Article 2 - HIGH HAZARD OCCUPANCIES

Section 27-400

Section 27-400

  §  27-400  Application.  This section shall apply to the construction,
alteration, and use of buildings or spaces for high  hazard  occupancies
classified in occupancy group A under the provisions of subchapter three
of this chapter.

Section 27-401

Section 27-401

  §  27-401  Explosion  hazard  and  unlisted  occupancies. Buildings or
spaces of high hazard occupancies that involve explosion hazards or that
are not specifically provided for in this code, shall be constructed  to
provide  any  necessary  additional  protection  adequate for the hazard
involved subject to approval by the commissioner.

Section 27-402

Section 27-402

  §  27-402  Other  requirements.  The  occupancy and use of high hazard
buildings  and  spaces  shall  also  be  subject   to   the   applicable
requirements of chapter four of this title.

Section 27-403

Section 27-403

  §  27-403  Location.  High  hazard  occupancies  shall  not be located
within, or attached to, a building occupied for any  other  use,  unless
separated  from such other use by noncombustible construction having not
less than a four hour fire resistance rating.

Section 27-404

Section 27-404

  §  27-404  Sprinkler  requirements.  Sprinkler  protection meeting the
construction requirements of subchapter seventeen of this chapter  shall
be  installed  in  all  high hazard occupancies. Where the nature of the
fire hazard is such that water is  not  effective  as  an  extinguishing
agent,  the  extinguishing  agent  to  be  used, shall be subject to the
approval of the fire commissioner.

Section 27-405

Section 27-405

  §  27-405 Ventilation of storage occupancies. Rooms or spaces used for
the storage of flammable paints, solvents, anesthetic  agents,  fuel  or
other oils having a flashpoint under two hundred degrees Fahrenheit (Tag
closed  cup)  or other inflammable vaporous materials shall be vented to
the outdoors by gravity or mechanical means, with independent supply and
exhaust openings or ducts. If ventilation is provided by gravity  means,
the total net free openable area of supply and exhaust openings shall be
equal  to  at  least  one percent of the floor area of the room, equally
divided between supply  and  exhaust.  If  ventilation  is  provided  by
mechanical  means,  the system shall be designed to provide at least two
air changes per hour. Where there are  explosion  hazards,  see  section
27-401  of  this  article.  The  construction of all ventilating systems
shall be in accordance with the requirements of subchapter  thirteen  of
this chapter.