  {8} All clearances and thicknesses are minimums: larger clearances and
thicknesses  are  acceptable.  Clearances are not to be less than 12 in.
from appliances.
  {9} To  calculate  the  minimum  allowable  clearance,  the  following
formula  may  be  used:  C{pr} = C{un} x (1-R/100). C{pr} is the minimum
allowable clearance. C{un} is the required clearance with no protection,
and R is the maximum allowable reduction in clearance.
  {10} Refer to Figures 14-11 and 14-12  for  other  reduced  clearances
using materials (a) through (h).

FRONT VIEW -- (See Figure 14-6)

CLEARANCE  TO  COMBUSTIBLE  WALL  WITH  PROTECTION  AS SPECIFIED -- (See
Figure 14-7)

MASONRY CLEARANCE REDUCTION SYSTEM -- (See Figure 14-8)

MASONRY WALL TIE -- (See Figure 14-9)

WALL PROTECTORS -- (See Figure 14-10)

Wall Protection Using Materials in Table 14-1 -- (See Figure 14-11)

Ceiling Protection Using Materials in Table -- (See Figure 14-12)

  (4) All clearances shall be measured from the  outer  surface  of  the
combustible  materials  to  the nearest point on the surface of the wood
burning appliance, disregarding any intervening  protection  applied  to
the combustible materials.
  (5)  All  clearances  provided  between  wood  burning  appliances and
combustible materials shall be large enough so as to maintain sufficient
clearance  between  chimney  connectors  and  combustible  materials  as
required in subchapter fifteen of this chapter.
  (i) Accessories. Factory-built accessories for wood burning appliances
such  as  heat exchangers, stove mats, floor pads and protection shields
shall be listed and accepted, and shall be installed in accordance  with
the terms of their listing and acceptance.

Section 27-848.09

Section 27-848.09

  §  27-848.09  Factory-built  fireplaces,  fireplace  stoves  and  room
heaters.  (a) Acceptance. Factory-built fireplaces, fireplace stoves and
room heaters shall be listed  and  accepted  for  use  as  wood  burning
appliances.
  (b)  Occupancy  group limitations. Factory-built fireplaces, fireplace
stoves and room heaters shall not be permitted in buildings  other  than
those in residential occupancy group classifications J-2 and J-3, except
that  installations  within  other occupancy groups may be authorized by
the commissioner pursuant to rules and regulations  promulgated  by  the
department.
  (c) Chimney requirements.
  (1)  The chimney systems of factory-built fireplaces, fireplace stoves
and room  heaters  shall  be  constructed  in  accordance  with  section
27-869.01.
  (2)  No  chimney  shall  serve  more than one factory-built fireplace,
fireplace stove or  room  heater  or  be  pierced  to  serve  any  other
appliance.
  (d) Additional limitations. Factory-built fireplaces, fireplace stoves
or room heaters shall be:
  (1) located only in exterior rooms, and
  (2)  limited  to  space  heating  of  the  room  within which they are
located.
  (e) Chimney connectors.
  (l) Stovepipe.
  a. The stovepipe (or chimney  connector)  connecting  a  factory-built
fireplace,  fireplace  stove  or room heater to a chimney may contain no
more than two elbows. The total length of the connecting pipe should  be
kept as short as possible while maintaining the required minimum spacing
between  the factory-built fireplace, fireplace stove or room heater and
combustible materials. See subdivision (h) of section 27-848.08 of  this
code.
  b. The connector pipe shall be as large as the flue collars (where the
connector  pipe  joins  the  factory-built fireplace, fireplace stove or
room heater), and shall be fabricated from  steel  coated  with  a  high
temperature rust inhibitor.
  c.  The pipe's horizontal section shall rise one-quarter inch for each
foot of pipe, with the highest point being at  the  chimney  inlet,  and
shall not be longer than three quarters of the chimney height.
  d.  When  joining  sections of pipe, the joints shall overlap at least
two inches, with  the  crimped  (male)  end  pointing  down  to  prevent
creosote  drip  or  leak.  Each  joint shall be secured with three sheet
metal screws.  All fits shall be snug.
  e. The thimble shall be cemented with high temperature cement  at  the
flue inlet. The pipe shall not project into the flue itself.
  f. Connector pipe clearance to combustible materials shall be at least
three  times the pipe diameter (e.g. eighteen inches for six inch pipe),
but not less than eighteen inches.
  g. Stovepipes shall not pass  through  floors,  ceilings  or  closets.
Stovepipes  shall  not  pass  through  exterior  walls  unless  directly
connected with a thimble to the chimney as noted in  subparagraph  h  of
this paragraph.
  h. Alternately, a listed and accepted noncombustible thimble larger in
diameter  than the connector pipe, or a burned fireclay or metal thimble
surrounded by not less than twelve inches of brickwork may be  used  for
protection.
  i.  Connectors  and  chimneys  for factory-built fireplaces, fireplace
stoves and room heaters shall be  designed,  located  and  installed  to

