Article 6 - DRY CLEANING ESTABLISHMENTS

Section 27-425

Section 27-425

  §  27-425  Application.  This section shall apply to the construction,
alteration, and use of buildings or  spaces  for  dry  cleaning  or  dry
dyeing operations.

Section 27-426

Section 27-426

  §  27-426  Classification.  Dry cleaning and dry dyeing establishments
shall be classified as follows:
  (a) High  hazard.  All  establishments  employing  gasoline  or  other
solvents having a flash point below 100° F (tag. closed-cup).
  (b)  Moderate  hazard.  All establishments employing solvents having a
flash point between 100° F and 138.2° (tag. closed-cup).
  (c) Low hazard. All establishments employing  solvents  with  a  flash
point higher than 138.2° F (tag. closed-cup).

Section 27-427

Section 27-427

  §  27-427 Construction requirements. (a) High hazard. The construction
or installation of high hazard  dry  cleaning  establishments  shall  be
prohibited.
  (b) Moderate hazard. Moderate hazard dry cleaning establishments shall
meet  all  of  the  requirements  of  this code applicable to industrial
occupancy group D-1 buildings. The floor finish in moderate  hazard  dry
cleaning establishments shall be noncombustible and impervious.
  (c)  Low hazard. Low hazard dry cleaning establishments shall meet all
of the requirements of this  code  applicable  to  industrial  occupancy
group D-2 buildings.
  (d)  Equipment. All dry cleaning machines and equipment shall be of an
approved type.

Section 27-428

Section 27-428

  §  27-428  Ventilation.  Mechanical  ventilation  systems  in moderate
hazard plants shall be adequate to effect ten complete air  changes  per
hour.    Low  hazard  dry cleaning establishments shall be provided with
mechanical ventilation adequate to effect four complete air changes  per
hour.    Ventilating  systems  shall  be  arranged  in such manner as to
prevent solvent vapors from being admitted to the combustion area of any
device  requiring  an  open  flame.  Sufficient  make-up  air  shall  be
introduced  into  all  parts  of  the  establishment  to  equal  the air
exhausted by the dry cleaning units,  dryers,  and  exhaust  ventilating
system.  Such  air  shall  not contain any flammable vapors. Openings or
stacks discharging solvent vapor-air mixtures to the outdoors  shall  be
located in accordance with the provisions of subchapter thirteen of this
chapter.

Section 27-429

Section 27-429

  §  27-429 Coin-operated units. In coin-operated establishments all dry
cleaning units shall be installed in such a manner that the  working  or
maintenance  portion  of the equipment shall be separated from the front
of the units by solid  noncombustible  partitions.  Coin-operated  units
shall  be located within a diked area, all parts of which are impervious
to the solvent used in such units. The diked section  shall  be  a  four
inch  curb  above the floor. Provisions shall be made for the collection
of solvent spillage into tanks of capacity sufficient to contain all  of
the  solvent  in  the  dry  cleaning units served, and for return of the
solvent to the cleaning units through a closed pipe system. Access doors
to the space in back of the units  shall  be  kept  closed  and  locked.
Solvent  storage  tanks and other sources of danger shall be so situated
as to be  inaccessible  to  the  general  public.  In  addition  to  the
mechanical   ventilation   required   for   low   hazard   dry  cleaning
establishments, the following mechanical ventilation shall be provided:
  (a) All dry cleaning units shall have facilities that create an inward
flow of one hundred cubic feet of air per minute into the unit when  the
loading door is opened.
  (b)  Emergency  ventilation  of  the space in back of the dry cleaning
units shall be provided so that in emergencies  a  minimum  of  one  air
change  per  minute  in  the  enclosed space will be provided. Emergency
ventilation equipment shall be on a circuit that is  separate  from  the
general lighting and power circuits, and shall be taken off ahead of the
main  switchboard, or shall be connected to the emergency lighting power
source when such source is provided.
  (c) A scavenger duct system shall be provided in the space in back  of
the  units  at  each  unit,  and  shall  be  designed  to  pick up vapor
surrounding the equipment near the floor and exhaust it at the  rate  of
one  hundred  cubic  feet  per minute. Scavenger ducts shall not be less
than five square inches in area.

Section 27-430

Section 27-430

  § 27-430 Sprinklers. Automatic sprinkler protection complying with the
construction  provisions  of  subchapter  seventeen  of  this chapter as
required for occupancy group D-1, shall be provided for moderate  hazard
dry   cleaning   establishments.   In   addition,   in  moderate  hazard
establishments each dry cleaning unit shall be provided  with  automatic
extinguishing equipment, such as a carbon dioxide system, or a steam jet
of not less than three-quarters of an inch at a pressure of fifteen psi.

Section 27-431

Section 27-431

  §  27-431  Separation  of  direct-fired dryers. In moderate hazard dry
cleaning establishments, direct-fired dryers shall not be used.  In  low
hazard  dry  cleaning  establishments  using nonflammable solvents only,
direct fired dryers may be used, but such dryers shall  not  be  located
within  twenty-five  feet of a dry cleaning unit unless a noncombustible
partition (which may be glazed), equipped with  self-closing  doors,  is
provided  between  the dry cleaning unit and the flame producing device.
This partition  may  provide  either  complete  or  partial  separation,
provided  that any partial separation shall be so arranged that the line
of air travel around the partition from the cleaning units to the  dryer
is a minimum of twenty-five feet. Where a solid noncombustible partition
is  constructed  extending  to  the  ceiling  and  all  portions  of the
enclosure are solid, except for self-closing access doors,  and  outdoor
air for combustion and drying is supplied, the separation may be reduced
to fifteen feet.