Article 7 - HELIPORTS

Section 27-432

Section 27-432

  §  27-432  Application.  This section shall apply to the construction,
alteration, and use of building roofs, or parts thereof, as heliports.

Section 27-433

Section 27-433

  §   27-433  Classification.  Heliports  on  building  roofs  shall  be
classified in industrial occupancy group D-1. They  shall  be  separated
from  all  other  portions  of  the building by construction meeting the
requirements of table 5-2 for fire divisions.

Section 27-434

Section 27-434

  §  27-434 Construction. Heliports shall be permitted only on buildings
classified  in  noncombustible  construction  group  I.   All   heliport
construction  above  the  building  roof  shall  be  noncombustible.  No
openings in the roof shall  be  permitted  in  the  landing  area.  Roof
openings  outside  the  landing  area  shall be protected from flammable
liquid spillage by four inch curbs and  shall  be  surrounded  by  metal
railings  at  least  three  feet  complying  with  the  requirements  of
subchapter nine of this chapter. The landing area shall be enclosed with
a substantial metal fence or skirt.

Section 27-435

Section 27-435

  §  27-435  Limitations. No refueling facilities shall be provided, and
no major aircraft repair or maintenance facilities shall be provided.

Section 27-436

Section 27-436

  § 27-436 Exits. At least two means of egress, meeting the requirements
of  subchapter  six  of this chapter, shall be provided for each landing
area. The exits shall be remote from each other and shall  lead  to  the
building stairways.

Section 27-437

Section 27-437

  §  27-437  Fire protection. Heliports shall be provided with fire-foam
extinguishing equipment and fire alarm facilities meeting the  following
requirements:
  (a)  At  least  two  hose  stations  housing  approved foam generating
equipment shall be provided remote from each other and located  adjacent
to  outlets  of  the  building standpipe system or other source of water
supply. Hoses shall be provided with nozzles and related  equipment  for
dispensing foam to all portions of the roof.
  (b)  The  building  standpipe  system  or other source of water supply
shall  be  capable  at  all  times  of  providing   two   hose   streams
simultaneously,  each  of  which will afford foam application at a total
water rate of at least sixty gallons per minute at a nozzle  presure  of
seventy-five psi for a period of ten minutes.
  (c)  A  fire  alarm  system  meeting  the installation requirements of
subchapter seventeen of this chapter shall be  provided  with  a  direct
connection to the central station of an operating fire alarm company and
with a local alarm to all heliport personnel.