permit  ready access for internal inspection and cleaning, in compliance
with the requirements of subchapter fifteen of this chapter.
  (2)  Connection  to  masonry fireplace flue. A factory-built fireplace
stove or room heater or insert may use a masonry fireplace flue when the
following conditions are met:
  a. There is a connector which extends from the fireplace stove or room
heater to the flue liner.
  b. The cross-sectional area of the flue is no more  than  three  times
the  cross-sectional  area  of  the  flue  collar  of  the factory-built
fireplace, fireplace stove or room heater.
  c. There is a  noncombustible  seal  below  the  entry  point  of  the
connector if the appliance vents directly through the chimney wall above
the smoke chamber.
  d. The chimney system can be inspected and cleaned.
  e.  Air  from  the  habitable  space  is not used to dilute combustion
products in the chimney flue.
  f.  Hearth  extensions   are   provided   in   accordance   with   the
manufacturer's   instructions   or  are  of  masonry  of  noncombustible
construction in accordance with subdivision (d) of section 27-848.07.

Section 27-848.10

Section 27-848.10

  § 27-848.10 Fireplace heat exchangers and fireplace inserts. Fireplace
heat  exchangers  and  fireplace  inserts  shall not be inserted into or
connected to factory-built fireplaces  unless  listed  by  a  nationally
recognized  testing  laboratory  and  accepted  for  use in the specific
fireplace.

Section 27-848.11

Section 27-848.11

  §  27-848.11  Imitation  fireplaces.  Only natural gas-fired fireplace
heaters accepted in accordance with the provisions of article twelve  of
subchapter  thirteen  of  this  chapter  shall  be  used  with imitation
fireplaces and shall be installed in accordance with the  conditions  of
the acceptance.

Section 27-848.12

Section 27-848.12

  §  27-848.12  Precautionary requirements. (a) Smoke detecting devices.
Smoke detecting  devices,  complying  with  article  six  of  subchapter
seventeen  of  this  chapter,  are  required where fireplaces, fireplace
stoves or room heaters are installed. At least one device  shall  be  in
the same room as the installation or in an adjacent room.
  (b)  Fire  extinguisher. A fire extinguisher rated for class "A" fires
shall be available in the vicinity of a fireplace,  fireplace  stove  or
room heater.
  (c)  Latching.  The  fireplace  stove  fuel  door  shall be latched to
prevent burning  wood  from  falling  out  or  an  overfired  fire  from
occurring due to an oversupply of air.
  (d)  Fireplace  screens.  Fireplace  stoves  shall  be  equipped  with
fireplace screens to minimize spark emission.
  (e) Warnings. Warnings on fireplace stoves shall be as required by the
United Consumer Products Safety Commission  and  reference  standard  RS
14-20.
  (f)  Floor  protection. Floor protection for fireplace stoves required
by section 27-848.08(f) shall extend  a  minimum  of  twenty-six  inches
beyond the stove at the front or side where the ashes are removed and at
least eight inches on the other sides.