Section 27-518
§ 27-518 Application. This article shall apply to the construction,
alteration and use of buildings or spaces wherein nitric acid is stored.
Section 27-519
§ 27-519 Location. Carboys containing nitric acid shall be stored in
storage vaults.
Section 27-520
§ 27-520 Construction requirements. (a) Vaults shall be constructed of
incombustible acid-resistant material with a fire resistance of at least
one hour.
(b) Doors opening into such storage vaults shall be self-closing,
noncombustible fire doors with a fire-protection rating of at least
three quarters of an hour.
(c) Vault floors shall be constructed of acid-resistant brick,
concrete treated with sodium silicate or other acid-proof material and
shall incorporate a dike constructed of the same material, whose height
shall be adequate to contain the acid plus the neutralizing substance
that would be necessary to neutralize said acid plus six inches.
(d) The floor shall be provided with a valved drain which shall be
connected to the drainage system in accordance with the requirements of
subchapter sixteen of this chapter.
Section 27-521
§ 27-521 Ventilation. Mechanical ventilation systems for storage
vaults shall be adequate to effect ten complete air changes per hr.
Exhaust shall be taken from within twelve inches above the level of the
top of the dike. The exhaust system shall be independent of exhaust
systems serving other parts of the building and the openings to the
outdoors shall be located in accordance with the provisions of
subchapter thirteen of this chapter for system conveying vapors.